Impulse DSCA33 User Manual

DSCA33
Isolated True RMS Input Signal Conditioners
Description
Each DSCA33 True RMS input module provides a single channel of AC input
converted to standard process voltage or current output (Figure 1).
The field voltage or current input signal is processed through an AC coupled
pre-amplifier and RMS converter on the field side of the isolation barrier. The
converted dc signal is then filtered and chopped by a proprietary chopper
circuit and transferred across the transformer isolation barrier, suppressing
transmission of common mode spikes and surges. The computer side circuitry
reconstructs, filters and converts the signal to industry standard outputs.
Module output is either voltage or current. For current output models a
at terminal 4 (-OUT). The system-side load may be either floating or grounded.
Special input circuits provide protection against accidental connection of
power-line voltages up to 480VAC and against transient events as defined
by ANSI/IEEE C37.90.1. Protection circuits are also present on the signal
output and power input terminals to guard against transient events and power
reversal. Signal and power lines are secured to the module using screw
terminals which are pluggable terminal blocks for ease of system assembly and
reconfiguration.
DSCA33 modules have excellent stability over time and do not require
recalibration, however, both zero and span settings are adjustable to
accommodate situations where fine tuning is desired. The adjustments are
made using potentiometers located under the front panel label and are
non-interactive for ease of use.
High Performance Signal Conditioners
Features
 Interfaces RMS Voltage (0  300V) or
RMS Current (0  5A)
 Designed for Standard Operation with
Frequencies of 45Hz to 1000Hz
(Extended Range Operation to 20kHz)
 Compatible with Standard Current and
Potential Transformers
 Industry Standard Output of either 0-1mA,
0-20mA, 4-20mA, 0-5V, or 0-10VDC
 ±0.25% Factory Calibrated Accuracy
(Accuracy Class 0.2)
 ±5% Adjustable Zero and Span
 1500Vrms Transformer Isolation
 Input Overload Protected to 480V
(Peak AC & DC) or 10A RMS Continuous
 ANSI/IEEE C37.90.1 Transient Protection
 Easily Mounts on Standard DIN Rail
 C-UL-US Listed
 CE and ATEX Compliant
DSCA
Figure 1: DSCA33 Block Diagram
134
* Current Input Models only
** Add jumpers for Current Input Modules
(provided with DSCA33-06, -07)
For information call 800-444-7644
High Performance Signal Conditioners
DSCA
Specifications
Module
Input
Signal Range 100mV to 300Vrms, 0 to 5Arms
Standard Frequency Range 45Hz to 1000Hz
Extended Frequency Range 1kHz to 20kHz
Impedance 1 M ±1% // <100pF (-01 thru -05), 0.10Ω (-06), 0.025 (-07)
Coupling AC
Protection
Continuous (-01 thru -05) 480V peak AC & DC max
Continuous (-06 thru -07) 10 Arms max
Transient (-01 thru -05) ANSI/IEEE C37.90.1
Transient (-06 thru -07) See note 1
Output
Signal Range See Ordering Information
Adjustability ±5% Zero & Span
Load Resistance 10k max. (0-1mA models), 600 max. (0/4-20mA models)
Current Limit 1.4mA (0-1mA models), 30mA (0/4-20mA models),
Protection
Short to Ground Continuous
Transient ANSI/IEEE C37.90.1
Ripple and Noise <0.025% Span rms
(2) (3)
Accuracy
Sinusoid
50/60Hz ±0.25% Span
45Hz-1kHz ±0.25% Reading Additional Error
1kHz-20kHz ±0.75% Reading Additional Error
Non-Sinusoid
Crest Factor = 1 to 2 ±0.05% Reading Additional Error
Crest Factor = 2 to 3 ±0.15% Reading Additional Error
Crest Factor = 3 to 4 ±0.30% Reading Additional Error
Crest Factor = 4 to 5 ±0.40% Reading Additional Error
Vs. Temperature ±100ppm/°C
Isolation (Common Mode)
Input to Output, Input to Power
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1
Output to Power
Continuous 50VDC max
Response Time (0 to 99%) <400ms
CMR (50 or 60Hz) 100dB
Power Supply
Voltage 19 to 29VDC
Current 60mA (V
Sensitivity ±0.0002%/%
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temp. Range -40°C to +80°C
ATEX Group II, Category 3 -20°C to +40°C
Storage Temp. Range -40°C to +80°C
Relative Humidity 0 to 95% noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
R F Performance A ±0.83% Span Error
ESD, EFT, Surge, Voltage Dips Performance B
Mechanical Dimensions (h)(w)(d) 2.95" x 0.89" x 4.13" (75mm x 22.5mm x 105mm)
Mounting DIN EN50022-35x7.5 or -35x15 rail
NOTES:
(1) For 1 to 25 seconds the max allowable transient current rating is 2500 / (event time). For less than 1 second, ANSI/IEEE C37.90.1 applies with a 0.05 load. For greater than 25 seconds, the 10A max continuous rating applies.
(2) For 10-100% rated span. Add 0.25% accuracy error (-02 thru -07), or 1.00% accuracy error (-01), for 0-10% Span measurements.
Accuracy includes nonlinearity, hysteresis and repeatability but not source or external shunt inaccuracy (if used).
(3) At standard 60Hz factory calibration. Consult factory for calibration at other frequencies.
Typical at TA=+25°C and +24V supply voltage
8mA (0-5/10V models)
DSCA33
), 80mA (I
OUT
OUT
)
Ordering Information
Model Input (rms)Output (dc)
DSCA33-01 0-100mV 2, 3, 4, 5, 6
DSCA33-02 0-1V 2, 3, 4, 5, 6
DSCA33-03 0-10V 2, 3, 4, 5, 6
DSCA33-04 0-150V 2, 3, 4, 5, 6
DSCA33-05 0-300V 2, 3, 4, 5, 6
DSCA33-06 0-1A 2, 3, 4, 5, 6
DSCA33-07 0-5A 2, 3, 4, 5, 6
Modules can be ordered with other input/output ranges. Consult
factory for ordering details and specifications


Output Ranges Available
Output Range Part No. Suffix Example
2. 0V to +10V NONE DSCA33-01
3. 4 to 20mA C DSCA33-01C
4. 0 to 20mA E DSCA33-01E
5. 0V to +5V A DSCA33-01A
6. 0 to 1mA B DSCA33-01B
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B,
C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair
Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless
Power Has Been Switched Off or The Area is Known to be Non-Hazardous.
DSCA
Visit our website www.dataforth.com
135