Immergas VICTRIX PRO 55 1 A User's Installation And Operation Manual

User Installation
Instruction Manual
AU
VICTRIX PRO
55 1 A
Wall mounted
heating only boiler
Our compliments for having chosen a top-quality Hunt Heating/Immergas product, able to assure well-being and safety for a long period of time, you can also count on a qualied aer-sales service, prepared and updated to guarantee constant eciency of your boiler. Read the following pages carefully; you will be able to draw useful suggestions regarding the correct use of the appliance, the respect of which, will conrm your satisfaction for our product. For any interventions or routine maintenance contact Hunt Heating for Authorised Service Personal.
Dear Client,
All Immergas products are protected with packaging suitable for transport.
e material must be stored in dry environments and protected from bad weather.
e instruction book is an integral and essential part of the product and must be consigned to the new user also in the case of transfer or succession of ownership.
It must be stored with care and consulted carefully, as all of the warnings provide important safety indications for installation, use and maintenance stages.
is instruction booklet contains technical information on how installing Immergas boilers. For other issues related to installation of boilers (i.e.: safety in work sites, environment protection, injury prevention), comply with the laws in force and technical standards.
In compliance with legislation, the systems must be designed by qualied professionals, within the dimensional limits established by the Law. Installation and maintenance must be performed in compliance with the regulations in force, according to the manufacturer’s instructions and by qualied professionals.
Improper installation or assembly of Immergas appliance and/or components, accessories, kit and devices can cause unexpected problems to persons, animals and objects. Read the provided product instructions carefully in order to install the product correctly.
Maintenance must be carried out by Authorised Service Personal.
e appliance must only be destined for the use for which it has been expressly declared. Any other use will be considered improper and therefore potentially dangerous.
If errors occur during installation, operation and maintenance, due to non compliance with technical laws in force, standards or instructions contained in this book (or however supplied by the manufacturer), the manufacturer is excluded from any contractual and extra-contractual liability for any damages and the appliance warranty is invalidated.
e Immergas range of high eciency boilers are wall mounted, fan assisted, room-sealed boilers. e burner is lit electronically and the heat output is controlled by a modulating gas valve. e VICTRIX PRO 55 1A is a heating only boilers used for hydronic heating. Domestic hot water is an available option (Hunt Heating only) used in con­junction with a stainless steel hot water storage tank, diverter valve and probe. e boilers are supplied with a pump, pressure relief valve, pressure gauge fully assembled and tested. ey are designed for use with a fully sealed and pressurised central heating system using only Natural Gas or LPG. e VICTRIX PRO 55 1A is suitable for central heating loads of between 5,0 and 49,9 kW.
General recommendations
Introduction
IMPORTANT
It is the law that all gas appliances are installed by a qualied and registered technician in accordance with local laws and AS/NZS 5601.
is appliance meets the requirements of IPX5D. Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the law is complied with.
Manufacturerís instructions must NOT be taken in anyway as over-riding statutory obligations.
WARNINGS
- Do not spray aerosols in the vicinity of this appliance while it is in operation;
- do not use or store ammable materials in or near this appliance;
- do not place articles on or against this appliance;
- do not modify this appliance.
NOTE e Boilers MUST only be used with Immergas Condensing ue components. THIS BOILER IS NOT SUITABLE FOR POOL OR SPA HEATER UNLESS CONNECTED TO A SUITABLE APPROVED HEAT EXCHANGER.
On conformity to AS/NZS 5263.1.2
e manufacturer declines all liability due to printing or transcription errors, reserving the right to make any modications to its technical and commercial documents without prior notice.
INDEX
USER page INSTALLER page MAINTENANCE TECHNICIAN page
1 Boiler installation .......................................5
1.1 Installation recommendations. ................. 5
1.2 Position of the appliances. ........................ 6
1.3 Aeration and Ventilation of
the installation rooms. ...............................6
1.4 Outdoor installation. ..................................6
1.5 Anti-freeze protection. ...............................6
1.6 Main dimensions. .......................................7
1.7 Connection. ................................................. 7
1.8 Hydraulic connection. ................................7
1.9 Electric connection. .................................... 8
1.10 Optional boiler controllers. .......................9
1.11 External temperature probe. .....................9
1.12 Immergas ue systems. ............................ 10
1.13 Tables of equivalent length factors. ........ 11
1.14 Concentric horizontal kit installation. ... 12
1.15 Concentric Vertical kit installation. .......13
1.16 Installation of vertical terminals 80 ø. ...14
1.17 Installation of 80 ø horizontal terminals. 15
1.18 Flue exhaust with boilers in cascade. .....16
1.19 System lling. ............................................16
1.20 Condensate trap lling. ............................16
1.21 Gas system start-up. .................................16
1.22 Boiler start up (ignition). .........................16
1.23 Circulation pump......................................17
1.24 Kits available on request. .........................17
1.25 Boiler components. ...................................18
1.26 Hydraulic diagram with optional. ..........19
1.27 Installation examples of
individual boiler. .......................................20
2 Use and maintenance instructions .........21
2.1 Cleaning and maintenance. .....................21
2.2 Aeration and Ventilation of
the installation rooms. .............................21
2.3 General warnings. ..................................... 21
2.4 Control panel.............................................22
2.5 Using the boiler. ........................................22
2.6 Troubleshooting. .......................................24
2.7 Info menu. .................................................26
2.8 Boiler shutdown. ......................................26
2.9 Restoring central heating
system pressure. ........................................26
2.10 System drainage. ...................................... 26
2.11 Anti-freeze protection. .............................26
2.12 Case cleaning. ............................................ 26
2.13 Decommissioning. ....................................26
3 Boiler commissioning
(initial check). ...........................................27
3.1 Hydraulic diagram. ...................................27
3.2 230 v circuit wiring diagram. ..................28
3.3 very low voltage wiring diagram. ...........29
3.4 D.H.W. pump boiler and tank probe
wiring diagram. .........................................30
3.5 Common ow probe and 3-way
boiler wiring diagram...............................30
3.6 Simple cascade boiler with D.H.W. pump
and tank probe wiring diagram. .............30
3.7 Troubleshooting. .......................................31
3.8 Programming the boiler P.C.B. ............... 31
3.9 Converting the boiler to
other types of gas. .....................................34
3.10 Checks following conversion to another
type of gas. ................................................. 34
3.11 Adjustment of the air-gas ratio. .............. 34
3.12 CH output adjustment. ............................34
3.13 Output adjustment during DHW (only in combination with an optional
external storage tank). ..............................34
3.14 “Chimney Sweep” function. .................... 34
3.15 3-way pump anti-block function
(optional). ..................................................35
3.16 Radiators anti-freeze function. ...............35
3.17 Anti-humidity electrode function. .........35
3.18 Inlet 0 ÷ 10 V. ............................................ 35
3.19 Functioning with common ow probe. .35
3.20 Autodetection. ...........................................35
Simple cascade (max. 2 boilers) ................35
3.21
3.22 Yearly appliance check
and maintenance. ......................................36
3.23 Casing removal. ........................................37
3.24 Variable heat output. ................................39
3.25 Combustion parameters. .........................40
3.26 Technical data. ..........................................40
3.27 Exploded boiler diagram. ........................41
3.28 Spare part list. ............................................42
3.29 Boiler registration. ....................................43
3.30 Commissioning boiler check list. ...........44
3.31 Service records. ......................................... 45
BOILER
1
INSTALLATION

1.1 INSTALLATION RECOMMENDATIONS.

Only professionally qualied heating/plumbing technicians are authorised to install Immergas gas appliances.
Victrix Pro 55 1A boilers in individual or cascade installation can be installed outdoors or in a suitable room. e installation must comply with all laws and standards in force. e place of installation of the appliance and relative Immergas accessories must have suitable features (technical and structural) such to allow (always in safety, efficiency and comfortable conditions):
- installation (according to the provisions of the
technical legislation and technical regulations);
- maintenance operations (including scheduled,
periodic, routine and special maintenance);
- removal (to outdoors in the place for loading
and transporting the appliances and compo­nents) as well as their eventual replacement with appliances and/or equivalent components.
Installation must be carried out according to regulation standards AS/NZS 5601 or Local Authority laws.
Attention: these boilers must be used to heat
rooms and the like; they are for heating water to a temperature lower than boiling point at atmospheric pressure. erefore, they must be connected to a heating system that is suitable for their performance and their power.
Attention: Immergas declines all liability for damages caused by boilers removed from other systems or for any non-conformities of such equipment.
Before installing the appliance, ensure that it is delivered in perfect condition; if in doubt, contact Hunt Heating immediately. Packaging materials (staples, nails, plastic bags, polystyrene foam, etc.) constitute a potential haz­ard and must be kept out of the reach of children. Keep all ammable objects away from the ap­pliance (paper, rags, plastic, polystyrene, etc.). In the event of malfunctions, faults or incorrect operation, turn the appliance o and contact the installer before contacting Hunt Heating. Do not attempt to modify or repair the appli­ance alone. Failure to comply with the above implies personal responsibility and invalidates the warranty.
- Installations MUST comply with AS/NZS
5601 and Local laws. Use AS/NZS 5601 as a guide for specic locations see below.
• Installation regulations: these boilers are not in any way designed for installation on bases or oors (Fig. 1-1), but exclusively for wall installation. e wall surface must be smooth, without any protrusions or recesses enabling access to the rear part. Wall mounting of the boiler must guarantee stable and ecient sup­port for the boiler. e plugs (standard supply)
are to be used only in conjunction with the mounting brackets or xing template to x the appliance to the wall; they only ensure adequate
support if inserted correctly (according to technical standards) in walls made of solid or semi-hollow brick or block. In the case of walls made from hollow brick or block, partitions
with limited static properties, or in any case walls other than those indicated, a static test must be carried out to ensure adequate support. e boilers must be installed in a way to prevent collisions and tampering.
N.B.: the hex head screws supplied in the bli­ster pack are to be used exclusively to x the mounting bracket to the wall.
N.B.: it is recommended to use a suitable ‘Safe Tray’, if boiler is installed in a lo, above a cei­ling, or any area where damage can be caused by water.
YES
NO
1-1
INSTALLERUSER
Flue terminal positions
Use as a guide only. Refer to AS/NZS 5601 or gas tting rules for specic location.
D - Door
a
j
W
f
c
k
j
D
I
k
h
T
e
j
h
h
T
g
e
P
c
d
g
M
k
b
T
I - Mechanical air inlet M - Gas meter T - Flue Terminal W - Window
Flue terminal positions. Shaded area indicates prohibited area
Ref. Item Min. Clearance mm
Below eaves, balconies and other projections (Appliances over 50MJ/h) 300
a
From the ground, above a balcony or other surface 300
b
From a return wall or external wall 300
c
From a gas meter 1000
d
From an electricity meter or fusebox/breaker panel 500
e
From a drain pipe or soil pipe 75
f
Horizontally from any building structure or obstruction facing a ue terminal 500
g
From any other ue terminal, cowl or combustion air intake 300
h
Horizontally from any opening window, door, non-mechanical air inlet or other opening into a building with the exception of sub-oor ventilation 300
j
From a mechanical air inlet including a spa blower 1000
k
Vertically below an opening window, non-mechanical air inlet or any other opening into a building with the exception of sub-oor ventilation 500
n
• e location of the ue terminal must comply with the clea­rances shown on this page.
If you are unsure about clearances not indicated here, in general refer to AS 5601 or your local autority.
• All measurements are the minimum clearances required.
• Terminals must be positioned so to aviod combustion products entering the building.
MAINTENANCE TECHNICIAN
1-2
5

1.2 POSITION OF THE APPLIANCES.

e boilers can be installed:
- outdoors;
- in outdoor environments, also adjoining the building served, located in uncovered space, as long as structurally separated and without walls in common, or situated on the at covering of the building served, always without walls in common;
- in building also destined for other use or in places inserted in the volume of the building
INSTALLERUSER
served.
ese rooms must be intended exclusively to house CH systems and must have characteristics that comply with legislation in force.
Attention: the installation of appliances powered with gas with a greater density than 0.8 (L.P.G.) is only allowed in places out of the ground, also communicating with places that are on the ground. In both cases the walkway must not have hollows or depressions such to create gas pockets that determine dangerous conditions.
Height of the installation room.
Installation of individual appliance: the room must have a minimum ceiling height of 2 m.
Installation of multiple appliances in cascade: con­sidering the size of the boiler, the ue manifold (which must be installed on a 3% gradient) and the hydraulic manifolds, the room must have a minimum ceiling height of 2.3 m.
e aforementioned heights allow for correct installation of the appliances and observe the technical regulations in force.
Position of the appliances in the room.
Individual appliance: the distances between any external point of the boiler and the vertical and horizontal walls of the room must allow accessibility to the regulation, safety and control elements for routine maintenance.
Multiple appliances, not interconnected, but in­stalled in the same room: the minimum distance
to maintain between several boilers installed on the same wall must be 200 mm, in order to allow accessibility to the regulation, safety and control elements and routine maintenance of all appliances installed.
Cascade installation: e instructions for correct cascade installation are provided in the respec­tive documents or on the www.immergas.com
MAINTENANCE TECHNICIAN
website in the high power section.

1.3 AERATION AND VENTILATION OF THE INSTALLATION ROOMS.

e rooms must have one or more permanent openings for aeration on external walls. The openings used for aeration can be protected using metal grills, meshes and/or rain-proof ns as long as the net aeration surface is not reduced.
Aeration for installation in outdoor places. e minimum free surfaces, in relation to the overall heat input must not be below: a) above-ground rooms (S ≥ Q x 10)
S > 515 cm
(ex: to install 3 Victrix Pro 55 1A in cascade,
the minimum surface is 515 x 3 = 1545 cm
2
for every Victrix Pro 55 1A
2
b) basements and underground rooms up to a
height of -5 m from the reference surface (S ≥ Q x 15).
S > 775 cm
(ex: to install 3 Victrix Pro 55 1A in cascade,
the minimum surface is 775 x 3 = 2325 cm
2
for every Victrix Pro 55 1A
2
c) underground rooms at quota between -5 m
and -10 m from the reference surface (S ≥ Q x 20 with a minimum of 5000 cm
S > 5000 cm
2
for all congurations
In all cases each opening must not have a net surface area less than 100 cm
2
).
2
.
Attention: in the case of installation of appliances powered with gas with greater density than 0.8 (L.P.G.) in outdoor places, above-ground, at least 2/3 of the aeration surface must be ush with the oor, with a minimum height of 0.2 m. e aeration openings must be at least 2 m for heating capacities not exceeding 116 kW and 4.5 m for higher heating capacities, cavities, depres­sions or openings communicating with rooms below the walkway surface or draining ducts.
Aeration for installation in building also des­tined for other use or in places inserted in the volume of the building served. e aeration
surface must not be less than 3000 cm
2
in the case of natural gas and must not be less than 5000 cm2 in the case of L.P.G..
e installation must comply with the require­ments of all relevant codes and standards.

