Immergas CARV2 Instructions For Use Manual

Page 1
CAR
V2
Modulating remote control
0 3 6 9 12 15 18 21 24
Instructions for use
Page 2
2
Our compliments for having chosen a top-quality
Immergas product, able to assure well-being and
safety for a long period of time.
As an Immergas customer you can also count on a
qualied after-sales service, prepared and updated to
guarantee constant eciency of your "Remote Control".
We would like to supply you with some important
indications, the respect of which will confirm your
satisfaction with the Immergas product:
• Read the following pages carefully: you will obtain
useful suggestions regarding the correct use of the
appliance.
• For any interventions or routine maintenance
contact "Immergas Authorised Centres": they
have original spare parts and specic preparation.
Page 3
3
INDEX
How to use the instruction book ................................................4
Foreword ...................................................................................... 4
General recommendations ..........................................................4
Case cleaning ................................................................................5
1. Installation .............................................................................. 6
1.1 Installation recommendations. .................................6
1.2 Installation operations. ...............................................6
2. Description of Controls ........................................................ 9
3. Description of display .........................................................10
4. Start-up .................................................................................12
4.1 Programming current day and time. ......................12
4.2 Selection of functioning mode ................................12
5. Summer mode functions ....................................................15
5.1 DHW temperature setting. ......................................15
5.2 DHW timer (for storage tank unit). .......................15
6. Winter mode functions.......................................................16
6.1 Manual functioning. ................................................. 16
6.2 Automatic functioning. ............................................ 17
6.3 Forced automatic functioning. ................................ 17
6.4 Boiler ow temperature. ...........................................18
6.5 Room anti-freeze function. ......................................18
6.6 Functioning in winter mode with external
temperature probe. ...................................................18
7. Cooling mode functions .....................................................19
7.1 Manual functioning. ................................................. 19
7.2 Automatic functioning. ............................................ 20
7.3 Forced automatic functioning. ................................ 20
8. Information .........................................................................21
9. Programming CAR V2 remote control. .............................22
9.1 Setting comfort and economy room
temperature. ...............................................................22
9.2 Programming functioning time. .............................23
10. Diagnostics and errors ........................................................25
10.1 Diagnostics.................................................................25
10.2 Reset errors. ...............................................................25
10.3 Reset CAR V2 remote control. ..................................25
11. Special functions .................................................................. 26
11.1 LANGUAGE (language selection). .........................26
11.2 REGULT (Management of regulation
parameter). .................................................................26
11.3 HOLIDY (holiday program). ................................... 27
11.4 LEGION (anti-legionella function ). ......................27
11.5 REMOTE (telephone control). ................................27
11.6 CODE. ........................................................................27
12. Functions protected by code (CODE). .............................28
12.1 AMB (room probe - On / O or modulating
functioning mode). ................................................... 28
12.2 REDUCT (functioning in reduced mode).............28
12.3 FRO PR (anti-freeze level). ......................................29
12.4 ZONE (function not present on this model).........29
12.5 SERVIC (programmed maintenance). ...................29
13. Disabling the chrono-thermostat. .....................................29
14. Technical characteristics ..................................................... 30
15. Factory setting .....................................................................31
Page
Page 4
4
HOW TO USE THE INSTRUCTION
BOOK
e instruction book has been divided into 3 main parts:
in the rst, for the installer, the assembly and connection phases of the remote control with the boiler are described;
in the second, all functioning program customisation phases are described;
in the third and last part, all operations for displaying and keeping system functioning under control are described.
FOREWORD
e “Immergas” “CAR V2 modulating remote control has been designed to guarantee ideal temperature conditions at any time of the day and night for each individual day of the week. Only a few minutes are required for installation: it is connected to the boiler by just 2 cables, through which, it receives and sends the adjustment and control commands and receives the power supply. On completion of installation it is ready to function thanks to the pre-set program inside. e customer can modify the basic program according to requirements. Programming of the "CAR V2" remote control is extremely easy and a wide display allows constant control of all values set.
GENERAL RECOMMENDATIONS
is manual has been drawn-up for: the Installer and the User.
• Carefully read the warnings contained in this document as they are required to indicate the use of the CAR V2 remote control envisioned by the design hypothesis, the technical features, the installation, assembly, programming, adjustment and use instructions.
• e system must be in compliance with the IEC Standards in force.
• e instruction manual must be considered a part of the CAR V2 remote control and must be “kept for future reference”.
