![](/html/70/70ae/70ae2bef98990001e6557608ba5cf5fde86179fc45ed6bb3bdd699248aec1f62/bg1.png)
Industrial Loop Isolators and Transmitters
DSCL
DSCL24 (Multi-Channel
)
Factory Configurable Isolator - DIN or Panel Mount
Description
Each multi-channel DSCL24 module provides up to 252 different configurations
of process current or voltage inputs and outputs. The factory default setting
provides 4-20mA input and output current. Alternatively, users may complete
and submit a specific configuration table that instructs the factory on how to solder
in configuration jumpers.
Each module provides full 3-way isolation with 2300Vrms CMV input to output
and 3700Vrms CMV power supply to I/O protection. Two module versions are
offered that accept universal power supply of either 24 to 60VDC or AC and
85 to 230VDC or AC with the alternating current usage accepting 45 to 400Hz
power.
▲
Features
Uses Universal Power Supply of 24 to 60V or
85 to 230V AC/DC
Factory Configured Soldered Jumpers Allows
up to 250+ I/O Settings
One Input to Two Output Splitter Simplifies a
Common Requirement
Three-Way Isolation for 2300Vrms Protection
Prevents Ground-Loop Problems
Prevents the Transfer of Interference
Voltages and Currents
High Accuracy Over Full Span
No Recalibration or Maintenance Required
Narrow DIN Package, Mounts up to 27
Devices into a 19 Rack Space
DIN Rail or Panel Mountable
CE Compliant
Figure 1: DSCL24 Block Diagram
Visit our website www.dataforth.com
DSCL
175
![](/html/70/70ae/70ae2bef98990001e6557608ba5cf5fde86179fc45ed6bb3bdd699248aec1f62/bg2.png)
Industrial Loop Isolators and Transmitters
DSCL
Specifications
Module
Input Range
(1)
Typical at TA=+25°C and 24VDC or 230VAC ±10% supply voltage
DSCL24-11,-12,-21,-22
4-20mA
Input Limit 40mA, ±40mA(Iin); 40V, ±40V(Vin)
CMV Input to Output 2300Vrms, 1 min.
CMV Power Supply to I/O 3700Vrms, 1 min.
Accuracy (at 250Ω Load) ±0.1% Span Typical, ±0.2% Span Max
Input Resistance 15Ω Current Mode, 100kΩ Voltage Mode
Non-linearity Included in Accuracy
Stability <100ppm/°C
Input Overshoot <20µA (Typical 5µA)
Output Range
(1)
4-20mA
Limit Upper Range 40mA
Bandwidth, -3dB 15Hz
CMR (50Hz or 60Hz) 110dB
NMR 16dB at 50/60Hz
Response Time 30ms, to 90% Span
Load Resistance Range ≤600Ω Current Mode, ≥2kΩ Voltage Mode
Output Noise <0.5% p-p
Power Supply
Voltage (24 to 60) or (85 to 230)VDC/AC at 45-400Hz
Tolerance DC 15% to +33%, AC ±15%
Power Consumption DC ≤1.6W, AC ≤3.4VA
Environmental Weight Approximately 180g.
Housing Material Lexan 940 (UL 94 V-O)
Shock Test 50g (3 Shocks, 6 Axis)
Operating Temp Range -25°C to +55°C
Storage Temp Range -40°C to +70°C
Relative Humidity 0 to 75% Noncondensing
Emissions EN50081-2 (Radiated, Conducted)
Immunity EN50082-2 (ESD, RF, EFT)
NOTES:
(1) 250+ unique I/O ranges are factory configurable. See Table 1 for configuration options.
Configuration Options
The default setting of factory stock modules is 4 to 20mA for both module input
and output.
Alternatively, users may complete and submit Table 1 specifics that the factory
will use to apply solder-in jumpers configuring the module as desired.
NOTE: Modules once configured for a specific user I/O range cannot be
subsequently reconfigured.
Factory Configuration
Check-mark the desired Input and Output range for each channel in the table
at right. Copy and submit this configuration sheet with your purchase order. The
factory will assign a DSCL24-xxxx part number to your specific configuration.
This part number may be used on subsequent orders. The Span and Zero
potentiometers allow ±10% adjustments beyond the following factory solder
jumper settings.
Table 1: Configuration Checklist
Input Current (mA) Chn 1 Chn 2 *
0 to 0.1
0 to 0.2
0 to 0.5
0 to 1
0 to 2
0 to 5
0 to 10
0 to 20
0.2 to 1
1 to 5
2 to 10
4 to 20
-0.1 to 0.1
-0.2 to 0.2
-0.5 to 0.5
-1 to 1
-2 to 2
-5 to 5
-10 to 10
-20 to 20
Input Voltage (V) Chn 1 Chn 2 *
0 to 0.1
0 to 0.2
0 to 0.5
0 to 1
0 to 2
0 to 5
0 to 10
0 to 20
0 to 40
0.2 to 1
1 to 5
2 to 10
4 to 20
-0.1 to 0.1
-0.2 to 0.2
-0.5 to 0.5
-1 to 1
-2 to 2
-5 to 5
-10 to 10
-20 to 20
Output Current (mA) Chn 1 Chn 2
0 to 20
4 to 20
-20 to 20
Output Voltage (V) Chn 1 Chn 2
0 to 10
2 to 10
-10 to 10
* NOTE:
Inputs on Channel 2 only available on DSCL24-11 and 12