1.4 OUTDOOR INSTALLATION.

e boiler has an IPX5D electric insulation rat­ing and can also be installed outdoors, without additional protections.
Attention: all optional kits that can be potentially connected to the boiler must be protected on the basis of their electrical protection rating.
1.5 ANTIFREEZE PROTECTION. Minimum temperature -5°C. e boiler comes
standard with an anti-freeze function that ac­tivates the pump and burner when the system water temperature in the boiler falls below 5°C. e anti-freeze function is only guaranteed if:
- the boiler is correctly connected to gas and electricity power supply circuits;
- the boiler is powered constantly;
- Main switch is inserted;
- the boiler is not in no ignition block
- the boiler essential components are not faulty.
In these conditions the boiler is protected against freezing to an ambient temperature of -5°C.
)
Minimum temperature -15°C. If the boiler is installed in a place where the temperature falls below -5°C and in the event there is no gas (or the boiler goes into failed ignition block), the appliance can freeze.
To prevent the risk of freezing follow the instructions below:
)
- Protect the central heating circuit from freezing by inserting a good-quality antifreeze liquid into this circuit, which is specially suited for central heating systems and which is manufacturer guaranteed not to cause damage to the heat exchanger or other components of the boiler.
e antifreeze liquid must not be harmful to
one’s health.
. e instructions of the manufacturer of this
liquid must be followed scrupulously regarding the percentage necessary with respect to the minimum temperature at which the system must be kept. An aqueous solution must be made with a potential water pollution class of 2 (EN 1717:2002 or local regulations in force).
e materials used for the central heating circuit of Immergas boilers withstand ethylene and propyl­ene glycol based antifreeze liquids (if the mixtures are prepared perfectly).
For life and possible disposal, follow the supplier’s instructions.
- Protect the condensate drain trap and relative drain against freezing by using an accessory supplied on request (anti-freeze kit) comprising two electric resistances, the relevant cables and a control thermostat (carefully read the instal­lation instructions contained in the accessory kit pack).
Boiler anti-freeze protection is thus ensured only if:
- the boiler is correctly connected to electricity power supply circuits;
- main switch is inserted;
- the anti-freeze kit components are ecient.
In these conditions the boiler is protected against freezing to temperature of -15°C. e warranty does not cover damage due to inter­ruption of the electrical power supply and failure to comply with that stated on the previous page.
6

1.6 MAIN DIMENSIONS.

INSTALLERUSER
Key: V - Electrical connection G - Gas supply R - System return F - System ow SC - Condensate drain (minimum
internal diameter Ø 13 mm)
Height (mm) Width (mm) Depth (mm)
843 442 457
Connections
GAS SYSTEM
G R M
3/4” 1”1/2 1”1/2

1.7 CONNECTION. Gas connection.

Our boilers are designed to operate with natural gas (G20) and L.P.G. Supply pipes must be the same as or larger than the 3/4” G boiler tting.
N.B.: the gas supply pipe must be suitably di­mensioned according to current regulations in order to guarantee correct gas ow to the burner even in conditions of maximum generator output and to guarantee appliance eciency (technical specications). e connection to the gas supply must conform to standards. Before connecting the gas line, carefully clean inside all the fuel feed system pipes to remove any residue that could impair boiler eciency. Also make sure the gas corresponds to that for which the boiler is prepared (see boiler data-plate). If dierent, the appliance must be converted for operation with the other type of gas (see convert­ing appliance for other gas types). e dynamic gas supply (methane or L.P.G.) pressure must also be checked according to the type used in the boiler, which must comply with EN 437 and relative attachments and with the local technical regulations in force, as insucient levels can reduce generator output and cause malfunctions. Ensure correct gas cock connection. Install a manual cut-o valve with quick closure manoeuvre for 90° rotation and end run stops in the all open or all closed positions on the gas sup­ply pipe in a visible and easily reachable position outside the room where the appliance is installed.
N.B.: the internal gas supply system must be built in compliance with the provisions and regulations and all legislation in force, and any other reference on good technique.
Fuel gas quality. e appliance has been de­signed to operate with combustible gas free of impurities; otherwise it is advisable to t special lters upstream of the appliance to restore the purity of the fuel.
Storage tanks (in case of supply from LPG depot).
- New LPG storage tanks may contain residual inert gases (nitrogen) that degrade the mixture delivered to the appliance causing problems with boiler operation.
- Due to the composition of the LPG mixture, layering of the mixture components may occur during the period of storage in the tanks. is can cause a variation in the heating power of the mixture delivered to the appliance, with subsequent change in its performance.
1-3

1.8 HYDRAULIC CONNECTION.

Attention: in order not to void the condensation
module warranty, before making the boiler con­nections, carefully wash the CH system (pipes, radiators, etc.) with special pickling or descaling products to remove any deposits that could com­promise correct boiler operation.
A treatment of the heating and water system wa­ter is required, in compliance with the technical standards in force, in order to protect the system and the appliance from deposits (e.g. scale), slurry or other hazardous deposits.
It is recommended to prepare a filter in the system to collect and separate any impurities present in the system (slurry remover lter). In order to avoid deposits, scaling and corrosion in the central heating system, the provisions set forth in the technical regulation in force on water treatment in heating systems for civil use must be respected.
Water connections must be made in a rational way using the couplings on the boiler template. e discharge of the boiler safety valve must be connected to a tundish and then the waste should be connected to the sewer. Otherwise, the manufacturer declines any responsibility in case of ooding if the drain valve cuts in.
Cold Water connection.
Attention: Filling the system, Hunt Heating
recommends the use of Auto fill valves sold as an optional extra. Once satisfactory system pressure is achieved, Auto ll valve MUST BE TURNED OFF.
MAINTENANCE TECHNICIAN
7
Attention: Immergas and Hunt Heating declines all liability in the event of damage caused by the inclusion of automatic lling.
In order to meet the system requirements es­tablished by EN 1717 and in observance of local technical regulations in force on the pollution of drinking water, we recommend installing an anti-backflow kit to be used upstream of the cold water inlet connection of the boiler. We also recommend using a category 1, 2 or 3 heat transfer uid (ex: water + glycol) in the boiler’s primary circuit (CH circuit), as dened
INSTALLERUSER
in standard EN 1717.
Attention: to preserve the duration of appliance eciency features, we recommend the installation of a suitable device for water treatment in presence of water whose characteristics can lead to the deposit of lime scale.
Condensate drain. To drain the condensate produced by the appliance, it is necessary to connect to the drainage system by means of acid condensate resistant pipes, with an internal Ø of at least 13 mm. e system connecting the appliance to the drainage system must be carried out in such a way as to prevent freezing of the liquid contained in it. Before appliance ignition, ensure that the condensate can be correctly removed. N.B.: pre-ll the condense trap with water before operating the boiler. Also, comply with national and local regulations on discharging waste waters. In the event con­densate is not discharged into the wastewater drainage system, a condensate neutraliser must be installed to ensure compliance with the pa­rameters established by the legislation in force.

1.9 ELECTRIC CONNECTION.

e operations described below must be performed aer having disconnected the electrical supply from the appliance.
e electrical system must be built in compliance with technical standards and all legislation in force. e boiler has an IPX5D protection rating for the entire appliance. Electrical safety of the appliance is reached only when it is correctly connected to an efficient earthing system as specied by current safety standards.
Attention: Immergas S.p.A. and Hunt Heating decline any responsibility for damage or physical injury caused by failure to connect the boiler to an ecient earth system or failure to comply with the reference standards.
Also ensure that the electrical installation corre­sponds to maximum absorbed power specica­tions as shown on the boiler data-plate. Boilers are supplied complete with a power cable and Australian plug type 1 conforming to AS3112. The power supply cable must be connected to a 230V ±10% / 50Hz mains supply respecting L-N polarity and earth connection;
, this network must also have a multi-pole cir­cuit breaker with class III over-voltage category. The main switch must be installed outside the rooms in a position that is indicated and accessible. When replacing the power supply cable, contact a qualied company. e power cable must be laid as shown (Fig. 1-4). In the event of mains fuse replacement on the connection terminal board, use a 3.15A fast fuse. For the main power supply to the appliance, never use adapters, multiple sockets or exten­sion leads.
Important: if the Digital Remote Control is used, arrange two separate lines in compliance with current regulations regarding electrical sys­tems. No boiler pipes must ever be used to earth the electric system or telephone lines. Ensure elimination of this risk before making the boiler electrical connections.
Installation with system operating at direct low temperature. The boiler can directly supply a low temperature system, limiting the value of the “P02” parameter, which denes the generator’s ow temperature.
Attention: during the chimney sweep function,
the flow temperature is not limited by the “P02” parameter but instead by the maximum allowable temperature (97°C).
To avoid the risk of exceeding the optimal tem-
perature of operation in low temperature, due to external causes (e.g.: incorrect adjustment, prolonged system stop, etc.), you must insert in series with the supply voltage of the boiler, a special safety kit (optional) consisting of a thermostat (with adjustable temperature, de­pending on the characteristics of the system). The thermostat must be positioned on the system ow pipe at a distance of more than 2 metres from the boiler.
Attention: in gure 4 is described the standard
electrical connection with the pump connected to the terminals “Q” and “P”; in this way the external pump is fed making it run in parallel to the boiler pump. For specic installations refer to paragraphs 3.18 to 3.21.
MAINTENANCE TECHNICIAN
230 Vac
50Hz
Supply cable
1-4
External reset
230 Vac
ALARM
FREE CONTACTS
MAX 1 A. 230 Vac
8
EXTERNAL RELAY
(OPTIONAL)
230 Vac COIL
MAX 0.1 A
ANALOGUE
INPUT
1-5

1.10 OPTIONAL BOILER CONTROLLERS.

e boiler is prepared for the application of a cascade and zone regulator, zone manager and external probe. ese components are available as separate kits to the boiler and are supplied on request. Carefully read the user and assembly instructions contained in the accessory kit.
• e cascade and area regulator (Fig. 1-6) is connected to the boiler using only two wires, powered at 230 V and allows to:
- manage a hydraulic circuit with 2 mixed
zones (mixing valve); 1 direct zone; 1 Storage tank unit and relative pumps;
- self-diagnosis system to display any boiler
functioning anomalies;
- set two room temperature value: one for
daytime (comfort temperature) and one for nighttime (lower temperature);
- to manage the temperature of the DHW (with
a storage tank unit);
- to manage the boiler ow temperature de-
pending on the external temperature;
- to select the desired operating mode from
the various possible alternatives for each individual hydraulic circuit:
- permanent operation in comfort temp.;
- permanent operation in lower temp.;
- permanent operation in adjustable anti-freeze
temp.
• Zone manager (Fig. 1-7). In addition to the functions described in the previous point, the zone manager panel allows to control all the important information regarding operation of the appliance and the heating system with the opportunity of easily intervening on the previously set parameters without having to go to the place where the appliance is installed. e climate chrono-thermostat incorporated into the zone manager enables the system ow temperature to be adjusted to the actual needs of the room being heated, in order to obtain the desired room temperature with extreme precision and therefore with evident saving in running costs. It also allows to display the eective room temperature and the external temperature (if external probe is present). e zone manager is powered directly by the cascade heat adjuster via 2 wires.
ermostat electrical connection (Fig. 1-5).
ermoregulation electrical connections must be carried out on the boiler terminal board eliminating jumper X40.
-
Thermostat or On/Off environment chrono­thermostat: must be connected to clamps “E” and “F”. Make sure that the On/O thermostat contact is of the “clean” type, i.e. independent of the mains voltage, otherwise the P.C.B. would be damaged.
-
Cascade and zone regulator: must be con­nected through clamps 37 and 38 to clamps “M” and “O” respecting polarity. e connec-
tion with incorrect polarity will not damage the thermoregulator, but will not allow it to operate.

