Immergas ARES 150 TEC ERP, ARES 300 TEC ERP, ARES 350 TEC ERP, ARES 250 TEC ERP, ARES 200 TEC ERP Instructions And Warnings

Page 1
Instructions and warnings
Installer
Maintenance technician
IE
ARES 150 TEC ERP ARES 200 TEC ERP ARES 250 TEC ERP ARES 300 TEC ERP ARES 350 TEC ERP
Modular condensing boiler
*1.042909ENG*
*1.042909ENG*
Page 2
Page 3
Warning this manual contains the exclusive instructions for use for professionally qualied installers and/or maintenance technicians, in compliance with laws in force. e individual in charge of the system is NOT authorised to work on the boiler. e manufacturer will not be held liable in the case of damage to people, animals or property due to the failure to observe the instructions contained in the manuals supplied with the boiler
INDEX
1 General information ...................................................................4
1.1 Symbols used in the manual ........................................................4
1.2 Compliant use of the appliance ...................................................4
1.3 Information to be provided to the user .....................................4
1.4 Safety warnings .............................................................................5
1.5 Regulations for installation..........................................................6
1.6 Installation .....................................................................................6
1.7 Water treatment ............................................................................7
1.8 General warnings .......................................................................... 8
2 Technical characteristics and dimensions .................................9
2.1 Technical characteristics .............................................................. 9
2.2 Internal view with indications of main components .............10
2.3 Dimensions ..................................................................................12
2.4 Operating data / general characteristics ..................................13
2.5 Technical parameters for combination boilers
(in compliance with Regulation 813/2013). ............................14
3 Instructions for installation .....................................................17
3.1 General recommendations ........................................................17
3.2 Packaging .....................................................................................18
3.3
Removing the boiler from the pallet and putting on the feet
3.4 Positioning the heating control unit.........................................20
.....
19
3.5 Connecting the boiler ................................................................21
3.6 Gas connection............................................................................22
3.7 System ow and return pipe connection .................................23
3.8 Additional safety, protection and control devices ..................24
3.9 Determining the primary circuit pump or boiler pump .......26
3.10 Condensate drain ........................................................................27
3.11 Connecting the ue ....................................................................28
3.12 Flue exhaust manifold connection ...........................................28
3.13 Electrical connections ................................................................30
3.14 Connection diagram ..................................................................33
3.15 Practical connection diagram ...................................................37
3.16 System lling and emptying ......................................................39
3.17 Boiler frost protection ................................................................39
3.18 Check the adjustment of the pressure to the burner .............. 40
3.19 Emergency and safety operations ............................................42
3.20 First ignition ................................................................................43
4 Inspections and maintenance ..................................................44
4.1 Instructions for inspection and maintenance ......................... 44
4.2 Programming the operation parameters .................................50
4.3 BMM. parameters .......................................................................51
4.4 BCM. parameters ........................................................................52
4.5 Error code ....................................................................................53
Instructions on how to correctly dispose of the product.
At the end of its life, this appliance must not be disposed of as mixed municipal waste. It is mandatory to separate this type of waste so that the materials making up the appliance can be recycled and reused. Contact
authorised operators for disposal of this type of appliance. Incorrect management of waste and its disposal has potential negative eects on the environment and on human health. e symbol on the appliance represents the prohibition of disposing of the product as mixed municipal waste.
e company IMMERGAS S.p.A., with registered oce in via Cisa Ligure 95 42041 Brescello (RE), declares that the design, manufacturing and aer-sales assistance processes comply with the requirements of standard UNI EN ISO 9001:2015.
For further details on the product CE marking, request a copy of the Declaration of Conformity from the manufacturer, specifying the appliance model and the language of the country.
e manufacturer declines all liability due to printing or transcription errors, reserving the right to make any modications to its technical and commercial documents without forewarning.
Page 4
General information
GENERAL
1
INFORMATION
1.1 SYMBOLS USED IN THE MANUAL
When reading this manual, pay special attention to the parts marked with these symbols:
DANGER!
Serious danger to
safety and life
ATTENTION!
Possibly dangerous
situation for the product
and environment
NOTE!
Tips for the user
1.2 COMPLIANT USE OF THE APPLIANCE
e ARES Tec appliance was built based on the current technical level and recognised technical safety rules. Nevertheless, following improper use the safety and life of the user or other people may be exposed to danger, i.e. damage to the appliance or other objects. e appliance is designed for operation in hot water circulating heating systems. Any other use is considered improper. Immergas will not be held liable for any damage resulting from improper use. Any use in accordance with the envisioned purposes includes the strict observance of the instructions in this manual.
1.3 INFORMATION TO BE PROVIDED TO THE USER
e user must be instructed in the use and operation of his/her heating system, in particular:
- Deliver these instructions to the user, as well as the other documents relative to the appliance contained in the packaging in an envelope. e user must keep this documentation safe so that it is available for future consultation.
- Inform the user of the importance of aeration vents and the ue exhaust system, highlighting how essential they are and how it is strictly forbidden to change them.
- Inform the user on how to control the water pressure in the system as well as the operations required to restore it.
- Inform the user on how to correctly regulate the temperature, control units/thermostats and radiators in order to save energy.
- Remember it is compulsory to carry out regular maintenance on the system once a year and a combustion analysis every two years (as per national legislation).
- If the appliance is sold or transferred to another owner or if the owner moves, leaving the appliance behind, always ensure the manual accompanies the appliance so that it may be consulted by the new owner and/or installer.
DANGER!
Scalding hazard!
OBLIGATION! Wear protective
gloves
e manufacturer will not be held liable in the case of damage to people, animals or property due to the failure to observe the instructions contained in this manual.
4
Page 5
1.4 SAFETY WARNINGS
ATTENTION! e appliance must not be used by people with reduced physical, mental and sensorial capabilities, without experience and knowledge. ese people must be duly instructed and supervised during manoeuvring operations.
ATTENTION! Installation, adjustment and maintenance of the appliance must be carried out by professionally authorised company, in compliance with regulations and provisions in force, as incorrect installation can cause damage to people, animals and property, for which the manufacturer will not be held liable.
DANGER! Maintenance or repair work on the boiler must be carried out by professionally authorised company, authorised by Immergas; it is advisable to sign a maintenance contract. Poor or irregular maintenance can compromise the operational safety of the appliance and cause damage to people, animals and property for which the manufacturer will not be held liable.
Changes to parts connected to the appliance
Do not make changes to the following elements:
- to the boiler
- to the gas, air, water and power supply lines
- to the ue pipe, safety valve and exhaust pipe
- to the constructive elements that aect the operational safety of the appliance.
