Thank you for choosing Impecca air conditioners, please read this owner’s manual carefully
before operation and keep it for future reference.
Impecca reserves the right to interpret this manual which will be subject to any change due
to product improvement without further notice.
v. 1
.1
Page 2
Page 3
Preface
Flex + Series adopt the advanced manufacturing technology and takes the environmental-
friendly R410A as refrigerant, which is a green product in the 21st century. Please carefully read
the manual before installation and operation.
1
)Flex + Series systems conform to design standard ARI 210240-2008.
2)To ensure safety when operating this system, please strictly follow the instructions in this
manual.
3)Make sure that the manual is kept by the operators or serviceman.
4)The refrigerant pipes and accessories must be designed exclusively for R410A.
5)The total capacity of the indoor units which runs at the same time cannot exceed the capacity of
the outdoor units; otherwise, the cooling (heating) effect of each indoor unit would be lower
than the nominal capacity.
6)In case of malfunction, please examine the following items and contact our appointed service
centers as soon as possible.
Nameplate (model, cooling capacity, product code, ex-factory date).
Malfunction status (detail description of conditions before and after malfunction occurs).
7)It is a normal phenomenon that the fan of indoor unit will still run for 20~70 seconds after the
indoor unit receives the “stop” signal so as to make full use of the waste heat.
8)When the work mode of the indoors is conflict with the modes of outdoor units, it will be
indicated on the display of the wired controller in five seconds and then the indoor unit will
stop. In this case, please harmonize their work modes: the cooling mode is compatible with the
dry mode.
9)If the supply power fails when the unit is running, then the indoor unit will send the “start”
signal to the outdoor unit three minutes later after the power recovery.
10) The power cable and transmission line must not be twisted together, but instead of separated
with an interval of at least 2cm; otherwise it may be result in communication problem.
11) This appliance is not intended for use by persons (including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance by a person responsible for
their safety. Children should be supervised to ensure that they do not play with the appliance.
12) All graphics and information in this manual are only for reference. Manufacturer reserves the
right for changes in terms of sales or production at any time and without prior notice.
This product must not be disposed together with the domestic waste. This product has
to be disposed at an appointed place for recycling of electrical and electronic appliances.
Thank you for purchasing Impecca air conditioners. Before using, please read
this manual carefully and keep it properly for further reference.
13.3 Check before the Seasonal Use ................................................................................... 28
13.4 Maintenance after Seasonal Use ................................................................................. 28
14 After-sales Service .................................................................................................................. 28
II
Page 7
1 Safety Precautions
Flex + Series
WARNING
CAUTION
NOTICE
This is t
hazards. Obey all safety messages that follow this symbol to avoid possible injury or
death.
This mark indicates procedures which, if improperly performed, might lead to the
death or serious injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result
in personal harm to the user, or damage to property.
NOTICE is used to address practices not related to personal injury.
he safety alert symbol. It is used to alert you to potential personal injury
WARNING
1)Instructions for installation and use of this product are provided by the manufacturer.
2)Installation must be performed in accordance with the requirements of NEC and CEC by appointed
personnel only.
3)The installation should be left to the appointed service center and according to the instructions given in the
manual. Improper installation may cause fall down, water leakage, electric shock or fire etc.
4)For operating the air conditioner pleasantly, please install it as outlined in this installation manual.
5)The power supply must adopt the special circuit with air switch protection and assure it has enough capacity
6)Connect the indoor unit, BU module and outdoor unit with the room air conditioner piping and cord
available from our standard parts. This installation manual describes the correct connections using the
installation set available from our standard parts.
7)Before installation, check the parameter of power cord and make sure that it complies with the power
supply requirement on the nameplate. Make sure the power supply is safe.
8)This air conditioner must be properly grounded through the receptacle to avoid electric shock. The ground
wire shouldn’t be connected with gas pipe, water pipe, lightning arrester or telephone line.
9)If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact
with a flame, it produces toxic gas.
10) Do not power on until all installation work is complete.
11) During installation, make sure that the refrigerant pipe is attached firmly before you start up the compressor.
Do not operate the compressor under the condition of refrigerant piping not attached properly with valve
open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
12) When installing and relocating the air conditioner, do not mix gases except the specified refrigerant
(R410A) to enter the refrigerant cycle. If air or other gas enters the refrigerant cycle, the pressure inside the
cycle will rise to an abnormally high value and cause breakage, injury, etc.
13) This appliance is not intended for use by persons (including children) with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person responsible for their safety. Children should be
supervised to ensure that they do not play with the appliance.
14) Never cut off or damage power cables and transmission wires. If the power cable or transmission line were
damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to
avoid a hazard.
15) After the power cord is connected, please install the cover of electric box to avoid danger.
1
Page 8
Flex + Series
16) When installing or relocating the unit, please contact the appointed service center for the repair or
relocation. Meanwhile the specialized parts and accessories must be used. Otherwise, it may result in water
leakage, electric shock or fire hazard.
17) Diameter of power cord must be large enough. Damaged power cord or connecting wire must be replaced
by specialized electric cable.
18) The power wire and transmission line must be more than one meter away from televisions or radios which
can emit electromagnetic waves to prevent image interference or noise. Otherwise, the unit maybe not work
19) Nitrogen must be charged according to technical requirements.
20) For units with wired controllers, do not connect power supply until the wired controller is well installed.
Otherwise, the wired controller cannot be used.
21) When installation is finished, please check and make sure the drain pipe, pipeline and electric wire are all
well connected so as to avoid water leakage, refrigerant leakage, electric shock and fire hazard.
22) Never extend fingers or objects into air outlet or return air grille.
23) Please keep the room well-ventilated and it could avoid oxygen deficit.
24) Never start or stop the air conditioner by inserting or removing the power cord.
25) Before startup of the compressor, please turn on the main power switch of the unit for more than 8 hours
and it makes sure that the heater belt of the compressor has been energized for at least eight hours! Once the
compressor is started, it must be guaranteed that it works continuously for at least 30 minutes, otherwise it
would be damaged!
26) Never operate the unit with wet hands. Otherwise, it may cause electric shock.
27) Before cleaning and repairing, it is necessary to stop working and turn off the power supply. Otherwise, it
may cause electric shock or damage.
28) Do not spray water on the air conditioner or it will cause malfunction or electric shock.
29) The air conditioner is not support to install in the circumstances as the following that where there is full of
mist of oil, damp or corrosive gas, flammable gases, the acidic or alkaline vapor and the ocean.
30) Volatile liquid like thinner or gasoline will damage the appearance of air conditioner. (Please use soft dry
cloth and wet cloth with mild detergent to clean unit’s appearance.)
31) Never standing or place objects on outdoor unit. Person or objects falling from the unit may cause injury.
32) If abnormal condition occurs (e.g. unpleasant smell), please turn off the unit at once and disconnect power
supply. Then contact appointed service center. If the air conditioner continues to operate despite of
abnormal condition, it may be damaged and cause electric shock or fire hazard.
33) The drain pipe should be installed as instructed in the manual to guarantee the proper drainage; meanwhile
it should be insulated to prevent condensing; otherwise the improper installation would cause water leakage
and then wet the household wares in the room.
34) Don't attempt to repair the air conditioner by yourself. The improper repair will lead to electric shock or
fire, please contact the appointed service center and ask professional technicians to repair it.
35) Please take notice of the installation foundation of the unit after long use, if it is damaged, it may lead to the
fall of the unit and cause the injury.
36) Be sure to shut off the power supply when you do not use the air conditioner for a long time. Otherwise, the
dusts may accumulate in it, which may cause overheating or fire hazards.
37) Impecca is not responsible for any personal injury or property loss caused by improper installation,
improper debugging, unnecessary repair or not following the instruction
s of this manual.
2
Page 9
Flex + Series
2 Attention for Installation
2.1 Precautions for R410A
It is very strict that the refrigerant pipes should be clean and dry.
It does not support to let a lot of refrigerant go into the ambient atmosphere, because it will
2.2 Precaution for Installation
The unit is so heavy that it is more than 110kg, so more than two persons will be needed to
When remove the units, please place the hands on the corner and take care not to hurt the hands
It is very likely to dispose the waste to the garbage bin after the installation.
e R410A is a mixed refrigerant, when adding the refrigerant to the unit, it must be
Th
in its liquid state. If the refrigerant is in gas state, the composition has been changed and the
capability of the unit will decrease.
When the refrig
frostbite.
strengthen the green house effect. Otherwise, it will produce toxic gas when the refrigerant
contacts with the fire.
remove the unit. The package cannot bear it, so do not grasping it.
by the fins.
erant leaks out, please do not touch the leakage. Otherwise, it will result in
2.3 Precaution for Operation Test
In order to protect the compressor from vibrating during transportation and 2 metal gaskets are
used. They must be removed prior to commissioning and tied back the nut firmly; otherwise the unit
might not be operated well.
2.4 Accessories
For the accessories of the air conditioner, please look out the Packing List in the package.
3
Page 10
Flex + Series
3 Product Introduction
Impecca Flex + Series adopts inverter compressor technology. According to change
The
displacement of compressor, stepless capacity regulation within range of 10%~100% can be
realized. Various product lineups are provided with capacity range from 14kW to 16kW, which
can be widely used in residential house, business office, hotel and where especially applicable
to the place with variable load change. Impecca air conditioner is absolutely your best choice.
