IMO DIN Rail Mounting PID Temperature User Manual

www.imopc.com
DIN Rail Mounting PID Temperature/ Process Controller DTP40with Comms Option
DIN rail mounting dual display 4 digit PID process/ temperature controller with auto-tuning.
Multi-input selectable One alarm standard PID controller or transmitter modesPID with Auto-tune, PD or on/off modesRS485 Communication option with IMO/ModbusHeater Burnout alarm optionCompact size - 22.5mm wideConforms to UL/CSA & CE
Options and ordering codes
DTP40/03/03
Y
E
A
R
G
U
A
R
A
N
T
E
E
DTP40A R M C5 240AC
Relay output Signal Voltage for SSR Analogue Current 4-20mA Analogue Voltage 0 – 10V
Multi-
sensor
Input
100-240VAC supply 24VAC/DC supply
Heater burnout Alarm 5A rated Heater burnout alarm 10A rated RS485 serial communications
R S A V
240AC 24VAC
W(5A)
W(10A)
C5
-/
Input type Scale
K
0 to 1370°C 0 to 2500°F
0 to 400°C 0 to 750°F J 0 to 1000°C 0 to 1800°F R 0 to 1760°C 0 to 3200°F S 0 to 1760°C 0 to 3200°F
Thermocouple B 0 to 1820°C 0 to 3300°F
E 0 to 800°C 0 to 1500°F T -199.9 to 400.0°C -199.9 to 750.0°F N 0 to 1300°C 0 to 2300°F PL-II 0 to 1390°C 0 to 2500°F C (W/Re5-26) 0 to 2315°C 0 to 4200°F
Pt100
-200 to 850°C -300 to 1500°F
RTD
-199.9 to 850.0°C -199.9 to 999.9°F
JPt100
-200 to 500°C -300 to 900°F
-199.9 to 500.0°C -199.9 to 900.0°F
DC
4 to 20mA DC 0 to 20mA DC 0 to 1V DC
-1999 to 9999-199.9 to 999.9
DC
0 to 10V DC
-19.99 to 99.99-1.999 to 9.999
1 to 5V DC
• As for DC input, scaling and decimal point place change are possible.
• As for DC current input, shunt resistor 50is needed as an external device.
Input ranges
DIN rail mounting
controller with
one alarm
Note: For DC current output type [Option: W] cannot be added
www.imopc.com
DTP40 continued
DTP40/03/03
Display
PV [Red 4 digits, Character size: 7.5 x 4.1mm (H x W)], SV [Green 4 digits, Character size: 7.5 x 4.1mm (H x W)]
Input: Thermocouple
External resistance: 100or less (However, for B input: 40or less)
Input: RTD
3-wire system (Allowable input wire resistance per wire: 10or less)
Input: DC Current
Input impedance: 50(Connect shunt resistor 50between input terminals.) Allowable input current: 50mA or less (When shunt resistor 50is used)
Input: DC Voltage (0-1V)
Input impedance: 1Mor greater Allowable input voltage: 5V or less Allowable signal source resistance: 2kor less
Input: DC Voltage (0-5V, 1-5V, 0-10V)
Input impedance: 100kor greater Allowable input voltage: 15V or less Allowable signal source resistance: 100or less
Accuracy: Thermocouple (Setting • Indicating) Within ±0.2% of each input span ±1 digit or ±2°C (4°F) whichever is greater However, R or S input 0 to 200°C (0 to 400°F): Within ±6°C(12°F), B input 0 to 300°C (0 to 600°F): Accuracy is not guaranteed. K, J, E, and N input less than 0°C (32°F): Within ±0.4% of each input span ±1 digit
Accuracy: RTD (Setting • Indicating) Within ±0.1% of each input span ±1 digit or ±1°C (2°F) whichever is greater
Accuracy: DC Current & V (Setting • Indicating) Within ±0.2% of each input span ±1 digit
Input sampling period 0.25 seconds Output: Relay types
SPNO/NC: 3A 250V AC Resistive load, 1A Inductive load cosϕ=0.4
Output: signal voltage types
12VDC +2VDC/-0VDC, Max. 40mA (Short-circuit protected)
Output: analogue current 4 to 20mA DC Load resistance: Max. 550 Output: analogue voltage 0-10VDC – Output impedance 500 Control action
User selectable: PID (with auto-tuning function), PI, PD (with manual reset function), P (with manual reset function), ON/OFF
Proportional band (P) 0.0 to 110.0% Integral time (I) 0 to 1000 seconds Derivative time (D) 0 to 300 seconds Proportional cycle 1 to 120 seconds (Not available for DC current output type) ARW 0 to 100% Hysteresis
Thermocouple and RTD: 0.1 to 100.0°C (°F ) DC current and DC voltage: 1 to 1000
Alarm (A1) Open collector, Control capacity: 24Vdc 0.1A Max.