• Aer having removed the packaging, check the integrity of the CAR V2 remote control. If in doubt, do not use it and contact the Dealer or Manufacturer.
• e CAR V2 remote control is destined only for the use for which it has been expressly designed. Any other use must be considered improper and therefore dangerous.
• Our products are realised in compliance with the Safety Standards in force, it is therefore recommended to use all those devices or attentions in a way that injury/damage is not caused to persons or objects.
Page 5
5
• Do not remove parts of the CAR V2 remote control when it is functioning.
• Do not use the CAR V2 remote control exposed to heat sources or under the scorching sun.
• e manufacture is relieved from any liability in the following cases:
a) Incorrect installation.
b) Boiler functioning defects to which the Remote
Control is applied.
c) Unauthorised modications or interventions.
d) Total or partial failure to comply with instructions.
e) Exceptional events etc.
CASE CLEANING
To clean the case of CAR V2 remote control use damp cloths. Never use abrasive or powder detergents.
WARNING
Immergas reserves the right to make improvements and modifications to details and accessories, excepting the essential features of the model described and illustrated herein.
Page 6
6
1. INSTALLATION
1.1 Installation recommendations.
e CAR V2 remote control, including the relative cables and connections to the boiler, must be installed by specialised sta. On the free initial check of the boiler, when the CAR
V2
remote control is inserted into the system, the Immergas authorised aer-sales centre checks the connection to the generator terminal board and adjusts functioning. e free check just of the CAR V2 remote control is not envisioned by the Immergas authorised aer-sales centre is requested successively to the start phase of the boiler warranty.
Important: laying of the CAR V2 remote control cables is excluded from the free boiler checks; it is the responsibility of the installer company.
1.2 Installation operations.
1) Separate the xing template from the body of the CAR
V2
remote control using a screwdriver as a lever in the relevant recess (Fig. 3). Install the CAR V2 remote control away from heat sources and in a suitable position to detect the room temperature correctly (Fig. 1 and 2).
Note:
the presence on the rear of the remote control of the pipe for electric connection cables with the boiler could recall air from outside the establishment and interfere with the correct detection of the room temperature (e.g.: boiler
installed outside and use of the suction hood in the kitchen). Have the job carried out by qualied sta.
2) Install the CAR V2 remote control using the holes made in the rear of the same directly onto the wall (Fig. 4) or on a recess box (Fig. 5) using the relative supplied screws.
Fig. 2
Fig. 1
OK
1,5m
NO
Page 7
7
Fig. 3
1
2
3
3
4
Important: the xing screws (action n° 3) on rst installation are no present on the CAR V2 remote control, but are supplied in a bag present in the packaging box. Once the template is xed to the wall, x the body of the CAR V2 remote control using the 2 screws.
Page 8
8
Fig. 5
Fig. 4
3) To make the electrical connections (Fig. 4) do not operate when the boiler is live. e connection must be made respecting the polarity of the wires (+ and -). e jumper on clamps 40 and 41 of the boiler P.C.B. (if present) must also be eliminated.
Connect the CAR V2 remote control to the boiler clamps
envisioned at communication with the CAR remote control or, if not present, to the clamps envisioned for the CRD.
Note: refer to the electrical connections stated in the boiler instruction book.
e connection to the boiler is made using two wires (Fig.
5)with minimum section of 0.50 mm2 and maximum of 1.5 mm2 and with maximum length of 50 metres.
N.B: for correct installation prepare a dedicated line for the connection of the CAR V2 remote control according to the Standards in force regarding electrical systems. If this is not possible interference due to other electric cables could cause malfunctioning of the CAR V2 remote control itself.
4) Fix the body of the CAR V2 remote control to the support template, engaging it with pressure and using the two screws provided (Fig. 3).
5) Aer the boiler has been powered, wait about 30 seconds before regulation in a way that the communication between CAR V2 remote control and boiler has established.
Telephone control (optional)
Boiler
CAR
V2
Page 9
9
2. DESCRIPTION OF CONTROLS
Fig. 6
Ref. Description
1
Main selector: O, Stand-by/anti-freeze, Summer, Winter, Cooling
2
“Reset” boiler anomalies/“Esc” escape parameter or return to previous menu button (programming mode)
3
Comfort and economy room temperature setting button
4
Reset button for starting CAR V2 remote control in event of anomaly of the same.