1.11 EXTERNAL TEMPERATURE PROBE.

e boiler is designed for the application of the Room ermostat (Fig. 1-8), which is available as an optional kit. Refer to the relative instruction sheet for positioning of the external probe. e probe can be connected directly to the boiler electrical system and allows the max. system ow temperature to be automatically decreased when the external temperature increases, in order to adjust the heat supplied to the system according to the change in external temperature. e electric connection of the external probe must take place on clamps G and J on the con­nection in the boiler (Fig. 1-5). By default, the external probe is not enabled. It is necessary to set parameters “P14” and “P15” for correct operation. e correlation between ow temperature to the system and external tempe­rature is determined by the curves represented in the diagram (parameter “P14”) and by setting the oset (parameter “P15”) (Fig. 1-9). In case “P32” is bigger than “P15”, “P32” will be the minimum limit for the set. In case “P32” is lower than “P15”, “P32” will not be considered.
N.B.: if the external probe is connected to the cascade regulator, boiler parameter “P14” must be set at “0”, and external probe control is dele­gated to the cascade regulator.
INSTALLERUSER
31
45
58
1-8
1-6 1-7
Note: this graph is prepared with the oset value (P15) at 30°C (default
value). By changing the oset value, the origin of the ow temperature curve will also change accordingly and not the inclination.
Ex: with Oset = 40 the graph origin is 40 and not 30 °C and curve 5
with TE = -4°C, TM goes from 60°C to 70°C..
9
MAINTENANCE TECHNICIAN
1-9

1.12 IMMERGAS FLUE SYSTEMS.

Hunt Heating can supply various solutions for ueing and air supply.
Attention: the boiler must be installed ex­clusively with an original Immergas “Green Range” inspectionable air intake system and fumes extraction system made of plastic, with the exception of the C6 conguration, as re­quired by the regulations in force.
e plastic pipes cannot be installed outdoors, for lengths longer than 40 cm, without suitable
INSTALLERUSER
protection from UV rays and other atmos­pheric agents.
is system can be identied by an identi­cation mark and special distinctive marking bearing the note: “only for condensing boilers”.
Conguration type B, open chamber and fan assisted. e boiler leaves the factory with type
“B
” conguration.
23
Air intake takes place directly from the envi-
ronment in which the boiler is installed via relevant slots made in the back of the boiler
and ue exhaust in the individual ue or to the outside. Boiler with this type of conguration are classied as type B standard EN 297 and relative standards in
(in accordance with
23
force).
With this conguration:
- air intake takes place directly from the room
in which the appliance is installed;
- the ue exhaust must be connected to its own
individual ue or channelled directly into the external atmosphere.
- Type B open chamber boilers must not be
installed in places where commercial, artisan or industrial activities take place, which use products that may develop volatile vapours or substances (e.g. acid vapours, glues, paints, solvents, combustibles, etc.), as well as dusts (e.g. dust deriving from the working of wood, coal nes, cement, etc.), which may be harm­ful for the components of the appliance and jeopardise operation.
Type C conguration, sealed chamber and fan assisted. e boiler leaves the factory with "B
" conguration, to change the conguration
23
of the boiler to type "C" (sealed chamber and fan assisted), disassemble the 80 Ø adapter, the bracket and the gasket present on the boiler cover and install the designated ue.
MAINTENANCE TECHNICIAN
N.B.: the 80 Ø adapter and gasket will be dis-
carded.
• Coupling extension pipes and concentric elbows. To install push-tting extensions with other elements of the ue, proceed as follows: Install the concentric pipe or elbow with the male side (smooth) on the female section (with lip seal) to the end stop on the previously installed element in order to ensure sealing eciency of the coupling.
Attention: if the exhaust terminal and/or
concentric extension pipe needs shortening, consider that the internal duct must always protrude by 5 mm with respect to the external duct.
N.B.: for safety purposes, do not obstruct the boiler intake-exhaust terminal, even temporar­il y.
N.B.: when installing horizontal pipes, a min­imum inclination of 3% must be maintained and a section clamp with pin must be installed every 1.5 metres.
Maximum extension. Each individual compo­nent has a resistance corresponding to a certain length in metres of pipe with the same diameter (par. 1.13). With installations that involve using various types of parts, deduct the length of the added part from the maximum admissible length of the kit.
Example: if you need to add a 90° bend to
a concentric system 125 Ø you will need to deduct 1.9 m from the maximum admissible length.
Positioning of the gaskets (black) for “green range” ue extraction systems. Position the gasket correctly (for bends and extensions) (Fig. 1-10):
- gasket (A) with notches, to use for bends;
- gasket (B) without notches, to use for exten-
sions;
N.B.: if component lubrication (already carried
out by the manufacturer) is not sucient, re­move the residual lubricant using a dry cloth, then to ease tting coat the parts with talc.
(A)
1-10
(B)
10

1.13 TABLES OF EQUIVALENT LENGTH FACTORS.

Equivalent length in
DUCT TYPE
Concentric pipe 80/125 Ø m 1
m of concentric pipe
80/125 Ø
1.0 m
DUCT TYPE
Pipe 80 Ø, 1 m
Equivalent length in
metres of pipe 80 Ø
Exhaust
1.0 m
Concentric bend 90° 80/125 Ø
Concentric bend 45° 80/125 Ø
Terminal complete with concentric horizontal intake-exhaust 80/125 Ø
Concentric horizontal intake-exhaust
terminal 80/125 Ø
Terminal complete with concentric verti-
cal intake-exhaust 80/125 Ø
Concentric vertical intake-exhaust
terminal 80/125 Ø
1.9 m
1.4 m
5.5 m
4.7 m
3.4 m
2.7 m
Complete exhaust terminal 80 Ø, 1 m
Exhaust terminal 80 Ø
Bend 90° 80 Ø
45° 80 Ø Bend
Terminal complete with vertical
exhaust 80 Ø
Exhaust
2.6 m
Exhaust
1.6 m
Exhaust
2.1 m
Exhaust
1.3 m
Exhaust
m 3
INSTALLERUSER
11
MAINTENANCE TECHNICIAN

1.14 CONCENTRIC HORIZONTAL KIT INSTALLATION.

Type C configuration, sealed chamber and fan assisted.
e position of the terminal (in terms of dis­tances from openings, overlooking buildings, decking, etc.) must be set up in compliance with technical regulations in force as well as the references of good technique (ex.: EN 15287) for generators with a single maximum nominal heat input of 35 kW and also for generators with a single maximum nominal heat input of 35 kW.
INSTALLERUSER
is terminal is connected directly to the outside of the building for air intake and ue exhaust. e horizontal kit can be installed with the rear, right side, le side or front outlet. For installation with frontal outlet, one must use the xing plate and a concentric bend coupling in order to ensure sucient space to carry out the tests required by law upon commissioning.
• e intake/exhaust terminal, if properly in-
stalled, is pleasant to look at on the outside of the building. Make sure that the external silicone sealing plate is properly inserted in the wall and that the ue is adequately sealed to the wall the ue passes through.
Horizontal intake-exhaust kit Ø 80/125 Kit assembly (Fig. 1-11): install the 80/125 Ø adapter (1) on the central hole of the boiler fully home. Slide the gasket (2) along the adapter (1) up to the relevant groove, x it to the lid using the previously disassembled sheet steel plate (3). Engage the bend (4) with the male side (smooth) until it is fully home on the adapter (1). Fit the Ø 80/125 (5) concentric terminal pipe with the male end (smooth) to the female end of the bend (4) (with lip seals) up to the stop; making sure that the internal (6) and external wall sealing plates (7) have been tted, this will ensure sealing and joining of the elements making up the kit.
• Maximum length (MAX L) (Fig. 1-12). e kit with this conguration can be extended up to a max. measurement of 14.5 m for Victrix Pro 55 1A, including the grid-covered terminal and the concentric bend on the boiler outlet.
MAINTENANCE TECHNICIAN
4
5
3
e kit includes:
2
Adaptor Ø 80/125 (1) Gasket (2)
1
Concentric bend Ø 80/125 a 87° (4) Int./exhaust concentric terminal 80/125 Ø (5) Internal ring (6) External ring (7)
6
7
C13
1-11
C13
1-12
12

1.15 CONCENTRIC VERTICAL KIT INSTALLATION.

Type C configuration, sealed chamber and fan assisted.
Concentric vertical intake and exhaust kit. is vertical terminal is connected directly to the out­side of the building for air intake and ue exhaust.
N.B.: the vertical kit with aluminium tile en­ables installation on terraces and roofs with a maximum slope of 45% (approx. 25°) and the height between the terminal cap and half-shell (260 mm) must always be observed.
Vertical kit with aluminium tile Ø 80/125.
Kit assembly (Fig. 1-13): install the 80/125 Ø adapter (1) on the central hole of the boiler fully home. Slide the gasket (2) along the adapter (1) up to the relevant groove, Fix it to the lid using the previously-disassembled sheet steel plate (3) Installation of the fake aluminium tile: replace the tiles with the aluminium sheet (5), shaping it to ensure that rainwater runs o. Position the xed half-shell (6) on the aluminium tile and insert the intake-exhaust pipe (7). Fit the 80/125 Ø concentric terminal pipe with the male end (6) (smooth) to the female end of the adapter (1) (with lip gasket) up to the stop; making sure that the wall sealing plate (4) has been tted, this will ensure sealing and joining of the elements making up the kit.
• Maximum length (MAX L) (Fig. 1-14). e kit with this conguration can be extended up to a max. measurement of 18.0 m with Victrix Pro 55 1A, including the terminal.
INSTALLERUSER
C33C33
8
7
6
5
4
3
2
e kit includes: Adaptor Ø 80/125 (1) Gasket (2) Ring (4) Aluminium tile (5) Fixed half-shell (6) Int./exhaust concentric terminal Ø 80/125 (7) Mobile half-shell (8)
1
1-13 1-14
MAINTENANCE TECHNICIAN
13

1.16 INSTALLATION OF VERTICAL TERMINALS 80 Ø.

Configuration type B, open chamber and forced draught.
80 Ø Vertical kit (plastic for indoor applica­tions).
Kit assembly (Fig. 1-15): install the 80 Ø terminal (2) on the central hole on the boiler up to stop, making sure that the wall sealing plates (1) have been tted. is will ensure the sealing eciency of the kit components.
INSTALLERUSER
• Maximum length (MAX L) (Fig. 1-16). e kit
with this conguration can be extended up to a max. measurement of 30.0 m with Victrix Pro 55 1A, including the terminal.
Using the Ø 80 vertical terminal for direct dis­charge of the combustion products, the terminal must be shortened (see quotas Fig. 1-17). e wall sealing plate (1) must also be inserted in this case going up to stop on the boiler cover.
80 Ø Vertical kit (steel for outdoor applica­tions).
Kit assembly (Fig. 1-18): install the 80 Ø terminal (1) on the central hole on the boiler up to the stop, ensuring the sealing eciency of the kit components.
e 80 Ø steel terminal is used to install the boiler outdoors with a direct exhaust. e terminal cannot be shortened and once it is installed it will extend out by 630 mm (Fig. 1-19).
MAINTENANCE TECHNICIAN
B23
e kit includes: Ring (1) 80 Ø exhaust termi-
nal (2)
B23
B23
2
1
1-15
B23
1-16
1-17
B23
e kit includes: Steel 80 Ø exhaust terminal (1)
1
1-18
1-19
14

1.17 INSTALLATION OF 80 Ø HORIZONTAL TERMINALS.

Configuration type B, open chamber and forced draught.
Ø 80 horizontal kit with wall ue exhaust.
Kit assembly (Fig. 1-20): install the 80 Ø bend (1) with the male side (smooth) fully home on the central hole of the boiler. Fit the exhaust terminal (2) with the male end (smooth) to the female end of the bend (1) up to the stop; making sure that the internal (3) and external (4) wall sealing plate has been tted. is will ensure sealing and joining of the elements making up the kit.
Horizontal kit Ø 80 with exhaust in ue. Kit assembly (Fig. 1-22): install the 80 Ø bend (1) with the male side (smooth) fully home on the central hole of the boiler. Fit the exhaust pipe (2) with the male end (smooth) to the female end of the bend (1) up to the stop; making sure that the internal wall sealing plate (3) has been tted. is will ensure sealing and joining of the elements making up the kit.
• Maximum length (MAX L) (Fig. 1-21 and 23).
e kit with this conguration can be extended up to a max. measurement of 30.0 m with Victrix Pro 55 1A, including the terminal.
INSTALLERUSER
1
e kit includes: Bend 90° Ø 80 (1) 80 Ø exhaust terminal (2) Internal ring (3) External ring (4)
1
e kit includes: 90° 80 Ø bend (1) 80 Ø drain pipe (2) Internal ring (3)
B23
B23
2
3
4
MAINTENANCE TECHNICIAN
1-20 1-21
B23 B23
2
3
1.5 m
Minimum gradient 3 %
1-22
MAX
1-23
15
1.18 FLUE EXHAUST WITH BOILERS IN
CASCADE.
e boilers installed in cascade composed of any number between 2 and 5 boilers, can be manifolded to a unique ue exhaust pipe, which ows into a ue. Immergas supplied an appropriate and original ue exhaust system separately to the boilers.

1.19 SYSTEM FILLING.

When the boiler has been connected, ll the sys­tem. Filling is performed at low speed to ensure
INSTALLERUSER
release of air bubbles in the water via the boiler and heating system vents. The boiler incorporates two automatic vent valves tted on the circulator pump and on the condensing module. Check if the cap is loose. Open the radiator vent valves. Close radiator vent valves when only water escapes from them.
N.B.: during these operations start up the cir­culation pump at intervals, acting on the main switch positioned on the control panel. Vent the
circulation pump by loosening the front cap and keeping the motor running. Tighten the cap aer
the operation.
Attention: this boiler is not equipped with an expansion vessel on the system. It is mandatory to install a closed expansion vessel to guarantee correct boiler operation. e expansion vessel must comply with the European and Austral­ian standards in force. e dimensions of the expansion vessel depend on the data relative to the central heating system. Install a vessel whose capacity responds to the requisites of the Standards in force (''R'' collection).
1.22 BOILER START UP IGNITION.
To commission the boiler (the operations listed below must only be performed by a qualied rm and without any unauthorised persons):
- check that the internal system is properly sealed according to the specications set forth by regulations in force; Up to operating pressures of 40 mbar it is also possible to use the testing method adopted by the technical regulations in force for systems served by single appliances (or in cascade set-up), with nominal thermal capacities greater than 35 kW. For greater pres­sure levels you will need to refer to legislation in force and/or other eectively tried and tested methods;
- make sure that the type of gas used corresponds to boiler settings;
- check that there are external factors that may cause the formation of fuel pockets;
- switch the boiler on and check correct ignition;
- make sure the fan rpm matches the value pro­vided in the book (Par. 3.24);
- ensure that the safety device intervenes in the event of gas supply failure and check the relative intervention time;
- check activation of the main switch located upstream from the boiler and in the boiler;
- check that the intake/exhaust concentric ter­minal (if tted) is not blocked.
e boiler must not be started up even if only one of the checks should be negative.

1.20 CONDENSATE TRAP FILLING.

Pre-fill the condense trap with water before operating the boiler, to ensure products of com­bustion do not discharge from the trap itself.
1.21 GAS SYSTEM STARTUP.
To start up the system, refer to the technical standard in force: is divides the systems and therefore the start-up operations into three categories: new systems, modified systems, re-activated systems. In particular, for new gas systems:
- open windows and doors;
- avoid presence of sparks or open ames;
- bleed all air from the pipelines;
- check the seal of the internal system by follow­ing the instructions provided by the technical
MAINTENANCE TECHNICIAN
regulations in force (refer to the pertaining lo­cal regulations for the "sealing test" on systems served by single or cascade generators with a nominal thermal capacity greater than 35 kW.
16

1.23 CIRCULATION PUMP.

ese boilers are equipped with a variable speed pump.
During CH mode, the pump speed is dened according to parameters “P27” and “P28” and it is adjusted in order to keep a constant DT of 18°C between ow and return.
During DHW mode, the pump always runs at the maximum speed.
Pump release. If, aer a prolonged period of inactivity, the circulation pump is blocked, unscrew the front cap and turn the motor sha using a screwdriver. Take great care during this operation to avoid damage to the motor.