General information
ATTENTION!
To tighten or loosen the screw-attached ttings, use suitable wrenches only. Improper use and/or unsuitable tools can cause damage (for ex. water and gas leaks).
ATTENTION! Instructions for appliances running on propane gas
Make sure that the gas tank has been deaerated prior to installing the appliance. For a thorough deaeration of the tank contact the liquid gas supplier and in any case authorised company, in accordance with the law. Ignition problems can arise if the tank is not thoroughly deaerated. In this case contact the liquid gas tank supplier.
Smell of gas
In case of the smell of gas observe the following safety instructions:
- do not use electric switches
- do not smoke
- do not use the telephone
- shut o the gas cut-o valve
- aerate the room where the gas leak occurred
- notify the gas supply company or a company specialised in the installation and maintenance of heating systems.
Explosive and easily ammable substances
Do not use or deposit explosive or easily ammable materials (for ex. petrol, paints, paper) in the room where the appliance is installed.
ATTENTION!
Do not use the appliance as a base to support any object. Specically, do not place receptacles containing liquids (Bottles, Glasses, Containers or Detergents) on top of the boiler. If the appliance is installed inside a box, do not insert or place other objects inside it
ATTENTION!
e heat unit must be installed so as to avoid, under the envisioned operating conditions, the liquid contained in it from freezing and avoid exposing the command and control parts to temperatures below -15°C and over +40°C. e heat unit must be protected from climatic/environmental variations by:
- insulating the hydraulic and condensation exhaust pipes
- adopting specic anti-freeze products in the hydraulic system.
5
Page 6
General information
1.5 REGULATIONS FOR INSTALLATION
ARES Tec is a gas category II
e appliance must be installed in accordance with the instructions contained in this manual.
Installation must be carried out by a professionally authorised company,
who is in charge of enforcing observance of all local and/or national laws published in the Ocial Gazette, as well as all applicable technical regulations.
It is necessary to observe the standards, regulations and requirements for installation provided below, constituting a rough and non-exhaustive list, in order to follow the evolution of the "state of the art". We
would like to underline that updating the list of standards is the responsibility of the technicians authorised to carry out installation.
heating unit.
2H3P
Also observe the standards regarding the heating control unit, construction regulations and requirements on combustion heating in the country of installation.
The appliance must be installed, commissioned and subject to maintenance in accordance with the current "state of the art". is also applies to the hydraulic system, the ue exhaust system, the installation room and the electrical system.
Failure to observe the above regulations will void the warranty.
1.6 INSTALLATION
When the appliance is installed on existing systems, make sure that:
- e ue is suitable for condensation appliances, for the temperatures of the combustion products, calculated and built in accordance with regulations in force. at is it a straight as possible, water-tight and insulated and does not have any obstructions or constrictions.
- e ue is equipped with an attachment to evacuate the condensation.
- e heating control unit is equipped with a pipe for the evacuation of the condensation produced by the boiler.
- e electrical system is built in accordance with specic regulations and by professionally authorised company.
- e ow rate, head and direction of ow of the circulation pumps is appropriate.
- e fuel feed line and any existing tanks are set up in accordance with regulations in force.
- e expansion vessels ensure complete absorption of the dilation of the uid contained in the system.
- Slurry and build-up have been cleaned out of the system.
If ARES Tec is being installed on existing Systems: If it is possible to schedule the replacement, it is necessary to wash
the system preventively, with alkaline dispersants. Washing must be carried out four weeks prior to replacement, with a system operating between 35°C - 40°C.
ATTENTION! If the new boiler has been replaced in an old system without having preventively washed it as described above, do not wash the system, as any residues of the product in the circuit may ll the generator with residues aer replacement. It is advisable to contact a company specialised in water treatment.
Otherwise, if ARES Tec is being installed on a new system it is advisable to wash it thoroughly in any case, using products that are suitable for the entire system, and install a Y-strainer with two cut-o valves on the return pipe to the boiler, so that it can be cleaned as needed. is lter will protect the boiler from sediments coming from the heating system.
In both cases it is necessary to keep the head losses localised in the primary circuit, for the correct sizing of the pump.
6
Page 7
General information
1.7 WATER TREATMENT
Treating the supply water allows you to prevent problems and maintain the functionality and eciency of the generator over time.
e purpose of this treatment is to eliminate or signicantly reduce problems that can be outlined as: build-up corrosion sediments biological growth (mould, fungus, algae, bacteria, etc.).
e chemical analysis of the water provides a lot of information on the state and "health" of the system. e pH level is a numerical indication of the acidity or alkalinity of a solution. e pH scale goes from 0 to 14, where 7 corresponds to neutral. Values below 7 indicate acidity, values above 7 indicate alkalinity.
e ideal pH value in heating systems with aluminium boilers is between 6.5 and 8,5, with a hardness of 15°F.
Water in a system with a pH value outside of this range considerably accelerates the destruction of the protective oxide layer which forms naturally inside the aluminium bodies, and would not occur naturally: if the pH level is lower than 6,5 it contains acid, if it is above 8 the water is alkaline, either due to an alkaline treatment (for example phosphates or glycols operating as antifreeze) or in some cases the natural generation of alkalis in the system. Vice versa, if the pH value is between 6.5 and 8, the aluminium surfaces in the body are passivated and protected from further corrosive attacks.
To minimise corrosion, it is essential to use a corrosion inhibitor. In order for it to work eciently, however, the metal surfaces must be clean. The best inhibitors on the market also contain an aluminium protection system that stabilises the pH levels of the ller water, preventing sudden changes (buer eect). It is advisable to systematically check (at least twice a year) the pH value of the water in the system. In order to do so a chemical laboratory analysis is not required, but a simple check using a analysis "kit" contained in a carry cases, easily available on the market.
It will therefore be necessary to set up the devices shown in the gure in the heating system.
THE COUPLING MUST BE SET UP ON THE RETURN PIPE TO THE PRIMARY CIRCUIT DOWNSTREAM OF THE PUMP.
All of the precautions required to avoid the formation and localisation of oxygen in the water of the system. For this reason the plastic pipes used in the under-oor heating systems must not be permeable to oxygen.
Make sure that any anti-freeze products are compatible with aliminium and any other parts and materials in the system.
ATTENTION! Any damage caused to the boiler, due to the formation of build-up or corrosive water, will not be covered by the warranty.
Example of water treatment unit
ATTENTION! These appliances are designed and developed to transfer heat to a heat carrying uid possessing the characteristics described here, they are not suitable to directly heat water intended for human consumption.