3.1 Names of Main Parts
NO. ①②③④⑤
Name Fan motor Axial flow fan bladeElectrical box
Fig. 1
Gas side stop
valve
Liquid side stop
3.2 Combinations for Outdoor and Indoor Units
Table 1
Sorts GWHD(56S)ND3CO
No. of indoor units to be
connected
No. of BU modules to be
connected
Total capacity of indoor units to
be connected(Btu/h)
Min2
Max9
Min1
Max3
Min28000
Max81000
valve
Page 11
Flex + Series
Parts and Components of Unit
3.3
For the Flex + Series, one outdoor unit is able to drive up to three BU modules and nine
indoor units which include cassette type, duct type, wall mounted type, floor ceiling type and
console type. The outdoor unit will run as long as any one indoor unit receives the running
command, and all indoor units stop once the outdoor unit is turned off.
Power supply wire for outdoor
unit and BU module(3 wires)
Connection pipe
Transmission line(2 wires)
Power supply wire for
indoor unit(4 wires)
BU 3
Indoor unit
Duct type
Wall mounted
type
Floor ceiling
type
Console type
Outdoor unit
Ground
The 2nd
branch
The 1st
branch
Power
(60Hz, 208/230V)
Ground
Power
(60Hz, 208/230V)
BU 2
Ground
Power
(60Hz, 208/230V)
BU 1
Ground
Power
(60Hz, 208/230V)
Fig. 2
Wall mounted
type
Cassette type
Cassette type
Duct type
Wall mounted
type
3.4 Working Temperature Range
Maximum cooling48℃(118℉)
Minimum cooling-18℃(0℉)
Maximum heating24℃(75℉)
Minimum heating-20℃(-4℉)
Table 2
(BD :erutarepmet edistuO stroS℃/℉)
5
Page 12
Flex + Series
4 Selection of Installation Location and Precautions
WARNING
1)The installation of the air conditioner must be in accordance with the national and local laws and
regulations.
2)The quality of the installation will affect the capability of air conditioner directly. The installation
should be left to the appointed service center. Please contact your dealer after purchasing this machine.
Professional installation workers will provide installation and test services according to the installation
manual.
3)The air conditioner should not install in this place where the small animals exist, because they may
cause malfunctions, smoke or fire. Please keep the area around the unit clean.
4.1 Selection of Installation Location
WARNING
1)The outdoor unit must be installed on a firm and solid support which can withstand the weight,
meanwhile the mounting surface must be horizontal plane. Otherwise, the unit would fall down and
cause injury or death.
2)The location must be out of children’s reach, please keep the unit away from children.
3)During installation, if the outdoor unit has to be exposed to strong wind, it must be fixed securely.
4)There is enough space for the installation and maintenance. Meanwhile, there is not any obstacle near
the air inlet and outlet of the indoor and outdoor units.
5)The place should be well-ventilated, so the machine can absorb and discharge sufficient air.
6)Avoid place the outdoor unit under the windows or between the constructions, hence to prevent normal
operating noise from entering the room.
7)When strong winds of 5 m/sec or more exist in the place of the installation, the outlet of the unit cannot
face the wind. If the wind blows against the outdoor unit's air outlet, it will cause deterioration of the
operational capacity and maybe break the fan.
8)Do not install in the place where there is heat source, flammable or explosive gas, a place subject to
severe dust, salty fog and polluted air.
9)Installation at the following places might lead to the air conditioner malfunction, such as where is full of
machine oil, saline-sodic soil near the sea, sulphide fog, high frequency facilities or special conditions.
If it is unavoidable, please contact the appointed service center.
NOTICE
1)It is better that do not install the unit where it will be exposed to direct sunlight. (If necessary, please
install a blind that does not interfere with the air flow.)
2)The unit should be free from getting dirty or getting wet by rain as much as possible
3)Outdoor unit shall be installed close to the indoor unit, hence to minimize the length and bends of
cooling pipe.
4)Do not place animals and plants in the path of the air inlet and outlet of the units.
5)Make sure that the unit will not cause any operating vibration or noise after installation.
6
Page 13
4.2 Outline Dimension of Outdoor Unit
Flex + Series
3 (unit: mm/inch)
Fig.
4.3 Installation and Servicing Space
1)In case of installing only one unit
In case obstacles exist around the unit, the required installation space is in the Fig. 4.
2)In case of installing multiple units(2 units or more)
In case multiple rows of series installation, the required installation space is in the Fig. 5.
Fig. 4 (unit: mm) Fig. 5 (unit: mm)
7
Page 14
Flex + Series
5 Installation Instruction
1)Check the installation location and ensure it is strength and level, so that the unit will not cause
any operating vibration or noise after installation.
2)In accordance with the foundation drawing in the following figure, please drill 4 holes in the
installation location.
A
: The outlet side B: Bottom view (mm) C: Drain hole
Fig. 6
3)Fix the unit securely with the foundation bolts. You can get the M10 or M12 foundation bolts,
nuts and washers from the market.
Fig. 7
4)Rub
5)Screw the foundation bolts into the ground and it is better that its length is less than 20mm
ber or spring shock absorbers should be used during the installation of the outdoor unit to
meet the noise and vibration requirements.
(4/5inch) from the foundation face.
8
Page 15
6 Installation of Refrigerant Pipes
6.1 Allowable Length and Drop Height of Connecting Pipe
Flex + Series
Maximum
allowable
length
Maximum
allowable
length
Minimum
allowable
length
Fig. 8 (8 indoor units)
Table 3
The sorts The pipes Length(m/feet)
Total length between outdoor unit and BU
modules
Total length between indoor units and
BU
Between indoor unit and BU module 1A;1B;1C;2A;2B;2C;3A;3B ≤15(49)
Between indoor unit and the 1st branch
Between outdoor and indoor units H1 ≤30(99)
Between outdoor units and BU modules H2 ≤30(99)
Between BU and BU modules H3 ≤15(49)
Between indoor and indoor units H4 ≤15(49)
Between outdoor and the 1st branch L1 ≥5(16)
Between BU and the branch L3;L4;L5
L1+L2+L3+L4+L5 ≤55(181)
1A+1B+1C+2A+2B+2C+
3A+3B
L4+1B;L2+L5+2A;
L2+L3+3B
≤90(295)
≤40(131)
as possible as
short
NOTICE! BU module should be placed within the level between the outdoor unit and indoor
unit.
9
Page 16
Flex + Series
6.2 Dimension of Connecting Pipe
Sorts
Table 4
Gas Pipe
(mm/inch)
Liquid Pipe
(mm/inch)
Outdoor unit
Between outdoor unit and the
1st branch
Between the 1st and the 2nd
branch
ISMO-6021
The pipe L1 Φ19.05(3/4) Φ9.52(3/8)
The pipe L2 Φ15.9(5/8) Φ9.52(3/8)
Φ15.9(5/8) Φ9.52(3/8)
6.3 Connection of Branch Pipe
1)If two or three BU modules used, Y-type branch pipe of FQ01A/A will be chosen.
FQ01A/A (Liquid pipe) FQ01A/A (Gas pipe)
Fig. 9
2)Y-type branch pipe is equipped with auxiliary tubes to adjust the diameter of different pipes. If
the dimension of the pipe selected is different from the dimension of branch pipe joint, Cut the
copper tube in the middle with tube cutter and clear up burrs. Please do that as following figure.
Fig. 10
3)Y
-type branch pipe must be installed in vertical or horizontal direction. In the inlet of the branch
pipe, keep at least 500mm straight pipe.
Fig. 11
10
Page 17
Flex + Series
6.4 Connection of Refrigerant Pipes
CAUTION
1)Conform to the following principles during pipe connection: Outdoor unit shall be installed close to the
indoor unit, hence to minimize the length and bends of connection pipes; the height gap of outdoor unit
and indoor units should be as small as possible; the radius of curvature should be as large as possible.
2)The brazing operation must be strictly in accordance with the process requirements. Rosin joint or pin
hole is not allowed.
3)During the installation, do not damage the pipeline. The pipeline’s radius of bending must be over than
200mm(8inch). The pipes cannot repeatedly be bent or straightened. Otherwise it will get harden and
crack. Do not bend or straight the pipes for more than 3 times at the same position.
1)The process of flaring
①Using the tube cutter to cut the connecting pipe in the appropriate place and remove the burrs.
②Install the nut before the flaring operation.
③Check the flared portion, whether there is fractured or not.
Fig. 12
2)Precaution for elbow operation
① The elbow operation could be done by hands. Be careful and do not damage the pipe.
Fig. 13
② If the thermal insulation of the refrigerant pipe is not removed, please do not bend the pipe.
Otherwise, it maybe leads the pipe to crack. It is better to make an incision with a knife in the
thermal insulation and removes it. After elbow operation is finished, recover the thermal
insulation with binding band.
3)The process of install refrigerant pipes
① Remove the screw caps from the pipes.
② Align the flared end of copper tube with the center of pipe joint. Tighten the nuts by hands. (If
the flared end of copper tube and the center of pipe joint are not in coaxial, it is hard to tighten
the nuts by hands, please do not tighten it with spanners, because the screw thread may be
broken by force).
③ Tighten the flaring nuts with torque wrench until you hear a “click”. (The spanner and torque
11
Page 18
Flex + Series
wrench should be perpendicular to the refrigerant pipeline).
④ The following table for the torque required to tighten the nuts.
4)Additional refrigerant charge record for future maintenance
Table 8
Diameter(mm) Total length(m/feet)Additional refrigerant charge(kg/oz)
Φ6.35(1/4)
Φ9.52(3/8)
Total
6.8.2 Proced
ures for adding refrigerant
15
Page 22
Flex + Series
NO. 1 2 3 4 5
Name
NO. 6 7 8 9
Name Hi-knob Lo-knob R410A tank Scale
1)When the liquid and gas stop valves have not been opened, the system is under the vacuum:
①Refer to the left of the figure above; connect the R410A tank to the system.
②Turn on the R410A tank and the Hi-knob; charge the R410A refrigerant into the unit from the
liquid side stop valve. The Lo-knob should be closed completely.
③Turn off the R410A tank and the Hi-knob immediately, when the adding refrigerant is enough.