1.24 KITS AVAILABLE ON REQUEST.

• Cascade and zones heat adjuster kit.
• Support kit for xing the heat adjuster to the wall.
• Zone manager kit.
• Modulating room thermostat kit.
• External probe kit.
• System ow probe kit.
• DHW probe kit for external storage tank.
• Anti-freeze with -15 °C resistance kit.
• Individual boiler safety devices stub pipes kit.
• Boilers in cascade safety devices stub pipes kit.
• ree-way valve kit for coupling external stor­age tank unit.
• Individual boiler hydraulic manifold kit.
• Hydraulic connection manifolds kit with two boilers in cascade.
• Additional boiler in cascade hydraulic manifold kit.
• Flue exhaust manifold kit with ue adjusting devices with two boilers in cascade.
• Flue exhaust manifold kit with ue adjusting device with additional boiler in cascade.
• Ø80/125 horizontal concentric kit.
• Ø80/125 vertical concentric kit.
• Ø 80 horizontal kit with ue exhaust.
• 80 Ø horizontal terminal kit with wall ue exhaust.
• Ø80 vertical terminal kit.
• Safety marker thermostat kit.
e above-mentioned kits are supplied complete with instructions for assembly and use.
INSTALLERUSER
Head available to the system.
Head (kPa)
MAINTENANCE TECHNICIAN
Key: A = Available pump head B = Pump electrical consumption
(dotted area)
A
B
Pump Electrical Consumption (W)
Flow rate (l/h)
17
1-24

1.25 BOILER COMPONENTS.

INSTALLERUSER
MAINTENANCE TECHNICIAN
Key: 1 - P.C.B. 2 - Gas valve 3 - Absolute pressure switch 4 - Gas nozzle 5 - Sleeve with seats for Venturi 6 - Air fan 7 - System ow regulation NTC probe 8 - Overheating safety thermostat 9 - Detection electrode 10 - Manifold cover 11 - Condensation module cover 12 - Igniter 13 - Ignition electrode 14 - Flue probe 15 - Condensing module air vent valve 16 - Fumes hood
17 - Sample points (air A) - (ue gas F) 18 - Heat exchanger safety thermal fuse 19 - Manual air vent valve 20 - Condensation module 21 - Heat-exchanger safety thermostat (manual reset) 22 - Burner 23 - Air intake pipe 24 - System return regulation NTC probe 25 - System ow meter 26 - Vent valve 27 - Pump 28 - Condensate trap 29 - Flow manifold 30 - 4 bar safety valve 31 - Gas cock 32 - Draining funnel.
1-25
18

1.26 HYDRAULIC DIAGRAM WITH OPTIONAL.

INSTALLERUSER
Key: 1 - Generator 2 - Manometer pocket
3 - Minimum pressure switch 4 - Probe for fuel shut-o valve bulb 5 - Manometer 6 - Damper coil 7 - Manometer-holder cock 8 - ermometer 9 - Manual rearm thermostat 10 - Attachment for expansion vessel 11 - Manual rearm pressure switch 12 - Fuel shut-o valve 13 - Expansion vessel 14 - Boiler connection 3-way valve 15 - Hydraulic manifold/mixer 16 - Slurry collection brass lter
Attention: the sensitive elements of the automat­ic regulation and block circuit breaker switches and of the thermometer (not supplied as standard with the boiler) must be set-up as described in the installation instructions in compliance with the provisions of the "R" collection. Whenever the generators are not installed in cascade according to the instructions and the Immergas original kits, the sensitive elements must be installed on the ow piping to the central heating system, immersed in the current of water at not more
than 0.5 metres from the boiler outlet. the boilers must be installed in the congurations and with their own original Immergas cascade and safety kits. declines all liability whenever the installer does not use the devices and Immergas original kits or uses them improperly.
Immergas S.p.a. and Hunt Heating
MAINTENANCE TECHNICIAN
1-26
19

1.27 INSTALLATION EXAMPLES OF INDIVIDUAL BOILER.

INSTALLERUSER
15 - Storage tank unit feeding pump
16 - Zone 1 safety thermostat (CMI-1)
17 - Zone 2 safety thermostat (CMI-2)
19 - Fuel shut-o valve bulb
20 - Manometer-holder cock
21 - ermometer
22 - Manual rearm thermostat
23 - Manual rearm pressure switch
24 - Attachment for expansion vessel
25 - Expansion vessel
26 - Manifold/mixer
27 - External storage tank unit
28 - Fuel shut-o valve
29 - Non return valve
30 - Slurry collection system lter
31 - Manometer pocket
32 - Damper coil
33 - Manometer
34 - Minimum pressure switch
MAINTENANCE TECHNICIAN
Zone 3
Zone 2
Zone 1
Key:
1 - Generator
2 - Cascade and zone regulator
3 - Zone manager
4 - Modulating room thermostat
5 - External probe
6 - Zone 1 temperature probe (CMI-1)
7 - Zone 2 temperature probe (CMI-2)
8 - Common ow probe
9 - Storage tank unit temperature probe
10 - Zone 1 mixing valve (CMI-1)
11 - Zone 2 mixing valve (CMI-2)
12 - Zone 1 central heating circuit pump (CMI-1)
13 - Zone 2 central heating circuit pump (CMI-2)
14 - Zone 3 direct circuit pump (CD)
20
1-27
USE AND MAINTENANCE
2
INSTRUCTIONS

2.1 CLEANING AND MAINTENANCE. Attention: to preserve the boiler’s integrity and

keep the safety features, performance and relia­bility which distinguish it unchanged over time, maintenance operations must be carried out on a yearly basis in compliance with that stated in the “annual check and maintenance of the appliance” section, in compliance with AS/NZS 5601, by a qualied licensed operative.

2.2 AERATION AND VENTILATION OF THE INSTALLATION ROOMS.

Consult the "Aeration and ventilation of instal­lation rooms" chapter contained herein and, in any case, always refer to the provisions set forth by standards and all legislation in force.

2.3 GENERAL WARNINGS.

Use of the boiler by unskilled persons or children is strictly prohibited. For safety purposes, check that the concentric air intake/flue exhaust terminal (if fitted), is not blocked. If temporary shutdown of the boiler is required, proceed as follows: a) drain the heating system if anti-freeze is not
used;
b) shut-o all electrical, water and gas supplies.
N.B.: in the case of maintenance interventions on the boiler that lead to the closure of one or both system cut-o cocks, the boiler must be o. In the case of work or maintenance to structures located in the vicinity of ducting or devices for ue extraction and relative accessories, switch o the appliance and on completion of operations ensure that a qualied technician checks ecien­cy of the ducting or other devices. Never clean the appliance or connected parts with easily ammable substances. Never leave containers or ammable substances in the same environment as the appliance.
Attention: the use of components involving use
of electrical power requires some fundamental rules to be observed:
- do not touch the appliance with wet or moist
parts of the body; do not touch when bare­foot;
- do not pull electric cables;
- the appliance power cable must not be re-
placed by the user;
- in the event of damage to the cable, switch
off the appliance and contact exclusively qualied sta for replacement;
- if the appliance is not to be used for a certain
period, disconnect the main power switch.
INSTALLERUSER
MAINTENANCE TECHNICIAN
21

2.4 CONTROL PANEL.

INSTALLERUSER
Key: 1 - Main switch 2 - CH temperature adjustment buttons 3 - Sliding door 4 - DHW temperature adjustment buttons (optional) 5 - Boiler manometer 6 - Summer / winter mode button (A) 7 - Reset, info, conrm parameters button (B) 8 - Multifunction button: anomalies records, DHW exclusion (C) 9 - Multi-function display 10 - CH function enabled 11 - Temperature indicator, boiler info and error codes 12 - Not used 13 - Boiler parameter and info display 14 - Not used 15 - Not used 16 - Parameter adjustment in progress 17 - Boiler in stand-by 18 - External probe connected (optional) 19 - unit of measurement 20 - DHW production phase operation enabled (optional) 21 - Domestic hot water exclusion 22 - Flame detection symbol 23 - Resettable presence of anomalies 24 - Pump running 25 - Summer mode

2.5 USING THE BOILER.

Before ignition, make sure that the system is full of water, checking that the manometer (5)
MAINTENANCE TECHNICIAN
indicates a base value at which the system has been designed and calculated and however not less than 0.5 bar.
- Open the gas cock upstream from the boiler.
- Turn the main switch, and the boiler run a
self-diagnosis. It will then go back to the status it was in prior to being switched o.
• “A” operating mode button (
the boiler on, press the button (A) repeatedly to change the operating mode. It will alternate
from summer mode ( only) to winter mode (room and DHW heat­ing).
N.B.: the DHW heating function is only active
in presence of the specic optional kit (tank probe automatic recognition).
) (DHW heating
): with
With the boiler on but not running, the screen will display the ow probe temperature reading.
2-2
2-1
If requested, the boiler switches on and the rel­ative symbols will be displayed, indicating the ow probe temperature reading.
2-3
22
Summer ( ): in this mode the boiler only
operates for domestic hot water heating.
By pressing the + or - buttons just once (4
Fig. 2-1) it is possible to read the temperature setting. By pressing them again you can change the settings as needed. You will need to press “B” to save the new value. e temperature reading will flash during adjustment. If a certain amount of time lapses without saving the value, the boiler will exit setting mode and maintain the previous setting.
2-4
• Winter : in this mode the boiler functions both
for heating domestic hot water and heating the environment.
By pressing the + or - (2 Fig. 2-1) buttons
once, you can view the temperature setting. By pressing them again you can change the setting as needed. You will need to press “B” to save the new value. e temperature reading will ash during adjustment. If a certain amount of time lapses without saving the value, the boiler will exit setting mode and maintain the previous setting.
• Stand-by mode ( ): by pressing buttons “A”
and “C” at the same time it is possible to place the boiler in stand-by.
2-6
In this mode the boiler is considered powered
on but not active. Accordingly, the appliance's anti-freeze function is guaranteed. To turn it back on simply press "B".
2-7
• DHW exclusion (
for DHW heating, press “C” momentarily to exclude DHW heating mode operation. To restore DHW heating, press "C" again.
): with the boiler set up
• Anomaly records: press and hold “C” down to
access the records of the last 8 anomalies that have aected the boiler (list from H i 0 to H i 7, where H i 0 is the most recent anomaly). When you are in the menu, the screen will display, in order, number “bu 0”, the number and code for the anomaly.
INSTALLERUSER
2-8
To scroll through the list, press buttons + and
- (ref. 2 Fig. 2-1).
To exit the menu, press and hold "C" down
again.
Warning: anomalies with a code over “90” are
not saved in the anomaly records.
- Slave boiler anomalies (simple cascade installation). Slave boiler anomalies are
displayed on the Master boiler. Aer entering the menu, press + and - (ref. 8 Fig. 2-1) to alternate between Master “bu 0” and Slave “bu 1” boilers.
2-5
MAINTENANCE TECHNICIAN
23

2.6 TROUBLESHOOTING.

e boiler will let you know of any anomalies by the ashing screen and code. ere are dierent types of codes that can be divided up as follows:
- “0Axx” for resettable anomalies (Fig. 2-9). (Before resetting the anomaly you will need to wait for the boiler to nish its post-ventilation function, which lasts approximately 60 sec­onds).
- “0Exx” and “FExx” for non-resettable anoma­lies.
INSTALLERUSER
e “xx” sux stands for the error code de­scribed in the following tables.
Simple cascade: in case of simple cascade, anomalies will be displayed on the master boiler (without the “0” sux on the Slave boiler) and slave boiler anomalies are displayed on the mas­ter boiler with sux “1”.
Example: “0A1” anomaly
Anomaly on Master boiler = 0A1
Anomaly on Slave boiler = A1
Slave boiler anomaly displayed on Master boiler
= 1A1
Error Code
0A1 No ignition block
0A2 Parasite ame block
0A3 Overheating block
0A5 Fan signal anomaly is occurs if the fan speed is incorrect. Press the Reset button (1)
0A7
0A9
0A15
0A16
0A17
0A18
0A21 P.C.B. error An error is detected on the P.C.B. and the boiler does not start up Press the Reset button (1)
0A30
MAINTENANCE TECHNICIAN
0A31
0A37
0A43
0A44
0A80
(1) If the block or anomaly persists, contact a qualied licensed operative for assistance.
Anomaly signalled Cause Boiler status/Solution
In the event of request of room central heating or domestic hot water
Flue temperature anomaly
Gas valve electric circuit anomaly
Flow and return NTC probe temperature detection incorrect (in stand-by)
Poor thermal ow NTC probe contact
Poor thermal return NTC probe contact
Flow and return NTC probe temperature detection incorrect
Flow NTC probe in short circuit
Flow NTC probe outside the operating range
Insucient system pressure / ow rate
Return NTC probe in short circuit
Return NTC probe outside the operating range
Flow and return NTC probe connection error
production, the boiler does not switch on within the preset time. Upon appliance commissioning or aer extended downtime, it may be necessary to eliminate the block.
is occurs during the power-on phase in the event of a leak on the detection circuit or anomaly in the ame control unit.
During normal operation, if a fault causes excessive overheating inter­nally, the boiler goes into overheating block.
If the boiler fails, the ue circuit will provide an excessively high temperature reading and the boiler will switch o.
e board detects an anomaly in the gas valve circuit Press the Reset button (1)
With the boiler in stand-by, the board detects an anomalous dierence between the NTC probe ow and return temperatures. e error may be caused by a failure in one of the two probes
During boiler operation the board does not detect a change in the ow NTC probe temperature. e error may be caused by a poor thermal probe contact or a system with excessive thermal inertia.
During boiler operation the board does not detect a change in the return NTC probe temperature. e error may be caused by a poor thermal probe contact or a system with excessive thermal inertia.
If the board detects a sudden drop in temperature on one of the two NTC probes (ow and return), it will report an anomaly. is may be caused by the failure of one of the two probes
e board detects a short circuit on the ow NTC probe. Press the Reset button (1)
e board detects an open contact on the ow NTC probe. Press the Reset button (1)
If the system ow rate / pressure is too low for a certain period, the boiler will detect the anomaly.
e board detects a short circuit on the return NTC probe Press the Reset button (1)
e board detects an open contact on the return NTC probe. Press the Reset button (1)
If the electrical connection between the two NTC probes is switched around, the board will detect the anomaly (it may be necessary to wait 3 minutes for the error to be detected).
Press the Reset button (1)
Press the Reset button (1)
Press the Reset button (1)
Press the Reset button (1)
Press the Reset button (1)
Press the Reset button (1)
Press the Reset button (1)
Press the Reset button (1)
Check the ow meter, check the pres­sure switch and check the system. Press the Reset button (1)
Press the Reset button (1)
24
Error Code
0E2 Parasite ame block
0E13 Maximum N° of reset Number of allowed resets that have already performed.
0E25 P.C.B. error An error is detected on the P.C.B. and the boiler does not start up (2) (1)
0E32
0E33
0E34
0E37
0E45
0E46
0E81
0E98
Anomaly signalled Cause Boiler status/Solution
DHW NTC probe in short circuit
DHW NTC probe outside the operating range
Low power supply voltage
Insucient system pressure / ow rate
Flue NTC probe in short circuit
Flue NTC probe outside the operating range
Flow and return NTC probe temperature detection incorrect (in stand-by)
Simple cascade com­munication anomaly
is occurs during the power-on phase in the event of a leak on the detection circuit or anomaly in the ame control unit.
e board detects a short circuit on the DHW NTC probe (2) (1)
e board detects an open contact on the DHW NTC probe. (2) (1)
is occurs when the power supply voltage is lower than the allowed limits for the correct boiler operation.
If the system ow rate / pressure is too low the boiler switches o.
e board detects a short circuit on the ue NTC probe. (2) (1)
e board detects an open contact on the ue NTC probe. (2) (1)
With the boiler in stand-by, the board detects an anomalous dierence between the NTC probe ow and return temperatures. e error may be caused by a failure in one of the two probes
Occurs if the communication between the display boards breaks down
(2) (1)
Attention: it is possible to reset the anom­aly up to 5 consecutive times within 15 minutes. (1) By switching the appliance on and o the 5 attempts are re-acquired.
(2) (1)
Check on the boiler pressure gauge (1) that the system pressure is between 1÷1.2 bar and restore the correct pressure if necessary. Make sure that the boiler input is suitable for the installed circuit. (2) (1)
(2) (1)
Check the bus’ electric connection. Perform the Auto detection. Check whether the soware versions match. (2) (1)
INSTALLERUSER
Check the boiler’s wiring.
Internal
0E99
communication anomaly
(1) If the block or anomaly persists, contact a qualied licensed operative for assistance. (2) If normal operating conditions are restored, the boiler re-starts without having to be reset.
Error Code
FE94 Display board anomaly An error is detected on the display's P.C.B.. (2) (1)
FE95
FE96
FE97 Conguration error
(1) If the block or anomaly persists, contact a qualied licensed operative for assistance. (2) If normal operating conditions are restored, the boiler re-starts without having to be reset.
Anomaly signalled Cause Solution
Shared common ow probe short-circuited or out of range
External probe anomaly
In the event of simple cascade, even in the case of a communication error between the display boards..
e board detects an incorrect value on the ow NTC probe or “P38” parameter not set correctly.
An anomaly is detected on the external probe.
P.C.B. conguration error.
TIt may occur also in the event of replacement of the electronic boards with an incorrect model.
Check the bus’ electric connection. Perform the Auto detection in the event of simple cascade installation. (2) (1)
(2) (1)
Check the boiler conguration, check the external probe (2) (1)
Check the conguration parameters. Perform the Auto detection. (2) (1)
MAINTENANCE TECHNICIAN
25