Key: 1 - Ball valve 2 - Sample trap 3 - Filling unit 4 - Cut-o device 5 - Water treatment unit 6 - Litre meter (recommended) 7 - "Y" strainer
1 2 3 4 5 2 7 16
7
Page 8
General information
1.8 GENERAL WARNINGS
e instruction handbook is an integral and essential part of the product and must be kept safe by the individual in charge of the system.
Read the warnings contained in the handbook carefully, as they provide important instructions regarding installation, user and maintenance safety.
Keep the handbook safe for future consultation.
e appliance must be installed and maintained in accordance with regulations in force, pursuant to the instructions of the manufac­turer, the state of the art and by authorised and qualied personnel, in accordance with the law. Domestic hot water production systems must be built entirely with compliant materials.
Professionally qualied personnel means sta with specic technical skills in the sector of heating system parts for civil use, hot water production for domestic use and maintenance. is personnel must have the authorisations required by legislation in force.
Incorrect installation or poor maintenance can cause injury to persons and animals and damage to objects, for which the manufacturer is not liable.
Before carrying out any cleaning or maintenance operations, cut the appliance o from the power mains by acting on the switch on the system and/or using the cut-o devices. Do not obstruct the intake/exhaust pipe terminals.
In case of breakdown and/or poor operation of the appliance, switch it o, and do not attempt in any way to repair it or intervene directly. Only contact an authorised company that has been authorised in accordance with the law.
Any repairs to the products must be carried out by an authorised company only, using original spare parts only. Failure to observe the above can jeopardise the safety of the appliance and will void the warranty.
e guarantee the eciency of the appliance and its correct operation it is essential for authorised company to carry out annual maintenance.
If the appliance is put out of use for downtime, any part that is susceptible to posing a potential source of danger must be made safe.
Before re-commissioning an appliance that has been put out of use, proceed to washing the domestic hot water production system, making water ow through it for the amount of time required to change the water completely.
If the appliance is sold or transferred to another owner or if the owner moves, leaving the appliance behind, always ensure the handbook accompanies the appliance so that it may be consulted by the new owner and/or installer.
All appliances with optionals or kits (including electric) must only use original spare parts.
e appliance must only be employed for its expressly foreseen use. Any other use must be considered improper and therefore dangerous.
8
Page 9
Technical characteristics and dimensions
TECHNICAL
2
CHARACTERISTICS AND DIMENSIONS
2.1 TECHNICAL CHARACTERISTICS
- Heat generator, to heat Low Nox condensation gas
- Comprised of a heat module designed to operate on its own or in a set
- Can be set up directly outside (IP X5D)
- Low water content
- High response speed to load changes
- Single ue exhaust that can be positioned on 3 sides
- Unied ow and return hydraulic manifolds
- Comprised of 4 or more heating elements (between 4 and 8), aluminium/silicon/magnesium casting
- Including total irradiation premixing modulating burners
- None of the heating elements have hydraulic cut-o devices
- Single gas supply pipe
- Modulated power between 22 ÷ 108 kW/element.
TEMPERATURE CONTROL DEVICES:
- ROOM NTC sensor (every heating element)
- Room Limit ermostat (every heating element)
- Flow NTC sensor (General)
- Return NTC sensor (General)
- Approved safety thermostat
- BCM global ow probe.
POP-UP control panel composed of:
- ON-OFF switch see parag. 3.25
- HSCP boiler thermoregulation/manager
- BCM (internal cascade management board)
- Protection fuses
- Any limit thermostats
- Fan air pressure switch
- Condensation water level sensor
- Gas pressure switch
- Exhaust pressure switch (anti-obstruction).
- e entire heating unit is equipped with global temperature control NTC sensors on the ow and return manifolds.
- Integral insulation with non-allergenic synthetic wool.
- Total premix burner, modulating, with "metal foam" radiation combustion chamber. Premixing in the fan. Automatic separating backow diaphragm from the combustion chamber.
- Sound emissions at maximum power below 52 dBA for models 100­350, 54 dBA for models 440-770 and 56 dBA for 900.
- Operation during heating: determining the instantaneous power through a control microprocessor, with preset comparison parameters between requested temperature (or calculated by the outdoor thermoregulation) and global ow temperature.
- Logic of operation:
- Possibility of controlling the power of the single heating elements
for calibration and/or assistance with reserved access code.
- Domestic hot water production using a priority NTC probe, for
control by a storage tank loading pump or diverter valve, is done with an SHC module that is supplied with the boiler.
- Possibility of controlling the power of the single heating elements.
- Heat request control: temperature setpoint and modulation level.
- Monitoring the state of operation and temperatures.
- Alarm notication.
- Parameter setting.
- Control relay to switch on a pump at a xed speed.
- Analogue 0÷10V output to control a modulating pump.
- Emergency operation: this allows you to avoid the system from stopping due to an interruption in communication with the adjusting system or possible remote management of the control unit:
- Emergency temperature with maximum power 100%.
- Alarm management.
- Alarm reset input.
- Alarm notication Relay.
- Condensation collection tray with stainless steel exhaust trap.
- Easily removable integral panelling comprised of oven-painted steel panels suitable for outdoor installation.
- Condensation collection tray with stainless steel exhaust trap and ue chamber.
- Incorporated deaerator.
e request for heat can be generated by the HSCP thermoregulation/ manager or alternatively by the BCM (Boiler controller). The management logic envisions simultaneous operation of the maximum number of heat elements, so as to always obtain the maximum eciency. Since it guarantees the maximum exchange area based on the delivered power. e elements are made to operate so as to equally divide the operating time. e hot water that is produced is pushed by the pump located on the return of the primary ring to the ow of the hydraulic separator. From here a second pump (system - see suggested diagrams) will distribute to the various utilities. From the system, return the cooled water is taken in by the pump on the return, through the hydraulic separator, to start the cycle towards the generator again.
