Immergas VICTRIX 50 User Manual

Page 1
Wall mounted condensing boilers with low NOx
VICTRIX 50
1
1 SPECIFICATIONS
50 kW (43,000 kcal/h) wall-mounted premixed condensing boiler with sealed or open chamber, forced draught, high efciency and forced circulation. Approved for installation in both heating plants and outside buildin­gs. Can be used in two congurations:
Open chamber and forced draught (appliance type B23/ B
33
)
- Does not need any additional kit as it leaves the factory in this conguration.
Sealed chamber and forced draught (appliance type C13/C33/C63)
- if installed using the vertical or horizontal concentric kits. The generator consists of:
• combustion system of the total premixing type with cylindricel multigas burner made of steel, complete with ignition electrodes and ionizing monitoring probe;
• pneumatic type gas valve with double shutter;
• primary gas/water exchanger with coil made of AISI 316L stainless steel;
• combustion chamber in stainless steel insulated on the inside with ceramic panels;
• fumes extraction fan with electronically variable speed;
• condensation disposal circuit including syphon and exible drain hose;
• hydraulics consisting of a delivery manifold, primary circuit pressure switch, circulation pump including automatic air venting valve;
• 4 bar system safety valve (ISPESL approved), pressure gauge for the heating system;
• overtemperature safety thermostat;
• control panel equipped with electronic board with microprocessor and innite ame modulation for the heating process plus P.I.D. monitoring, modulation ranging from 10.0 to 50.0 kW (from 8,600 to 43,000 kcal/h);
• system delivery regulating probe;
• system return regulating probe;
• heating delivery temperature with 20 to 85°C factory setting;
• ignition delayer during the heating phase, antifreeze protection, pump anti-blocking system, chinmey-sweep function;
• the boiler operating parameters can be entered and regulated by means of keys while the status and operating modes are shown on the 4-digit display;
• autodiagnosis system with digital display of the temperature, the operating status and error codes on the permanently visible display;
• IPX5D electrical insulation degree;
• pre-engineered for connection of the Series Regulator and external probe;
• pre-engineered for connection of an external three-way valve for use with a separate water heater in order to produce domestic hot water;
• pre-engineered for operation in series (up to 3 generators);
• pre-engineered for installation of the ISPESL-approved safety stub pipe;
• can be used with the Ø 80 mm hose pipe connecting system.
Supplied complete with traps for combustion analysis, bottom protection grille and gas on-off cock.
Natural gas and L.P.G. fuelled Class II
2H3+
appliance. CE marking.
The following model is available:
• VICTRIX 50 code 3.015276
NOTE: to correctly install the boiler, use the "Green series" Immergas air intake/fumes exhaust kit dedicated to the VICTRIX 50 boiler in both the single and series (bank) congurations.
VICTRIX 50 is the new wall-mounted condensing boiler for room heating alone. It is pre-engineered for operation both independently and in series (up to 3 appliances connected), with the advantage of providing a globally higher efcien­cy at lower running costs. Condensing technology allows particularly high efciency ratings to be achieved (4 stars, as established by Directive 92/42/EEC). VICTRIX 50's high power is ideal when it comes to heating domestic systems that have to deal with large volumes (semi-detached houses, small condominiums and apartment blocks) and for com­mercial and industrial uses. If a single boiler is installed, an external three-way valve can be connected so as to use it with a separate water heater and produce domestic hot wa­ter. A hydraulic manifold can also be connected to boost the circulation in the system, thus making it versatile and quick to install. When operation is in series, several distribution manifolds can be connected by means of threaded mecha­nisms. The special environment-friendly burner guarantees particularly low polluting emissions (the boiler belongs to the most environment-friendly class established by the European standards, i.e. class 5).
Page 2
2
VICTRIX 50
3
VICTRIX 50
LEGEND: 1 - Electronic board 2 - Delivery manifold 3 - System pressure switch 4 - Condensation drain pipe 5 - Air intake pipe 6 - Air fan 7 - Gas nozzle 8 - Venturi 9 - Detection electrode 10 - Cover of condensing module 11 - Sleeve with Venturi housing 12 - Condensing module 13 - Draught diverter 14 - Intakes (air A) - (fumes F)
15 - Positive signal pressure point 16 - Negative signal pressure point 17 - System return regulating NTC probe 18 - Overtemperature safety thermostat 19 - Dummy electrode 20 - Ignition plug 21 - Condensate syphon 22 - Current transformer 23 - Air venting valve 24 - Gas valve 25 - Circolulation pump 26 - Drain funnel 27 - System delivery regulating NTC probe 28 - Burner 29 - 4-bar safety valve
2 MAIN COMPONENTS
Page 3
3
VICTRIX 50
Upper casing line
3 MAIN DIMENSIONS
3.1 CONNECTIONS
SC = Condensation discharge
Distance between upper casing line and Ø 80 outlet elbow: 170 mm
Distance between upper casing line and Ø 80/125 concentric inlet/outlet elbow: 200 mm
Model
VICTRIX 50
System delivery M
1" 1/2
System return R
1" 1/2
Gas supply G
3/4"
Model
VICTRIX 50
Height mm
950
Width mm
600
Depth mm
525
Page 4
4
VICTRIX 50
5
VICTRIX 50
4 DIMENSIONS AND WET CONNECTIONS (OPTIONAL) WITH A SINGLE BOILER
NOTE: Unlike the appliance, the ISPESL safety kit and the
three-way valve kit (electric valve motor) have the IPX4D electrical protection degree. If the appliance is installed ou­tdoors, these safety devices and components must therefore be adequately protected. Immergas declines all liability if the installer fails to use the genuine ISPESL-approved devices and kits manufactured by Immergas, or uses them improperly. The sensitive parts of the automatic thermal regulating and blocking switches and those of the thermometer (not part of the standard supply provided with the generator) must be
M
R
positioned as described in the installation instructions, in compliance with the provisions given in the "R" le. For ISPESL planning reasons, an ISPESL-approved pressure gauge must be added when the Immergas safety kit is instal­led (as part of the standard supply, the boiler comes already equipped with an ISPESL-approved 4-bar safety valve and drain funnel). The system return is pre-engineered with an expansion tank connection.
1" 1/2
1" 1/2
1"
2" 1/2
1"
Page 5
5
VICTRIX 50
5 DIMENSIONS AND WET CONNECTIONS (OPTIONAL) WITH BOILERS IN SERIES
(UP TO THREE APPLIANCES)
NOTE: Unlike the appliance, the ISPESL safety kit has the
IPX4D electrical protection degree. If the appliance is installed outdoors, these safety devices must therefore be adequately protected. Immergas declines all liability if the installer fails to use the genuine ISPESL-approved devices and kits manufactured by Immergas, or uses them improperly. The sensitive parts of the automatic thermal regulating and blocking switches and those of the thermometer (not part of the standard supply provided with the generator) must be positioned as described in the installation instructions, in compliance with the provisions given in the "R" le. For ISPESL planning reasons, an ISPESL-approved pressure gauge must be added when the Immergas safety kit is instal-
led (as part of the standard supply, the boiler comes already equipped with an ISPESL-approved 4-bar safety valve and drain funnel). The system return is pre-engineered with an expansion tank connection. The modular generators, or ones installed in the series conguration (bank) with the genuine Immergas hydraulic manifold kit, must be considered a single appliance which will have the serial number (factory number) of the generator nearest to the ISPESL safety device. The hydraulic manifolds are equipped with a check valve installed on the return pipe and system on-off cocks on the delivery and return pipes of each generator.
R
M
Page 6
6
VICTRIX 50
7
VICTRIX 50
6 CIRCULATOR HEAD AND FLOW RATE GRAPH
VICTRIX 50 boilers are supplied with built-in circulator and three-position electric speed governor. The circulator is the single-phase type (230 V - 50 Hz) are co-
mes already equipped with condenser. In new systems (single pipe and modules), it is advisable to use the circulator pump at top speed to obtain optimum operation from the boiler.
A = Available head at top speed with single boiler B = Available head at second speed with single boiler C = Available head at top speed with check valve for boilers in series (bank) D = Available head at second speed with check valve for boilers in series (bank)
DYL 63-15
Head (kPa)
A
Flow rate l/h
C
B
6.1 VICTRIX 50 CIRCULATOR
D
Head wc.)
Page 7
7
VICTRIX 50
7 THERMOREGULATION SYSTEMS (OPTIONAL)
8 SERIES AND ZONE REGULATOR (CODE 3.015244)
Single modular generators or ones installed in series need an adequate thermoregulation system able to dialogue with the boiler in a simple way and meet the most varied operating requirements. This is why the VICTRIX 50 generator can be tted with a series of accessories able to optimize the climatic adjustments made to the entire system. In short, VICTRIX 50 can be installed with two types of system:
• In series (with the system divided into one or more zones), using the series regulator with either the zone controller or modulating ambient thermostat that regulates the heat in the individual zones.
• Individually (with the system divided into zones) using the series regulator with either the zone controller or modulating ambient thermostat that regulates the heat in the individual zones. A commercially available timer-thermostat can be used if there is only one zone.
The Series and zone regulator allows the user to control, mo­nitor and program the operating sequence of the generators connected. The regulator can be set-up and programmed using parameters that guarantee ideal temperature condi­tions at all times of the day and night and throughout every day of the week for both the heating system and domestic hot water system (when VICTRIX 50 is used in conjunction with a water heater). The series regulator can be tted into a support afxed to a wall.
8.1 SPECIFICATIONS
The electrical connections are made with 2 wires powered at 230V (1.5 mm2 ) in diameter. 2 BUS data cables up to 50 meters in length are used to connect to the boiler, allowing the device to:
• control up to three zones (2 of which mixed if necessary) and a separate water heater unit. Since up to 5 series re­gulators can be installed (of which only one, the so-called Master, will be connected to the boiler board), systems with up to a total 15 zones (of which 10 mixed if necessary) and 5 separate water heater units can be controlled;
• enter two ambient temperature values, one for the daytime (comfort temp.) and one for the night (lower temp.);
• control the temperature of the domestic hot water (in conjunction with a water heater Unit);
• select the operating mode for the heating and hot water production functions of each individual hydraulic circuit:
- comfort temperature mode,
- low temperature mode,
- adjustable antifreeze temperature mode;
• control the boiler delivery temperature according to the ou­tdoor temperature (in conjunction with the external probe), with climatic curve settings;
• obtain information about the system:
- temperature of the system,
- operating mode,
- meter data,
- timer program,
- pump operating status,
- variable input values and operation;
• enter the operating parameters:
- operating times,
- operating mode,
- domestic hot water,
- direct, mixed 1, mixed 2 circuits,
- date and time;
• display operating faults with their relative error codes by means of the check-control system;
• display the date, time, day of the week and temperature of the generator.
Page 8
8
VICTRIX 50
9
VICTRIX 50
9 ZONE CONTROLLER (CE 3.015264)
The zone controller only operates in conjunction with the series regulator. Besides the functions described for the series thermoregulator, it allows the user to keep all the important information concerning the operation of the appliance and heating system under control and particularly ready to hand. This means that the previously set parameters can be easily modied without having go go to the place where the series regulator is installed. the climatic timer-thermostat built into the remote control panel allows the system's delivery temperature to be adapted to the effective needs of the place being heated so as to obtain the required ambient temperature with the utmost precision and, thus, with evident savings in running costs. The controller also allows the ambient tempe­rature and effective outdoor temperature to be displayed (this latter if the external probe is installed). The zone controller is powered by the series thermoregulator by means of 2 BUS data cables.
9.1 SPECIFICATIONS
2 BUS data cables up to 50 meters in length are used to connect to the series and zone regulator, allowing the device to:
• control up to one zone;
• enter two ambient temperature values, one for the daytime (comfort temp.) and one for the night (lower temp.);
• control the temperature of the domestic hot water (in conjunction with a water heater Unit);
• select the operating mode for the heating and hot water production functions of each individual hydraulic circuit:
- comfort temperature mode,
- low temperature mode,
- adjustable antifreeze temperature mode;
• control the boiler delivery temperature according to the ou­tdoor temperature (in conjunction with the external probe), with climatic curve settings;
• obtain information about the system:
- temperature of the system,
- operating mode,
- meter data,
- timer program,
- pump operating status,
- variable input values and operation;
• enter the operating parameters:
- operating times,
- operating mode,
- domestic hot water,
- direct, mixed 1, mixed 2 circuits,
- date and time;
• display operating faults with their relative error codes by means of the check-control system;
• display the date, time, day of the week and temperature of the generator.
Page 9
9
VICTRIX 50
11 EXTERNAL PROBE (CODE 3.015266)
The external probe allows the maximum temperature delive­red to the system to be automatically lowered or raised as the outdoor temperature rises or lowers, thus adapting the heat supplied to the system to suit the outdoor temperature variations. The probe is connected straight to the boiler's terminal board with two wires. Once connected, it always acts even without the thermoregulation kit.
10 MODULATING AMBIENT THERMOSTAT (CODE 3.015245)
The modulating ambient thermostat (not a conventional On/Off model) only operates in conjunction with the series regulator and allows the user to regulate the ambient tempe­rature of one of the zones into which the system is divided (both in individual and series installations). The regulation curve of the ambient temperature in the zone can be modied by means of the series regulator itself. The modulating ambient thermostat is powered by the series thermoregulator via 2 BUS data cables.
10.1 SPECIFICATIONS
2 BUS data cables up to 50 meters in length are used to connect to the series and zone regulator, allowing the device to:
• control up to one zone;
• vary the ambient temperature of the zone;
• select the operating mode for the zone heating function:
- xed comfort temperature mode,
- xed low temperature mode,
- operation with the timer program.
Page 10
10
VICTRIX 50
11
VICTRIX 50
12 EXAMPLES OF VICTRIX 50 INSTALLATIONS WITH A SINGLE BOILER
LEGEND:
1 - VICTRIX 50 generator
2 - Series and zone regulator
3 - Zone controller
4 - Modulating ambient thermostat
5 - External probe
6 - Zone 1 temperature probe 1 (CMI-1)
7 - Zone 2 temperature probe 2 (CMI-2)
8 - Common delivery probe
9 - Temperature probe of Water heater unit
10 - Zone 1 mixer valve (CMI-1)
11 - Zone 2 mixer valve (CMI-1)
12 - Zone 1 heating circuit pump (CMI-1)
13 - Zone 2 heating circuit pump (CMI-2)
14 - Zone 3 direct circuit pump (CD)
15 - Water heater unit supply pump
16 - Zone 1 safety thermostat (CMI-1)
17 - Zone 2 safety thermostat (CMI-2)
19 - Fuel on-off valve bulb
20 - ISPESL approved pressure gauge cock
21 - ISPESL approved thermometer
22 - ISPESL approved manually reset pressure switch
23 - ISPESL approved manually reset thermostat
24 - Expansion tank connection
25 - Expansion tank
26 - Manifold/mixer
27 - External water heater unit
28 - Fuel on-off valve
29 - Check valve
30 - Sludge collecting system lter
31 - Thermometer trap
Page 11
11
VICTRIX 50
13 EXAMPLES OF VICTRIX 50 INSTALLATIONS IN SERIES
LEGEND:
1 - VICTRIX 50 generator
2 - Series and zone regulator
3 - Zone controller
4 - Modulating ambient thermometer
5 - External probe
6 - Zone 1 temperature probe (CMI-1)
7 - Zone 2 temperature probe (CMI-2)
8 - Common delivery probe
9 - Water heater unit temperature probe
10 - Zone 1 mixer valve (CMI-1)
11 - Zone 2 mixer valve (CMI-1)
12 - Zone 1 heating circuit pump (CMI-1)
13 - Zone 2 heating circuit pump (CMI-2)
14 - Zone 3 direct circuit pump (CD)
15 - Water heater unit supply pump
16 - Zone 1 safety thermostat (CMI-1)
17 - Zone 2 safety thermostat (CMI-2)
19 - Fuel on-off valve bulb
20 - ISPESL approved pressure gauge cock
21 - ISPESL approved thermometer
22 - ISPESL approved manually reset pressure switch
23 - ISPESL approved manually reset thermostat
24 - Expansion tank connection
25 - Expansion tank
26 - Manifold/mixer
27 - External water heater unit
28 - Fuel on-off valve
29 - Check valve
30 - Sludge collecting system lter
31 - Thermometer trap
32 - Draught circuit air lock
33 - Condensation drain pipe
34 - System on-off cock
Page 12
12
VICTRIX 50
13
VICTRIX 50
OPTIONAL ELECTRICAL CONNECTIONS.
The M and O terminals of thr Bus are connected in order to use the series and zone regulator. The ambient thermostat (S20) must be connected to terminals F and E, eliminating jumper X40. The external probe (B4) must be connected to terminals G and J.
LEGEND:
B1 - Delivery probe B2 - Domestic water probe (optional) B4 - External probe (optional) B5 - Return probe E1 - Ignition electrode E2 - Detection electrode E4 - Safety thermostat M1 - Boiler circulator M20 - Fan
M30 - Three-way valve (optional) R8 - Water heater function inhibiting resistance S1 - Main switch S5 - System pressure switch micro S16 - Summer switch (optional) S20 - Ambient thermostat (optional) T10 - Low voltage transformer X40 - Ambient thermostat jumper Y1 - Gas valve (24 Vdc)
14 WIRING DIAGRAM
The domestic water probe (B2) must be connected to termi­nals R and H, eliminating the resistance (R8). The three-way valve (M30) should be connected to terminals T, S and K. The summer switch (S16) must be connected to terminals V and U.
Page 13
13
VICTRIX 50
LEGEND:
1 - Visible funnel outlet 2 - ISPESL-approved 4 bar safety valve 3 - Boiler emptying cock 4 - Absolute pressure switch 5 - Delivery manifold 6 - Condensation trap 7 - Gas valve 8 - Air intake pipe 9 - Air ventilator 10 - Gas nozzle 11 - Detection electrode 12 - Condensing module cover 13 - Condensing module 14 - Draught diverter
15 - Air analyzer intake 16 - Fumes analyzer intake 17 - Δp gas pressure point 18 - System delivery regulating probe 19 - System return regulating probe 20 - Overtemperature safety thermostat 21 - Ignition electrode 22 - Burner 23 - Venturi negative signal (P2) 24 - Venturi positive signal (P1) 25 - Air/gas Venturi manifold 26 - Automatic air venting valve 27 - Boiler circulator
15 HYDRAULIC LAYOUT
Page 14
14
VICTRIX 50
15
VICTRIX 50
“GREEN SERIES” INTAKE/EXHAUST KIT FOR VICTRIX 50
16 TYPE OF INSTALLATION
VICTRIX 50 boilers are approved for installation both inside and outside the heat plant. The "VICTRIX 50" boiler leaves the factory in the "B23" con­guration (open chamber and forced draught). To change the boiler conguration to type "C" (sealed chamber and forced draught), dismantle the Ø 80 adapter, the plate and the seal on the boiler cover so that the relative Ø 80/125 kits can be used. To correctly install the boiler, use the special Immergas "Green" series air intake/fumes exhaust kit since the materials, components and accessories have been specically designed for this type of appliance. The kits are made of plastic material so as to provide high resi­stance to corrosion and make them very quick and functional to install, also thanks to the push-in connection mechanism and the silicone seals.
The boiler classication varies when the type of installation changes:
Configuration type C with sealed chamber and forced draught.
The boiler is installed using the relative Ø 80/125 concentric kits after having disassembled the Ø 80 adapter, the plate and the seal from the boiler cover. Air is thus inlet and fumes exhausted directly outside the building.
The following can be used as concentric intake/exhaust kit: Concentric Ø 80/125 horizontal kit Code 3.015242;
Concentric Ø 80/125 vertical kit Code 3.015243.
Configuration type B23 with open chamber and forced draught.
The boiler is installed using the Ø 80 adapter provided with the boiler as part of the standard supply and to which the relative Ø 80 fumes exhaust kit should be connected. The air is taken straight from the room in which the boiler is installed, while the fumes are exhausted through the ue or straight outdoors. This means that the installation must only be made in conjunction with one of the following fumes exhaust kits:
Ø 80 horizontal terminal kit for wall-mounted exhausts
Code 3.015255;
Ø 80 horizontal kit for ue exhausts
Code 3.015254;
Ø 80 vertical terminal kit for direct exhausts
Code 3.015256.
When installed singly, again in the "B23" conguration, VICTRIX 50 can also be used in conjunction with the Ø 80 hose pipe system for condensing boilers. This method is particularly suitable for stacks or ues (or technical apertures) that are not perfectly straight and where a rigid piping system could be difcult to install.
When installed in series in heat plants or technical rooms, special fumes manifolds can be used for exhausting into ues equipped with non-return devices (air-locks) to prevent the boiler's products of combustion from interfering with the combustion circuits of other boilers that are off.
Page 15
15
VICTRIX 50
MAXIMUM TOLERATED LENGTH OF Ø 80/125 HORIZONTAL KIT
Available resistance factor 100 Horizontal meters 14 + the rst
90° elbow
2
1
3
4
7
5
6
17 Ø 80/125 CONCENTRIC HORIZONTAL KIT (CODE 3.015242)
THE KIT INCLUDES:
1 - 1 (one) Ø 80/125 adapter 2 - 1 (one) seal Part (3) is standard supply with the boiler 4 - 1 (one) Ø 80/125 concentric elbow a 87° 5 - 1 (one) Ø 80/125 concentric intake/exhaust terminal 6 - 1 (one) internal rose 7 - 1 (one) external rose
Page 16
16
VICTRIX 50
17
VICTRIX 50
MAXIMUM TOLERATED LENGTH OF Ø 80/125 VERTICAL KIT
Available resistance factor 100 Vertical meters 18
THE KIT INCLUDES:
1 - 1 (one) Ø 80/125 adapter 2 - 1 (one) seal Part (3) is standard supply with the boiler 4 - 1 (one) rose 5 - 1 (one) aluminium plate 6 - 1 (one) xed half-shell 7 - 1 (one) Ø 80/125 concentric int./exh. terminal 8 - 1 (one) movable half-shell
2
1
3
4
5
8
7
6
18 Ø 80/125 CONCENTRIC VERTICAL KIT (CODE 3.015243)
Page 17
17
VICTRIX 50
MAXIMUM TOLERATED LENGTH OF Ø 80 VERTICAL KIT
Available resistance factor 100 Vertical meters 30
THE KIT INCLUDES:
1 - 1 (one) rose 2 - 1 (one) Ø 80 exhaust terminal
2
1
19 Ø 80 VERTICAL KIT (CODE 3.015256)
Page 18
18
VICTRIX 50
19
VICTRIX 50
MAXIMUM TOLERATED LENGTH OF Ø 80 HORIZONTAL KIT
Available resistance factor 100 Horizontal meters 30
20 Ø 80 HORIZONTAL TERMINAL KIT FOR
WALL-MOUNTED EXHAUST (CODE 3.015255)
20.1 Ø 80 HORIZONTAL TERMINAL KIT FOR STACK EXHAUSTS (CODE 3.015254)
THE KIT INCLUDES:
1 - 1 (one) 90° Ø 80 elbow 2 - 1 (one) Ø 80 exhaust pipe 3 - 1 (one) internal rose
THE KIT INCLUDES:
1 - 1 (one) 90° Ø 80 elbow 2 - 1 (one) Ø 80 exhaust pipe 3 - 1 (one) internal rose 4 - 1 (one) external rose
Page 19
19
VICTRIX 50
Each component of the air intake/combustion product exhausting system possesses a resistance factor calcu­lated by means of tests and given in the following tables. The resistance factor of each individual component is a dimensionless magnitude. This parameter is conditioned by the temperature of the uid and, thus, varies depending on
whether the component in question is installed in the air intake section or in the part where the combustion products are exhausted.
Each component also has a resistance corresponding to a certain length in meters of pipe of the same diameter: this is the so-called “equivalent length” obtained from the ratio between the relative resistance factors. To identify the link between these two parameters in the best possible way, rst consider an 80 mm diameter 90° elbow as an example. It possesses a 2.6 resistance factor on the exhausting part. However, if a pipe 80 mm in diameter and 1 meter in length is taken as a reference, it will be found to have a 1.2 resistance factor on the exhausting part. The equivalent length “Leq” of the considered elbow will therefore be:
Leq = 2,6 : 1.2 = 2.1 m of Ø 80 mm pipe (on the exhaust).
Very briey, the loss of head of an 80 mm diameter 90° elbow is the same as that of a 2.1 m length straight pipe of the same diameter (installed on the fumes outlet). All boilers have a maximum resistance factor of 100, cal­culated experimentally. The maximum tolerated resistance factor corresponds to the resistance found with the maximum tolerated pipe length. All this information allows calculations to be made in order to ascertain whether the various congurations of the system are feasible. In short, to ensure that the appliance operates in the correct way, every air intake/combustion product exhaust
conguration must have a maximum overall resistance factor of 100. This limit must not therefore be exceeded
when the resistance factors of the individual components used are added together.
The resistance factors and equivalent losses in meters are given in the catalogue in relation to:
- the “Green series” fumes exhaust pipes to use when making the combustion-aiding air supply pipes and fumes exhaust pipes (i.e. the pipes that connect the appliance and the stack/ue/ducted pipe);
- the components to use for making the Ø 80 mm hose pipe ducting system for condensing boilers, described further on in this brochure (meaning the mainly vertical pipe specically installed to collect the eliminate the pro­ducts of combustion as well as being able to withstand their components and condensation and t for installation in an already existing and not perfectly straight stack/ue/ technical aperture).
21 RESISTANCE FACTORS AND EQUIVALENT LENGTHS
Page 20
20
VICTRIX 50
21
VICTRIX 50
TYPE OF DUCT
Resistance
Factor
(R)
Equivalent
length in m of Ø 80/125
concentric pipe
Equivalent
length
in m of Ø 80 pipe
Ø 80/125 m 1 concentric pipe
4.9
Intake
and
exhaust
1.0 m
4.0 m
exhaust
90° elbow Ø 80/125 concentric pipe
9.5
Intake
and
exhaust
1.9 m
7.9 m
exhaust
45° elbow Ø 80/125 concentric pipe
6.8
Intake
and
exhaust
1.4 m
5.6 m
exhaust
Terminal complete with Ø 80/125 horizontal concentric
intake-exhaust pipe
26.8
Intake
and
exhaust
5.5 m
22.3 m
exhaust
Ø 80/125 horizontal concentric intake-exhaust terminal
22.9
Intake
and
exhaust
4.7 m
19.0 m
exhaust
Terminal complete with Ø 80/125 vertical concentric
intake-exhaust pipe
16.7
Intake
and
exhaust
3.4 m
13.9 m
exhaust
Ø 80/125 vertical concentric intake-exhaust terminal
13.3
Intake
and
exhaust
2.7 m
11.0 m
exhaust
Page 21
21
VICTRIX 50
TYPE OF DUCT
Resistance
factor
(R)
Equivalent
length in m of Ø 80/125
concentric pipe
Equivalent
length in m of
Ø 80 pipe
Ø 80 m 1 pipe
1.2
exhaust
0.24 m
1.0 m
exhaust
Terminal complete with Ø 80 m 1 exhaust pipe
3.1
exhaust
0.63 m
2.6 m
exhaust
Ø 80 exhaust terminal
1.9
exhaust
0.38 m
1.6 m
exhaust
90° Ø 80 elbow
2.6
exhaust
0.53 m
2.1 m
exhaust
45° Ø 80 elbow
1.6
exhaust
0.32 m
1.3 m
exhaust
Terminal complete with Ø 80 vertical exhaust pipe
3.6
exhaust
0.73 m
3 m
exhaust
Page 22
22
VICTRIX 50
23
VICTRIX 50
4
7
5
8
2
1
10
11
9
3
6
22.1 FUMES EXHAUST MANIFOLD KIT WITH ADDITIONAL BOILER IN SERIES (CODE 3.015241)
THE KIT INCLUDES:
1 - 1 (one) stub pipe with air lock 2 - 1 (one) stub pipe with air lock 4 - 1 (one) elbow (can be inspected) 5 - 1 (one) elbow (can be inspected) 7 - 1 (one) short pipe 8 - 1 (one) long pipe 10 - 1 (one) pipe 11 - 1 (one condensation drain pipe
To complete the installation and connect the fumes manifold to a stack, use a kit comprising a 2 m length Ø 125 mm extension pipe Code 3.015250.
THE KIT INCLUDES:
3 - 1 (one) stub pipe with air lock 6 - 1 (one) elbow (can be inspected) 9 - 1 (one) long pipe
22 FUMES EXHAUSTING MANIFOLD KIT WITH TWO BOILERS IN SERIES (CODE 3.015240)
Page 23
23
VICTRIX 50
23 Ø 80 HOSE PIPE DUCTING SYSTEM
The Immergas Ø 80 mm hose pipe ducting system for already existing stacks comprises a series of components, considered as single kits, which can be assembled to suit the specic installation requirements. This system is supplied in a con­guration that includes an 87° rising inlet elbow which then proceeds vertically with the Ø 80 hose pipe and the outlet terminal. The ducted pipe can be inspected through a ap in the part where it connects to the boiler. The kit consists of a 12 m length hose pipe. If the pipe is too short, it can be joined to other pieces by means of adapters. A centering spacer with expanding ns must be added every so often in order to ensure that the pipe keeps to the middle of the stack.
The maximum length that can be covered with this type of piping system is 30 m (approx.).
This length is obtained considering:
- 1 (one) Ø 80 mm 90° elbow for connection to the boiler (on the outlet);
- 1 m of Ø 80 mm discharge pipe;
- two direction offshoots in the vertical section;
- the Ø 80 mm bearing elbow;
- the vertical terminal kit for Ø 80/125 pipes.
It is important to note that:
- only one appliance can be used with this system;
- the system can only be used with condensing applian-
ces.
Page 24
24
VICTRIX 50
25
VICTRIX 50
24 TECHNICAL SPECIFICATIONS
VICTRIX 50
Maximum nominal heat input kW (kcal/h) 50.8 (43,655)
Maximum nominal heat output kW (kcal/h) 50.0 (43,000)
Minimum nominal heat input kW (kcal/h) 10.4 (8,958)
Minimum nominal heat output kW (kcal/h) 10.0 (8,600)
100% Pn efciency (80/60°C) % 98.5
Efciency at 30% of load (80/60°C) % 99.0
100% Pn efciency (50/30°C) % 106.0
Efciency at 30% of load (50/30°C) % 107.2
100% Pn efciency (40/30°C) % 107.0
Efciency at 30% of load (40/30°C) % 107.2
Heating circuit
Central heating temperature adjustment °C 20-85
Maximum heating temperature of system °C 90
Maximum operating pressure of system bar 4.4
Available head with 1000 l/h ow rate kPa (m w.c.) 52.9 (5.4)
Gas supply
NATURAL GAS (G20) MIN - MAX mbar 0.37 - 6.40
nozzles N°- ø mm 1 x 7.85
LPG (G30) MIN - MAX mbar 0.31 - 5.71
nozzles N°- ø mm 1 x 5.70
LPG (G31) MIN - MAX mbar 0.38 - 6.81
nozzles N°- ø mm 1 x 5.70
Electric power supply V/Hz 230 - 50
Nominal power draw A 0.85
Electric power installed W 180
Fan power draw W 59
Circulator power draw W 115
Electrical insulation degree IP X5D
Storage tank capacity liters 3.7
Weight of empty boiler kg 63
Energy efciency marking (Directive 92/42/EEC) stars ««««
Page 25
25
VICTRIX 50
The gas ow rates refer to the NHV at 15°C and with 1013 mbar pressure. The fumes temperature values refer to a 15°C inlet air temperature and 50°C delivery temperature.
25 COMBUSTION SPECIFICATIONS OF VICTRIX 50
Nat.gas (G20) LPG (G30) GPL (G31)
100% Pn combustion efciency (80/60°C) % 98.75 98.75 98.75
P min combustion efciency (80/60°C) % 97.5 97.5 97.5
100% Pn useful efciency (80/60°C) % 98.5 98.5 98.5
P min useful efciency (80/60°C) % 96.0 96.0 96.0
100% Pn useful efciency (50/30°C) % 106.0 106.0 106.0
P min useful efciency (50/30°C) % 106.5 106.5 106.5
100% Pn useful efciency (40/30°C) % 107.0 107.0 107.0
P min useful efciency (40/30°C) % 107.0 107.0 107.0
Stack losses with burner on (100% Pn) (80/60°C) % 1.25 1.25 1.25
Stack losses with burner on (P min) (80/60°C) % 2.50 2.50 2.50
Stack losses with burner off % 0.02 0.02 0.02
Outer casing losses with burner off % 0.47 0.47 0.47
Outer casing losses with burner on (100% Pn) (80/60°C) % 0.25 0.25 0.25
Outer casing losses with burner on (P min) (80/60°C) % 1.50 1.50 1.50
Fumes temperature at Max. nominal heat input °C 38 40 39
Fumes temperature at Min. nominal heat input °C 30 32 33
Fumes ow rate at Max. nominal heat input kg/h 81 72 82
Fumes ow rate at Min. nominal heat input kg/h 17 15 17
CO2 at maximum heat input % 9.26 12.3 10.5
CO2 at minimum heat input % 9.0 11.7 10.1
CO at maximum heat input mg/kWh 128 709 159
CO at minimum heat input mg/kWh 6 10 7
NOx at maximum heat input mg/kWh 69 392 132
NOx at minimum heat input mg/kWh 28 97 48
Weighted CO mg/kWh 38 - -
Weighted NOx mg/kWh 55 - -
NOx class - 5 5 5
Page 26
26
VICTRIX 50
27
VICTRIX 50
26 OPTIONALS
Series and zone thermoregulator kit
code 3.015244
Support kit for xing thermoregulator to the wall
code 3.015265
Zone controller kit
code 3.015264
External probe kit
code 3.015266
Modulating ambient thermostat kit
code 3.015245
System delivery probe kit
code 3.015267
Domestic water probe kit for external water heater
code 3.015268
Thermoregulator connector kit
code 3.015269
Page 27
27
VICTRIX 50
ISPESL safety pipe kit for single boiler
code 3.015222
ISPESL safety pipe kit for boilers in series
code 3.015227
Hydraulic manifold kit for connection
of two boilers in series
code 3.015225
Hydraulic manifold kit for additional boiler in series
code 3.015226
Hydraulic disconnector kit for single boiler
code 3.015224
125 fumes exhaust manifold extension kit
code 3.015250
Fumes exhaust manifold kit with air lock and
two boilers in series
code 3.015240
Fumes exhaust manifold kit with air lock and additional
boiler in series
code 3.015241
Page 28
28
VICTRIX 50
Three-way valve kit for use with external
water heater unit
(including water heater probe)
code 3.015223
UB 200 double water heater connection kit
code 3.015273
UB 200 re-circulation kit
code 3.015274
UB 200 connection kit for re-circulation in parallel
code 3.015342
UB 200 solar panel connection kit
code 3.015150
UB 200 kit for solar panel connection in parallel
code 3.015341
Antifreeze (-15°C) electric heating element kit code 3.015361
Page 29
Page 30
Page 31
Page 32
42041 Brescello (RE) Italy - Tel. 0522.689011 - Fax 0522.689102
www.immergas.com
During their working life, the performances of the products are influenced by external factors such as the hardness of the domestic water, the wea­ther conditions, scaling in the system, etc. The data indicated in this brochure re fe r t o new products , in stal led and use d in compliance with the cur­rent standards in force. NOTE: re mem b er t o ha ve y our ap pli anc e pe rio dic a lly se rvi ced.
Immergas reserves the right to make all modications to the models considered necessary for product development without prior notice.
Loading...