2.7 INFO MENU.

Press and hold down "B" to access the info menu containing all of the various information relative to boiler operation.
Once you are inside the menu, you will mo­mentarily see the parameter number followed by the value.
INSTALLERUSER
To scroll through the various parameters, press buttons + and - (ref. 2 Fig. 2-1).
To exit the menu, press and hold "B" down again.
While the parameter value is being displayed it is possible to momentarily see the relative code again by pressing button "A". e viewable pa­rameters are listed in the following tables.
2-10

2.8 BOILER SHUTDOWN.

Disconnect the main switch (1) taking it to the “0” position and close the gas cock upstream from the appliance. Never leave the boiler switched on if le unused for prolonged periods.

2.9 RESTORING CENTRAL HEATING SYSTEM PRESSURE.

Periodically check the system water pressure. e boiler manometer should indicate a value not below 0.5 bar.
If the pressure is below 0.5 bar (with cold system) the water inside the system must be restored.
N.B.: close the valve aer the operation. If pressure values reach around 4 bar the safety valve may be activated. In this case, remove water from an air vent valve of a radiator until reaching pressure of 1 bar, or ask for assistance from professionally qualied personnel. In the event of frequent pressure drops, contact qualified staff for assistance to eliminate the possible system leakage.

2.10 SYSTEM DRAINAGE.

To drain the boiler, use the appropriate system drain tting. Before draining, ensure that the system lling valve is closed.
2.11 ANTIFREEZE PROTECTION.
e boiler is supplied with an antifreeze function as standard that activates the function of the pump and the burner when the system water temperature in the boiler falls below 5°C. e antifreeze function is guaranteed if the boiler is fully operative, if it is not in "block" status and is electrically powered with the main switch on "ON". To avoid keeping the system switched on in case of a prolonged absence, the system must be drained completely or antifreeze substances must be added to the heating system water. In systems that are drained frequently, lling must be carried out with suitably treated water to eliminate hardness that can cause lime-scale.

2.12 CASE CLEANING.

Use damp cloths and neutral detergent to clean the boiler casing. Never use abrasive or powder detergents.

2.13 DECOMMISSIONING.

In the event of permanent shutdown of the boiler, contact professional sta for the procedures and ensure that the electrical, water and gas supply lines are shut o and disconnected.
MAINTENANCE TECHNICIAN
Info menu
Menu item Description Unit of measurement
P01 Flame current μA P02 Flow NTC probe temperature reading °C / °F P03 Return NTC probe temperature reading °C / °F P04 DHW NTC probe temperature reading (if installed) °C / °F P05 System water ow l/minute P06 Operating power % P07 Fan speed requested by the system RPM / 50 P08 Current fan speed RPM / 50 P09 Flue NTC probe temperature reading °C / °F
P10
P11 External probe temperature reading (if installed) °C / °F P12 Operating power in simple cascade mode % P13 Flow temperature requested by the system in heating °C / °F P14 Flow temperature requested by the system in DHW °C / °F P15 Not used ­P16 Number of burners on in simple cascade mode no. P17 Number of displays on no.
Common ow probe temperature reading (if installed) or boiler ow probe (based on the system’s conguration)
°C / °F
26
BOILER COMMISSIONING
3
INITIAL CHECK.
To commission the boiler:
- make sure that the type of gas used corresponds to boiler settings;
- check connection to a 230V-50Hz power mains, correct L-N polarity and the earthing connection;
- switch the boiler on and check correct ignition;
- check the CO imum and minimum ow rate;
- make sure the fan rpm matches the value pro­vided in the book (Par. 3.24);
- check activation of the safety device in the event of no gas, as well as the relative activation time;

3.1 HYDRAULIC DIAGRAM.

% in combustion gases at max-
2
- check the intervention of the main switch located upstream of the boiler and in the boiler;
- check the existing draught during normal functioning of the appliance, e.g. a draught gauge positioned at the exit of the appliance combustion products;
- check that there is no backow of combustion products into the room, even during function­ing of fans;
- check that the intake and/or exhaust terminals are not blocked;
- ensure activation of all adjustment devices;
- seal the gas ow rate regulation devices (if settings are modied);
- check sealing eciency of water circuits;
- check ventilation and/or aeration of the instal­lation room where provided.
- ensure the gas inlet working pressure is correct,
1.1 Kpa (Natural Gas), 2.75 Kpa (LPG).
- pre ll condense trap with clean water.
- ll and set system pressure to 1- 1.5 bar.
- check expansion vessel is tted, correctly sized and is set to the correct pressure.
If even only a single safety check oers a negative result, do not commission the system.
Key: 1 - Draining funnel on view 2 - Boiler draining valve 3 - 4 bar safety valve 4 - Flow manifold 5 - Absolute pressure switch 6 - Condensate trap siphon 7 - Gas nozzle 8 - Air fan 9 - Manifold cover 10 - Ignition electrode 11 - Condensation module cover 12 - Condensation module 13 - Flue probe 14 - Condensing module air vent valve 15 - ermofuse 16 - Air sample point 17 - Flue sample point 18 - Venturi positive sign (P1) 19 - Fumes hood 20 - Safety thermostat exchanger
(manual reset) 21 - Over temperature safety thermostat 22 - System return regulation probe 23 - System ow regulation probe 24 - Detection electrode 25 - System ow meter 26 - Burner 27 - Air intake pipe 28 - Sleeve with seats for Venturi 29 - Automatic vent valve 30 - Boiler circulator pump 31 - Gas valve
INSTALLERUSER
MAINTENANCE TECHNICIAN
F SC G R
27
F - System ow SC - Condensate drain G - Gas supply R - System return
3-1

3.2 230 V CIRCUIT WIRING DIAGRAM.

INSTALLERUSER
Colour key:
BK - Black
BL - Blue
BR - Brown
G - Green
GY - Grey
OR - Orange
P - Purple
PK - Pink
R - Red
W - White
W/BK - White / Black
Y - Yellow
Y/G - Yellow / Green
MAINTENANCE TECHNICIAN
4
73
5
6
5
4
2
1
S1 - Main switch
Y1 - Gas valve
1 - External reset
2 - Free contact alarm MAX. 1 A 230 Vac
3 - System side pump Potential-free contact Max. 1st 230 Vac.
4 - External relay (optional)
5 - Coil 230 Vac MAX. 0.1 A
6 - External pump (Driven by M1 pump)
7 - D.H.W. pump
For safety reasons the P.C.B. envisions a fuse that cannot be restored in series with the electric power supply of the gas valve.
Congure the corresponding parameters when connecting in “simple cascade”, or when con­necting in “system side ow probe”, or “D.H.W. p um p”.
28
Key:
A2 - P.C.B.
A4 - Display board
E1 - Ignition electrode
E2 - Detection electrode
G2 - Igniter
M1 - Boiler circulator pump
M20 - Fan
M30 - ree-way valve (optional)
3-2

3.3 VERY LOW VOLTAGE WIRING DIAGRAM.

INSTALLERUSER
Colour key:
BK - Black
BL - Blue
BR - Brown
G - Green
GY - Grey
OR - Orange
P - Purple
PK - Pink
R - Red
W - White
W/BK - White / Black
Y - Yellow
Y/G - Yellow / Green
M20 - Fan
S5 - Absolute pressure switch
S20 - ON/OFF room thermostat (optional)
X40 - Room thermostat jumper
1 - Testing
2 - “Simple cascade” communication bus
3 - 0 - 10 V analogue input
1
3
(manual reset)
2
B10 - Flue probe
B25 - System ow meter
E4 - Safety thermostat
E5 - -Heat-exchanger safety thermostat
E13 - Flue safety thermofuse
M1 - Boiler circulator pump
1
MAINTENANCE TECHNICIAN
e jumper X40 must be removed when the Room thermostat is connected; in addition, it must be eliminated also in case of connection on the “M-O” terminals or when the 0 ÷ 10 V
inlet is used. A thermostat can be used instead of “B2” (set P29 = 17).
29
Key:
A2 - P.C.B.
A4 - Display board
B1 - Flow probe
B1-2 - System side ow probe
B2 - Domestic hot water probe (optional)
B4 - External temperature probe (optional)
B5 - Return probe
3-3
Congure the corresponding parameters when connecting in “simple cascade”, or when con­necting in “system side ow probe”, or “D.H.W. p um p”.

3.4 D.H.W. PUMP BOILER AND TANK PROBE WIRING DIAGRAM.

INSTALLERUSER
3.5 COMMON FLOW PROBE AND 3WAY BOILER WIRING DIAGRAM.
Key: B1 -System ow probe (NTC) B2 -Domestic hot water probe (NTC) B4 -External probe M2 -Plant CH pump M3 -Domestic hot water pump
Note (probe B1, B2, B4): Connection cable diameter 3÷7 mm Cable section 0.5 ÷ 1.5 mm
“IT” - “IK” outlet = 230 Vac Max 1 A “C” - “D” inlet = Clean contact Max 230
Vac 1 A
3-4
Key: B1 -System ow probe (NTC) B2 -Domestic hot water probe (NTC) B4 -External probe M2 -Plant CH pump M30 - 3-way valve

3.6 SIMPLE CASCADE BOILER WITH D.H.W. PUMP AND TANK PROBE WIRING DIAGRAM.

Note (probe B1, B2, B4): Connection cable diameter 3÷7 mm Cable section 0.5 ÷ 1.5 mm
MAINTENANCE TECHNICIAN
“IT” - “IK” outlet = 230 Vac Max 1 A
“C” - “D” inlet = Clean con­tact Max 230 Vac 1 A
Note (probe B1, B2, B4): Connection cable diameter 3÷7 mm Cable section 0.5 ÷ 1.5 mm
“IT” - “IK” outlet = 230 Vac Max 1 A “C” - “D” inlet = Clean contact Max 230
Vac 1 A
3-5
Key: B1 -System ow probe (NTC) B2 -Domestic hot water probe
(NTC) B4 -External probe M2 -Plant CH pump M3 -Domestic hot water pump
Note (Connection bus): Connection cable diameter 3÷7 mm Cable section 0.5 ÷ 1.5 mm Maximum length 3 m
30
3-6

3.7 TROUBLESHOOTING. N.B.: maintenance interventions must be carried

out by a qualied licensed operative.
- Smell of gas. Caused by leakage from gas circuit pipelines. Check sealing eciency of gas intake circuit.
- Repeated ignition blocks. No gas, check the presence of pressure in the network and that the gas adduction valve is open. Incorrect adjustment of the gas valve, check the correct calibration of the gas valve.
- Irregular combustion or noisiness. It may be caused by: a dirty burner, incorrect combustion parameters, intake-exhaust terminal not cor­rectly installed. Clean the above components and ensure correct installation of the terminal, check correct setting of the gas valve (O-Set setting) and correct percentage of CO gases.
- e over temperature safety thermostat, the ow probe or the return probe are triggered frequently. It can depend on the lack of water in the boiler, little water circulation in the system or blocked pump. Check on the manometer that the system pressure is within established limits. Check that the radiator valves are not closed and also the functionality of the pump.
In addition:
- Also check the integrity of the thermofuse, and if it has been triggered it will be necessary to check the integrity of the module and the ue circuit.
- Check that the exchanger safety thermostat has not intervened. If it has, check the integrity of the module and ceramic bre panel, replace the cover gasket of the manifold and reset the thermostat by pressing the specic button.
- Heat exchanger clogged. is may be caused by the trap being blocked. Check, by means of the condensate drain cap, that there are no residues of material blocking the ow of condensate.
in ue
2
- Noise due to air in the system. Check opening of the special air vent valve cap (Fig. 1-25 Ref.
19). Check that system lling and air bleeding has been performed according to the require­ments.
- Noise due to air inside the condensation module. Use the manual air vent valve (Fig. 1-25 Ref. 15) to eliminate any air present in the condensation module. When the operation has been performed, close the manual vent valve.
- No DHW is produced. e boiler is equipped with a function that automatically recognises when there is an optional DHW probe, and an anomaly is reported if there is a failure aecting the DHW NTC probe. If there is a power out­age, or if the boiler is switched o and back on again during the failure, it will not be possible to detect said failure, but it will, however, be recorded in the errors anomaly records.
- In case of ΔT > 35 °C, the boiler lowers the power to avoid surpassing that value. When this status is on, the ow temperature symbol ashes.