9
Page 10
Technical characteristics and dimensions
2.2 INTERNAL VIEW WITH INDICATIONS OF MAIN COMPONENTS
KEY
Error
code
1 HSCP CONTROL PANEL 2 VG GAS VALVE 3 BURNER COVER 4 E. ACC. IGNITION 5 E. RIL. IONISATION 6 SR ROOM NTC PROBE 7 TL LIMIT THERMOSTAT 8 BURNER 9 SILICON ALUMINIUM EXCHANGER 10 SL LEVEL SENSOR
Wiring
diagram
Description
Min. depth 100 mm
Error
code
11
12 FRAME 13 CONDENSATE DRAIN OUTLET 14 DRAINING VALVE 15 SRR RETURN GLOBAL NTC
16 SMG
17 AUTOMATIC AIR BLEED VALVE 18 FAN
Wiring
diagram
Description
CONDENSATION COLLECTION PAN / FLUE FITTING
PROBE FLOW GLOBAL NTC
10
Page 11
Technical characteristics and dimensions
Note:
PF (20) and PFmin. (19) they are opposite each other as shown in the photo, in the dra­wing they are shown side by side for clarity.
ue gas outlet RIGHT side (supply condition) - LEFT side and REAR side (order rear ue gas outlet kit)
ow RIGHT side (supply condition) - LEFT side return RIGHT side (supply condition) - LEFT side Gas intake RIGHT side (supply condition) - LEFT side
KEY
Error
code
19 PF min MINIMUM FLUE PRESSURE SWITCH 20 PF FLUE PRESSURE SWITCH
Wiring
diagram
Description
If it is necessary to position the ue exhaust, on the le side of the boiler, it is necessary to move cover "A" with relative cabling, level sensor and pressure switch pipe, on the rear side of the boiler. e rear cover (previously removed) must be put back on the right side of the boiler.
11
Page 12
L
1150
833
P (770)
318
Technical characteristics and dimensions
2.3 DIMENSIONS
FRONT VIEW RIGHT SIDE VIEW
70
S
(Supply condition for le side attachments)
387 384
G
M
20
R
106
750
390
L1
(•) ARES 200 - 300 Tec Terminal inside the casing
120
275
255
276
352 353
LEFT SIDE
PRETRANCIO MANDATA
FLOW PRE-
LATO
SECTION
SINISTRO
LEFT SIDE
PRETRANCIO RITORNO
FLOW PRE-
LATO
SECTION
SINISTRO
LEFT SIDE VIEW
LEFT SIDE
PRETRANCIO GAS
GAS PRE-
LATO
SECTION
SINISTRO
(P1) 705
TOP VIEW
ARES Tec 150 200 250 300 350
Dimensions Unit
Heating elements 3 4 5 6 7 Height mm 1150 1150 1150 1150 1150 Width "L" mm 764 1032 1032 1300 1300 Width "L1" mm 706 974 974 1242 1242 Depth "P" mm 770 770 770 770 770 Depth "P1" mm 705 705 705 705 705
Attachment sizes
G Gas tting mm (inch) 50 (2) 50 (2) 50 (2) 50 (2) 50 (2) F System ow mm (inch) 64 (2½) 64 (2½) 64 (2½) 64 (2½) 64 (2½) R System return mm (inch) 64 (2½) 64 (2½) 64 (2½) 64 (2½) 64 (2½) Flue tting mm 150 150 200 200 200 Condensate drain mm 40 40 40 40 40
12
Page 13
Technical characteristics and dimensions
2.4 OPERATING DATA / GENERAL CHARACTERISTICS
ARES Tec ErP 150 200 250 300 350
Boiler category II
2H3P
Modulation ratio 1 : 12,5 1 : 16,7 1 : 20,8 1 : 25 1 : 29 Nominal heat input on L.V.C. Qn kW 150 200 250 300 348 Minimum heat input on L.C.V. Qmin kW 12 12 12 12 12 Nominal eective power (Tr 60 / Tf 80 °C) Pn kW 146,1 195,2 244,5 294,0 341,7 Minimum eective power (Tr 60 / Tf 80 °C) Pn min kW 11,7 11,7 11,7 11,7 11,7 Nominal eective power (Tr 30 / Tf 50 °C) Pcond kW 150 200,4 251,3 302,7 354,6 Minimum eective power (Tr 30 / Tf 50 °C) Pcond min
kW 12,8 12,8 12,8 12,8 12,8 Eciency at nominal power (Tr 60 / Tf 80°C) % 97,4 97,6 97,8 98,0 98,2 Eciency at minimum power (Tr 60 / Tf 80°C) % 97,16 97,16 97,16 97,16 97,16 Eciency at nominal power (Tr 30 / Tm 50°C) % 100,0 100,2 100,5 100,9 101,9 Eciency at minimum power (Tr 30 / Tm 50°C) % 106,5 106,5 106,5 106,5 106,5 Eciency at 30% of the load ( Tr 30°C) % 107,3 107,3 107,3 107,3 107,3 Eciency class according to directive 92/42 EEC -- 4 4 4 4 4 Combustion eciency at nominal load % 97,8 97,8 98,0 98,1 98,3 Combustion eciency at a reduced load % 98,3 98,3 98,3 98,3 98,3 Losses from operating burner casing (Qmin) % 1,2 1,2 1,2 1,2 1,2 Losses from operating burner casing (Qn) % 0,4 0,2 0,2 0,1 0,1 Flue temperature at net of Tf-Ta (min)(*) °C 33,4 33,4 33,4 33,4 33,4 Flue temperature at net of Tf-Ta (max)(*) °C 45,1 46,5 47,3 48,2 49,1 Maximum permitted temperature °C 100 100 100 100 100 Maximum operating temperature: °C 85 85 85 85 85 Mass ue ow rate (min) kg/h 19,6 19,6 19,6 19,6 19,6 Mass ue ow rate (max) kg/h 245 327 409 490 569 Air excess % 25,5 25,5 25,5 25,5 25,5 Chimney losses with burner in operation (min) % 1,7 1,7 1,7 1,7 1,7 Flue losses with burner in operation (max) % 2,2 2,2 2,0 1,9 1,7 Minimum pressure of heating circuit bar 0,5 0,5 0,5 0,5 0,5 Maximum pressure of heating circuit bar 6,0 6,0 6,0 6,0 6,0 Water content l 14,2 18,3 22,4 26,5 30,6 Methane gas consumption G20 (supp.press. 20 mbar) at Qn m3/h 15,9 21,1 26,4 31,7 36,8 Methane gas consumption G20 (supp.press. 20 mbar) at Qn m3/h 1,3 1,3 1,3 1,3 1,3 Gas consumption G25 (supp.press. 20/25 mbar) at Qn m3/h 18,4 24,6 36,7 36,9 42,8 Gas consumption G25 (supp.press. 20/25 mbar) at Qn m3/h 1,5 1,5 1,5 1,5 1,5 Propane gas consumption (supp.press. 37/50 mbar) at Qn kg/h 11,6 15,5 19,4 23,3 27 Propane gas consumption (supp.press. 37/50 mbar) at Qn kg/h 0,9 0,9 0,9 0,9 0,9 Maximum pressure available at ue base Pa 100 100 100 100 100 Max condensate production kg/h 23
Emissions
CO at maximum heat input with 0% O2 mg/kWh 83 83 83 83 83 NOx at maximum heat input with 0% O2 mg/kWh 77 77 77 77 77 NOx class 6 6 6 6 6 (***) Sound pressure level dBA 52 52 52 52 52
Electrical data
Frequency/Power supply voltage: V/Hz 230/50 230/50 230/50 230/50 230/50 Supply fuse A (R) 6,3/10 6,3/10 6,3/10 6,3/10 6,3/10 (**) Degree of protection IP X5D X5D X5D X5D X5D
II
2H3P
II
2H3P
II
2H3P
II
2H3P
30,60 38,3 45,9 53,6
(*) Room Temperature = 20°C (**) See "NOZZLES - PRESSURES" table (***) e IP X5D degree of protection is obtained with the lid lowered.
