Imperial Tools 2601 User Manual

START
COMPRESSOR
RUN
COMMON
CHASSIS GROUND
GREEN
RED
Starting Capacitor
WHITE
BLACK
YELLOW
YELLOW
POWER
QUIK- START
Fuse
R
Start
U N
Off
CAPACITOR START COMPRESSORS
Follow Split Phase procedure except for the two YELLOW lead con­nections. These leads are connected to the starting capacitor as shown-above. The capacitor can be any value and voltage equal to or greater than the original supplied with the compressor. A 200 MFD 220V capacitor will start most of the compressors in use.
ACCESSORIES
LIMITED WARRANTY
All products sold are warranted against defects in workmanship or materials under normal use for one year. Manufacturer assumes no liability on the actual use of this equipment. Safety responsibility lies with the user.
In return for shipping the merchandise PREPAID to factory service location, Thermal Engineering Company will make a good faith effort for prompt disposition regarding any product which proves to be de­fective whether in or out of warranty. A complete description of the problem should be included. If product is damaged in transit to you, file a claim with the carrier.
INSTRUCTIONS
FOR MODEL
2601 QUIK-START
HERMETIC
COMPRESSOR
STARTER
Model 2601 Quik-Start will start all single phase compressors up to 5HP—110, 220, or 277 VAC. Read these instructions carefully before using the Quik-Start.
This device is intended for use only by qualified air conditioning and refrigeration service technicians. Use extreme caution when using this unit. Make sure the system being tested is disconnected from power before connecting the Quik-Start. Do not use fuses rated higher than 30A. Read the safety precautions carefully before using.
Before using the Quik-Start, check the compressor for grounded windings. Connect an ohmmeter from the COMMON terminal to the compressor case. If the ohmmeter shows any reading less than infinity (open), the compressor is defective and the Quik-Start should not be used. Compressor amperage draw can be measured by placing a clamp-on ammeter around the WHITE Quik-Start lead.
Revised 02/05/07
For repair return to your local distributor or Thermal Engineering.
Thermal Engineering Company
A division of Airserco Manufacturing Company
7555 Tyler Blvd.—Unit 1
Mentor, OH 44060
USA
www.thermalengineeringcompany.com
Thermal Engineering Company
A division of Airserco Manufacturing Company
7555 Tyler Blvd.—Unit 1
Mentor, OH 44060
USA
www.thermalengineeringcompany.com
USA
www.thermalengineeringcompany.com
Mentor, OH 44060
7555 Tyler Blvd.—Unit 1
A division of Airserco Manufacturing Company
Thermal Engineering Company
compressor does not start, turn STARTING switch to OFF. will remain in the RUN position until manually turned to OFF. If
5. Release STARTING switch when compressor starts. The switch
4. Push STARTING switch to START position and hold.
compressors use adaptor leads from 2605 kit.
3. Plug in the Quik-Start power cord to grounded outlet. For 220V connected together.
www.thermalengineeringcompany.com
USA
Mentor, OH 44060
7555 Tyler Blvd.—Unit 1
A division of Airserco Manufacturing Company
Thermal Engineering Company
3. The remaining unidentified terminal is RUN. remaining terminal is START.
2. Find the two terminals with the lowest resistance. The The remaining terminal is COMMON.
1. Find the two terminals that give the highest resistance reading.
set to OHMS X 1 and measuring the resistance between terminals. The compressor terminals can be identified by using an ohmmeter
COMPRESSOR TERMINAL IDENTIFICATION
2. Connect the leads as shown above. The two YELLOW leads are
1. Set Quik-Start STARTING switch to the OFF position.
SPLIT PHASE COMPRESSORS
CORD POWER
altering its performance. terminals will automatically discharge the capacitor without Soldering a 15000 ohm 1 watt resistor across the capacitor the capacitor terminals with a screw driver or test lead. Start leads after testing, discharge capacitors by shorting across
7. Before removing the system wiring and before removing Quik-
Fuse
Off
N U
Start
R
YELLOW
YELLOW
QUIK- START
GREEN
WHITE
Capacitor Starting
RED
BLACK
CHASSIS GROUND
COMMON
RUN
START
COMPRESSOR
Lead Kit, properly ground the green lead at the 220V source.
6. When using the 220V adaptor leads from the Model 2605 Test
windings are grounded.
5. Do not attempt to use the Quik-Start if the compressor
4.. Do not touch the compressor case when using the Quik- Start.
components before connecting the Quik-Start to power.
3. Make all required connections to the compressor and
the Quik-Start.
2. Disconnect the system being tested from power before using
could endanger the operator and will void the warranty.
1. Do not use fuses rated higher than 30A. The use of larger fuses
Safety Precautions