3.8 PROGRAMMING THE BOILER P.C.B.

e boiler is prepared for possible programming of several operation parameters. By modifying these parameters as described below, the boiler can be adapted according to specic needs.
- Access programming by pressing and holding down buttons “B” and “C”.
3-7
- Scroll through the parameters by pressing the + and - heating adjustment buttons,
- Change the parameter by pressing the + and ­DHW adjustment buttons.
3-9
Save the parameters by switching from one
parameter to the next or by pressing “B”.
3-10
- Exit the programming mode by pressing and Exit the programming mode by pressing and holding down buttons “B” and “C” or wait approximately 2 minutes without touching the buttons.., the boiler will then run a self-diag­nosis of the parameters by displaying “PARA” followed by “Auto”.
- While the value of a parameter is being dis­played, press “B” quickly to see the code again.
INSTALLERUSER
31
3-8
MAINTENANCE TECHNICIAN
INSTALLERUSER
MAINTENANCE TECHNICIAN
Programming menu
Menu item Description Adjustment range Default Value
Heating Set Temp is denes the boiler's ow temperature during heating 20 ÷ P02 °C 85
P01 P02
Max Heating Set Temp is denes the maximum settable ow temperature during heating 20 ÷ 95 °C 85
P03
Heating Hysteresis is denes the power-o hysteresis during the heating phase 2 ÷ 10 °C 5 Heating Anti-Cycle
P04
Time Burner Stabilization
P05
Time
P06
Heating Temp Rise
Heating Pump
P07
Overrun Time Boiler Power Used
P08
During Max Heating Mode
Boiler Power Used
P09
During Min Heating Mode
Minimum system
P10
ow rate
Electrode Anti-
P11
Humidity Fan Speed
Boiler’s modulation
P12
ratio Boiler power Used to calculate the boiler power in the event of simple cascade. 0 ÷ 255 kW 50
P13
P14
External probe curve
P15
External probe oset is denes the CH oset in relation to the selected external probe curve 20 ÷ 70 °C 30 °C
P16
DHW Set Temp is denes the DHW temperature 20 ÷ 65 °C 65 °C
P17
DHW Conguration
P18
DHW Hysteresis is denes the DHW power-on hysteresis during CH 2 ÷ 10 °C 5 °C DHW Pump Overrun
P19
Time Boiler Power Used
P20
During Max DHW Mode
Boiler Power Used
P21
During Min DHW Mode
Flow Delivery Temp
P22
During DHW Mode
P23
DHW Modulation
P24
DHW O Increment
P25
Max Fan Speed
is is used to set a waiting time to avoid the boiler from switching on multiple times and frequently during CH mode
is is the amount of time that the boiler needs to stabilise, when the burner runs at minimum power for the set amount of time
e amount of time that the boiler takes to reach the required temperature, number of degrees per minute (0 means no ramp)
e amount of CH post circulation once the CH phase is fnished 1 ÷ 30 minutes 3 minutes
is denes the maximum power percentage to be used during the set CH phase
is denes the minimum power percentage to be used during the set CH phase
is denes the minimum system ow rate required to power-on the boiler Attention: do not change this parameter
is denes fan speed and operating mode, to avoid humidity inside the condensing module, which could otherwise cause the electrodes to malfunction (0 = disabled function, recommended value = 40) (RPM speed is calculated by multiplying the value displayed by 50)
It denes the boiler’s modulation ratio (Do not modify) 0 ÷ 100 %
is is used to select the external probe operating curve (optional) (0 = disabled probe)
- With a single boiler it controls an external 3-way.
- With single boiler and common ow probe, it lets you choose between an external D.H.W pump and a 3-way one.
- With a simple cascade, it manages a D.H.W. pump (downstream an hydraulic separator).
is is the post circulation time during DHW once DHW production is nished
is denes the maximum power percentage to be used during the set DHW phase
is denes the minimum power percentage to be used during the set DHW phase
In combination with a storage tank and a separate thermostat, this denes the ow temperature during DHW operation
Summed with the “Set San” (P16) parameter, this denes the ow temperature set that the boiler has to modulate the power on during DHW
is denes the time that the boiler allows the burner to switch o during DHW, by an increment of 5 °C on top of the ow temperature
is denes the max fan speed and therefore the maximum relative boiler operating power
0 ÷ 15 minutes 3 minutes
3 ÷ 10 minutes 3 minutes
0 ÷ 60 °C/minute 4 °C/minute
P09 ÷ 100% 100%
0 ÷ P08% 0%
5 ÷ 47 l/minutes 14 l/minutes
P26 ÷120 0
0 ÷ 10 0
0 = 3 Ways
1 = D.H.W. pump
0 ÷ 180 seconds 60 seconds
P21 ÷ 100 % 50 %
0 ÷ P20 % 0 %
35 ÷ 90 °C 80 °C
5 ÷ 30 °C 15 °C
0 ÷ 255 seconds 60 seconds
P26 ÷ 255
Customised
Value
10%
0
Met. 131 LPG 129
32
Programming menu
Menu item Description Adjustment range Default Value
Min Fan Speed
P26
P27
Min Pump Speed
Pump Speed Used
P28
During Ignition DHW Sensor
P29
Conguration
Fan Speed During
P30
Ignition
P31
Unit of measurement is denes the unit of measure on the display, whether metric or Imperial
P32
Min Heating Set Temp
Anti-Freeze Activation
P33
Temp Anti-Freeze
P34
Deactivation Flow Temp
Second Boiler Time
P35
Delay On/O Temperature
P36
adjustment calculation time
P37
0 ÷ 10 V inlet It denes whether the boiler must function with the temperature or probe set
Common ow probe
P38
conguration
is denes the min fan speed and therefore the minimum relative boiler operating power (RPM speed is calculated by multiplying the value displayed by 50)
Denes the minimum pump speed in heating mode at the minimum boiler power Attention: do not go below 77 %
Denes the minimum pump speed in heating mode during burner ignition Attention: do not go below 77 %
is is used to select the DHW operating mode, choosing between NTC probe or on/o thermostat
is denes the fan speed during burner ignition Attention: do not change this parameter (RPM speed is calculated by multiplying the value displayed by 50)
Limits the minimum value of the heating set. (e parameter takes priority in relation to the value set from the pushbutton panel)
Activates the antifreeze function launched by the common ow probe. e boiler turns on once there is a drop below the set value
Deactivates the antifreeze function launched by the common ow probe. e boiler turns o once the set temperature is reached
With its simple cascade operation, it avoids unnecessarily turning the second boiler on and o
is denes the time interval required to calculate the boiler temperature Attention: do not change this parameter
It activates the common ow probe functioning.
0 ÷ P25
1 ÷ 100 % 77 %
1 ÷ 100 % 77 %
1 = NTC probe
17 = on/o thermostat
0 ÷ 114
(range limited by
parameters P25 and
P26)
0 ÷ 127 = °C - kW
128 ÷ 256 = °F -
kBTu/h
20 ÷ 50 20
2 ÷ 20 °C 5°C
2 ÷ 20 °C 15°C
0 ÷ 255 seconds 60 seconds
1 ÷ 10 seconds 3 seconds
0 = temperature set
1 = power set
0 = no probe
1 = probe present
Customised
Value
35 kW Met. 20 35 kW LPG 20 55 kW Met. 22 55 kW LPG 21
INSTALLERUSER
1
46
0
0
0
33
MAINTENANCE TECHNICIAN

3.9 CONVERTING THE BOILER TO OTHER TYPES OF GAS.

If the boiler has to be converted to a dierent gas type to that specied on the data plate, request the relative conversion kit for quick and easy conversion. Boiler conversion must be carried out by a qua­lied Licensed operative. To convert to another type of gas the following operations are required:
- disconnect the appliance;
- Change the sleeve with Venturi (det. 5 Fig.
INSTALLERUSER
1-25);
- change the gas nozzle (det. 4 Fig. 1-25);
- re-power the appliance;
- regulate the maximum heat output by varying
the number of fan revs. (parameter P25 “Max number of fan revs in CH mode”) according to par. 3.24;
- regulate the minimum heat output by varying
the number of fan revs. (parameter P26 “Min number of fan revs in CH mode”) according to par. 3.24;
- activate the chimney sweep function;
- check the CO
especially:
- che ck the CO
sweep at 0%;
- che ck the CO
sweep at 100%;
value on the table in par. 3.24,
2
value in the ue with chimney
2
value in the ue with chimney
2
- exit the chimney sweep function;
- seal the gas ow rate regulation devices (if
settings are modied);
- after completing the conversion, apply the
sticker, contained in the conversion kit, near the data-plate. Using an indelible marker pen, cancel the data relative to the old type of gas.
ese adjustments must be made with reference to the type of gas used.

3.10 CHECKS FOLLOWING CONVERSION TO ANOTHER TYPE OF GAS.

After making sure that transformation was carried out with the Venturi and a nozzle of suitable diameter for the type of gas used and the calibration has been performed at the correct num. of revs, check that:
- the burner ame is not too high and that it is
stable (does not detach from burner);
MAINTENANCE TECHNICIAN
- there are no leaks from the gas circuit.
N.B.: all boiler adjustment operations must be carried out by a qualied licensed operative.
3.11 ADJUSTMENT OF THE AIRGAS RAT IO.
Calibration of minimum CO Turn the boiler on and start the chimney sweep
2
functions at minimum output (0%). To have an exact value of CO2 the technician must insert a ue gas analyzer sampling probe le hand sam­ple point, then check that the CO specied in the table in par. 3.24, if adjustment
value is that
2
is required, turn screw (3 Fig. 3-12) (O-Set regulator). To increase the CO adjustment screw (3) in a clockwise direction and
value, turn the
2
vice versa to decrease it.
Calibration of maximum CO When you nish the minimum CO2 adjustment,
.
2
turn the boiler on and start the chimney sweep function at the maximum output (100%). To have an exact value of CO2 the technician must insert a ue gas analyzer sampling probe le hand sam­ple point, then check that the CO2 value is that specied in the table in par. 3.24, if adjustment is required, turn screw (12 Fig. 3-12) (gas ow rate regulator). To increase the CO2 value, turn the adjustment screw (12) in an anti-clockwise direction and vice versa to decrease it. At every adjustment variation on the screw (12) it is necessary to wait for the boiler to stabilise itself at the value set (about 30 sec.).

3.12 CH OUTPUT ADJUSTMENT.

If it is necessary to change the CH output, you will need to adjust the “P08” maximum CH out­put and “P09” minimum CH output parameters. To check the regulated heat output value, com­pare the no. of fan revs with that in the table (par. 3.24).
3.13 OUTPUT ADJUSTMENT DURING DHW ONLY IN COMBINATION WITH AN OPTIONAL EXTERNAL STORAGE TANK.
If it is necessary to change the DHW output, you will need to adjust the “P20” maximum DHW output and “P21” minimum DHW output parameters. To check the regulated heat output value, com­pare the no. of fan revs with that in the table (par. 3.24).

3.14 “CHIMNEY SWEEP” FUNCTION.

is function allows the technician to check the combustion parameters. Boiler operation in chimney sweep function can be adjusted to an output between 0% and 100%. To enable the function press and hold down “A”
3-11
If there is a common ow probe, it is possible to activate the chimney sweep function by press­ing buttons “A” and “B” simultaneously. In this case, the plant pump is activated as well as the boiler (in the “simple cascade” both boilers are activated) e output is adjusted from the + and
- DHW adjustment buttons at a range between 0 and 100%, while using the + and - buttons for CH adjustment, the percentage changes by 1% each time they are pressed. In this state all adjustments are excluded and only the temperature safety thermostat and the limit thermostat remain active. When the checks are nished disable the function by pressing and holding down button “A”. If you enable the function, you will need to wait approximately 30’’ to reach the set output (3’ on the Slave boiler)
Gas Valve 848
P1
P3
2
1
+
+
12
Key: 1 - Gas valve inlet pressure point 2 - Gas valve outlet pressure point 3 - O/Set adjustment screw
3
12 - Outlet gas ow rate regulator
3-12
34
3.15 3WAY PUMP ANTIBLOCK FUNCTION OPTIONAL.
e boiler has a function that starts the pump and 3-way valve at least once every 24 hours for the duration of 20 seconds in order to reduce the risk of the pump becoming blocked due to prolonged inactivity.
3.16 RADIATORS ANTIFREEZE FUNCTION.
e boiler has a function that makes the pump start when the system ow water reaches 8 °C. If the system ow water is at a temperature below 5 °C, the boiler starts to operate until it reaches approximately 16 °C.
3.17 ANTIHUMIDITY ELECTRODE FUNCTION.
With cascade installations combined with their relative ue manifold kits with ue adjusting devices, humidity may develop on the electrodes, causing them to fail. Avoid the formation of humidity by enabling this function (by setting a value other than 0), which turns the fan on at the speed set in parameter “P11” (5 minutes on and 5 minutes o). e function is active when the burner is o and the ow NTC probe temperature reading is greater than 35°C. e function is disabled when the temperature drops below 30 °C.