13
Page 14
Technical characteristics and dimensions
2.5 TECHNICAL PARAMETERS FOR COMBINATION BOILERS IN COMPLIANCE WITH REGULATION 813/2013.
Eciencies in the following tables refer to the gross caloric value.
Model/s: ARES 150 Tec ErP
Condensing Boilers: YES
Low temperature boiler: NO
Boiler type B1: NO
Co-generation appliance for central heating: NO Fitted with supplementary heating system: NO
Mixed heating appliance: NO
Element Symbol Valu e Unit Element Symbol Value Unit
Nominal heat output P
n
146 kW
For central heating only and combination boilers: useful heat output For central heating only and combination boilers: useful eciency At nominal heat output in high tempera-
ture mode (*) At 30% of nominal heat output in a low
temperature mode (**)
P
4
P
1
146.1 kW
49.3 kW
Auxiliary electricity consumption Other items
At full load el
At partial load el
In standby mode P
0.210 kW Heat loss in standby P
max
0.040 kW Annual electrical consumption Q
min
0.000 kW Emissions of nitrogen oxides ref. PCI (PCS) NOX54 (49)
SB
For mixed central heating appliances
Stated load prole Domestic hot water production eciency η
Daily electrical power consumption Q
elec
Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY (*) High temperature mode means 60°C on return and 80°C on ow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return tem­perature.
Seasonal energy eciency of central heating
At nominal heat output in high tempera­ture mode (*)
At 30% of nominal heat output in a low temperature mode (**)
kWh Daily gas consumption Q
η
η
η
stby
HE
WH
fuel
s
4
1
92 %
87.7 %
96.7 %
0.94 kW
459 GJ
mg / kWh
%
kWh
14
Page 15
Technical characteristics and dimensions
Model/s: ARES 200 Tec ErP
Condensing Boilers: YES
Low temperature boiler: NO
Boiler type B1: NO
Co-generation appliance for central heating: NO Fitted with supplementary heating system: NO
Mixed heating appliance: NO
Element Symbol Valu e Unit Element Symbol Value Unit
Nominal heat output P
n
195 kW
For central heating only and combination boilers: useful heat output For central heating only and combination boilers: useful eciency At nominal heat output in high tempera-
ture mode (*) At 30% of nominal heat output in a low
temperature mode (**)
P
4
P
1
195.2 kW
64.4 kW
Auxiliary electricity consumption Other items
At full load el
At partial load el
In standby mode P
0.290 kW Heat loss in standby P
max
0.040 kW Annual electrical consumption Q
min
0.010 kW Emissions of nitrogen oxides ref. PCI (PCS) NOX54 (49)
SB
For mixed central heating appliances
Stated load prole Domestic hot water production eciency η
Daily electrical power consumption Q
elec
Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY (*) High temperature mode means 60°C on return and 80°C on ow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return tem­perature.
Seasonal energy eciency of central heating
At nominal heat output in high tempera­ture mode (*)
At 30% of nominal heat output in a low temperature mode (**)
kWh Daily gas consumption Q
η
η
η
stby
HE
s
4
1
92 %
87.5 %
96.7 %
0.98 kW
612 GJ
mg / kWh
WH
fuel
%
kWh
Model/s: ARES 250 Tec ErP
Condensing Boilers: YES
Low temperature boiler: NO
Boiler type B1: NO
Co-generation appliance for central heating: NO Fitted with supplementary heating system: NO
Mixed heating appliance: NO
Element Symbol Valu e Unit Element Symbol Value Unit
Nominal heat output P
n
240 kW
Seasonal energy eciency of central heating
η
s
92 %
For central heating only and combination boilers: useful heat output For central heating only and combination boilers: useful eciency At nominal heat output in high tempera-
ture mode (*) At 30% of nominal heat output in a low
temperature mode (**)
P
4
P
1
244.5 kW
80.5 kW
At nominal heat output in high tempera­ture mode (*)
At 30% of nominal heat output in a low temperature mode (**)
η
η
4
1
88.1 %
96.7 %
Auxiliary electricity consumption Other items
At full load el
At partial load el
In standby mode P
0.362 kW Heat loss in standby P
max
0.040 kW Annual electrical consumption Q
min
0.010 kW Emissions of nitrogen oxides ref. PCI (PCS) NOX54 (49)
SB
stby
HE
1.1 kW
766 GJ
mg / kWh
For mixed central heating appliances
Stated load prole Domestic hot water production eciency η
Daily electrical power consumption Q
elec
kWh Daily gas consumption Q
WH
fuel
%
kWh
Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY (*) High temperature mode means 60°C on return and 80°C on ow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return tem­perature.
15
Page 16
Technical characteristics and dimensions
Model/s: ARES 300 Tec ErP
Condensing Boilers: YES
Low temperature boiler: NO
Boiler type B1: NO
Co-generation appliance for central heating: NO Fitted with supplementary heating system: NO
Mixed heating appliance: NO
Element Symbol Valu e Unit Element Symbol Value Unit
Nominal heat output P
n
294 kW
For central heating only and combination boilers: useful heat output For central heating only and combination boilers: useful eciency At nominal heat output in high tempera-
ture mode (*) At 30% of nominal heat output in a low
temperature mode (**)
P
4
P
1
294.0 kW
96.6 kW
Auxiliary electricity consumption Other items
At full load el
At partial load el
In standby mode P
0.435 kW Heat loss in standby P
max
0.040 kW Annual electrical consumption Q
min
0.010 kW Emissions of nitrogen oxides ref. PCI (PCS) NOX54 (49)
SB
For mixed central heating appliances
Stated load prole Domestic hot water production eciency η
Daily electrical power consumption Q
elec
Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY (*) High temperature mode means 60°C on return and 80°C on ow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return tem­perature.