④Turn on the liquid and gas side stop valves in an anticlockwise direction slowly and completely.
2)If the pressure of the system is too high to charge refrigerant, you can do as follow.
①Turn on the liquid and gas side stop valves in an anticlockwise direction slowly and completely.
②Turn on the power of the air conditioner, and set cooling mode, running more than 0.5h when
outside temperature is higher than 15℃(59℉) DB.
a)Refer to the left of the figure above; connect the R410A tank to the system.
b)Turn on the R410A tank and the Lo-knob; charge the R410A refrigerant into the unit from
c)Turn off the R410A tank and the Lo-knob immediately, when adding refrigerant is enough.
③Turn on the power of the air conditioner, and set heating mode, running more than 0.5h when
outside temperature is lower than 15℃(59℉) DB.
a)Refer to the right of the figure above; connect the R410A tank to the system.
b)Turn on the R410A tank and the Hi-knob; charge the R410A refrigerant into the unit from
c)Turn off the R410A tank and the Hi-knob immediately, when adding refrigerant is enough.
Outdoor
unit
the gas side stop valve. The Hi-knob should be closed completely.
the service port. The Lo-knob should be closed completely.
Service port
Liquid side stop
valve
Fig. 19
Gas side stop
valve
Pressure-vacuum
gauge
CAUTION
1)Make sure that the liquid and gas side stop valves are opened completely after the installation.
2)Make sure that the length of liquid pipe is exactly.
3)Additional refrigerant charge must be measured exactly.
4)Make sure that the refrigerant which charge into the unit is in liquid state.
5)Please prevent the refrigerant leakage away from your body when remove the charging hose.
6)Please heat the refrigerant tank with hot water or hot air when the outside temperature is too low.
However, it must be forbidden to heat with fire directly, otherwise it may lead to explosion.
16
Page 23
7 Electrical Wiring Work
7.1 Wiring Connection
Flex + Series
NOTICE! The “L1”, “3” terminals are connected to the live wire, the “L2”,”N(1)” terminals
are connected to the neutral wire and the ”2” terminal is connected to the transmission line.
Fig. 20
7.2 Requirements of Power Circuit and Cable
Table 9
Phase and frequency 1Ph,60Hz
Voltage 208/230V
40A
2
2
2
Recommended cable of outdoor unit (Pieces × Sectional area)
Recommended cable of BU module
(Pieces × Sectional area)
Transmission line (Pieces × Sectional area)2×1.5 mm2
Recommended cable of indoor unit
(Pieces × Sectional area)
ISMO-6021
Capacity of the air switch
BU module 10A
3×6.0 mm
3×0.75 mm
4×0.75mm
NOTICE
1)The total length of the transmission line between the outdoor unit and the furthest BU module is not
more than 55m (180feet). Otherwise, the system cannot work possibility.
2)The specifications of the power cable and transmission line listed in the table above are determined
based on the maximum power (maximum amps) of the unit.
17
Page 24
Flex + Series
3)The specifications of the power cable listed in the table above are applied to the conduit-guarded
multi-wire copper cable (like, YJV copper cable, consisting of PE insulated wires and a PVC cable
jacket) used at 40℃(104℉) and resistible to 90℃(194℉), and shall be at least those of ordinary
polychloroprene sheathed cords. If the working condition changes, they should be modified according
to the related national standard.
4)The specifications of the air switch listed in the table above are applied to the breaker with the working
temperature at 40℃(104℉). If the working condition changes, they should be modified according to the
related national standard.
5)The length of the recommended power cable should be less than 15meters (49feet); otherwise, the
diameter of the power cable is not enough.
6)Mentioned power cable and transmission line length is just a reference value. It may be different
depending on the condition of installation, humidity or materials, etc.
7)An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be
connected in fixed wiring.
7.3 Ground Requirements
WARNING
1)The air conditioner is classified into the Class I appliances, so its ground ways must be reliable.
2)The ground wire must be fixed on the screw hole with the sign as the right figure.
3)The yellow-green wire of the air conditioner is the ground wire and must be fixed by the tapping screw.
And it cannot be used for other purpose or cut off. Otherwise, it will cause the hazard of electric shock.
4)The reliable ground terminal should be provided and the ground wire cannot be connected to any of the
following places: a. Water pipe; b. Coal gas pipe; c. Sewage pipe; d. Lightning rod
e. Telephone line f. Other unreliable places considered by a professional.
7.4 Precautions on the Electrical Wiring Work
WARNING
1)The electrical installation should be carried out by the professional as instructed by the local laws,
regulations and also this manual.
2)The ground connection should be reliable and the ground wire should be connected to the dedicated
device of the building by the professional.
3)Before starting work, the power must not be supplied to the unit.
4)The air switch coupled with the leakage current protection switch must be equipped in the circuits,
which is of enough capacity and of both magnetic and thermal tripping functions in case of the short
circuit and overload.
5)The electrical work should use a cable length enough to cover the entire distance with no connection. If
it is unavoidable, please make sure the connection should be reliable, the external forces will not act on
the wires and the joint is not bared. Otherwise it will cause electrical shock or fire etc.
6)The power cable with the rated voltage and exclusive circuit for the air conditioner should be used.
7)Do not pull the power cable by force after it is installed.
8)The diameter of the power cable should be large enough and once it is damaged, it must be replaced by
the dedicated one.
9)The multi-wire copper cable should be used for the power cable and the transmission line.
18
Page 25
Flex + Series
7.5 Precaution of Laying Wires
1)Use a wire stripper to strip off a length of the insulation layer at the end of the wires;
2)Loosen the screws on the terminal block of the air conditioner;
3)Press the ends of the cable tightly onto the round terminals corresponding to the size of the
screws.
4)Pass the screw through the round terminals and fix it onto the terminal block.
Fig. 21
7.6 Procedures for Electrical Wiring Work
1)Knock the holes in the plate of the chosen direction with the hammer.
2)Place the rubber ring on the knockout hole.
3)Let the power cable and transmission line go through the knockout hole.
4)Connect the power cable of the outdoor unit to the L1, L2 terminals with the sign of the XT1
and as well as the ground screw.
5)Connect the transmission line of the outdoor unit to the N(1), 2 terminals with the sign of the
XT2.
6)Fix the power cable and transmission line firmly by cable fixing clip. In order to protect the
power cable and transmission line from damage by the pipes or others, an interval of at least
2cm (3/4inch) away is essential.
7)Screw the coping plate, front side plate, right connection board, front connection board back.
8)Cover the through-holes with sealing materials to prevent the water, dust or small animals going
into the outdoor unit.
CAUTION
1)The transmission line and the power cable must be separated with an interval of at least 2cm (3/4inch);
otherwise it may be result in communication problem.
2)In order to protect the power cable and transmission line from damaging by the knockout hole, the
rubber ring must be placed on the hole. Otherwise, it may cause electrical shock or fire etc.
3)The power wire and transmission line must be more than 1 meter (3-1/4feet) away from televisions or
radios which can emit electromagnetic waves to prevent image interference or noise. Otherwise, the unit
maybe cannot work.
4)Confirm the each cable connected to the terminal screw is exactly and securely after finishing the
electric work.
5)Fix each ground wire separately with the ground screw.
6)If the connecting wire is connected to the terminal incorrectly, it may cause a fire.
19
Page 26
Flex + Series
8 Design of Drainage Pipeline
8.1 Installation of Drain Hose
1)Choose one drain hole in the bottom of the outdoor unit.
2)Connect the drain hose to the drain hole.
3)The drain hose should be kept at 5~10 degrees of gradient to facilitate discharge of the
condensing water. Take care that does not exert too much force on the hose.
4)Thermal insulation materials should be placed at the joints of the drain hose so as to prevent
from dew condensation. Fix the drain hose firmly by binding band.
Fig. 22
5)The
end of the drain hose should be inserted into the hole of drainage pipeline.
8.2 Design of Drainage Pipeline
1)The drainage pipeline should be kept at a certain gradient (1/50—1/100) so as to avoid bulges
of pipes where there might be water bends.
2)The drainage pipeline is form of the hard PVC pipes for common purposes which can be
purchased locally. The diameter of the PVC pipes is not less than 17mm (11/16inch) and the
pipeline should be fixed as close to the BU module as possible.
3)Insert the drain hose into the drain hole of drainage pipeline. Use binding band to fix it tightly.
It is not allowed to use adhesive glue to join the drain hose to the drainage hole.
4)When
the drainage pipeline is laid for a couple
should be approximately 100mm lower than the drainage hole of each module. In this case,
some special-purpose pipes with thicker walls will be used.
of units, the position of the shared pipeline
NOTICE! At intervals of about 1 meter (3-1/4feet), fix the drain pipes to the wall with
brackets, not floating in the air.
20
Page 27
Flex + Series
9 Installation of Protective Layer
1)The refrigerant pipes should be insulated by the heat insulation material and plastic tape in
order to prevent water condensation and leakage.
2)Do not use the foam on the branch pipe as the material for heat insulation, heat insulation
material of branches should be the same as that of the pipeline.
NOTICE! The heat resistance of heat insulation material should be over than 120℃(248℉)
and its thickness is more than 9mm(3/8inch).
3)The joints of the system should be wrapped with the heat insulation material and no gap is
allowed on the joint of the system, as shown in the following figure.
Fig. 23
4)Bun
5)Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where it enters the wall.
dle the refrigerant pipe and transmission line together with tape, and separate them from the
drain pipe to prevent the condensate water overflowing.
During the wrapping, the later circle should cover half of the former one.
CAUTION
1)At intervals of about 1 meter (3-1/4feet), fix the refrigerant pipes to the wall with brackets, that is, don’t
let the unit withstand the weight of it or float it in the air.
2)After the pipe is protected well enough, never bend it to form a small angle(<90°), otherwise it would
crack or break.