5 Access button to time, day and timer
6
Access button to the programming/conrm parameters menu
7
Domestic hot water temperature selector switch
8
Central heating water temperature selector switch
9 Information buttons
10 Manual, automatic functioning button
11 Temperature decrease button
12 Temperature increase button
Page 10
10
3. DESCRIPTION OF DISPLAY
Symbol Description
winter - DHW heating and room central heating buttons are enabled
summer - only the DHW central heating function is enabled
cooling - the cooling and DHW central heating function is enabled
request for room central heating or cooling by CAR V2 remote control
aqua celeris active/DHW comfort in progress
request for DHW in progress
room central heating in progress
description of functioning of the button (2 g. 6) - Reset, or esc
displays room temperature and numerical data
Symbol Description
external temperature display
internal temperature display
function activation from remote
functioning with holiday timer program
not used on this model description of functioning state
in use
anomaly in boiler presence symbol
indicates that it is possible to modify a parameter via the two buttons (11 and 12 g. 6)
functioning with solar system active
functioning with external temperature probe active
functioning in wireless mode (not used on this model)
Page 11
11
Symbol Description
description of functioning of the button (6 g. 6) - Menu or Ok
ame presence symbol (only appears with the connection to some boiler models)
symbols that identify the functioning mode in the hourly programming
time bar that identies the functioning period at “comfort” and “economy” temperature on the basis of the type of programming (cooling, central heating, DHW)
functioning with automatic program
functioning with manual program
display of days of the week
N.B.: Some icons can assume dierent meanings according to the context, see the successive paragraphs to identify the functions activated by the presence of several icons at the same time.
Page 12
12
4.2 Selection of functioning mode
According to the functioning mode selected, the CAR V2 remote control performs the requests of the user, displaying the results on the display. By turning the main selector (ref. 1 g. 6) the following functions can be selected: Stand-by/Anti-freeze, Summer, Winter, Cooling.
Note: the room anti-freeze function is active in the following modes: antifreeze, summer, winter.
Off mode. The room anti-freeze function is not
guaranteed in this mode (the boiler anti-freeze function remains active). e CAR V2 remote control is o but remains powered and therefore the times and programs remain memorised.
4. STARTUP
4.1 Programming current day and time.
Switch the remote control on by turning the main selector onto one of the functions available. Press the button to enter time and current time mode and press the button to modify the settings. On entering the programming mode, the time starts to ash. Modify the hour and minutes by pressing the + / - buttons and the button to conrm. Select the day of the week and conrm using the button. Once regulation has been completed, press the button to escape the regulation mode.
Fig. 7
Page 13
13
Fig. 8
Fig. 9
Stand-by/anti-freeze mode ( ). In this mode, the boiler can only function in the event of anti-freeze request. In this state, the day, current time, any functioning anomalies and the room temperature are displayed (g.
8).
Summer mode ( ). In this mode the boiler is enabled for producing domestic hot water excluding heating the environment. e display shows the day and the current time, the room temperature and hour bar with daily programming of the DHW timer along with the relative symbols (g. 9).
Winter mode ( ). In winter mode the boiler is enabled for producing domestic hot water and for central heating the environment. In winter mode the CAR V2 remote control can function in automatic or manual mode. For the description of functioning see chapter 6. e display shows the day and current time, the room temperature and the hour bar with the daily programming of the central heating timer along with the relative symbols (g.
10).
Fig. 10
Page 14
14
Cooling mode ( ). In cooling mode the boiler is enabled for the production of DHW and to control a chiller (only for models set-up) for cooling rooms. In "cooling" mode the CAR V2 remote control can function in automatic or manual mode. For the description of functioning see chapter 7. e display shows the day and current time, the room temperature and the hour bar with the daily programming of the cooling timer along with the relative symbols (g. 11).
Fig. 11
Page 15
15
5. SUMMER MODE FUNCTIONS
With the CAR V2 remote control in summer mode ( ), only the production of DHW is enabled. The boiler produces hot water according to the DHW temperature set on the CAR V2 remote control.
5.1 DHW temperature setting.
By turning the selector ( ) it is possible to set the temperature of the DHW (see g. 12). By turning in a clockwise direction the temperature increases and in an anti-clockwise direction it decreases. e temperature is memorised aer the selector remains still for a few seconds.
Fig. 12
5.2 DHW timer (for storage tank unit).
If the temperature of the DHW contained in the DHW storage tank on two distinct levels (comfort and minimum) is to be regulated, this is possible using the “HW PRG” function. Regarding this, see the activation mode in the chapter relative to programming.