Seasonal energy eciency of central heating
At nominal heat output in high tempera­ture mode (*)
At 30% of nominal heat output in a low temperature mode (**)
kWh Daily gas consumption Q
η
η
η
stby
HE
s
4
1
92 %
88.3 %
96.7 %
1.15 kW
920 GJ
mg / kWh
WH
fuel
%
kWh
Model/s: ARES 350 Tec ErP
Condensing Boilers: YES
Low temperature boiler: NO
Boiler type B1: NO
Co-generation appliance for central heating: NO Fitted with supplementary heating system: NO
Mixed heating appliance: NO
Element Symbol Valu e Unit Element Symbol Value Unit
Nominal heat output P
n
342 kW
Seasonal energy eciency of central heating
η
s
92 %
For central heating only and combination boilers: useful heat output For central heating only and combination boilers: useful eciency At nominal heat output in high tempera-
ture mode (*) At 30% of nominal heat output in a low
temperature mode (**)
P
4
P
1
341.7 kW
112.0 kW
At nominal heat output in high tempera­ture mode (*)
At 30% of nominal heat output in a low temperature mode (**)
η
η
4
1
88.5 %
96.7 %
Auxiliary electricity consumption Other items
At full load el
At partial load el
In standby mode P
0.507 kW Heat loss in standby P
max
0.040 kW Annual electrical consumption Q
min
0.010 kW Emissions of nitrogen oxides ref. PCI (PCS) NOX54 (49)
SB
stby
HE
1.39 kW
1069 GJ
mg / kWh
For mixed central heating appliances
Stated load prole Domestic hot water production eciency η
Daily electrical power consumption Q
elec
kWh Daily gas consumption Q
WH
fuel
%
kWh
Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY (*) High temperature mode means 60°C on return and 80°C on ow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return tem­perature.
16
Page 17
17
Page 18
Instructions for the installer
INSTRUCTIONS FOR
3
INSTALLATION
3.1 GENERAL RECOMMENDATIONS
ATTENTION! is boiler must only be employed for its explicitly intended use. Any other use must be considered improper and therefore dangerous. is boiler is used to heat water to below boiling temperature in atmospheric pressure.
ATTENTION! These appliances are designed exclusively for installation inside suitable technical compartments.
Before connecting the boiler, have professionally authorised company:
a) Accurately washing all of the pipes in the system
to remove any residues or sediments could stop the boiler form running eciently, even in terms of health and hygiene.
b) Making sure the boiler is set up to operate with the
available type of fuel. e type of fuel is stated on the packaging and technical characteristics plate.
c) Make sure that the chimney/ue has an adequate
draught, that it is not choked, and that there are no other exhausts for other appliances, unless the ue is designed for multiple utilities, in accordance with standard specications and requirements in force. Only once this check has been carried out can the tting between boiler and chimney/ue be set up.
ATTENTION! In rooms with aggressive vapour or dust, the appliance must operate independently of the air in the room of installation!
ATTENTION! e appliance must be installed by an authorised company possessing professional-technical qualications in accordance with the law, who, under his/her own responsibility, enforces the observance of regulations according to the rules of good practice.
ATTENTION! Assemble the appliance in observance of the minimum required distances for installation and maintenance.
e boiler must be connected to a heating system compatibly with its specications and power.
18
Page 19
C
Instructions for the installer
3.2 PACKAGING
e ARES Tec boiler is supplied assembled in a sturdy cardboard box.
Once the two straps have been removed, slide the box o from the top and make sure the contents are intact.
Packaging materials (cardboard box, straps, plastic bags, etc.) constitute a potential hazard and must be kept
out of the reach of children. e manufacturer will not be held liable in case of
damage caused to people, animals or property due to failure to observe the above.
OBLIGATION! Wear protective gloves
- Only transport the boiler using appropriate transport means, for example a trolley with xing strap.
- When the boiler is shipped, it must be secured to the transport equipment.
- Protect all parts against impacts, if they must be transported.
- Follow the transport instructions on the package.
- e boilers must always be lied and carried with a trolley or suitable transport equipment.
- A box containing:
- Gasket between pan and terminal
- Collar gasket
- Two bends + one T + plastic cap for condensate drain
- Screws required to secure the ue terminal
- e probes: external, ow, storage tank
- Flue inspection cap
- Kit of resistances
- Plate and fairlead for power output
On the right side of the boiler:
- Condensate drain trap pipe
- RT and LT side platform.
On the rear side of the boiler:
- Front and rear platform.
Above the boiler cover:
- A plastic bag containing:
- Installer and maintenance technician instructions handbook
- System manager instructions handbook
- HSCP control unit user handbook
- BCM 2.0 user handbook
- Warranty certicate
- Hydraulic test certicate
- Pins to block the set of fans in raised position.
Composition of packaging:
On the front of the boiler there are:
- e ue exhaust manifold anchored to the front crossbeam with screws
- A box containing:
- 4 supporting feet
- 3 closing plugs to invert manifolds
- 3 insulating gaskets for manifolds (outdoor boiler)
B
A
Model A (mm) B (mm) C (mm)
150 200 250 300 350
840 1110 1110 1375 1375
890 890 890 890 890
1250 1250 1250 1250 1250
Gross
Weight (kg)
236 295 325 386 419
19
Page 20
Instructions for the installer
3.3 REMOVING THE BOILER FROM THE PALLET AND PUTTING ON THE FEET
1 3
2 4
A
A
- Dismantling the boiler
- Liing the boiler using a sling hoist or forkli
- Remove the four "A" screws
- Put in the 4 feet contained in the box
- Attach the feet to the frame using the 4 previously removed "A" screws
- Stand the boiler on the screed and cover with the casing.
20
Page 21
Instructions for the installer
3.4 POSITIONING THE HEATING CONTROL UNIT
Special attention must be paid to local standards and regulations regarding heating control units, especially the minimum distances that must be observed. Installation must be comply with the requirements contained in the most recent standards and legislation regarding heating control units, heating system installation and hot water production, ventilation, ues suitable for condensation boiler combustion product exhaust, and any other applicable regulation.
e boiler can be placed on a at platform that is suciently sturdy in size, in plan, no smaller than the boiler measurements and with a minimum height of at least 100 mm so that the trap for condensate drainage can be installed. Alternatively, a trap can be built from this platform, next to the boiler, at a depth of 100 mm so that the trap can be placed in it (Parag. 3.16). When installation is complete the boiler should be perfectly horizontal and rmly stable (to reduce vibrations and noise).
Sifone
Tra p
A
B
D
C
A > 400 mm B > 400 mm C = 100 mm D= 500 mm
Observe the minimum clearance distances required to perform normal maintenance and cleaning operations.
21
Page 22
Instructions for the installer
3.5 CONNECTING THE BOILER
e ARES Tec boiler leaves the factory set up for hydraulic (flow and return), gas and flue exhaust connections located on the right side of the boiler. To invert the connections from the right side (standard supply) to the le side it is necessary to carry out the operations below, depending on the connection that needs to be moved.