3)Do not wrap the refrigerant pipes very tight, otherwise the insulation effect would be weakened.
Additionally, make sure the drain hose is separated from the refrigerant pipes.
4)After that, cover the hole on the wall with sealing materials to prevent wind and noise going into the
room.
21
Page 28
Flex + Series
10 Test Operation
10.1 Check after Installation
Table 10
Items to be checked Possible malfunction
Has it been fixed reliable? The unit may drop, vibrate or make noise.
Has the gas leakage been checked? It may cause insufficient cooling(heating) capacity.
Is the thermal insulation of the unit sufficient? It may cause condensation and dripping.
Is the drainage well? It may cause condensation and dripping.
Is the voltage in accordance with the rated
voltage marked on the nameplate?
Are the lines and pipelines correctly installed?
Has the unit been safely grounded? It may cause electrical leakage.
Are the models of lines in conformity with
requirements?
Are there any obstacles near the air inlet and
outlet of the indoor and outdoor units?
Have the length of connection pipes and
refrigerant charge amount been recorded?
It may cause electric malfunction or the
components may be burned out
It may cause electric malfunction or the
components may be burned out
It may cause electric malfunction or the
components may be burned out
It may cause insufficient cooling(heating) capacity.
It is not easy to decide the charge amount of
refrigerant.
10.2 Test Operation
1)Before test operation
The appearance of the unit and the refrigerant pipes cannot be damaged during the installation.
Do not switch on power before installation is finished completely.
Electrical wiring must be connected correctly and securely.
The stop valves of the outdoor unit should be opened fully.
All the impurities such as scraps and thrums must be cleared from the unit.
2)Test operation method
① The test operation should be carried out by the professionally skilled personnel on the premise
that all items listed above are in normal conditions.
② Set the status of the power supply switch as “ON” eight hours before the start of operation
③ Press mode button, to select the COOL, or HEAT. Whether the air conditioner is work
normally or not.
The fan motor of the indoor unit will run automatically in one minute.
The fan motor and compressor of the outdoor unit will run automatically in one minute.
④ Make sure that every combination of indoor units can work well.
WARNING
If the unit cannot work nor has any abnormal noise after the compressor is started, turn off the unit for an
immediate check.
22
Page 29
Flex + Series
11 Testing Board Introduction
11.1 Compose of the Testing Board
The testing board is in front of electrical box and can be observed well. It has several following
advantages: detect indoor unit numbers and indoor unit address, displays real running function and
error code automatically. It is composed of the function section, data section and button section.
Function section
Data sectionButton section
11.2 Instruction of Function and Data Section
Running state The display of function section The display of data section
① If the function section displays the
numbers of the indoor units, the data
section will display the outside
temperature. For example, the “35” is
represented of 35℃.② If the function section displays the
address of the indoor unit,the data
section will display the model of the
indoor unit, for example, the “35” is
represented of 35 model.
It displays the target gear of the
compressor. If the gear is zero, it will
display “0”. For example, the gear is
the fifteenth; it will display “15”. The
range of the gear is from 0 to 60.
Stop
Normal
① The section will display the numbers of the
indoor units which have established
communication with the outdoor unit. For
example, if there are seven established indoor
units, the section will display “7”.
② It will display the address of the indoor units
by turns. For example, the “1b” is represented
of the indoor unit 1B.
(BU module:1/2/3,Indoor unit: A/b/C/d/E)
The code of running state:
Code
UE
UP Pump down F7 Oil returning
UC Cooling H1 Defrosting
Running
state
Pressure
equalization
CodeRunning state
UHHeating
Malfunction
If the malfunction occurs in the system, the
section will display the error code. If there are
several malfunctions, it will display the error
codes by turns at intervals of 2 seconds.
23
① If the malfunction occurs in the
outdoor unit, the section displays
nothing;
② If the malfunction occurs in the
indoor units, the section displays the
address of the indoor unit.
Page 30
Flex + Series
12 Troubleshooting
WARNING
1)In the event of abnormal conditions (like, stinky smell), please shut off the power supply immediately
and then contact the appointed service center; otherwise, the abnormal running would damage the air
conditioner and also would cause electric shock or fire hazard .
2)Do not repair the air conditioning personally but instead contact the professionally skilled personnel at
the appointed service center, as the incorrect repair would cause electric shock or fire hazard etc.
12.1 Check before Contacting Service Center
Please check the following items before contacting the maintenance serviceman.
Conditions CausesCorrective actions
Broken fuse or breaker is off
Power off
The unit does not
run at all
The unit stops
soon after it starts
Cooling or heating
is abnormal
Power supply plug is loose Plug the power supply properly
The batteries voltage of the remote
controller is insufficient
Remote controller is out of the control
scope
Air inlet or outlet of indoor unit or
outdoor unit is blocked
Air inlet or outlet of indoor unit or
outdoor unit is blocked
Temperature setting is improper
Air speed is set too low
Improper airflow direction
Door or window is open Close the door or window
Under direct sunshine
Too many people in the room
Too many heat sources indoors Reduce the heat sources
The filter screen is dirt or blocked Clean the filter screen
NOTICE! If the air conditioner still runs abnormally after the above check and handling,
please contact the local appointed service center and also give a description of the error
occurred as well as the model of the unit.
Replace the damaged fuse or
close the breaker
Restart the unit after power
supply resumes
Replace with new batteries
The distance shall be within 8m
Remove the obstacles
Remove the obstacles
Adjust the setting of remote
controller or wire controller
Adjust the setting of remote
controller or wire controller
Adjust the setting of remote
controller or wire controller
Hang curtain or blinders over the
window
24
Page 31
12.2 Problem Handling
The conditions listed below are not classified into errors.
Conditions Causes
When restart the unit soon after
The unit does
not run
The unit blows
out mist
The unit
generates noise
The unit blows
out dust
The unit emits
odors
it is stopped
As soon as power supply is on
When the cooling operation
starts
The unit “clatters” as soon as it
starts running
The unit “swishes” during the
cooling operation
The unit “swishes” when it is
started or stopped
The unit “swishes” when it is in
and after the running
The unit “squeaks” when it is in
and after the running
When the unit restarts after it is
not used for a long time
When the unit is running The odors absorbed in are blown out
Flex + Series
The overload protection switch of the unit let
the startup delayed for three minutes
The unit will stand by for approximate one
minute
The hi-humidity air indoor is cooled quickly
It is the sound generated during the
initialization of the electronic expansion
valve
It is the sound when the refrigerant gas runs
inside the unit
It is the sound when the refrigerant gas stops
running
It is the sound when the draining system is
operating
It is the sound of frication generated by the
skin plate etc which swells due to the
temperature change
The dust inside the unit is blown out again
12.3 Error Description
If some error occurs when the unit is running, the error code will be displayed and check for
more details about the meaning of each error.
Errors of definition
Main control display for outdoor unit
Yellow LEDRed LED Green LED
The compressor is startup Flash 1 time
IPM current protection Flash 3 times
IPM temperature protection Flash 5 times
PFC current protection Flash 7 times
PFC temperature protection Flash 8 times
Low voltage protection Flash 9 times
High voltage protection Flash 10 times
Low pressure protection Flash 11 times
High pressure protection Flash 12 times
High pressure switch protection Flash 13 times
Capacitor charging error Flash 14 times
AC current protection Flash 15 times
Indoor
unit code
H5 H5
P8 P8
P8 P8
PL PL
PH PH
E5 E5
Testing
board code
HC
E3
E8
E1
PU
25
Page 32
Flex + Series
Memory card error Flash 16 times
Compressor demagnetizing
protection
Compressor desynchronizing Flash 18 times
Compressor phase lack Flash 19 times
Compressor phase circuit detection
error
Compressor power protection Flash 21 times
Compressor overload protection Flash 22 times
Compressor discharge temperature
protection
Lack of refrigerant or jam protection Flash 31 times
Normal operation Flash 1 time
Frequency limitation for AC current Flash 2 times
Oil returning Flash 3 times
Defrosting Flash 4 times
Frequency limitation for IPM
temperature
Frequency limitation for PFC
temperature
Frequency limitation for compressor
overload
Frequency limitation for compressor
discharge temperature
Frequency limitation for low pressure Flash 10 times
Frequency limitation for high
pressure
Discharge temperature sensor error Flash 12 times
Outdoor temperature sensor error Flash 13 times
Suction temperature sensor error Flash 15 times
Condenser temperature sensor error Flash 16 times
Sub-cool temperature sensor error Flash 17 times
Low pressure sensor error Flash 18 times
High pressure sensor error Flash 19 times
Fan motor error for indoor unit Flash 20 times
Driving board is connected Flash 1 time
Testing board is connected Flash 2 times
Computer is connected Flash 4 times
Indoor unit 1 is connected Flash 5 times
Indoor unit 2 is connected Flash 6 times
Indoor unit 3 is connected Flash 7 times
Indoor unit 4 is connected Flash 8 times
Indoor unit 5 is connected Flash 9 times
Flash 17 times
Flash 20 times
Flash 23 times
Flash 5 times
Flash 6 times
Flash 8 times
Flash 9 times
Flash 11 times
EE
HE HE
H7 H7
U2 U2
U1 U1
L9 L9
H3 H3
E4 E4
F0 F0
F8
F7
H1 H1
EU
EU
LU
F9
Pn
F6
F5 F5
F3 F3
dc
A7 A7
bC
dL
e1
H6 H6
26
Page 33
Flex + Series
Indoor unit 6 is connected Flash 10 times
Indoor unit 7 is connected Flash 11 times
Indoor unit 8 is connected Flash 12 times
Indoor unit 9 is connected Flash 13 times
Indoor unit anti-freeze protection
Indoor temperature sensor error
Indoor evaporator midway
temperature sensor error
Temperature sensor error for liquid
pipe of BU module
Temperature sensor error for gas pipe
of BU module
Running mode conflicts
Communication error
Communication error between the
main board and driving board
Communication error between the
main board and testing board
Gas sensor error of indoor unit
Humidity sensor error of indoor unit
Water full error of indoor unit
Jumper terminal error of indoor unit
Phase lack of power supply
Fan motor error of outdoor unit
Refrigerant recovery mode
E2 E2
F1 F1
F2 F2
b5 b5
b7 b7
E7 E7
E6
E6
unit address
CE
E9 E9
C5 C5
Fo Fo
Display mode of Red LED and Yellow LED: At intervals of half a second, flash for half a
second; if there are several malfunctions, it will display the error codes by turns at intervals of
one second.
