IMO Emergency Stop Relay User Manual

www.imopc.com
Operating voltage 24VDC, 115, 230VAC Voltage tolerance ±10% Power consumption Approx 1VA Control voltage on T11 24VDC Control current Approx 40mA Contacts 2 n/o safety-contacts Maximum, switching voltage 250VAC Switching capacity of contacts AC: 250V, 1500VA, 6A, DC: 24V, 30W, 1.25A Minimum current (contacts) 24V, 20mA Fuse external (contacts) 4A Terminals Screw, maximum 2.5mm
2
Contact material AgCdo Mechanical life 1 x 10 (7) switching operations Electrical service life 1 x 10 (5) switching operations Temperature range -15 +55˚C (DC) -15 to +40˚C (AC) Conforms to VDE0113, part 1/06.93, EN60204-1:1992 EN954-1:1996
SR2C/03/03
Emergency Stop Relay (type 4) SR2C
Extremely compact universal emergency stop relay. Designed to be used in safety-circuits in accordance with EN60204-1
Operating voltage 24VDC to 230VACCompact housing 22.5mmForce-guided contactsSelf monitoring with redundancyOne or two channel emergency stop circuitCross short-circuit monitoringSafety category 4 and stop category 0Conforms to EN60204-1, VDE0113-1, EN954-1
Specification
Dimensions (mm)
Description
The IMO safety relay SR2C is equipped with force-guided and redundant relays (two safety relay contacts) enabling the SR2C to interrupt quickly and safely the dangerous parts of the machine.
Additionally each ON/OFF cycle ensures an automatic functional monitoring, which ensures that if a safety circuit failure occurs NO switching ON is impossible (self-monitoring).
Applications include one and two channel emergency stop and two channel safety guard monitoring. A single-fault occurrence does not lead to the loss of the safety function. It will be recognised at or before the next requirement of the safety function. The SR2C satisfies stop category 0 EN60204-1 and type 4 safety category of EN954-1.
Y
E
A
R
G
U
A
R
A
N
T
E
E
22.5
114
99
www.imopc.com
Emergency Stop Relay (type 4) SR2C
continued
SR2C/03/03
Wiring connections
Two channel emergency stop with cross short-circuit monitoring and shorting to ground
To activate the cross-circuit monitoring T11 and T14 must be connected. The emergency stop button will be looped in lines T11-T12 and T10-T13, ON and RESET will be connected between T12 and T21. To activate the detection of shorting to ground T10 needs to be connected with PE. After connecting the power supply to A1 and A2 the safety contacts can be actuated via the ON button.
One channel emergency stop
In accordance with EN954-1, the SR2C can be used as an emergency stop relay with a single-channel push button. For this purpose T10 and T13 as well as T12 and T14 need to be connected. The one channel emergency stop button is looped in line between T11­T12/T14. Ground shorting is available in this application if T10 is connected with PE.
Two channel safety guard monitoring with cross short circuit and ground monitoring
This application conforms to the two channel emergency stop standard, however the emergency stop button is replaced by two limit switches, which monitor the guard door. At least one of the limit switches should be positive force opening (see IMO Safety Limit Switches).
Emergency stop
Emergency stop
On
A1
only 24V
only 24V
only 24V
only 24V
only 24V
only 24V
T11
T21
T12
T13
13
23
14
Relay control and error
monitoring incl. aux relay K1
Relay control and error
monitoring incl. aux relay K1
K1
K2
+
T14
24
A2
T10
Safety guard closed
On
A1
T11
T21
T12
T13
13
23
14
24
K1
T14
K2
A2
T10
On
A1
T11
T21
T12
T13
13
23
T10
Relay control and error
monitoring incl. aux relay K1
K1
K2
T14
14
24
A2