Reversing ue exhausts. To move the ue exhaust from Rt to Lt simply switch the two sides on the casing around. To move the exhaust located on the rear side, proceed as described below, depending on the boiler model.
- ONLY FOR MODELS 250 - 300 - 350 (Fig. A) it is necessary to request
the ue kit comprised of a "T" and a closing plate over the hole on the Rt side of the casing.
- ONLY FOR MODELS 150 and 200 (Fig. B) it is necessary to request
the ue kit comprised of a closing plate over the hole on the Rt side of the casing.
Reversing Gas (Fig. C). Switch the blind ange around with the
anged stud pipe.
Reversing system ow and return (Fig. D). Switch the blind
ange around with the anged stud pipe. Reversing hydraulic attachments (Fig. E). Remove the pre-sectioned
part on the attachments that you intend to move to the opposite side (only one or both) and close the Rt side of the casing with the caps supplied with the boiler.
Fig. C
Fig. A
Fig. B
Fig. D
Fig. E
22
Page 23
Instructions for the installer
3.6 GAS CONNECTION
e gas intake pipe must be connected to the boiler using the respective G 2" tting as indicated in parag. 2.3.
e supply pipe must have a section equal to or larger than the one used
in the boiler and must nevertheless provide the correct gas pressure. It is nevertheless advisable to adhere to the standard specications
and requirements in force, setting up a cut-o valve, gas lter, anti­vibration joint, etc.
Before commissioning an internal gas distribution system and therefore,
before connecting it to the meter, it is necessary to thoroughly check the seal.
If any part of the system is not in view, the sealing test must be carried out before covering the pipe.
Danger! e gas connection must be set up by an authorised installation technician who must observe and apply the contents of the legislation in force and the local requirements of the gas supply company, as incorrect installation can cause damage to people, animals and property, for which the manufacturer will not be held liable.
Before installation it is advisable to clean the inside of the fuel intake pipe thoroughly, in order to remove any residues that could stop the boiler from operating sm oothly.
If you notice the smell of gas: a) Do not work the electrical switches, the telephone
or any other object that can generate sparks;
b) Immediately open doors and windows to create an
air current that puries the room; c) Close the gas valves; d) Seek the assistance of professionally qualified
personnel.
In order to prevent any gas leaks it is advisable to install a surveillance and protection system composed of a gas leak detector combined with a cut-o electrovalve on the fuel supply line.
1 2 3 4 5 66
Key: 1 - Fuel shut-o valve 2 - Double membrane regulator 3 - Gas lter 4 - Anti-vibration joint 5 - Gas electrovalve 6 - Cut-o valve
EXAMPLE OF GAS INTAKE SYSTEM
INTERIOR OF
INTERNO
THE HEATING
CENTRALE
CONTROL
TERMICA
UNIT
EXTERIOR OF
ESTERNO
THE HEAT-
CENTRALE
ING CONTROL
TERMICA
UNIT
23
Page 24
Instructions for the installer
3.7 SYSTEM FLOW AND RETURN PIPE CONNECTION
e heating ow and return must be connected to the boiler by the respective 2½" ttings F and R as indicated in parag. 2.3.
For heating circuit pipe sizing it is necessary to take into account the head losses induced by the components of the system and its conguration.
e layout of the pipes must be set up taking every necessary precaution to avoid air pockets and to facilitate continuous degassing of the system.
ATTENTION! Before connecting the boiler to the system proceed by thoroughly washing the pipes terminating at the boiler with a suitable product, in compliance with standards, in order to eliminate metal residues from machining and welding, any oil and grease that could aect its operation. Do not use solvents to wash the system, as they might damage the system and/or its components. Failure to observe the instructions in this manual can cause damage to people, animals and property, for which the manufacturer will not be held liable.
Make sure the pipes in the system are not used as earthing connections for the electrical or telephone system. ey are absolutely not suitable for this purpose. Serious damage to pipes, boiler and radiators could occur in a short amount of time.
ATTENTION! IT IS ABSOLUTELY FORBIDDEN TO SET UP CUT­OFF DEVICES ON THE GENERATOR BEFORE THE SAFETY DEVICES.
ATTENTION! THE MANUFACTURER DECLINES ALL LIABILITY IN THE EVENT OF DAMAGE CAUSED BY THE INSTALLATION OF AN AUTOMATIC FILLING SYSTEM.
BCM
G
M
R
24
Page 25
Instructions for the installer
3.8 ADDITIONAL SAFETY, PROTECTION AND CONTROL DEVICES
Certicate of additional safety devices: closely consult the legislative
regulations and safety provisions in force in the country of installation of the appliance. Use the fuel safety and cut-o valves suitable for application and compliant with provisions in force. e boiler is not equipped with an expansion vessel on the system. It is mandatory to install a closed expansion vessel to guarantee correct boiler operation. e expansion vessel must be compliant with standard requirements in force. e dimensions of the expansion vessel depend on the data for the central heating system. Install a vessel with a capacity, determined by an authorised designer, that responds to the requisites of the standards in force.
Safety devices. 1 Gas cut-o valve: this has the function of directly cutting-o the
gas supply if the limit value of the water temperature is reached. e detection element must be installed as close as possible to the generator output (ow pipe) at a distance of < 500 mm, and must not have a cut-o device installed on it. Not supplied by Immergas
2 Safety valve: this has the function of unloading the uid contained
in the generator into the atmosphere when it reaches the maximum
operating temperature for any reason. Not supplied by Immergas 2a Visible draining funnel. Not supplied by Immergas Set up a safety valve, on the ow pipe, sized for boiler capacity, within
0.5 m of the boiler, and in compliance with regulations in force.
Attention! Remember it is forbidden to set up any type of cut-o device between the boiler and the safety valve, and it is also advisable to use valves for operation that does not exceed the maximum allowed operating pressure.
Protection devices. 10 Safety thermostat: this is designed to stop the generator if the safety
thermostat installed on the boiler fails to operate correctly. It must have an IMMOVABLE calibration of < 100°C.
15 Minimum pressure switch: this is designed to stop the generator if
the minimum operating pressure drops (can be calibrated between
0.5 ÷ 1.7 bar). It must be manually re-armed.
16 Extra sleeve G1". 18 Safety pressure switch: this is designed to stop the generator if the
maximum operating pressure is reached (can be calibrated between 1 ÷ 5 bar).