Display mode of Green LED: At intervals of 1/4 second, flash for 1/4 second; and it displays
the running states by turns at intervals of half a second.
indoor
P6
Fn
L1
dJ
L3
27
Page 34
Flex + Series
13 Maintenance
Check, maintenance and care regularly should be performed by professional personnel, which
will prolong the unit service life.
13.1 Outdoor Condenser
Outdoor condenser is required to be cleaned every two months. Use vacuum cleaner with nylon
brush to clean up dust and sundries on the surface of condenser. Blow away dust by compressed air
if it is available. Never use water to wash the condenser.
13.2 Drain Pipe
In order to drain condensate smoothly, please check the drain pipe regularly is clogged or not.
13.3 Check before the Seasonal Use
Check the air inlet and outlet of the indoor and outdoor units to confirm there is no blockage.
Check the ground wire to confirm the grounding is reliable.
Check the batteries of the wireless remote controller to ensure that they have been replaced.
Check the filter screen that it has been set soundly.
If the air-conditioning unit shall be operated again after a long-term shut off, set the status of
the power supply switch as “ON” eight hours before the start of operation, so as to ensure the
successful startup of the air-conditioning unit.
Check the outdoor unit to ensure the installation of it is steady. Contact the appointed service
center if there is any abnormal condition.
13.4 Maintenance after Seasonal Use
Turn off the power supply of the air conditioning unit and set the status of the power supply
switch as “OFF”.
Clean the filter screen and the housing of the indoor and outdoor units.
Remove the dust and the foreign matters of the outdoor unit.
In the event of rusting, please use the anti-rust paint to stop spreading of rust.
Refer to the Insta
maintenance.
llation and Operation
Manual
each indoor unit respectively for detailed
of
14 After-sales Service
If the unit cannot work or has any problem, please contact the local after-sales service
agency designated by Impecca.
Warranty should meet the following requirements:
①The installation and test operation of the unit should be operated by professional personnel from
appointed service center.
②Only Impecca manufactured accessories
③All the instructions listed in this manual should be followed.
④Warranty will be automatically invalid if fails to obey any item mentioned above.
can be used on the machine.
Page 35
CUSTOMER SUPPORT
15
Before contacting customer support, please see the troubleshooting guide above.
V isit our website to contact us, find answers to Frequently Asked Questions, and for other resources
wh ich may include an updated version of this user's guide.
WWW.IMPECCA.COM
If you wish to contact us by phone, please be sure to have your model number and serial number ready
and call us between 9:00am and 6:00pm ET, at +1 866-954-4440.
Keep tabs on Impecca's newest innovations & enter contests via our social network feeds:
Flex+ Series adopt the advanced manufacturing technology and takes the environmental-
friendly R410A as refrigerant, which is a green produc
the manual before installation and operation.
1)Flex+ Series systems conform to design standard ARI 210240-2008.
2)To ensure safety when operating this system, please strictly follow the instructions in this
manual.
3)Make sure that the manual is kept by the operators or serviceman.
4)The refrigerant pipes and accessories must be designed exclusively for R410A.
5)The total capacity of the indoor units which runs at the same time cannot exceed the capacity of
the outdoor units; otherwise, the cooling (heating) effect of each indoor unit would be lower
than the nominal capacity.
6)In case of malfunction, please examine the following items and contact our appointed service
centers as soon as possible.
Nameplate (model, cooling capacity, product code, ex-factory date).
Malfunction status (detail description of conditions before and after malfunction occurs).
7)It is a normal phenomenon that the fan of indoor unit will still run for 20-70 seconds after the
indoor unit receives the “stop” signal so as to make full use of the waste heat.
8)When the work mode of the indoors is conflict with the modes of outdoor units, it will be
indicated on the display of the wired controller in five seconds and then the indoor unit will
stop. In this case, please harmonize their work modes: the cooling mode is compatible with the
dry mode.
9)If the supply power fails when the unit is running, then the indoor unit will send the “start”
signal to the outdoor unit three minutes later after the power recovery.
10) The power cable and transmission line must not be twisted together, but instead of separated
with an interval of at least 2cm; otherwise it may be result in communication problem.
11) This appliance is not intended for use by persons (including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance by a person responsible for
their safety. Children should be supervised to ensure that they do not play with the appliance.
12) All graphics and information in this manual are only for reference. Manufacturer reserves the
right for changes in terms of sales or production at any time and without prior notice.
t in the 21st century. Please carefully read
This product must not be disposed together with the domestic waste. This product has
to be disposed at an authorized place for recycling of electrical and electronic appliances.
Thank you for purchasing Impecca air conditioners. Before using, please read
this manual carefully and keep it properly for further reference.
Gas liquid Φ9.52(3/8) Φ9.52(3/8) Φ9.52(3/8) Φ15.9(5/8)
2)Installation and service space
Outdoor unit side
(mm/inch)
NO.
Name Servicing space Ceiling Electrical box side
①②
Fig. 6 (mm)
7
③
Page 48
BU Module
3.6 Outline Dimension and Servicing Space of IS-BU15
1) Outline dimension
(mm)
Fig. 11
Table 7
Sorts Indoor unit side (mm/inch) Outdoor unit side (mm/inch)
Liquid pipe Φ6.35(1/4) Φ9.52(3/8)
Gas pipe Φ9.52(3/8) Φ15.9(5/8)
2)Installation and service space
NO.
Name Servicing space Ceiling Electrical box side
①②
Fig. 12 (mm)
10
③
Page 49
BU Module
4 Installation Instruction
1)Check the installation location and ensure it is strength and level. Otherwise, there should be
enough space to install drainage pipe, so that the condensed water can be discharged.
2)Reference to the size of hanger metal and drill 4 holes in the installation location.
3)Hang the hanger bolts.
Fig. 13
4)Fix the modules securely with the hanger bolts. You can get the M10 or M8 hanger bolts, nuts
and washers from the market.
Fig. 14 (mm)
5)Adjusting the nuts position, so that the BU module should be level in front/back and left/right.
11
Page 50
BU Module
5 Installation of Refrigerant Pipes
5.1 Allowable Length and Drop Height of Connecting Pipe
Fig. 15 (8 indoor units)
Table 8
The sorts The pipes Length(m/feet)
Maximum
allowable
length
Maximum
allowable
length
Minimum
allowable
length
Total length between outdoor unit and BU
modules
Total length
between indoor
units and BU
Between indoor unit and BU module 1A;1B;1C;2A;2B;2C;3A;3B ≤15(49)
Between indoor unit and the 1st branch
Between outdoor and indoor units H1 ≤30(99)
Between outdoor units and BU modules H2 ≤30(99)
Between BU and BU modules H3 ≤15(49)
Between indoor and indoor units H4 ≤15(49)
Between outdoor and the 1st branch L1 ≥5(16)
Between BU and the branch L3;L4;L5
ISMO-6021
L1+L2+L3+L4+L5 ≤55(181)
1A+1B+1C+2A+2B+2C+
3A+3B
L4+1B;L2+L5+2A;
L2+L3+3B
≤90(295)
≤40(131)
as possible as
NOTICE! BU module should be placed within the level between the outdoor unit and indoor
unit.
short
5.2 Installation of Piping Adapter (IS-BU12IS-BU13 and IS-BU15)
If the pi
indoor units, it should prevail with the piping connection size of the outdoor unit and indoor units.
ping connection size of BU module does not match with that of the outdoor unit and
12
Page 51
BU Module
Install the optional piping adapters to the BU module, so that the piping connection size of BU
module can match with that of the outdoor unit and indoor units.
1)Piping adapter(Optional accessories)
Table 9
NO. Name
1 Φ15.9→Φ19.05Φ15.9(5/8) Φ19.05(3/4)
2 Φ9.52→Φ12.7 Φ9.52(3/8) Φ12.7(1/2)
3 Φ9.52→Φ15.9 Φ9.52(3/8) Φ15.9(5/8)
4 Φ6.35→Φ9.52 Φ6.35(1/4) Φ9.52(3/4)
2)Install the piping adapter
① Refer to the piping connection size of the outdoor unit and indoor units, the appropriate piping
adapter should be adopted.
② Align the flared end of copper tube with the center of pipe joint. Tighten the nuts with hands.
Then tighten the flaring nuts with torque wrench until you hear a “click”.
Port A
(mm/inch)
Port B
(mm/inch)
Fig. 16
Fig. 17
3)Sealing the unconnected port
If the port of BU module indoor side does not connected to one indoor unit, the port must be
sealed t
with torque wrench until you hear a “click”.
o prevent refrigerant leaks. Please tighten the copper flaring nuts to the unconnected port
13
Page 52
BU Module
5.4 Precaution for Connection
CAUTION
1)Conform to the following principles during pipe connection: Outdoor unit shall be installed close to the
indoor unit, hence to minimize the length and bends of connection pipes; the height gap of outdoor unit
and indoor units should be as small as possible; the radius of curvature should be as large as possible.
