Inaxsys SW1210-16CB, SW1205-4CB, SW1210-8CB, SW1205-8CB Product Installation Document

SW1210-16CB
Products
Power output
Number of
outputs
Battery
Charger
Enclosure dimensions
SW1205-4CB
12VDC@5.5 Amps
4
Yes
9.25”. x 8.25” in. x 3.5” (23.3 cm x 21 cm x 9 cm)
SW1205-8CB
12VDC@5.5 Amps
8
Yes
9.25”. x 8.25” in. x 3.5” (23.3 cm x 21 cm x 9 cm)
SW1210-8CB
12VDC@11 Amps
8
Yes
17”L x 13.5”W x 4.75”H (43.2 cm x 34.3cm x 12.06 cm)
SW1210-16CB
12VDC@11 Amps
16
Yes
17”L x 13.5”W x 4.75”H (43.2 cm x 34.3cm x 12.06 cm)
1. Overview:
The Inaxsys SW1210-16CB switching power supply/distribution unit converts 120VAC input into 12VDC at 11 amps of continuous supply current. The built-in 16-output distribution board allows for power delivery across multiple outputs while offering electronically fused protection on each circuit. This general­purpose power supply has a wide range of applications for access control, security and CCTV systems that require additional power. For convenient installation, the unit comes completely assembled with a compact steel enclosure, power cord and all connecting hardware.
2. Features:
Designed for quick installation
Individually protected, electronically fused outputs
Built in battery backup/charger on selected models(see below)
Short circuit isolation technology for uninterrupted operation
Class 2, Power limited outputs
Removable output terminal blocks for quick installation
Diagnostic LEDs for quick troubleshooting
Automatic switch over to stand-by battery
AC line cord included
Lifetime warranty
3. Specifications:
UL listed to UL-60950 Information Technology Equipment. CE/LVD EN60950-1 CE/EMC:EN55022,EN55024 FCC PART 15, ICES 003-2012
Maximum temperature range:-20° C to 40° C; (For indoor use only.)
● Relative humidity: 20% 90%
85% of Efficiency with full load. Maximum ripple 150mVp-p, Maximum noise 200mVp-p Built-in charger for sealed lead acid battery. Individual outputs current limited at 2.5 Amps per circuit. Maximum battery charge 500mA (Subtract from total output). Red LED’s indicate DC power presence on each circuit.
Note: When using the battery charger for backup /charging, 500mA needs to be subtracted from the total output power listed above in table.
Products
AC current draw
(Full load)
120VAC@50/60hz
AC current draw
(Full load)
240VAC 50/60Hz
Max output
per circuit
Number of
batteries required
for backup
SW1205-4CB
1.3Amps
650mA
2.5Amps
1
SW1205-8CB
1.3Amps
650mA
2.5Amps
1
SW1210-8CB
2.6Amps
1.3Amps
2.5Amps
2
SW1210-16CB
2.6Amps
1.3Amps
2.5Amps
2
Equipment is to be installed and serviced by authorized / trained personnel only. Installation should conform to all local codes and in accordance with the National Electrical Code. Shut branch circuit power before installing / servicing equipment. Product is intended for indoor use only.
4. Installation Instructions:
1. Unpack product. Do not discard packaging material until installation is complete.
2. Pre-drill holes on the wall where enclosure is to be mounted. Choose a vertical surface (wall) strong enough to support the full weight of the assembly. Select a mounting location in an area without excessive moisture; for indoor installation only and in a secured area (Electrical Room).
3. Secure enclosure to the desired wall location with the appropriate sized fasteners using the four mounting holes in the cabinet.
4. Disconnect power to the branch circuit to which the product will be connected.
5. Connect incoming AC power (120 V, 60 Hz):
– Hot (L1) (black) to terminal marked “L”. – Neutral (L2) (white) to terminal marked “N”.
– Ground (Green) to terminal marked “G”.
6. Use the knockout in bottom of cabinet for 120 VAC wiring. Route the 120VAC wiring at least 1/4" from (low voltage) wiring.
7. Keep a 1/4" (0.635 cm) separation between power­limited wiring and on-power-limited wiring. Use separate knockouts for power limited wiring.
8. Connect external loads to appropriate terminals shown in Fig 1: Connect circuit #1 to terminals marked “VO1+” and
VO1–”. Connect circuit #2 to terminals marked “VO2+” and “VO2–”. Continue to connect the remaining circuits,
carefully observing polarity.
9. Power the branch circuit and observe red output LEDs illuminated. Illuminated LEDs 1-4 or 1-8 mean that Dc power is present on outputs.
10. To avoid potential damage, verify that output voltage and load current does not exceed output
limitations. (A single extinguished LED can mean an overload condition) See troubleshooting
guide for more information.
11. For Battery backup: If battery backup is required, use the provided battery leads and connect the Lead Acid battery(s) 7AH 12V to the battery charger terminals while carefully observing polarity. Set the output voltage on the trim pot shown in Fig. 1 to 13.8VDC for proper charging. Battery(s) not supplied with power supply unit. We suggest using Power Sonic Battery part NO. PS1270, UL File NO.MH20845 or any Recognized Lead Acid UL Battery of same capacity and type,7AH 12V.