Impulse DSCA32 User Manual

DSCA32
Analog Current Input Signal Conditioners
Description
Each DSCA32 current input module provides a single channel of analog input
Signal filtering is accomplished with a five-pole filter which which is optimized for
step response. An anti-aliasing pole is located on the field side of the isolation
barrier, and the other four poles are on the system side. After the initial field-side
filtering, the input signal is chopped by a proprietary chopper circuit. Isolation
is provided by transformer coupling, again using a proprietary technique to
suppress transmission of common mode spikes or surges.
Module output is either voltage or current. For current output models a dedicated
loop supply is provided at terminal 3 (+OUT) with loop return located at terminal
4 (-OUT). The system-side load may be either floating or grounded.
Special input circuits provide protection against accidental connection of
power-line voltages up to 240VAC and against transient events as defined by
ANSI/IEEE C37.90.1. Protection circuits are also present on the signal output
and power input terminals to guard against transient events and power reversal.
Signal and power lines are secured to the module using screw terminals which
are in pluggable terminal blocks for ease of system assembly and reconfiguration.
The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±5% to accommodate
situations where fine-tuning is desired. The adjustments are made using
potentiometers located under the front panel label and are non-interactive for
ease of use.
High Performance Signal Conditioners
Features
 Accepts Milliamp Level Signals
 Industry Standard Output of either 0 to 10V,
0 to 20mA, or 4 to 20mA
 1500Vrms Transformer Isolation
 ANSI/IEEE C37.90.1 Transient Protection
 Input Protected to 240VAC Continuous
 True 3-Way Isolation
 Wide Range of Supply Voltage
 105dB CMR
 5 Poles of Filtering
 ±0.03% Accuracy
 ±0.01% Linearity
 Easily Mounts on Standard DIN Rail
 C-UL-US Listed
 CE and ATEX Compliant
DSCA
Figure 1: DSCA32 Block Diagram
132
For information call 800-444-7644
High Performance Signal Conditioners
DSCA
Specifications
Module
Typical at T
=+25°C and +24V supply voltage
A
DSCA32
Input Range 0-20mA or 4-20mA
Input Resistance
Normal <100 Power Off <100 Overload 65k
Input Protection
Continuous 240Vrms max
Transient ANSI/IEEE C37.90.1
Output Range See Ordering Information
Load Resistance (I
Current Limit 8mA (V
Output Protection
) 600 max
OUT
OUT
), 30mA (I
Short to Ground Continuous
Transient ANSI/IEEE C37.90.1
CMV, Input to Output, Input to Power
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1
CMV, Output to Power
Continuous 50VDC max
CMR (50Hz or 60Hz) 105dB
(1)
Accuracy
±0.03% Span
Nonlinearity ±0.01% Span
Adjustability ±5% Zero and Span
Stability
Offset ±6ppm/°C (V
Gain ±40ppm/°C
Output Noise, 100kHz Bandwidth 300µVrms (V
), ±20ppm/°C (I
OUT
), 1.2µArms (I
OUT
Bandwidth, 3dB 100Hz
NMR (-3dB at 100Hz) 100dB/decade Above 100Hz
Response Time, 90% Span 5m s
Power Supply
Voltage 15 to 30VDC
Current 25mA (V
Sensitivity ±0.0001%/%
), 55mA (I
OUT
Protection
Reverse Polarity Continuous
Transient ANSI/IEEE C37.90.1
Environmental
Operating Temp. Range 40°C to +80°C
ATEX Group II, Category 3 20°C to +40°C
Storage Temp. Range 40°C to +80°C
Relative Humidity 0 to 95% Noncondensing
Emissions EN61000-6-4 ISM, Group 1
Radiated, Conducted Class A
Immunity EN61000-6-2 ISM, Group 1
R F Performance A ±0.05% Span Error
ESD, EFT, Surge, Voltage Dips Performance B
Mechanical Dimensions 2.95" x 0.89" x 4.13"
(h)(w)(d) (75mm x 22.5mm x 105mm)
Mounting DIN EN 50022 -35x7.5 or -35x15 rail
NOTES:
(1) Includes nonlinearity, hysteresis and repeatability.
OUT
OUT
Ordering Information
Model Input Range Output Range
DSCA32-01 4mA to 20mA 2, 3, 4
DSCA32-02 0mA to 20mA 2, 3, 4
DSCA32-03 ±20mA 1
DSCA32-04 ±20mA 2, 3, 4


Output Ranges Available
)
Output Range Part No. Suffix Example
1. -10V to +10V NONE DSCA32-03
2. 0V to +10V NONE DSCA32-01
3. 4 to 20mA C DSCA32-01C
4. 0 to 20mA E DSCA32-01E
)
OUT
)
OUT
DSCA
)
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.