2)The brazing operation must be strictly in accordance with the process requirements. Rosin joint or pin
hole is not allowed.
3)During the installation, do not damage the pipeline. The pipeline’s radius of bending must be over than
200mm (8inch). The pipes cannot repeatedly be bent or straightened. Otherwise it will get harden and
crack. Do not bend or straight the pipes for more than 3 times at the same position.
1)The process of flaring
① Using the tube cutter to cut the connecting pipe in the appropriate place and remove the burrs.
② Install the nut before the flaring operation.
③ Check the flared portion, whether there is fractured or not.
Fig. 21
2)Precaution for elbow operation
① The elbow operation could be done by hands. Be careful and do not damage the pipe.
15
Page 53
BU Module
Fig. 22
② If the thermal insulation of the refrigerant pipe is not removed, please do not bend the pipe.
Otherwise, it maybe leads the pipe to crack. It is better to make an incision with a knife in the
thermal insulation and removes it. After elbow operation is finished, recover the thermal
insulation with binding band.
3)The process of install refrigerant pipes
① Remove the screw caps from the pipes.
② Align the flared end of copper tube with the center of pipe joint. Tighten the nuts by hands. (If
the flared end of copper tube and the center of pipe joint are not in coaxial, it is hard to tighten
the nuts by hands, please do not tighten it with spanners, because the screw thread may be
broken by force).
③ Tighten the flaring nuts with torque wrench until you hear a “click”. (The spanner and torque
wrench should be perpendicular to the refrigerant pipeline).
④ The following table for the torque required to tighten the nuts.
1)During the connection of the indoor unit and BU module to the refrigerant pipe, never pull any joints of
the indoor unit and the BU module by force; otherwise the capillary pipe or other pipe may crack,
which then would result in leakage.
) The refrigerant pipe should be supported by brackets; that is, don’t let the unit support its weight.
2
3) For the Flex+ system, each pipe should be labeled to tell which system it belongs to avoid
mistaken, inaccurate piping.
16
Page 54
6 Electrical Wiring Work
6.1 Wiring Connection
BU Module
NOTICE! The “L1”, “3” terminals are connected to the live wire, the “L2”,”N(1)” terminals
are connected to the neutral wire and the ”2” terminal is connected to the transmission line.
Fig. 24
6.2 Requirements of Power Circuit and Cable
Table 11
Phase and frequency 1Ph,60Hz
Voltage 208/230V
Recommended cable of outdoor unit
(Pieces × Sectional area)
Recommended cable of BU module (Pieces × Sectional area) 3×0.75 mm2
Transmission line (Pieces × Sectional area) 2×1.5 mm2
Recommended cable of indoor unit (Pieces × Sectional area) 4×0.75mm2
Capacity of the air switch
ISMO-6021
ISMO-6021
BU module 10A
3×6.0 mm
40A
2
NOTICE
1)The total length of the transmission line between the outdoor unit and the furthest BU module is not
than 180 feet (55m). Otherwise, the system cannot work possibility.
more
2)The specifications of the power cable and transmission line listed in the table above are determined
based on the maximum power (maximum amps) of the unit.
3)The specifications of the power cable listed in the table above are applied to the conduit-guarded
17
Page 55
BU Module
multi-wire copper cable (like, YJV copper cab
jacket) used at 104℉ (40℃) and resistible to 194℉ (90℃), and shall be at least those of ordinary
polychloroprene sheathed cords. If the working condition changes, they should be modified according
to the related national standard.
4)The specifications of the air switch listed in the table above are applied to the breaker with the working
temperature 104
related national standard.
) The length of the recommended power cable should be less than 49 feet (15 meters); otherwise,
5
the diameter of the power cable is not enough.
) Written power cable and transmission line length is just a reference value. It may be different
6
depending on the condition of installation, humidity or materials, etc.
) An all-pole disconnection switch having a contact separation of at least 3mm (1/8 inch) in all poles
7
should be connected in fixed wiring.
℉ (40℃). If the working condition changes, they should be modified according to the
le, consisting of PE insulated wires and a PVC cable
6.3 Ground Requirements
WARNING
1)The air conditioner is classified into the Class I appliances, so its ground ways must be reliable.
2)The ground wire must be fixed on the screw hole with the sign as the right figure.
3)The yellow-green wire of the air conditioner is the ground wire and must be fixed by the tapping screw.
And it cannot be used for other purpose or cut off. Otherwise, it will cause the hazard of electric shock.
4)The reliable ground terminal should be provided and the ground wire cannot be connected to any of the
following places: a. Water pipe; b. Coal gas pipe; c. Sewage pipe; d. Lightning rod
e. Telephone line f. Other unreliable places considered by a professional.
6.4 Precautions on the Electrical Wiring Work
WARNING
1)The electrical installation should be carried out by the professional as instructed by the local laws,
regulations and also this manual.
2)The ground connection should be reliable and the ground wire should be connected to the dedicated
device of the building by the professional.
3)Before starting work, the power must not be supplied to the unit.
4)The air switch coupled with the leakage current protection switch must be equipped in the circuits,
which is of enough capacity and of both magnetic and thermal tripping functions in case of the short
circuit and overload.
5)The electrical work should use a cable length enough to cover the entire distance with no connection. If
it is unavoidable, please make sure the connection should be reliable, the external forces will not act on
the wires and the joint is not bared. Otherwise it will cause electrical shock or fire etc.
6)The power cable with the rated voltage and exclusive circuit for the air conditioner should be used.
7)Do not pull the power cable by force after it is installed.
8)The diameter of the power cable should be large enough and once it is damaged, it must be replaced by
the dedicated one.
9)The multi-wire copper cable should be used for the power cable and the transmission line.
18
Page 56
BU Module
6.5 Precaution of Laying Wires
1)Use a wire stripper to strip off a length of the insulation layer at the end of the wires;
2)Loosen the screws on the terminal block of the air conditioner;
3)Press the ends of the cable tightly onto the round terminals corresponding to the size of the
screws.
4)Pass the screw through the round terminals and fix it onto the terminal block.
Fig. 25
6.6 Procedures for Electrical Wiring Work
1)Unscrew the electrical equipment plate.
2)The structure of behind the electrical equipment plate.
a) IS-BU12
19
Page 57
BU Module
b
) IS-BU13
c) IS-BU15
NO. 1 2 3
Name
NO. 4 5 6
Name
3)Let the power cable and transmission line go through the rubber ring. In order to protect the
4)Connect the power cable of the BU module to the L1, L2 terminals with the sign of Power and
5)Connect the transmission line of the BU module to the N(1), 2 terminals with the sign of
6)If the transmission line need to be connected to the other BU module, please connect the extra
Terminal black for BU
module power supply
Terminal black for indoor
unit power supply
power cable and transmission line from damaging by the hole, the rubber ring cannot fall from
that, otherwise, it may cause electrical shock or fire etc.
as well as the ground screw.
Outdoor unit/BU module.
Terminal black for
transmission line
DIP switch Printed circuit board
Fig. 26
20
Ground screw
Page 58
BU Module
line to the N(1), 2 terminals with the sign of BU module.
7)Connect the power cable of the indoor unit to the N(1), 2 and 3 terminals with the sign of
Indoor unit A (B, C, D and E) and as well as the ground screw.
8)Fix the power cable and transmission line firmly by cable fixing clip.
9)Screw the electrical equipment plate.
CAUTION
1)The transmission line and the power cable must be separated with an interval of at least 2cm (3/4inch);
otherwise it may be result in communication problem.
2)Confirm the each cable connected to the terminal screw is exactly and securely after finishing the
electric work.
3)Fix each ground wire separately with the ground screw.
4)When connecting indoor units, make sure to connect refrigerant pipes and power cables to the same
connection ports marked with matching signs (A, B, C ,D and E).
5)If the connecting wire is connected to the terminal incorrectly, the unit will not work normally.
6)The refrigerant pipe should be supported by brackets, that is, don’t let the unit withstand the weight of
it.
7)For the Flex+ system, each pipe should be labeled to tell which system it belongs to avoid
mistaken inaccurate piping.
6.7 Instructions for DIP Switch
2 digits DIP is adopted to assign the address when using multi-BU modules and the address
cannot be repeated in the same unit.
One outdoor unit can connect to no more than 3 BU modules.
“ON” side means "ON" and the opposite side represents "OFF".
NOTICE!: The black part is lever.
Table 12
Number
1OFFOFFBU 1
2OFFON
DIP Code
IconAddress
DIP 1 DIP 2
BU 2
3ONOFFBU 3
21
Page 59
BU Module
7 Design of Drainage Pipeline
7.1 Installation of Drain Hose
1)Remove the rub
2)Connect the drain hose to the drain hole of BU module.
3)The drain hose should be kept at 5-10 degrees of gradient to facilitate discharge of the
condensing water. Take care that does not exert too much force on the hose.
4)Thermal insulation materials should be placed at the joints of the drain hose so as to prevent
from dew condensation. Fix the drain hose firmly by binding band.
ber stopper of drain hole.
Fig. 27
5)The end of the drain hose should be inserted into the hole of drainage pipeline.
7.2 Design of Drainage Pipeline
)The drainage pipeline should be kept at a certain gradient (1/50-1/100) so as to avoid bulges of
1
pipes where there might be water bends.
2)The drainage pipeline is form of the hard PVC pipes for common purposes which can be
purchased locally. The diameter of the PVC pipes is not less than 31mm (1-1/4inch) and the
pipeline should be fixed as close to the BU module as possible.
3)Insert the drain hose into the drain hole of drainage pipeline. Use binding band to fix it tightly.
It is not allowed to use adhesive glue to join the drain hose to the drainage hole.
4)When the drainage pipeline is laid for a couple of units, the position of the shared pipeline
should be approximately 100mm lower than the drainage hole of each module. In this case,
some special-purpose pipes with thicker walls will be used.