3.18 INLET 0 ÷ 10 V.

e microprocessor has an analogue 0 ÷ 10 V inlet (“Y” and “Z” terminals Fig. 1-4) that enables the boiler to be controlled from the outside. By setting the “P37” parameter, it is possible to set-up the inlet by choosing the functioning mode between temperature set and power set. e inlet activates a 2 V (minimum) request and increases it proportionally up to 9.5 V (max­imum). e request is deactivated below 1 V.
Notes:
- If “P37” is set at “0”, it is not active when the
boiler is in “stand-by” or “summer” mode.
e calculated set is dened within the “P02”
÷ 20 °C range. e maximum and minimum temperature within the set is limited by “P01” and “P32”.
- If “P37” is set on “1” it is always active. It is not
limited by the “P08” and “P09” parameters and does not have priority over the DHW request.
- Input voltage = -2.5 ÷ 12.5 V
- Input = 200 μA
- Impedance = > 50 KΩ

3.19 FUNCTIONING WITH COMMON FLOW PROBE.

With a hydraulic circuit breaker, there must be a common ow probe (with boiler ow probe functions) and a pump to be connected down­stream of the plant. e probe must be connected to terminals “S1” and “S2” and parameter “P38” must be set up, whereas the pump must be connected to termi­nals “C” and “D”. If there is a DHW circuit, it can be connected via an external 3-way to be connected to “IT”, “IS” and IK terminal, or use a suitable pump to be connected to “IT” and “IK” terminals. e DHW circuit has priority over the heating circuit. Please refer to chart Fig. 3-13 for the correct conguration.

3.20 AUTODETECTION.

This function enables the association of the display board to the boiler’s P.C.B. In addition, in case of “simple cascade” installation, it enables the detection and combination of cascade boilers. Turn the boiler on, programme it according to your needs, press and hold the “-” (Fig. 2-1 ref.
2) button down until “AUTO” appears, then press
“RESET” until “bu 1” appears.
3.21
SIMPLE CASCADE MAX. 2 BOILERS
It is possible to create a “simple cascade” by directly connecting two boilers. e two boilers turn on alternatively based on the plant’s requirements. Carry out the connection as indicated in the diagram (Fig. 3-6). With this configuration, there must be a common flow probe on the thermal plant, see the chart (Fig. 3-13) for the possible options. In order for the system to recognise the two boilers, you must activate the Autodetection and make sure both boilers are on. ey are associated when “bu 2” appears on the Master boiler and “SLA 2” appears on the Slave boiler. From this moment on, all programming is car­ried out on the Master boiler, while the “SLA 2” caption always appears on the Slave boiler, except in case of anomaly. e customised parameters of the Master boiler are automatically replicated on the Slave boiler. Warning: it is not possible to combine the cascade and zone regulator to the plant in this case. It is possible to connect an On/O room thermostat or use the 0 ÷ 10 V inlet (which must only be connected to the Master) to control the plant.
INSTALLERUSER
MAINTENANCE TECHNICIAN
boilers
Common ow probe present = 1
1 x x No
1 x x Central heating Domestic hot water
1 x x
2 x Not admitted Central heating Just as limit thermostat
2 x xx
“P38” parameter “P17” parameter
Common flow probe absent = 0
DHW pump (downstream the distribution ma nifold) = 1
3-way valve = 0
-
Common ow probe Boiler ow probe
Domestic hot water
Central heating
Domestic hot water
Central heating
Domestic hot water
Central heating
Just as limit thermostat
Just as limit thermostat
35
3-13

3.22 YEARLY APPLIANCE CHECK AND MAINTENANCE.

e following checks and maintenance should be performed every 24 months.
- Clean the ue side of the heat exchanger.
- Clean the main burner.
- If deposits are detected in the combustion
chamber one must remove them and clean the exchanger coils using nylon or sorghum brushes; it is forbidden to use brushes made of metal or other materials that may damage
INSTALLERUSER
the combustion chamber itself.
- Check the integrity of the insulating panels
inside the combustion chamber and if damaged replace them.
- Visually check for water leaks or oxidation
from/on fittings and traces of condensate residues inside the sealed chamber.
- Check contents of the condensate drain trap.
- Via the condensate drain cap check that there
are no residues of material that clog condensate passage; also check that the entire condensate drainage circuit is clear and ecient.
In the event of obstructions (dirt, sediment,
etc.) with consequent leakage of condensate in the combustion chamber, one must replace the insulating panels.
- Check that the burner seal gaskets and the lid
are intact and perfectly ecient, otherwise replace them. In any case the gaskets must be replaced at least every two years, regardless of their state of wear.
- Check that the burner is intact, that it has no
deformations or cuts and that it is properly xed to the combustion chamber lid; otherwise it must be replaced.
- Visually check that the water safety drain valve
is not clogged.
- Check that the system static pressure (with
system cold and aer relling the system by means of the ller cock) is not below 0.5 bar.
- Visually check that the safety and control
devices have not been tampered with and/or shorted, in particular:
- temperature safety thermostat;
- Check the condition and integrity of the elec-
trical system and in particular:
- electrical power cables must be inside the
fairleads;
- there must be no traces of blackening or
MAINTENANCE TECHNICIAN
burning.
- Check ignition and operation.
- Check correct calibration of the burner in
central heating phase.
- Check the operation of the appliance control and adjustment devices and in particular:
- intervention of the main electrical switch on
the boiler;
- system regulation probes intervention;
- Check sealing eciency of the gas circuit and the internal system.
- Check the intervention of the device against no gas ionisation ame control. e relative intervention time must be less than 10 seconds.
N.B.: in addition to maintenance, one must also check the thermal system, with frequency and procedures that comply with the indications of the technical regulations in force.
36

3.23 CASING REMOVAL.

To facilitate boiler maintenance the casing can be completely removed as follows:
- take the two screws out (3) from the bottom of the front (2);
- take the front down (2) by gripping its bottom handle, then pulling it towards yourself to de­tach it from the central hooks, and then slide it downwards;
- take the two clamping screws out (4) from the control panel, with their rings (5);
- press the two side hooks (7) and tilt the control panel (6);
- remove the lower grid (8) by loosening the 4 screws (9);
- at this point, if necessary, you can take down the protective cover (10) and side panels (12);
- take the cover down (10) by removing the relative screws (11);
- take down the two side panels (12) by removing the front screws (13) and unhooking the panels (ref. A Fig. 3-15).
INSTALLERUSER
MAINTENANCE TECHNICIAN
2
1
5
4
3
3
3-14
37
INSTALLERUSER
13
11
10
A
Ref. A
Rif. A
MAINTENANCE TECHNICIAN
13
A
13
12
7
1
7
6
8
13
12
9
38
9
3-15

3.24 VARIABLE HEAT OUTPUT.

NG (G20) LPG (G31)
HEAT OUTPUT
(kW) (MJ/h) (m
GAS
CONSUMPTIONS
BURNER GAS FLOW
RAT E
3
/h) (n°) (kg/h) (n°)
REVS
FAN
BURNER GAS FLOW
RAT E
49,9 227,4 5,43 6550 3,98 6450
49,0 223,1 5,32 6430 3,91 6330
47,0 213,4 5,09 6170 3,74 6060
45,0 204,0 4,87 5910 3,57 5810
43,0 194,6 4,64 5660 3,41 5550
41,0 185,4 4,42 5410 3,25 5300
39,0 176,3 4,21 5160 3,09 5050
37,0 167,2 3,99 4910 2,93 4810
35,0 158,3 3,78 4670 2,77 4570
33,0 149,4 3,57 4430 2,62 4330
31,0 140,6 3,35 4200 2,46 4090
29,0 131,8 3,14 3960 2,31 3860
27,0 123,0 2,94 3720 2,16 3620
25,0 114,3 2,73 3490 2,00 3390
23,0 105,5 2,52 3260 1,85 3160
21,0 96,8 2,31 3020 1,69 2930
19,0 88,0 2,10 2790 1,54 2700
17,0 79,1 1,89 2550 1,39 2470
15,0 70,2 1,68 2310 1,23 2240
13,0 61,3 1,46 2080 1,07 2000
11,0 52,2 1,25 1840 0,91 1770
9,0 43,0 1,03 1590 0,75 1530
7,0 33,7 0,81 1350 0,59 1290
5,0 24,3 0,58 1100 0,43 1050
REVS
FAN
INSTALLERUSER
N.B.
- e power data provided in the table is ob­tained with 0.5 m long intake/exhaust pipe.
- Gas ow rates refer to heating output below a temperature of 15°C and pressure of 1013 mbar.
- Burner pressure values refer to use of gas at 15°C.
- e number of revs for the fan on the display is expressed in revs / 50 (Ex.: 1000 revs = 20).
MAINTENANCE TECHNICIAN
39

3.25 COMBUSTION PARAMETERS.

NG (G20) LPG (G31)
Gas nozzle diameter mm 8,4 6,5 Supply pressure kPa 1,13 2,75 Flue ow rate at nominal heat output kg/h 81 82 Flue ow rate at min heat output kg/h 9 9
at Q. Nom./Min. % 9,40 / 9,10 10,60 / 10,10
CO
2
CO / CO NO Flue temperature at nominal output °C 52 53
INSTALLERUSER
Flue temperature at minimum output °C 48 48
at Nom./Min. Q. Nom./Min. - 0,00157 / 0,00001 0,00184/ 0,00001
2
at 0% of O2 at Q. Nom./Min. mg/kWh 43 / 17 43 / 21
X
Combustion parameters: measuring conditions of useful eciency (ow temperature/return temperature= 80/60 °C), ambient temperature reference = 15°C.

3.26 TECHNICAL DATA.

Nominal heat input kW (MJ/h) 51,3 (204,9)
Minimum heat input kW (MJ/h) 5,5 (21,9)
Nominal heat output (useful) kW 49,9
Minimum heat output (useful) kW 5,0
* Eciency 80/60 Nom./Min. % 97,3 / 91,2
* Eciency 50/30 Nom./Min. % 106,8 / 99,7
* Eciency 40/30 Nom./Min. % 107,4 / 103,5
Heat loss at casing with burner O/On (80-60°C) % 0,30 / 0,90
Heat loss at ue with burner O/On (80-60°C) % 0,03 / 1,80
Central heating circuit max. operating pressure kPa 440
Central heating circuit max. operating temperature °C 90
Adjustable central heating temperature °C 20 - 85
Head available with 1000 l/h ow rate kPa (m H
O) 60,10 (6,13)
2
Weight of full boiler kg 54,2
Weight of empty boiler kg 51,4
Boiler water content l 2,8
Electrical connection V/Hz 230/50
Nominal absorption A 1,0
Installed electric output W 155
Pump consumption W 57
EEI value - ≤ 0,23 - Part. 3
Fan power consumption W 79
MAINTENANCE TECHNICIAN
Equipment electrical system protection - IPX5D
Functioning room max. temperature °C +50
Functioning room min. temperature °C -5
Functioning room min. temperature with anti-freeze kit (Optional) °C -15
Flue gas max. temperature °C 75
class - 5
NO
X
Weighted NO
X
mg/kWh 39
Weighted CO mg/kWh 15
Type of appliance C13 / C33 / C63 / B23p / B33 / B53p
- The maximum sound level emitted during
- (*) Eciencies refer to the lower heating value. boiler operation is < 55dBA. e sound level value is referred to semianechoic chamber tests with boiler operating at max. heat output, with extension of ue gas exhaust system according to product standards.
40

