DSCL20
Loop Powered Isolator - Component Module
Description
Each DSCL20 loop powered isolator provides a single channel of analog signal
protection by electrically isolating its input from output for any DC process
signal in the range of 0-20mA (or 4-20mA). The DSCL20 operates passively,
obtaining its power from the transmitted signal (see Figure 1).
The input signal is chopped by a proprietary DC chopper circuit, isolation is
provided by transformer coupling, a proprietary technique is used to suppress
transmission of common mode spikes or surges, and the output signal from
the secondary of the transformer is reconstructed to the original input signal.
Industrial Loop Isolators and Transmitters
▲
Features
No Power Supply Required, Signal Powered
From 0-20mA (or 4-20mA) Input
Simplified Wiring, Easy to Install Plug-In
Accessories
Small OEM Modular Package Ideal for
PCB Mounting
I/O Packaging for Vertical or Horizontal
Mounting
500Vrms Transformer Isolation
Prevents Ground-Loop Problems
Prevents the Transfer of Interference
Voltages and Currents
High Accuracy Over Full Span
CE Compliant
DSCL
Figure 1: DSCL20 Block Diagram
162
For information call 800-444-7644
Industrial Loop Isolators and Transmitters
DSCL
Specifications
Module
Input Range 0/4-20mA
Input Current 50mA max at 18V max
CMV Input to Output 500Vrms, 1 Minute
(1)
Accuracy
Non-linearity Included in Accuracy
Stability <50ppm/°C
Overshoot <20µA (Typical 5µA)
Compliance Voltage 18V ±5% max (with Zener Diode)
Voltage drop
Output Range 0/4-20mA
Limit Upper Range 30mA
Bandwidth, -3dB 750Hz
CMR (50Hz or 60Hz) 90dB
NMR 20dB per Decade Above 750Hz
Response Time 1ms, to 90% Span
Load Resistance Range 0-600Ω
Output Noise <20mV Peak-to-Peak (Typical <5mV)
Environmental Weight Approximately 1.5g
Housing Material Lexan 940 (UL 94 V-O)
Shock Test 50g (10 Shocks, 3 Axis)
Operating Temp Range -20°C to +65°C
Storage Temp Range -40°C to +85°C
Relative Humidity 0 to 75% Noncondensing
Emissions EN50081-2 (Radiated, Conducted)
Immunity EN50082-2 (ESD, RF, EFT)
NOTES:
(1) Additional error <0.2% at 500Ω load
(2) V
in=IORL
(at 100Ω Load) ±0.05% Span Typical
(2)
+ <2V
Typical at TA=+25°C
DSCL20
±0.1% Span Max
<2V (for 500Ω Load)
Ordering Information
Model Input Range Output Range
DSCL20-01 0-20mA (4-20mA) 0-20mA (4-20mA)
DSCL20-02 0-20mA (4-20mA) 0-20mA (4-20mA)
Accessory
Model Description
DSCX-01 Socket for DSCL20-02
Figure 1: DSCL20-01 (Bent Pins)
Figure 2: DSCL20-02 (Straight Pins)
Figure 3: DSCX-01 Socket and Hold-down Accessory for DSCL20-02
(Straight Pin Modules)
Visit our website www.dataforth.com
DSCL