Impulse DSCA43 User Manual

High Performance Signal Conditioners
DSCA43
General Purpose Input Signal Conditioners, with DC Excitation
Description
Each DSCA43 general purpose input module provides a single channel of
voltage output. Signal filtering is accomplished with a five-pole filter which is
optimized for step response. An anti-aliasing pole is located on the field side of
the isolation barrier, and the other four poles are on the system side. After the
initial field-side filtering, the input signal is chopped by a proprietary chopper
circuit. Isolation is provided by transformer coupling, again using a proprietary
technique to suppress transmission of common mode spikes or surges.
Transducer excitation is provided from the module by a stable 10V source. This
source is fully isolated, allowing the amplifier inputs to operate over the full range
of the excitation voltage. This feature enables the module to be interfaced to a wide
variety of sensors requiring exctitation.
Module output is either voltage or current. For current output models a dedicated
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal
4 (-OUT). The system-side load may be either floating or grounded.
Special input circuits provide signal input and excitation protection against
accidental connection of power-line voltages up to 240VAC and against transient
events as defined by ANSI/IEEE C37.90.1. Protection circuits are also present
on the signal output and power input terminals to guard against transient events
and power reversal. Signal and power lines are secured to the module using
screw terminals which are in pluggable terminal blocks for ease of system
assembly and reconfiguration.
however, zero and span settings are adjustable up to ±5% to accommodate
situations where fine-tuning is desired. The adjustments are made using
potentiometers located under the front panel label and are non-interactive for ease
of use.
Features
 Interfaces to Transducers and Other Devices
Requiring a Stable, Isolated DC Supply
 Industry Standard Output of Either 0-10V,
±10V, 0-20mA, or 4-20mA
 1500Vrms Transformer Isolation
 ANSI/IEEE C37.90.1 Transient Protection
 Input Protected to 240VAC Continuous
 True 3-Way Isolation
 Wide Range of Supply Voltage
 100dB CMR
 Fully Isolated Excitation Supply
 ±0.03% Accuracy
 ±0.01% Linearity
 Easily Mounts on Standard DIN Rail
 C-UL-US Listed
 CE and ATEX Compliant
DSCA
Figure 1: DSCA43 Block Diagram
150
For information call 800-444-7644
High Performance Signal Conditioners
DSCA
Specifications
Module
Input Range ±1V to ±10V
Input Bias Current ±0.05nA
Input Resistance
Normal >500k Power Off >500k Overload >500k
Signal Input Protection
Continuous 240Vrms max
Transient ANSI/IEEE C37.90.1
Excitation
Output Voltage (-EXC to +EXC) 10V ± 0.03%
Output Current 40mA maximum
Load Regulation ±5ppm/mA
Stability ±15ppm/°C
Protection
Continuous 240Vrms max
Transient ANSI/IEEE C37.90.1
Output Range See Ordering Information
Load Resistance (I
Current Limit 8mA (V
Output Protection
Short to Ground Continuous
Transient ANSI/IEEE C37.90.1
CMV, Input to Output, Input to Power
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1
CMV, Output to Power
Continuous 50VDC max
CMR (50Hz or 60Hz) 100dB
Accuracy
Nonlinearity ±0.01% Span
Adjustability ±5% Zero and Span
Stability
Output Noise, 100kHz Bandwidth 750µVrms
Bandwidth, 3dB 3kHz
NMR 100dB/Decade Above 3kHz
Response Time, 90% Span 170µs
Power Supply
Environmental
Emissions EN61000-6-4 ISM, Group 1
Immunity EN61000-6-2 ISM, Group 1
Mechanical Dimensions 2.95" x 0.89" x 4.13"
Mounting DIN EN 50022 -35x7.5
NOTES:
(1) Includes nonlinearity, hysteresis and repeatability.
(1)
Input Offset ±5µV/°C
Output Offset ±6ppm/°C (V
Gain ±55ppm/°C
Voltage 19 to 29VDC
Current 60mA (V
Sensitivity +0.0002%/%
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Operating Temp. Range 40°C to +80°C
ATEX Group II, Category 3 20°C to +40°C
Storage Temp. Range 40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Radiated, Conducted Class A
R F Performance A ±0.05% Span Error
ESD, EFT, Surge, Voltage Dips Performance B
(h)(w)(d) (75mm x 22.5mm x 105mm)
Typical at TA=+25°C and +24V supply voltage
DSCA43
) 600 max
OUT
OUT
±0.03% Span
OUT
OUT
or -35x15 rail
), 30mA (I
), ±20ppm/°C (I
), 80mA (I
OUT
OUT
Ordering Information
Model Input Range Output Range
DSCA43-01 -1V to +1V 1
DSCA43-02 -2V to +2V 1
DSCA43-03 -3V to +3V 1
DSCA43-04 -4V to +4V 1
DSCA43-05 -5V to +5V 1
DSCA43-06 -6V to +6V 1
DSCA43-07 -7V to +7V 1
DSCA43-08 -8V to +8V 1
DSCA43-09 -9V to +9V 1
DSCA43-10 -10V to +10V 1
DSCA43-11 -1V to +1V 2, 3, 4
DSCA43-12 -2V to +2V 2, 3, 4
DSCA43-13 -3V to +3V 2, 3, 4
DSCA43-14 -4V to +4V 2, 3, 4
DSCA43-15 -5V to +5V 2, 3, 4
DSCA43-16 -6V to +6V 2, 3, 4
)
DSCA43-17 -7V to +7V 2, 3, 4
DSCA43-18 -8V to +8V 2, 3, 4
DSCA43-19 -9V to +9V 2, 3, 4
DSCA43-20 -10V to +10V 2, 3, 4


Output Ranges Available
Output Range Part No. Suffix Example
1.-10V to +10V NONE DSCA43-01
2. 0V to +10V NONE DSCA43-04
3. 4 to 20mA C DSCA43-04C
4. 0 to 20mA E DSCA43-04E
)
OUT
)
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
DSCA
Visit our website www.dataforth.com
151