3.27 EXPLODED BOILER DIAGRAM.

INSTALLERUSER
82D
VICTRIX PRO 55 1 A
17/05/17
3.0244935647076
OF SERIES
SERIAL NUMBER START
MAINTENANCE TECHNICIAN
41

3.28 SPARE PART LIST.

(
)
(
)
)
(
)
)
)
)
)
(
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
y
)
)
(
)
(
)
(
)
)
)
)
)
)
p
)
)
(
)
(
)
)
)
)
)
)
(
)
)
)
)
)
(
)
)
)
153 1.031901 Cable clamp 154 1.031902 Locknut 155 1.036664 Gas nozzle (d.8,40
)
155 1.036688 Gas nozzle (d.6,50
)
156 1.035404 Crossheaded self-tapping screw for
p
lastic(3x25
)
157 1.8532 Crossheaded self-tapping screw
(
3,9x16
)
158 2.015402 Spark generator bracket 159 1.037212 Thermostat, manual reset 220°C 160 1.018320Absolute pressure switch 6863665 161 1.027887 Gasket
(
11,5x6,1x2
)
)
)
p
)
(
)
)
N. CODE DESCRIPTION
- 3.025107 Complete control panel
- 3.027207 Complete control panel 6863665 1 1.033648 Condensation module 2 1.012949 11.91x2.62 O-ring, nitrile, 70 sh 3 1.036632 Fitting 4 1.015436All-purpose valve + O-ring 5 1.034101 NTC fast immersion probe 6 2.015106 Module mount bracket 7 1.2275 Flat pointed crossheaded self-tapping
8 2.015218 Module mount 9 1.036541 Clip
10 1.034119 19x3.15 O-ring, epdm
INSTALLERUSER
11 1.033800 Condensation module - manifold pipe
12 1.026763 Pipe clip (d.18 13 1.1656 Nickel-plated crosshead self-tapping
14 1.016870 Klixon thermostat 105 °C 15 1.023435 NTC fast immersion probe 16 1.2269 9.25x1.78 O-ring, nitrile, 70 sh 17 1.033429 M5x10 hex screw 18 1.012468 Stainless steel elastic washer (M5 19 2.015102 Fiber element blocks 20 1.035086 Front paper 21 1.025689 Gas manifold gasket 22 1.038865 Cord packing 23 1.033862 Ceramic fibre panel 24 1.035087 Back paper 25 1.025911 Nut(M6 26 1.036639 Gas manifold 27 1.024898 Gasket for module inspection hole 28 2.013322 Flange for module cover inspection
29 1.2170 Crossheaded screw (M4x8 30 1.034606 Ceramic glass (d.20 31 1.0110 Crossheaded flat pointed self-tapping
32 1.7349 Crossheaded screw (M4x10 33 1.028702 Ignitor 34 1.034560 Ignition electrode gasket 35 1.033863 Burner gasket 36 1.2217 M5x12 screw, crosshead, stainless
37 1.038783 Burner 38 1.033614 Gas manifold cover 39 1.024084 Crossheaded screw (M5x14 40 1.028890 Detection electrode 41 1.036637 Seal fan 42 1.033960 Fan 43 1.038935 Venturi gasket 44 3.023870 Venturi 44 3.024157 LPG Venturi 45 1.023992 Gasket(24x16x2 46 1.034774 Flange, inlet 47 1.033864 Gasket for flange 48 1.033977 Clip wirelocking (d.50 49 1.036647Air intake pipe 51 1.033963 Outlet manifold 51 1.039709 Outlet manifold 6863665 52 1.4275 Drain fitting with hose union 53 1.2169 Cone pointed grub screw (M4x10 54 1.2558 Nitrile O-Ring (23,52x1,78, 70 sh 55 3.027339 Safety valve group (4 bar 56 1.016211 1''M-D.18 Vabco fitting 57 1.033964 D.18 pipe, manifold - draining funnel 58 1.038394 Gasket(34x27x1 59 1.038337 Lowered brass nut (3/4''F 60 1.018870 Draining funnel 61 1.016125 17.12x2.62 O-ring, epdm
MAINTENANCE TECHNICIAN
62 1.033793 Gas valve - venturi pipe (d.18 63 1.025986 Silicone pipe (4x8 64 1.018472 SIT 848 gas valve 65 1.023993 Gasket(14.8x8x2 66 1.013186 Screw(M3,5x16 67 1.033799 Flow switch - module pipe (d.18 68 1.035966 Flow switch 69 1.038609 Flowmeter cap 70 1.034551 Pump - flow switch pipe (d.18 71 1.023511 Gasket(30x22x2 72 1.033966 Pump(15-70 72 1.039695 Pump(15-75 73 3.024236 Pump mouting flange assembl 74 1.035733 Plastic siphon 75 1.021892 Siphon plug 76 1.0153 Crossheaded screw (M4x6 77 1.023581 Rubber adapter
screw
d.18
screw
hole
screw
steel
4.2x9.5
3,5x6,4
4,2x13
SERIAL NUMBER START OF
SERIES
6863665
78 1.019654 Flexible hose for siphon 79 1.034570 Gas manifold cover gasket 80 1.035734 Flexible hose gasket 81 1.016187 Silicone tube (8x12 82 1.029694 Energy metering coupler fitting 3/4"
83 1.016967 Spring pipe clamp for silicone pipe
84 1.039620 Spark generator 85 1.016246 Crossheaded self-forming screw
86 1.6984 Crossheaded flat pointed self-tapping
87 1.023676 Gasket(d.80 88 1.2364 Brass pressure point 89 1.034610Annealed copper washer (10x5,2x1 90 1.8599 Washer(4,3x12 91 3.023387 Flue hood group 92 1.025278 Plug for flange with sample points 93 1.036108 Flue exhaust pipe (d.80 94 1.020368 Lip gasket (d.80 95 1.034463 Frame 96 1.035251 Crossheaded self-tapping screw for
97 1.033967 Bezel, control panel 97 1.039518 Bezel, control panel 6863665 98 1.034464 Control panel door
99 1.035241 Spring 100 1.035335 Manometer 101 1.032513 Epdm O-ring (37,77x2,62, 55sh 102 1.033970 Control panel push-button 103 1.037404 Display board 104 1.026515 Gas valve connector 105 1.037403 PCB 106 1.037171 Clip in 107 1.033968 Control panel back cover 108 1.6658 Two-position main switch 109 1.034604 Knob 110 1.019286 Knob gasket 111 1.4005 5-way terminal block with fuse
112 1.4512 Crossheaded flat pointed self-tapping
113 1.7748 4-way terminal block 114 1.019641 7-way terminal block 115 1.7908 Black cable clamp 116 1.6011 Crossheaded flat pointed self-tapping
117 1.6811 6-way terminal block 118 2.015227 Bracket bottom 119 1.4066 Self-tapping screw (3,5x9,5 120 1.035182 Handle 121 1.034612Adhesive nameplate 121 1.039506Adhesive nameplate 6863665 122 2.015225 Front casing 123 1.024678 Insulating sheet 124 1.035207 Locking stud 125 1.035195 Stud 126 1.036640 Nut(M4 127 1.019761Adhesive foam strip (d.5x2 128 1.025801 Stud M4 129 2.015226 Lx casing 130 2.015224 Rx casing 131 1.013154Adhesive foam strip (d.15x3 132 1.034462 Thermoformed cover 133 1.023379 Sample points cover 134 1.038606 Hole gasket (d.80 135 2.012299 Gasket locking flange 136 1.025142 Clip 137 1.020312 Stainless steel crossheaded screw
138 1.025257 Self-tapping screw gasket (4,2x13,1 139 2.015377 Front tubular 140 2.015376 Frame cross lx member 141 2.015375 Frame cross rx member 142 3.024118 Frame group 143 2.015620 Valve supporting plate 144 2.010615 Boiler supporting bracket 145 1.022611 Hex headed screw (8x80 146 1.023203 Nylon masonry plug 147 1.011066 Washer(9x4,3x0,8 148 1.011163 Tropicalized washer (3,2x7x0,5 149 1.021519 Pressure switch locking clip 150 1.019640 Cone pointed crossheaded self-
151 1.026455 Red silicone O-ring (9,19x2,62 152 1.026457 Epdm O-Ring (7,6x2,62, 70 sh
153 1.031901 Cable clamp 154 1.031902 Locknut 155 1.036664 Gas nozzle (d.8,40 155 1.036688 Gas nozzle (d.6,50 156 1.035404 Crossheaded self-tapping screw for
157 1.8532 Crossheaded self-tapping screw
158 2.015402 Spark generator bracket 159 1.037212 Thermostat, manual reset 220°C 160 1.018320Absolute pressure switch 6863665 161 1.027887 Gasket(11,5x6,1x2
M-F
d.22
M4x8
screw
2.9x9.5
lastic(3x18
housing
2.9x19
screw
screw
3,5x9,5
M4x16
tapping screw
lastic(3x25
3,9x16
4,2x19
6863665
42

3.29 BOILER REGISTRATION.

is Commissioning Checklist is to be com­pleted in full by the competent person who commissioned the boiler as a means of demon­strating compliance with the appropriate Building Regulations.
Failure to install and commission according to the manufacturer’s instructions and complete this Commissioning Checklist may invalidate the warranty.
Customer name: Telephone number:
Address:
Boiler make and model:
Boiler serial number:
Commissioned by (PRINT NAME): Plumbing license number:
Company name: Telephone number:
Company address:
Commissioning date: Commissioning date:
Certicate of compliance number:
CONTROLS (tick the appropriate boxes)
Time and temperature control to heating
Time and temperature control to hot water Cylinder thermostat and programmer/timer Combination boiler
Heating zone valves Fitted Not required
Hot water zone valves Fitted Not required
ermostatic radiator Fitted Not required
Automatic bypass to system Fitted Not required
Boiler interlock Provided
Room thermostat and programmer/timer Programmable room thermostat
Weather compensation Optimum start control
INSTALLERUSER
ALL SYSTEMS
e system has been adequately ushed and cleaned? Yes
What system cleaner was used?
What inhibitor was used? Quantity Litres
Has a system lter been installed? Yes No
HEATING MODE measure and record:
Burner inlet gas working pressure (at maximum rate) Kpa OR gas inlet pressure Kpa
Central heating ow temperature °C
Central heating return temperature °C
COMBINATION BOILER  DOMESTIC HOT WATER MODE measure and record:
Burner inlet gas working pressure (at maximum rate) Kpa OR gas inlet pressure at maximum rate Kpa
Cold water inlet temperature °C
Hot water has been checked at all outlets Yes Temperature °C
Has a DHW tempering valve been tted to sanitary ttings? Yes Temperature °C
Water ow rate I/min
CONDENSING BOILERS ONLY
e condensate drain has been installed in accordance local laws in force? Yes
ALL INSTALLATIONS
Record the following:
e heating and hot water system complies with the appropriate Building Regulations Ye s
e boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions Yes
e operation of the boiler and system controls have been demonstrated to and understood by the customer Yes
e manufacturer’s literature, including Commissioning Checklist and Service Record, has been explained and le with the customer Yes
At max. Rate: Co Ppm Co
At min. Rate: (where possible) Co Ppm Co
% Ratio CO/CO Ratio
²
% Ratio CO/CO Ratio
²
MAINTENANCE TECHNICIAN
Commissioning Engineer’s Signature
Customer’s Signature
(To conrm satisfactory demonstration and receipt of manufacturer’s literature)
43

3.30 COMMISSIONING BOILER CHECK LIST.

A suggested method of commissioning the boiler, actual method can very according to the boiler make type and the installation. e boiler must always be installed, and commissioned by an qualified gas technician. The installer certies that this Boiler has been installed to the manufacturer’s instructions, has been lled, commissioned and is ready for use.
INSTALLERUSER
No. Description
1 Read carefully the instruction manuals supplied with this boiler.
2 BEFORE INSTALLING THIS BOILER FLUSH OUT THE PIPES UNTIL CLEAN WATER IS ACHIEVED. IF REPLACING
AN OLD BOILER, HUNT HEATING RECOMMENDS A POWER FLUSH
3 Turn o all service to this boiler - water, gas and power. Install the boiler as shown in the instructions following and
connect all services.
4 Turn on water to ll system, check for leaks regularly and bleed air from all points.
Bleed the air from all the pumps in the system, and rotate the impeller sha.
5 Check that all radiators valves are open, all lock shields remove the thermostatic valve heads, fully open.
6 Turn ON gas, bleed air out at the isolation valve union. Reseal and check for gas leaks.
7 Turn electricity on at the power point. At the boiler front panel set the temperature setting to the lowest setting, switch
boiler to ON position. e “Power on” Indicator should light. Turn the boiler o at the front panel.
8 Turn the room thermostat to the manual ON position set the temperature to a high level so that it does not switch o
during the commissioning phase. e thermostat will unusually click and shows an Indicator in the window.
9 Boiler should start fan, pump and ignite gas. If it fails rst few times this may be just residual air in the gas line. A noisy
water pump indicates there is air in the water pipes.
10 Boiler lights and heats the water. Check gas ame is the correct colour and for gas and water leaks as the system heats up.
11 Check that heat is circulating to all radiators through the manual or thermostatic radiator valve located on the ow pipe
(unless reverse ow thermostatic valves).
12 Allow the boiler to heat up to the set temperature and switch o. Re-adjust the boiler temperature to a mid temperature point.
CAUTION, if this is connected to a oor heating system. e boiler should re light and increase the water temperature to the new setting.
13 Check that all radiators are hot all the way up. If the radiator is cold at the top, then there is usually air in the radiator
Bleed the radiator. Balance the system so that all radiators are hot as according to the radiator installation manual. Adjust the boiler water temperature.
14 Set the room thermostat to the correct times and temperatures according to the manufacturer’s instructions.
15 On completion of the commissioning phase, complete the information sheet at the front of this manual.
Hand over the installation to the owner and demonstrate how the system works plus basic fault resolution and safety procedures. Make sure that this important document is kept in a safe accessible place.
when done
IF IN DOUBT ASK
MAINTENANCE TECHNICIAN
No. Description
Handover Instructions
1 Fill in all the details on this Boiler manual.
2 Instruct the owner/users on the correct operation of this heating system, this includes how to turn the system on and o,
adjust the time and temperature settings.
3 How to turn the heating system o in summer and on for winter.
4 Where all the major items are, their functions and how to check and turn them on or o. Simple fault resolution i.e. power on.
5 How to check and remove air in the radiators. Give them a bleed key.
6 e importance of this SERVICE RECORDS, keeping safe & accessible when required.
7 Recommend that the boiler should be serviced anually and that the service is recorded withing the allocated area of the
boiler installation manual.
44
when done

3.31 SERVICE RECORDS.

SERVICE 01
Engineer name:
Company name:
Telephone No:
Plumbing Licence No:
Record:
At max. rate: CO ppm CO
At mim. rate: CO ppm CO
Comments:
Signature
SERVICE 03
Engineer name:
Company name:
Telephone No:
Plumbing Licence No:
Record:
Comments:
At max. rate: CO ppm CO
At mim. rate: CO ppm CO
Date:
% CO/CO²Ratio
²
% CO/CO²Ratio
²
Date:
% CO/CO²Ratio
²
% CO/CO²Ratio
²
SERVICE 02
Engineer name:
Company name:
Telephone No:
Plumbing Licence No:
Record:
At max. rate: CO ppm CO
At mim. rate: CO ppm CO
Comments:
Signature
SERVICE 04
Engineer name:
Company name:
Telephone No:
Plumbing Licence No:
Record:
Comments:
At max. rate: CO ppm CO
At mim. rate: CO ppm CO
Date:
% CO/CO²Ratio
²
% CO/CO²Ratio
²
Date:
% CO/CO²Ratio
²
% CO/CO²Ratio
²
INSTALLERUSER
Signature
SERVICE 05
Engineer name:
Company name:
Telephone No:
Plumbing Licence No:
Record:
At max. rate: CO ppm CO
At mim. rate: CO ppm CO
Comments:
Signature
SERVICE 07
Engineer name:
Company name:
Telephone No:
Plumbing Licence No:
Record:
Comments:
At max. rate: CO ppm CO
At mim. rate: CO ppm CO
Date:
% CO/CO²Ratio
²
% CO/CO²Ratio
²
Date:
% CO/CO²Ratio
²
% CO/CO²Ratio
²
Signature
SERVICE 06
Engineer name:
Company name:
Telephone No:
Plumbing Licence No:
Record:
At max. rate: CO ppm CO
At mim. rate: CO ppm CO
Comments:
Signature
SERVICE 08
Engineer name:
Company name:
Telephone No:
Plumbing Licence No:
Record:
Comments:
At max. rate: CO ppm CO
At mim. rate: CO ppm CO
Date:
% CO/CO²Ratio
²
% CO/CO²Ratio
²
Date:
% CO/CO²Ratio
²
% CO/CO²Ratio
²
MAINTENANCE TECHNICIAN
Signature
Signature
45
SERVICE 09
Engineer name:
Company name:
Telephone No:
Plumbing Licence No:
Record:
Comments:
INSTALLERUSER
At max. rate: CO ppm CO
At mim. rate: CO ppm CO
Date:
% CO/CO²Ratio
²
% CO/CO²Ratio
²
SERVICE 10
Engineer name:
Company name:
Telephone No:
Plumbing Licence No:
Record:
Comments:
At max. rate: CO ppm CO
At mim. rate: CO ppm CO
Date:
% CO/CO²Ratio
²
% CO/CO²Ratio
²
Signature
Signature
MAINTENANCE TECHNICIAN
46
AS/NZS 5263.1.2
Cert. SAI-400090
is instruction booklet is made of ecological paper Cod. 1.039823 - rev. ST.002925/001 - 03/18
SAI Global
Loading...