The “comfort” temperature corresponds to the value regulated on the DHW selector. e “minimum” temperature corresponds to the minimum DHW value envisioned for the boiler to which the CAR V2 remote control is coupled.
N.B.: if the CAR V2 remote control is functioning at minimum temperature level it is possible to force the DHW temperature by acting on the DHW selector.
e CAR V2 remote control is factory set with the DHW always activated on "comfort" temperature (ON1 00.00 OFF1 24.00).
Page 16
16
6. WINTER MODE FUNCTIONS
With the CAR V2 remote control in winter mode ( ), the production of DHW and room central heating are enabled. Two main functioning modes can be selected for room central heating: automatic or manual. Plus a forced automatic timed program.
- Manual ( ): the room temperature is kept constant at the value set by the user every time, according to requirements.
- Automatic ( ): the room temperature is regulated on two levels (comfort and economy) during the day via a program set by the user.
- Forced automatic ( ashing): the room temperature is modified momentarily with respect to automatic functioning until the successive passage between comfort and energy mode of the automatic program set.
6.1 Manual functioning.
By pressing the button, pass alternately from automatic to manual functioning. Once manual functioning mode is set, the icon switches­on on the display (g. 13).
To set the desired room temperature, just press the + / ­buttons and the room temperature set will appear on the display (g. 14). Just wait a few seconds to conrm the new value. In manual functioning mode it is possible to select any room temperature from +10°C to +35°C, which will be kept constant until new adjustments or selection of a dierent functioning mode.
Fig. 14
Fig. 13
Page 17
17
6.2 Automatic functioning.
The CAR V2 allows automatic functioning, in which a program manages the room temperature during the hours of the day.
e desired room temperature can be adjusted onto two independent levels: comfort ( ) and economy ( ) via the
button, whose distribution throughout the day or the
week is managed by hourly programming.
Press the button until the icon switches-on on the display .
e CAR V2 is factory-set with a standard program stated in the table that follows. If this should not satisfy requirements, it is possible to modify it as described in the chapter relative to programming.
Fig. 15
Note: the system is designed to function on comfort and economy temperature levels depending on the hour program set. erefore also during functioning on economy level, if the room temperature measured is below that set, the boiler can ignite.
6.3 Forced automatic functioning.
If in automatic functioning mode ( ) the room temperature is modied by pressing the + / - buttons, the forced automatic functioning mode is activated (displayed by the switch-on of the ashing symbol). In this mode, the room temperature will be regulated to the value set until the next switch-on or switch-o phase of the automatic program set. e forced automatic function can be interrupted by simply pressing the button.
Days
16°C
20°C
Mon - Fri
(Day 1 - 5)
from 23 to 6 from 8 to 11
from 13 to 17
from 6 to 8 from 11 to 13 from 17 to 23
Sat - Sun
(Day 6 -7)
from 23 to 7 from 7 to 23
Fig. 16
Page 18
18
6.4 Boiler ow temperature.
From the winter function mode ( ) it is possible to regulate the boiler flow temperature. Regulate by rotating the selector ( ). Clockwise increases the ow temperature, anti-clockwise decreases it.
N.B.: an excessively low boiler ow temperature adjustment (below 60°C for traditional systems) may not allow to reach the desired room temperature.
e boiler ow temperature during normal functioning is however managed automatically of the CAR V2 remote control on the basis of the room temperature set. erefore, it is not certain that the boiler works at the temperature set but functions at a lower ow temperature, but correct to obtain the desired room temperature.
If the external temperature probe is present, the flow temperature will be set according to that described in the "Special functions" chapter.
6.5 Room anti-freeze function.
The anti-freeze function has maximum priority with respect to other settings. When the room temperature drops below 5°C (adjustable, see special functions chapter) a central heating request is made at minimum of the power programmed. is situation remains active until there is a variation in room temperature of 0.6°C equal to 5.6°C
measured in the room where the CAR V2 remote control is positioned.
6.6 Functioning in winter mode with external temperature probe.
If an external temperature probe is present, it is possible to set a ow temperature correction curve depending on the external temperature. By turning the selector switch ( ) the curve can be regulated from 0 to 9 according to the graphics g. 23. Regarding this, see the activation mode in the chapter relative to the special functions.
Page 19
19
7. COOLING MODE FUNCTIONS
With the CAR V2 remote control in cooling mode ( ), the of DHW heating and room cooling functions are enabled.