NOTICE! At intervals of about 1 meter (3-1/4feet), fix the drain pipes to the wall with
brackets, not floating in the air.
8 Test Operation
After all the installation has been accomplished, follow the “operation test” as described in the
outdoor unit owner’s manual.
22
Page 60
BU Module
9 Troubleshooting
WARNING
1)In the event of abnormal conditions (such as an unpleasant smell), please shut off the power supply
immediately an
damage the air conditioner and also would cause electric shock or fire hazard .
2)Do not repair the air conditioning personally but instead contact the professionally skilled personnel at
the appointed service center, as the incorrect repair would cause electric shock or fire hazard etc.
Errors
BU 1 is connected
BU 2 is connected
BU 3 is connected
Indoor unit A is connected
Indoor unit B is connected
Indoor unit C is connected
Indoor unit D is connected
Indoor unit E is connected
Indoor unit A gas tube
temperature sensor error
Indoor unit A liquid tube
temperature sensor error
Indoor unit B gas tube
temperature sensor error
Indoor unit B liquid tube
temperature sensor error
Indoor unit C gas tube
temperature sensor error
Indoor unit C liquid tube
temperature sensor error
Indoor unit D gas tube
temperature sensor error
Indoor unit D liquid tube
temperature sensor error
Indoor unit E gas tube
temperature sensor error
Indoor unit E liquid tube
temperature sensor error
d then contact the appointed service center; otherwise, the abnormal running would
Table 13
Indicating LED flashing times
Yellow
LED
Flash 1 time
Flash 2 times
Flash 3 times
Green
LED
Flash 1 time
Flash 2 times
Flash 3 times
Flash 4 times
Flash 5 times
Red
LED
Flash 1
time
Flash 2
times
Flash 3
times
Flash 4
times
Flash 5
times
Flash 6
times
Flash 7
time
Flash 8
times
Flash 9
time
Flash 10
times
Indoor
unit error
code
b7
b5
b7
b5
b7
b5
b7
b5
b7
b5
Outdoor unit error
code
b7 indoor unit
address
b5 indoor unit
address
b7 indoor unit
address
b5 indoor unit
address
b7 indoor unit
address
b5 indoor unit
address
b7 indoor unit
address
b5 indoor unit
address
b7 indoor unit
address
b5 indoor unit
address
10 After-Sales Service
If there is any quality or other issue, please contact the after-sales service center.
23
Page 61
CUSTOMER SUPPORT
Before contacting customer support, please see the troubleshooting guide above.
Visit our website to contact us, find answers to Frequently Asked Questions, and for other
resources which may include an updated version of this user's guide.
WWW.IMPECCA.COM
If you wish to contact us by phone, please be sure to have your model number and serial
number ready and call us between 9:00am and 6:00pm ET, at +1 866-954-4440.
Keep tabs on Impecca's newest innovations & enter contests via our social network feeds:
Flex Series R410A GMV Multi
VFR System-Indoor Unit (For
North America) Compact Panel
Cassette Type Indoor Unit
Owner's Manual
Air Conditioners
Model:
ISMI-C15
Thank you for choosing Air Conditioners, please read this owner’s manual carefully before operation
and retain it for future reference. If you have lost the Owner’s Manual, please contact the local agent or
visit www.Impecca.com for an electronic version.
Impecca reserves the right to interpret this manual which will be subject to any change due to
product
improvement without further notice.
Impecca reserves the final right to interpret this manual.
v. 1.1
Page 63
User Notice
When operating, the entire capacity of the cooperating indoor unit should be not larger
◆
than 150% of outdoor unit. Otherwise, it will cause the shortage of cooling (heating) capacity.
A Breaker(or fuse) need to be installed in every indoor unit, and the capacity should
◆
in according with indoor unit’s electrical parameter; all the indoor units are required to be
centralized controlled by a total Switch, this Switch can cut off the electric power supply in
case of emergency. The Breaker(or fuse) on each indoor units have the function of short
circuit prevention and abnormal overload avoiding, it should be connected in normal situation.
The total switch controlling the power supply of all the indoor units. Before clearing and
maintenance job being carried out to the indoor units, it is very important to turn off the total
power supply switch.
In order to turn on the units successfully, the main power switch should be opened 8
◆
hours before the operation.
After receiving the turn off signal, every indoor unit will continue to work for 20-70sec to
◆
make use of the rest cool air or the rest heat air in the heat exchanger, while preparing for the
next operation. And this is normal.
When the selected operating mode of the indoor unit are clash with the operating
◆
mode of the outdoor unit, the malfunction light will blink after 5s on the indoor unit or remote
controller showing that the operation clash, then the indoor unit will stop. At this time, change
the operation mode of the indoor unit to the one that would not clash with the outdoor operating
mode to make the operation normal. The cooling mode is not clash with the dry mode, while
the fan mode is not clash with any mode.
The appliance shall not be installed in the laundry.
◆
An all-pole disconnection switch having a contact separation of at least 3mm in all poles
◆
should be connected in xed wiring.
Information regarding transport/storage temperature (-25-55°C) is missing.
◆
Main switch provided by end user: main switch handle should be black or gray, it can be
◆
locked in “OFF” position with padlock.
The main disconnection device should be explained in user manual and the height
◆
should be recommended at 0.6-1.7m. over current protection is required(UL 1995,CSA C22.2).
The cooling range of the unit is the outdoor environment temp.-5~48°C DB, the heating
◆
range of the unit( only for the heat pump type unit) is the outdoor environment temp. -15~27°C
WB.
This product must not be disposed together with the domestic waste. This product
has to be disposed at an authorized place for recycling of electrical and electronic
appliances.
Thank you for your selecting of Impecca air conditioner, please read this usage
and install instruction carefully and keep it well in order to use this unit correctly.
Page 64
Contents
1 Safety Information .....................................................................................1
2 Install of The Compact Panel Cassette Type Indoor Unit .......................... 2
2.1 Schematic diagram of installation spaces ......................................................... 2
2.2 Select install location of the indoor unit ............................................................. 2
2.3 Important notice ................................................................................................ 3
2.4 Dimension of ceiling opening and location of the hoisting screw (M10) ............ 3
2.5 Main body of hoisting air conditioner ................................................................. 3
2.6 Connection of the refrigerant pipe ..................................................................... 4
Heat preservation
sheath of gas collection
tube (attachment)(for
gas tube)
Fig.5
Form 1: The tightening torque needed for tightening nut
Diameter(Inch
φ1/4’’
φ3/8’’
φ1/2’’
φ5/8’’
φ3/4’’
)
Surface thickness(mm
0.515-30 (N·m)
≥
0.7130-40 (N·m)
≥
145-50 (N··m)
≥
160-65 (N·m)
≥
170-75 (N··m)
≥
)
Tightening torque (N·m)
2.7 Drainage hose
(1). Install the drain hose
The diameter of the drain hose should be equal or bigger than the connection pipe’s. ( The
◆
diameter of polythene pipe: Outer diameter 25mm Surface thickness ≥1.5mm)
Drain hose should be short and drooping gradient should at less 1/100 to prevent the
◆
formation of air bubble.
If drain hose cannot has enough drooping gradient, drain raising pipe should be added.
◆
To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m.
◆
Fig.6
Use the drain hose and clamp attached. Insert the drain hose to the drain vent, and then
◆
tighten the clamp.
Entwine the big sponge on the clamp of drain hose to insulate heat.
◆
Heat insulation should be done to indoor drain hose.
◆
5
Page 70
Install of The Compact Panel Cassette Type Indoor Unit
Sponge(attachment)
Drain hose
Clamp(attachment)
Below 4mm
Clamp
Sponge (gray)
Fig.7
Drain stepup pipe note
The install height of the drain raising pipe should less than 280mm.
◆
The drain raising pipe should form a right angle with the unit, and distance to unit should not
◆
beyond 300mm.
Fig.8
Instruction
The slant gradient of the attached drain hose should be within 75mm so that the drain hole
◆
doesn’t has to endure the unnecessary outside force.
Fig.9
Please install the drain hose according to the following process if several drain hoses join
◆
together.
Fig.10
(2). Check the smoothness of drain after installation.
Check the drain state by immitting 600cc water slowly from the outlet vent or test hole.
◆
Check the drain in the state of refrigerating after installation of the electric circuit.
◆
6
Page 71
Install of The Compact Panel Cassette Type Indoor Unit
Fig.11
2.8 Electrical wiring
Note:The power of the entire indoor unit must be connected in outdoor unit.
About the electrical wiring, please see the circuit diagram attached with the unit.
◆
All the installation of electrical wiring must be done by professional personnel.
◆
Please do take the earthing treatment.
◆
Wiring method of connection unit and controller
Connection wiring (communication):
◆
Open electric box cover, drag the wiring (communication)from the rubber plug A, and impact
①
them well individually by impact fastener.
Wiring according to the indoor side circuit diagram.
②
Fix the impact fastener after connection.
◆
Entwine the small sponge on the electric wire( do entwine it to prevent condensation).
◆
Impact tightly by impact fastener after connection and then t on the electric box.
◆
Connect the 3 cord rubber wire to the counter terminal of the 3 way terminal board.
◆
The power cord reference Power cord standard recommending table
Power cord standard recommending table
Power Supply
(V, Ph, Hz)
208~203V-1Ph-60Hz
Fig.12
Min. Sectional Area of
Earth Wire(AWG)
UL1015 AWG 18*1 UL1015 AWG 18*3
Min. Sectional Area of
Power Cord(AWG)
7
Page 72
Install of The Compact Panel Cassette Type Indoor Unit
2.9 Install the panel
(1). Set the panel to the indoor unit body by matching the position of the swing ap motor of the
panel to the piping position of the panel to the piping position of the indoor unit as shown by g.13.