Alarms action
ON/OFF action, Hysteresis 0.1 to 100.0°C (°F) (1 to 1000 analogues) Alarm Functions Alarm Function and NO/NC can be selected by key operation.
• No alarm
• High limit alarm (Deviation setting)
Setting range: -(Input span) to Input span
• Low limit alarm (Deviation setting) Setting range: -(Input span) to Input span
• High/Low limits alarm (Deviation setting) Setting range: 0 to Input span
• High/Low limit range alarm (Deviation setting) Setting range: 0 to Input span
• Process high alarm
Setting range: Input range low limit value to Input range high limit value
• Process low alarm
Setting range: Input range low limit value to Input range high limit value
• High limit alarm w/standby (Deviation setting) Setting range: -(Input span) to Input span
• Low limit alarm w/standby (Deviation setting) Setting range: -(Input span) to Input span
• High/Low limits alarm w/standby (Deviation setting) Setting range: 0 to Input span
The negative low limit value is -199.9 or -1999 and the positive high limit value is 999.9 or 9999
Supply voltage
85 to 264VAC 50/60Hz (100 to 240VAC +10% -15%), 20 to 28VDC/AC 50/60Hz
Power consumption Approx. 6VA Insulation resistance >10Mat 500VDC Dielectric strength
1.5kV AC for 1min between input terminal and ground terminal, between input terminal and power terminal, between power terminal and ground terminal, between output terminal and ground terminal, between output terminal and power terminal
Ambient temperature 0 to 50°C Ambient humidity 35 to 85%RH (No condensation) Mounting DIN rail mounting External dimension 22.5(W) x 75(H) x 100(D)mm Weight Approx. 150g Case material Light grey flame resisting resin Standard functions
Sensor correction, Setting value LOCK, Power failure countermeasure, Self diagnosis, Automatic cold junction temperature compensation (Only thermocouple), Sensor burnout alarm, Input burnout.
Specification
www.imopc.com
DTP40/03/03
DTP40 continued
Optional features
Heater burnout alarm [W]
This function watches the heater current with a CT (current transformer), and detects the burnout.
Heater rated current must be selected from 5A, 10A, 20A and 50A. The heater burnout alarm will use the alarm 1 output
Serial communication [C5]
Various setting status changing, reading and setting of the TP Series can be performed from external computer, HMI or PLC.
Communication interface Based on EIA, RS-485 Communication method Half-duplex communication start-stop synchronous Data transfer rate (2400/4800/9600/19200bps) Select by key operation Communication protocol Based on IMO standard protocol or Modbus
(Selectable by key operation) When Modbus is selected, RTU mode or ASCII mode can be selected by key operation.
Number of connectable units A maximum of 31 units per communication port Communication error detection Parity check and Checksum
Key R/_ Relay contact ouput S/_ Non-contact voltage out A/_ DC Current output RS485 Serial communications EVT Alarm output
RS-232C
Communication converter
RS-485
Communication cable (sold separately)
CPM (3M)
CPP
PC
PC
Wiring connections
3 4
1 234
+
-
+
-
+
-
+
-
+
-
Vdc
RTD
TC
mAdc
56
567
ABC
EVT
R/
S/ or A/
100 t0 240Vac or 24Vadc
56789
Lower part of main body
CT input W
Communication C5 (RS-485)
COM
NC
YA (-)
YB (+)
NC
COM
1
1
2
3
4
5
6
6
Dimensions mm
100
97
22.5