Important: this function can only be used with boilers that an be coupled with a chiller.
Two main functioning modes can be selected: automatic or manual. Plus a forced automatic timed program.
- Manual ( ): the room temperature is kept constant at the value set by the user every time, according to requirements.
- Automatic ( ): the room temperature is regulated on two levels (comfort and economy) during the day via a program set by the user.
- Forced automatic ( ashing): the room temperature is modied momentarily with respect to automatic functioning until the successive passage between comfort and energy mode of the automatic program set.
7.1 Manual functioning.
By pressing the button, pass alternately from automatic to manual functioning. Once manual functioning mode is set, the icon switches on on the display (g. 17). To set the desired room temperature, just press the + / ­buttons and the room temperature set will appear on the
Fig. 18
Fig. 17
display (g. 18). Just wait a few seconds to conrm the new value. In manual functioning mode it is possible to select any room temperature from +15°C to +40°C, which will be kept constant until new adjustments or selection of a dierent functioning mode.
Page 20
20
7.2 Automatic functioning.
The CAR V2 allows automatic functioning, in which a program manages the room temperature during the hours of the day.
e desired room temperature can be adjusted onto two independent levels: comfort ( ) and economy ( ) via the
button, whose distribution throughout the day or the
week is managed by hourly programming.
Press the button until the icon switches-on on the display .
e CAR V2 is factory-set with a standard program stated in the table that follows. If this should not satisfy requirements, it is possible to modify it as described in the chapter relative to programming.
Note: the system is designed to function on comfort and economy temperature levels depending on the hour program set. erefore also during functioning in economy temperature conditions, if the room temperature measured is above that set, the chiller can switch-on.
7.3 Forced automatic functioning.
If in automatic functioning mode ( ) the room temperature is modied by pressing the + / - buttons, the forced automatic functioning mode is activated (displayed by the switch-on of the ashing symbol). In this mode, the room temperature will be regulated to the value set until the next switch-on or switch-o phase of the automatic program set. e forced automatic function can be interrupted by simply pressing the button.
Days
40°C
25°C
Mon - Fri
(Day 1 - 5)
from 23 to 11 from 13 to 17
from 11 to 13 from 17 to 23
Sat - Sun
(Day 6 -7)
from 23 to 13 from 13 to 23
Fig. 20
Fig. 19
Page 21
21
8. INFORMATION
By pressing the button, access a menu that allows to verify the functioning state of the CAR V2 remote control. If a determined value is not present “--” will be displayed. e display of the “info” is subject to the boiler model and the method of connection of the CAR V2 remote control. Press the button repeatedly to scroll the list . To go back to normal functioning mode, press the button or wait 60 seconds. e parameters that can be displayed are listed below:
- EXT T: external temperature (the optional external temperature probe if present).
- HF TMP: Central heating circuit ow temperature.
- HR TMP: central heating circuit return temperature.
- DWIN T: DHW input temperature.
- DHW T: DHW output temperature.
- PAN T: solar collector temperature.
- CH PRS: system pressure, central heating circuit.
- SERVIC: Days remaining before periodic maintenance.
- VER P “x”: “x” identies the type of communication protocol with the boiler in use: VER PC = CAR-Bus; VER PI = IMG-Bus.
e display shows the rmware version of the CAR
V2.
remote control
- ZONE: Not used on this model.
N.B.: the sizes displayed depend on the type of boiler to which the CAR V2 remote control is connected.
Page 22
22
9. PROGRAMMING CAR V2 REMOTE
CONTROL.
Programming of the CAR V2 remote control allows to set/ modify the following parameters:
- comfort and economy temperature levels (dierent for the “central heating” and “cooling” modes);
- daily/weekly functioning time program (dierent for the “central heating” and “cooling” and "DHW" modes).
9.1 Setting comfort and economy room
temperature.
e two temperatures are dierent depending whether they are in "winter" or "cooling" mode. By pressing the button, the “comfort” (fig. 21) and “economy” (g. 22) temperatures are displayed alternately. To regulate both parameters, just press the + / - buttons to regulate the temperature according to requirements. To conrm the new temperature, press the button, to exit without saving the modications, press the button.
Fig. 21
Fig. 22
Page 23
23
9.2 Programming functioning time.
By pressing the button, it is possible to enter the time periods programming window for programming the room temperatures and DHW timer (as well as setting the current time and day). By pressing the + / - buttons, the items that can be set in the menu are displayed alternately.
ere are, in fact, three types of program:
- CH PRG: room central heating program
- HW PRG: DHW heating program
e period in which the DHW temperature is in comfort
will be distinguished by the switch-on of the icon. N.B.: the function must only be activated in the presence of a cylinder. e DHW is always active as per standard.
- CHIPRG: room cooling program
By following the points described below, it is possible to create or modify the time program selected.
1) Press the button, select the program to modify
by pressing the + / - buttons, aer which conrm by pressing the button.
2) Select the day of group of days by pressing the + / - buttons and conrm the selection by pressing the button:
- Monday, Tuesday, Wednesday... Sunday (individual day)
- Mon - Fri (from Monday to Friday)
- Sat - Sun (from Saturday to Sunday)
- Mon - Sat (from Monday to Saturday)
- Mon - Sun (from Monday to Sunday)
3) Set the functioning times with comfort and economy temperature. Within the 24 hours it is possible to dene a maximum of 4 time periods with Comfort temperature, each of which is characterised by a switch-on time and a switch-o time.
e minimum variation of the switch-on and switch-o
time is 30 minutes.
Set the rst functioning period with comfort temperature (ON 1) indicated at the top and the switch-on time at the bottom. Press the + / - buttons to modify the switch-on time and press the button to memorise. At this point, pass to the next functioning period with comfort temperature (OFF) indicated at the top and the switch-o time at the bottom. Press the + / - buttons to modify the switch-o time and press the button to memorise. When the
Page 24
24
rst phase has been designed, pass automatically to the next functioning phases at comfort and economy temperature in order to program. is means repeating the points described previously up to phase 4. e sequences of the On and O states must always be sequential. For example, it is not possible to set “OFF 2” at
13.30 and “ON 3” at 11.00. Once the day or group of days have been programmed, proceed in the same way for the remaining days and the remaining programs.
N.B.: if only 3 switch-on times are used, set the fourth with switch-on/o time at 24.
N.B. in automatic functioning conditions ( ) the display will show the 24 hour bar indicating the dierent time phases with Comfort or Economy temperature
. The presenc e of t h e hyphen on the time bar corresponds to functioning in Comfort mode.
Page 25
25
10. DIAGNOSTICS AND ERRORS
10.1 Diagnostics.
The CAR V2 remote control continually controls the functioning status of the boiler and signals any anomalies, stating the corresponding error code on the display. e error codes have meaning depending on the boiler to which the CAR V2 remote control is connected. erefore, refer tot he boiler instruction book for a complete list of error codes and their relative meaning. In the case of a fault that cannot be reset, contact a qualied technician (e.g. the Immergas After-Sales Technical Assistance Service). “ERR>XX” appears on the display in the event of an error, where XX stands for the number that identies the error code as well as the ashing symbol. As well as the error codes referring to the functioning state of the boiler, the CAR V2 remote control also checks its own functioning state, indicating any malfunctions.
Code Description
ERR>CM
Communication error between CAR V2 remote control and boiler or switch-over phase between advanced type communication (e.g. Superior kW) and a normal type
ERR>TP
Error in reading the room temperature or value measured o scale (below 0°C or over 50°C)
10.2 Reset errors.
In the event of resettable boiler bock, the ashing icon appears on the display. In this case, by acting on the relevant button and holding it down for 5 seconds, it is possible to send a release signal to the boiler that allows to reset correct boiler functioning within a few seconds. If normal functioning conditions are set, it goes back to functioning as previously set. It is possible to operate up to a maximum of 5 consecutive reset attempts, aer which an hour must pass before another 5 attempts are available.
10.3 Reset CAR V2 remote control.
Acting on the hole for general rest (ref. 4 g. 6) the CAR V2 remote control hardware can be reset without loosing the settings made by the user, such as time, date and time prog.
If the CAR V2 remote control original factory set conditions are to be restored, act as follows. Press and release the button in the “reset” hole (ref. 4 g. 6) holding the button down (ref. 2 g. 6). At this point CAR V2 remote control will be restored with all factory set data, keeping current time and day.
Page 26
26
11. SPECIAL FUNCTIONS
By pressing the button, a list of options is accessed that allows to customise functioning of the CAR V2 remote control, according to the specic necessities. To scroll the list, press the + / - buttons and press the button to select the desired function.
11.1 LANGUAGE (language selection).
Allows to set the functioning language of the CAR V2 remote control. It is possible to select from Italian (ITA as per standard) and English (ENG).
11.2 REGULT (Management of regulation parameter).
Allows to customise the functioning parameters of the CAR
V2
remote control.
- CH MIN (central heating ow minimum temperature),
allows to regulate the central heating flow minimum temperature value. Moreover, this value is used to calculate the curves used for the external probe. Values that are too high can cause ow temperatures that are too high on average for room central heating.
- OFFSET (regulation constant), constant that can be regulated
from -15°C to +15°C and which in the presence of the external probe (optional) modies the set ow temperature (see g. 23)
set as per standard at 0°C.
TM-MAX/MIN = Selected ow temp. range. Te = External temperature.
EXTERNAL PROBE
FLOW TEMPERATURE CORRECTION LAWS.
EXTERNAL TEMPERATURE FUNCTION AND THE POSITION OF
THE USER TEMP. ADJUSTMENT CENTRAL HEATING.
Fig. 23
N.B.: if the self-learning function is enabled, the Oset value
could be modied automatically.
- BUILD (dimension and building inertia), adjustable from 1 to 20, as per standard set on 10. It establishes the reaction speed of the system depending on the type of system present. For example:
Value System type
5 system with little heat inertia
10
system with normal dimensions with radiators
Position of the central heating temperature user adjustment central heating temp.
Page 27
27
20
system with a lot of heat inertia (e.g. oor­standing system)
- AUTO A (self-learning), defines the activation of self­learning, as per standard set at OFF. is function allows the CAR V2 remote control to vary the oset, adapting it to the room in which it is installed.
11.3 HOLIDY (holiday program).
From winter functioning mode it is possible to dene a number of days (from 1 to 99) during which the system deactivates both the hot water heating function and the room central heating function. e value is decreased every midnight in the day change. At the end of the days set (the meter reaches 0) the previously active functions are restored. e activation of the holiday function is indicated by the ashing of the icon and the count of the days remaining. The holiday function can be deactivated by pressing the
button. In the event of remote activation from telephone control, the boiler is activated with the settings of the telephone control, omitting the Holiday program.
N.B.: the room anti-freeze function is however guaranteed also in holiday mode.
11.4 LEGION (anti-legionella function ).
Allows to activate the Anti-legionella function that takes the temperature of the cylinder to maximum allowed for 20 minutes. It is possible to select between the once a day at 2 in the night (ON 24H), every 7 days on Monday at 2 in the night (ON 7 DAYS) or deactivate it (OFF standard function).
N.B.: the function must only be activated in presence of boiler and eventually a thermostatic valve must be installed at the DHW output to prevent burns.
11.5 REMOTE (telephone control).
Allows to set the functioning of the CAR V2 remote control in a way that, in the event of remote activation, it functions with the automatic time program if set at AUTO. Vice versa, it functions at continuous comfort temperature (without time program) if set at ON. In the event of activation, it displays the ashing ( ) icon.
11.6 CODE.
To use this function, see the “Functions protected by code” chapter.
Page 28
28
12. FUNCTIONS PROTECTED BY CODE
CODE.
They are advanced character settings (reserved for an enabled technician), a four character code must be entered in order to access them (code: 1122). Press the button and scroll the options present until “CODE” appears, press the button and insert the code by selecting the characters using the + / - buttons and conrming them by pressing the button. Aer which it is possible to display and modify the following functions.
12.1 AMB (room probe - On / O or modulating
functioning mode).
Allows to activate or deactivate the room probe present in the CAR V2 remote control. On the basis of the parameter setting, it will be possible to regulate the following options:
- AMB: ON (standard value); it is possible to select a cor-
rection factor of the room probe reading and change the modulating function.
- AMB CR: room robe reading correction, the room
probe range reading can be corrected within a range of + 3.0 - 3.0°C.
- MODUL (On / O or Modulating functioning):
allows setting functioning of the CAR V2 remote control On/O or Modulating. Set at ON, the ow temperature will be varied depending on the room temperature set. Set at OFF, the ow temperature will be kept constant until the desired room temperature is reached. (Setting to be made on systems with zones control unit).
N.B.: if an external temperature probe is present, the
ow temperature will be set depending on the relative functioning curve.
- AMB: OFF, the system will not function, regulating the room temperature but only depending on the time program set. In this case the room anti-freeze function is not assured.
12.2 REDUCT (functioning in reduced mode).
if activated with AMB parameter at “OFF”, it denes how the ow temperature must be in Economy period.