(2). Install the panel
Install the panel on the indoor unit temporarily. When install, hang the latch on the hook
① .
that is located on the opposite side of the swing ap on the panel of the indoor unit. (2
positions)
Hang the remaining 2 latches to the hooks on the sides of the indoor unit.(Be careful not to
② .
let the swing motor lead wire get caught in the sealing material.)
Screw the 4 hexagon head screws under the latches in about 15mm. (The panel would
③ .
rise)
Adjust the panel by turning it toward the direction pointed by the arrow as shown in g.13,
④ .
so that the adjust board connect the ceiling well.
Tighten the screws until the thickness of the sealing material between panel and indoor
⑤ .
unit reduced to 5-8mm.
Fig.13
Notes:
Improper screwing of the screws may cause the troubles shown in g.14.
① .
8
Page 73
Install of The Compact Panel Cassette Type Indoor Unit
Air leak
Air leak from ceiling
Water condensatation, water drop
Fig.14
If gap still exist between ceiling and decoration panel after tightening the screws, readjust
② .
the height of the indoor unit. (As shown in g.15)
If the raising lever and drain hose are
not affect, can adjust the height of
indoor unit by the hole on the corner
of panel.
Gaps are not allowed
Fig.15
After xing, be sure no gap left between the ceiling and the panel.
※
Wiring of the decoration panel (Fig.16)
③ .
Connect the joints for swing ap motor lead wire (at 2 places) installed on the panel.
At bodyAt pane
At bodyAt pane
Fig.16
9
Page 74
Constitutes and Names of Parts of Compact Panel Cassette Type Indoor Unit
3 Constitutes and Names of Parts of Compact Panel Cassette Type
Indoor Unit
10
Page 75
Working Temperature Range
4 Working Temperature Range
Working Temperature Range
Indoor side stateOutdoor side stae
Dry bulb
temp.
℃
Rated Cooling27193524
Max. cooling32234826
Wet bulb
temp.
Dry bulb
℃
temp.
℃
Wet bulb
temp.
℃
Min. cooling211518
Rated Heating201576
Max. heating27
Min. heating
—
2015-
2418
15
-
—
16
11
Page 76
Malfunction Debarring
5 Malfunction Debarring
Warning!
Cut down the main power switch immediately if malfunction (such as smell the burning odor
◆
etc.) happened, and then contact service center. If the abnormal state is maintained, the unit may be
damaged or electric shock or re may be happened.
Do not ret the conditioner. Please contact service center to repair or move the conditioner.
◆
5.1 Check the following items before contacting maintenance center
PhenomenaReasonRemedial Measures
Blow of fuse or breakerChange fuse or close breaker
Air conditioner doesn’t
run at all
Air conditioner runs
but stops immediately
Abnormal cooling or
heating
Power cut
Don’t connect with powerConnect power well
Low batteries of wireless remote
controller
Wireless remote controller exceed
remote control area
Blockage in inlet or outlet vent of
indoor or outdoor unit
Blockage in inlet or outlet vent of
indoor or outdoor unit
Improper of temp. setting
Low setting of fan speed
Incorrect of wind direction
Door or window openedClose
Direct sun burn
Too many people in room
Restart when there is power
supply
Change new batteries
Signal could be received within
8m
Clean out blockage
Clean out blockage
Adjust settings in wireless remote
controller
Adjust settings in wireless remote
controller
Adjust settings in wireless remote
controller
Hang curtain or jalousie before
windows
Too many heater in room
Filter blocked by dirtClean lter
12
Page 77
Malfunction Debarring
5.2 Instruction
If problem still cannot found out after above checking, please contact service center and instruct
phenomena and model.
5.3 The following circumstance are not malfunction
“Malfunction”Reason
Air conditioner doesn’t
run
Mist is blown from air
conditioner
Noise is heard from
air conditioner
Dust be blown for air
conditioner
Odor gives out from
air conditioner
Start up unit immediately after
turned off
When opening power
When cooling
Slight click sound heard once
begin running
Hissing sound heard continuously
when cooling
Hissing sound heard when staring
or stopping
Slight hissing sound heard when
running or after running
Creak sound heard when running
or after running
Started up after long time’s doesn’t
runs
When running
The overload protects switch
makes it run after 3 minutes delay.
Run for about 1 minute without
other actions
The high humidity air in room is
cooled rapidly
Sound of initialization for electric
expand valve
The sound for gas refrigerant
owing in the unit
The sound for gas refrigerant
stops ow
Sound for running of drainage
system
The grating sound caused by
expands of panel and other parts
for the change of temperature
Dust in indoor unit be blown out
This is because when air
conditioning, odors or cigarette
smoke from the room that was
sucked in is discharged again.
5.4 After-sales Service
When having quality or other problems when purchasing air conditioner, please contact the local
service center.
13
Page 78
Maintenance Method
6 Maintenance Method
When air conditioner won’t be used for a long time, please cut off the main power supply
of air conditioner.
Warning!
Do turn off the unit and cut off the main power supply when cleaning the air conditioner,
◆
otherwise electric shock or harm may happen.
It is forbidden to wash air conditioner by water rinsing, otherwise electric shock may happen.
◆
6.1 Cleaning air lter
Air lters should be cleaned by professionals with proper operation to ensure personal safety.
When the usage environment has lots of dust, air lter should be cleaned more frequently (about
once 6 months).
(1). Open air inlet grille
Loosen two screws on the air inlet grille with a screwdriver. And
grille at the same time with the direction showed by arrow in g.17, pull down slowly. (Reverse when
closing)
(2). Disassembly air lter
As shown in fig.18, pull the handle behind air inlet grille, raise it and disassembly. Then
discharge the 3 purier xed on lter.
pull the 2 handle on air inlet
Fig.17Fig.18
(3). Clean
Adopts cleaner or water to wash lter; if the lter is too dirty ( like oil stain on it ), adopts warm
water ( lower than 45℃) with neutral scourer to clean it, then dry it in the shade.
Note
Do not clean the filter by hot water whose temp. is higher than 45
deformation.
Do not burn it on re or the lter would catches re or deformation.
(4). Install air lter
Fix the 3 puriers on lter, install lter on the several bulges on top of air inlet grille, pull the
handle behind air inlet grille toward inside to x lter. As shown in g.19.
!
14
to prevent fade or
℃
purifier
Page 79
Maintenance Method
(5). Close air inlet grille (Refer to the 1st step)
Maintenance Method
Fig.19Fig.20
6.2 Clean air inlet grille
(1). Open air inlet grille (the same with the 1st step of Clean Air Filter)
(2). Take out air lter (the same with the 2nd step of Clean Air Filter)
(3). Take out air inlet grille
Open air inlet grille for an angle of 45°, as shown in g.20, rise it.
(4). Clean
Clean it by pubescence brush, water and neutral cleaning, then throw water or dry it.
Note
!
Do not use water above 45℃ to wash the panel to prevent fade or deformation.
(5). Install air inlet grille (refer to 3rd step)
(6). Install air lter (refer to the 4th step of Clean Air Filter)
(7). Close air inlet grille (refer to the 1st step)
6.3 Install and change of air purier
(1). Open air inlet grille (the same the 1st step of Clean Air Filter)
(2). Disassembly purier
As shown in g.21, disassembly air lter, screw out xing bolts xed on purier on lter, then
purier could be disassembly.
(3). Take out the package sack of static ber net lter, then install the lter in stand of purier,
and x purier on air lter.
(4). Install air lter (the same with the 4th step of Clean Air Filter)
Air filter
Purifier filter
Stand for purifier
Fix bolt of
purifier
Fig.21
15
Page 80
Maintenance Method
Function and usage period for air purifying
Could adsorb CO, CO
◆
Could adsorb deleterious material that is smaller than 1μm in air, as dust, pollen, bacteria,
◆
and virus.
Usage period is 6 months to 1 year. If it is necessary to be changed, purchase new purier in
◆
the nearest Impecca special engaged maintenance
center. 6.4 Clean Outlet vent and Surface
Clean the surface panel by soft dry cloth or wet cloth with neutral scourer.
◆
Panel
It is forbidden to clean surface panel by gasoline, benzene, diluents, cleansing powder etc..
◆
If the guide louver is too dirty, it may be removed to be cleaned. (As narrated below)
◆
Disassembly and install of guide louver
(1). Disassembly guide louver
Screw bolts in both end of guide louver to loose.
Note
Do not wipe guide louver powerfully when cleaning, otherwise uff on surface would fall off.
(2). Install guide louver
Rotate guide louver slightly could install the protruding edge of both end into grooves on both
end of guide louver, and then tighten bolts.
!
, benzene, aldehydes and odor of gasoline etc..
2
6.5 Maintenance before or after usage season
Check before the usage season
Check if there is blockage in inlet or outlet vent of air conditioner.
◆
Check if the earthing wire had earthed reliably.
◆
Check if the air lter had been installed well.
◆
In order to start up the air conditioner smoothly after long time’s turned off, turn on the main
◆
power supply 8 hours before turning on the air conditioner.
Maintenance after usage season
Clean lter and body of air conditioner.
◆
Cut off the main power supply of air conditioner.
◆
The cooling or heating capacity and sound level are tested before leaving factory.
◆
If the parameter changed, refer to the data offered on nameplate.
◆
6.6 CUSTOMER SUPPORT
Before contacting customer support, please see the troubleshooting guide above.
Visit our website to contact us, find answers to Frequently Asked Questions, and for other resources which
may include an updated version of this user's guide.
WWW.IMPECCA.COM
If you wish to contact us by phone, please be sure to have your model number and serial number ready
and call us between 9:00am and 6:00pm ET, at +1 866-954-4440.
Keep tabs on Impecca's newest innovations & enter contests via our social network feeds: