Impulse DSCA40, DSCA41 User Manual

High Performance Signal Conditioners
DSCA40/41
Analog Voltage Input Signal Conditioners, Wide Bandwidth
Description
Each DSCA40/41 voltage input module provides a single channel of analog
output. Signal filtering is accomplished with a five-pole filter. An anti-aliasing pole
is located on the field side of the isolation barrier, and the other four poles are
on the system side. After the initial field-side filtering, the input signal is chopped
by a proprietary chopper circuit. Isolation is provided by transformer coupling,
again using a proprietary technique to suppress transmission of common mode
spikes or surges.
Module output is either voltage or current. For current output models a dedicated
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal
4 (-OUT). The system-side load may be either floating or grounded.
Special input circuits provide protection against accidental connection of power-
line voltages up to 240VAC and against transient events as defined by ANSI/
IEEE C37.90.1. Protection circuits are also present on the signal output and
power input terminals to guard against transient events and power reversal.
Signal and power lines are secured to the module using screw terminals which
are in pluggable terminal blocks for ease of system assembly and reconfiguration.
The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±5% to accommodate
situations where fine-tuning is desired. The adjustments are made using
potentiometers located under the front panel label and are non-interactive for
ease of use.
Features
 Accepts Millivolt and Voltage Level Signals
 Industry Standard Output of either 0-10V,
 1500Vrms Transformer Isolation
 ANSI/IEEE C37.90.1 Transient Protection
 Input Protected to 240VAC Continuous
 True 3-Way Isolation
 Wide Range of Supply Voltage
 100dB CMR
 3 kHz Signal Bandwidth
 ±0.03% Accuracy
 ±0.01% Linearity
 Easily Mounts on Standard DIN Rail
 C-UL-US Listed
 CE and ATEX Compliant
DSCA
±10V, 0-20mA, or 4-20mA
Figure 1: DSCA40/41 Block Diagram
146
For information call 800-444-7644
High Performance Signal Conditioners
DSCA
Specifications
Typical at TA=+25°C and +24V supply voltage
Model DSCA40 DSCA41
Input Range +10mV to +100mV ±1V to ±40V
Input Bias Current ±0.5nA ±0.05nA
Input Resistance
Normal 50M 500kΩ min Power Off 65k 500kΩ min Overload 65k 500kΩ min
Input Protection
Continuous 240Vrms max *
Transient ANSI/IEEE C37.90.1 *
Output Range See Ordering Information
Load Resistance (I
Current Limit 8mA (V
Output Protection
Short to Ground Continuous *
Transient ANSI/IEEE C37.90.1 *
CMV, Input to Output, Input to Power
Continuous 1500Vrms max *
Transient ANSI/IEEE C37.90.1 *
CMV, Output to Power
Continuous 50VDC max *
CMR (50Hz or 60Hz) 100dB *
(1)
Accuracy
Nonlinearity ±0.01% Span *
Adjustability ±5% Zero and Span *
Stability
Input Offset ±0.5µV/°C ±5µV/°C
Output Offset ±6ppm/°C (V
Zero Suppression ±50ppm(Vz)
Gain ±35ppm/°C ±55ppm/°C
Output Noise, 100kHz Bandwidth 750µVrms (V
Bandwidth, 3dB 3kHz *
NMR 100dB/decade above 3kHz *
Response Time, 90% Span 170µs *
Power Supply
Voltage 15 to 30VDC *
Current 25mA (V
Sensitivity ±0.0001%/% *
Protection
Reverse Polarity Continuous *
Transient ANSI/IEEE C37.90.1 *
Environmental
Operating Temp. Range 40°C to +80°C *
ATEX Group II, Category 3 20°C to +40°C *
Storage Temp. Range 40°C to +80°C *
Relative Humidity 0 to 95% Noncondensing *
Emissions EN61000-6-4 ISM, Group 1 *
Radiated, Conducted Class A *
Immunity EN61000-6-2 ISM, Group 1 *
R F Performance A ±0.05% Span Error *
ESD, EFT, Surge, Voltage Dips Performance B *
Mechanical Dimensions 2.95" x 0.89" x 4.13" *
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 *
NOTES:
* Same specification as DSCA40.
(1) Includes nonlinearity, hysteresis and repeatability.
is the nominal input voltage that results in 0V or 0mA output.
(2) V
z
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.
) 600 max *
OUT
), 30mA (I
OUT
OUT
)
±0.03% Span *
), ±20ppm/°C (I
OUT
(2)
/°C *
), 3µArms (I
OUT
), 55mA (I
OUT
)*
OUT
)*
OUT
)*
OUT
or -35x15 rail
Ordering Information
Model Input Range Output Range
DSCA40-01 -10mV to +10mV 1
DSCA40-02 -50mV to +50mV 1
DSCA40-03 -100mV to +100mV 1
DSCA40-04 -10mV to +10mV 2, 3, 4
DSCA40-05 -50mV to +50mV 2, 3, 4
DSCA40-06 -100mV to +100mV 2, 3, 4
DSCA40-07 0 to +10mV 2, 3, 4
DSCA40-08 0 to 50mV 2, 3, 4
DSCA40-09 0 to +100mV 2, 3, 4
DSCA41-01 -1V to +1V 1
DSCA41-02 -5V to +5V 1
DSCA41-03 -10V to +10V 1
DSCA41-04 -1V to +1V 2, 3, 4
DSCA41-05 -5V to +5V 2, 3, 4
DSCA41-06 -10V to +10V 2, 3, 4
DSCA41-07 -20V to +20V 1
DSCA41-08 -20V to +20V 2, 3, 4
DSCA41-09 -40V to +40V 1
DSCA41-10 -40V to +40V 2, 3, 4
DSCA41-11 0 to +1V 2, 3, 4
DSCA41-12 0 to +5V 2, 3, 4
DSCA41-13 0 to +10V 2, 3, 4
DSCA41-14 0 to +20V 2, 3, 4
DSCA41-15 0 to +40V 2, 3, 4


Output Ranges Available
Output Range Part No. Suffix Example
1. -10V to +10V NONE DSCA40-01
2. 0V to +10V NONE DSCA40-04
3. 4 to 20mA C DSCA40-04C
4. 0 to 20mA E DSCA40-04E
DSCA
Visit our website www.dataforth.com
147