- REDUCT OFF: in functioning periods in Economy mode, the boiler is switched-o.
- REDUCT ON: in functioning periods in Economy mode, it reduces the ow temperature by an amount equal to that set (adjustable from -1°C to -40°C).
Page 29
29
12.3 FRO PR (anti-freeze level).
Allows to set the room temperature for activation of the anti-freeze function. Can be regulated from 0°C to 10°C and is set at 5°C as standard.
12.4 ZONE (function not present on this model).
12.5 SERVIC (programmed maintenance).
Sets the period for periodic maintenance (can be set from 6 to 24 months or “O ”). When the period has been set, the telephone number that the user must contact to perform periodic maintenance is set.
13. DISABLING
THE CHRONOTHERMOSTAT.
If CARV2 must be used as a boiler control only (simple remote control function), proceed as follows:
- deactivate the room probe (para. 12.1):
- exclude the 4 time periods of the “PR RIS” in the “Mon
- Sun” group of days, setting the On and O of all 4 time periods (on1, o1, on2, o2, on3, o3, on4, o4) to 24.00;
- press the AUTO button to set the automatic mode.
N.B.: for the boiler to work in heating mode, the room
thermostat contacts (40-41) on the boiler board must be closed.
Page 30
30
14. TECHNICAL CHARACTERISTICS
• Dimensions (LxHxD): ..................................................................................................................................142 x 103 x 31 (mm)
• Power Supply: ................................................................................................ 24V nominal via twin-wire communication Bus
• CAR_BUS protocol power supply voltage: .............................................................................................................. 24 ÷ 35 Vdc.
• CAR_BUS protocol maximum input: ............................................................................................................. 10 mA - 350 mW.
• IMG_BUS protocol maximum power supply voltage: ....................................................................................................18 Vdc.
• IMG_BUS protocol maximum input: ............................................................................................................. 23 mA - 250 mW.
• Functioning room temperature: .................................................................................................................................... 0 - +40°C
• Warehouse temperature: ..............................................................................................................................................-10 - +50°C
• Protection rating according to EN 60730: .................................................................................................................................. II
• Protection rating according to EN 60529: ............................................................................................................................IP 20
• Connection technique: ........................................................................................................................................2 polarised wires
• Load reserve time: ......................................................................... 8 hours for hourly count (with at least 2 hours of charge)
• Connection cable max. length: .......................................50 m (with cable of 2x0.75mm2) (0.5 ÷mm2 min - 1.5 mm2 max)
• Precision indication room temp.: .....................................................................................................................+/- 0.5°C a 25°C*
• NTC room temp. sensor: ............................................................................................................................................50 k at 25°C
• Clock indication diversion ........................................................................................................................... +/- 15 minutes/year
* = the indication of the room temperature can be aected by the point of installation of the CAR V2 remote control (e.g.
hot wall, cold wall, height from the ground, etc.)
Page 31
31
15. FACTORY SETTING
• Functioning state ........................................................................................................................................................................O
• Functioning program ......................................................................................................................................................... Manual
• Central heating Comfort temperature ...............................................................................................................................20.0°C
• Central heating Economy temperature ..............................................................................................................................16.0°C
• Cooling Comfort temperature ............................................................................................................................................25.0°C
• Cooling Economy temperature ...........................................................................................................................................40.0°C
• Room temperature in manual .............................................................................................................................................20.0°C
• Anti-freeze ...............................................................................................................................................................................5.0°C
• Holiday Program..................................................................................................................................................HOLIDY = OFF
• Oset ....................................................................................................................................................................... OFFSET = 0°C
• Building inertia dimension ....................................................................................................................................... BUILD = 10
• Self-learning .........................................................................................................................................................AUTO A = OFF
• Room Probe ..................................................................................................................................................................AMB = ON
• Reading Correction ........................................................................................................................................... AMB CR = 0.0°C
• Reduction ............................................................................................................................................................. REDUCT = OFF
• Modulation .............................................................................................................................................................MODUL = ON
• Telephone control ................................................................................................................................................ REMOTE = ON
• Antilegionella: ......................................................................................................................................................LEGION = OFF
• Language: .................................................................................................................................................... LANG = ITA (Italian)
Page 32
Immergas S.p.A. 42041 Brescello (RE) Italy Tel. 0522 689011
CUSTOMER SERVICE Free Phone 800 - 306 306
immergas.com
Code 1.031170 - Rev. 15.033917/003 - 10/11
Loading...