Impulse SCMXRK-002 User Manual

Accessories for 8B Analog Modules
Features
• Single Channel DIN Rail Mounting Accessory
• 2-, 4-, 8-, 16-Position Backpanels
• 19-Inch Mounting Rack For Backpanels
SensorLex® 8B Isolated Analog Signal Conditioning Products
• Interface Cables
• Cable-to-Screw-Terminal Interface Board
• Power Supplies
8B
Single Channel DIN Rail Mount Carrier
Description
The 8BP01 is offered as a 5VDC powered (8BP01-X05) or 7VDC to 34VDC (8BP01-X24) powered single channel DIN rail mount carrier suitable for any 8B signal conditioner. The 8B carrier can be mounted on any standard DIN rail
Specifications
Module 8BP01-X05 8BP01-X24
Specifications Typical at TA=+25°C and +5V power Typical at TA=+25°C and +24V power Input Voltage Range 4.85 to 5.2VDC 7 to 34VDC
Over-Voltage Protection 6V TVS, 1A Fuse, OV detection 36V TVS, 1A Fuse, OV detection Over-Voltage Shutdown Voltage 5.6V max 35.5V max Under-Voltage Turn-on 6.5V min Reverse Voltage Protection 1A Fuse 1A Fuse
Output Voltage Regulation 5VDC ±1% Power Indicator Green LED Green LED Output Voltage Temp. Coeff. ±200ppm/°C ±200ppm/°C Output Current 250mA max (–40°C to +85°C) 250mA max (–40°C to +85°C)
Output Current Limit 0.8A, Auto Recovery Line Regulation ±0.25% Load Regulation ±0.5% Efficiency 75%
Output Ripple <50mVpk-pk
(EN 50022-35 and EN 50035-G32). The 8BP01 measures only 2.32” x 3.54” x
0.65” (59mm x 90mm x 16.5mm), making it ideal for use in high-density installations (see Figure 1).
8B
Ordering Information
Part Number Description
8BP01-205 5V Power, No CJC 8BP01-305 5V Power, CJC 8BP01-224 24V Power, No CJC 8BP01-324 24V Power, CJC
Mechanical Dimensions 2.32" x 3.54" x 0.65" 2.32" x 3.54" x 0.65"
(h)(w)(d) (59mm x 90mm x 16.5mm) (59mm x 90mm x 16.5mm)
Figure 1: 8BP01 Single Channel DIN Rail Mount Carrier
Visit our website www.dataforth.com
137
©1995-2009 Dataforth Corporation, All Rights Reserved ISO9001:2000-Registered QMS
SensorLex® 8B Isolated Analog Signal Conditioning Products
8BP02, 8BP04, 8BP08, 8BP16
2-, 4-, 8-, and 16-Position Analog I/O Backpanels
Description
The 8BP02, 04, 08, and 16 backpanels can accept any of the 8B analog I/O modules in any mixture and can be mounted on the SCMXRK-002 19-inch metal rack. Analog I/O signal channels provide each module with its own analog bus. All module outputs are simultaneously accessible to high-speed data acquisi­tion (ADC) boards. A temperature sensor is mounted on each channel to provide cold junction compensation for thermocouple input modules (see Figure 6 for schematic). Field connections are terminated with four screw terminals at each module site. Use system interface cable SCMXCA006-XX for connection to the host system.
Specifications
Operating Temperature –40°C to +85°C Relative Humidity 95% Noncondensing
Interface Connector:
Field high density screw clamp, 16 AWG max System high density screw clamp, 16 AWG max
8B
Figure 2: 8BP02 Analog I/O Backpanel
138
©1995-2009 Dataforth Corporation, All Rights Reserved ISO9001:2000-Registered QMS
For information call 800-444-7644
Figure 3: 8BP04 Analog I/O Backpanel
SensorLex® 8B Isolated Analog Signal Conditioning Products
8B
Electrical
Power
The 8B backpanels have two power supply options. A +5VDC ±5% supply can be connected to the ‘+5V Supply’ terminal block, or alternatively, a wide ranging 7-34VDC supply can be connected to the ‘Alternate Supply’ terminal block. In the latter case, the 8BPWR-2 module must be installed on the backpanel. The backpanel contains circuitry which automatically switches between the supplies such that only one at a time provides power to the modules. When power connections are made to both terminal blocks simultaneously, the 7-34VDC supply takes precedence over the +5VDC supply.
Fusing
Backpanel power is fuse-protected through F1 and F2. Zener diodes D3 and D4 provide extra protection from overvoltage and supply reversal.
Grounding
For full protection against large electrical disturbances on the field-side of the 8B modules, a #10-32 ground stud is provided on the backpanel. An electrical connection between this ground stud and the system ground should be provided with a large gage wire of the shortest possible length.
Ordering Information
Part Number Description
8BP02 Standard 2-channel backpanel with standoffs for mounting. 8BP02-1 8BP02 without cold junction compensation sensor. Use when
cost savings are desired and thermocouple input modules 8B37 and 8B47 will not be used.
8BP02-2 8BP02 with DIN rail mounting option. The backpanel is
captured by DIN rail mounting elements and is shipped fully assembled.
8BP02-3 8BP02-1 with DIN rail mounting option.
8BP04 Standard 4-channel backpanel with standoffs for mounting. 8BP04-1 8BP04 without cold junction compensation sensor. Use when
cost savings are desired and thermocouple input modules 8B37 and 8B47 will not be used.
8BP04-2 8BP04 with DIN rail mounting option. The backpanel is
captured by DIN rail mounting elements and is shipped fully assembled.
8BP04-3 8BP04-1 with DIN rail mounting option.
8BP08 Standard 8-channel backpanel with standoffs for mounting. 8BP08-1 8BP08 without cold junction compensation sensor. Use when
cost savings are desired and thermocouple input modules 8B37 and 8B47 will not be used.
8BP08-2 8BP08 with DIN rail mounting option. The backpanel is
captured by DIN rail mounting elements and is shipped fully assembled.
8BP08-3 8BP08-1 with DIN rail mounting option.
8B
Figure 4: 8BP08 Analog I/O Backpanel
8BP16 Standard 16-channel backpanel with standoffs for mounting. 8BP16-1 8BP16 without cold junction compensation sensor. Use when
cost savings are desired and thermocouple input modules 8B37 and 8B47 will not be used.
8BP16-2 8BP16 with DIN rail mounting option. The backpanel is
captured by DIN rail mounting elements and is shipped fully assembled.
8BP16-3 8BP16-1 with DIN rail mounting option.
Visit our website www.dataforth.com
©1995-2009 Dataforth Corporation, All Rights Reserved ISO9001:2000-Registered QMS
139