Control devices. 13 (Pressure indicator - not supplied) with (12) damper pipe and (11)
pressure gauge valve: it indicates the existing eective pressure in
the generator, it must be graduated in "bar", its full scale must match the maximum operating pressure and be equipped with a three-way valve with an attachment for the control pressure gauge.
14 ermometer: this indicates the eective temperature of the water
contained in the generator, it must be graduated in centigrade with a full scale of no more than 120°C.
17 Inspection traps: approved for the inclusion of control devices. 20 Flow switch: this is designed to stop the generator in case of poor
water circulation inside the primary ring.
3 Approved expansion vessel: this absorbs the increase in volume
of water in the system following an increase in temperature. Not
supplied. 7 Modulation pump (Not included in the kit). 4 Bleeder valve. Not supplied by Immergas. 6 Draining valve. Not supplied by Immergas.
Attention! Set up a runo pipe with funnel and trap on the heating safety valve, that lead to a suitable drain. e drain must be visually controlled. e manufacturer will not be held liable in the case of failure to observe this precaution, where any work on the safety valve may cause damage to people, animals and property.
25
Page 26
Instructions for the installer
Recommended installation
1
3
1a
BCM
2
2a
20
16
13
18
19
17
4
15
8
1112
14
10
7
5
6
26
Page 27
Portata (l/h )
Instructions for the installer
3.9 DETERMINING THE PRIMARY CIRCUIT PUMP OR BOILER PUMP
Immergas provides a series of primary rings complete with an accurately sized pump, if alternative solutions are being used, the boiler pump must have a head that is capable of ensuring the ow rates represented in the "Water side head losses" graph.
e pumps must be determined by the installer or designer based on the data for the boiler and system. e resistance curve on the water side of the boiler is represented in the table provided below. e pump is not an integral part of the boiler. It is advisable to choose a pump with a ow rate and head of approximately 2/3 of its typical curve.
e table below roughly indicates the ow rates of the pump based on the Δt of the primary circuit if the installation is equipped with a hydraulic separator.
Power in kW 150 200 250 300 350
Maximum ow rate in l/h (Δt = 15 K) 8376 11192 14018 16856 19712
Nominal requested ow rate in l/h (Δt = 20 K)
6 5,8 5,6 5,4 5,2
5 4,8 4,6 4,4
O
2
4,2
4 3,8 3,6 3,4
3,2
ar ic o (m/H )
3 2,8
i c
2,6 2,4
e d
2,2
2 1,8
Head loss (m/H2O)
1,6
Pe rdit
1,4 1,2
1
0,8 0,6 0,4 0,2
0
2000
0
4000 6000 8000 10000 12000 14000 16000 20000 22000 24000 2600018000
6282 8394 10514 12642 14784
200
250
300
350
150
Flow rate (l/h)
EXAMPLE: For a T 20K, of an ARES 250 Tec the maximum required ow rate is 10514 l/h. From the head loss graph it is possible to deduce that the pump must ensure a head of at least 1.6 m/H2O.
NOTE: it is advisable to always use the hydraulic separator between the boiler circuit and the system.
27
Page 28
Instructions for the installer
3.10 CONDENSATE DRAIN
e condensate drain into the sewer must be:
- built to avoid gaseous combustion products from leaking out into the environment or the sewer (trap).
- sized and built to allow liquid discharge to runo correctly, preventing any leaks (gradient of 3%).
- installed to avoid the liquid contained in it from freezing, under the envisioned operating conditions.
- can be easily inspected from the relative trap.
- mixed with household wastewater, for example, (washing machine and dish washer drains etc.) with a mainly alkaline pH so as to form a buer solution to send it into the sewers.
e condensate must not be le to stagnate in the combustion product drainage system (for this very reason the evacuation pipe must be set up at an inclination of at least 30 mm/m, running towards the drain) except for any liquid head, in the drain trap of the combustion product evacuation system (which must be lled aer installation and at a minimum height with all of the fans operating at maximum speed of at least 25 mm) - see gure.
It is forbidden to drain the condensate towards rain pipes, given the risk of ice and degradation of materials normally used to build the rain pipes themselves.
e drain tting must be visible. Given the degree of acidity of the condensate (pH between 3 and 5)
suitable plastic materials must be used to build the drain pipes. e condensate drain pipe outlet is set up towards the connection
side of the ue box manifold, removing the pre-sectioned part on the cover panel.
e recommended material for use must be PE (polyethylene) or PPI (polypropylene).
Before igniting the generator, ll the trap through the relative cap.
FRONT SIDE
TAPPO DI RIEMPIMENTO
INITIAL TRAP
INIZIALE
FILLER CAP
DEL SIFONE
150
PAVIMENTO
FLOOR OF THE
DELLA C.T.
H.C.U.
PLATFORM (H min 100 mm)
* Minimum safety trap enforced by regulation.
** Minimum head with boiler operating at maximum power.
If you do not want to or are able to create a platform, it is possible to install the boiler on the oor and set up the trap at a depth of 100 mm.
e top
generator of
the drain pipe must not be higher than the bottom of
the pan
TO THE
150
CONDENSATION DRAIN
28
Page 29
Instructions for the installer
3.11 CONNECTING THE FLUE
Exhaust is discharged at very low temperatures (Max 84°C approx) in condensation boilers. It is therefore necessary for the ue to be perfectly impermeable to combustion product condensate and built with suitable corrosion-resistant materials. e various slip on joints must be well-sealed and equipped with suitable gaskets to stop condensation from leaking out and air from getting in. In terms of ue section and height, it is necessary to refer to national and local regulations in force. Refer to regulations in force for sizing. In order to avoid the formation of ice during operation, the temperature of the inside wall at every point in the combustion product evacuation system, for its entire length, must not drop below 0°C. For condensation operating conditions of the appliance at project outdoor temperatures, it will be necessary to build a confluent condensate drainage system, based on the installation conditions, either to the boiler collection tank or separate from it.
The flue exhaust pipe must comply with local and national regulations. e evacuation pipe must be built using materials that are resistant to the combustion products, typically class W1 certied stainless steel or plastic materials.
Such as PVDF (polyvinyldimethyluoride) or PPS (simple translucent polypropylene) or aluminium or other materials with the same features, in observance of regulation in force.
e supplier is excluded from any contractual and extra-contractual liability for damage caused by errors in installation and use and nevertheless due to failure to observe the instructions provided by the manufacturer.
Model Modules Ø Attachment
150 3 150 200 4 150 250 5 200 300 6 200 350 7 200
3.12 FLUE EXHAUST MANIFOLD CONNECTION
To secure the ue exhaust manifold use the 6 nuts + CH 10 washers contained in the bag.
e ue point must be positioned on the rst straight section, within 1 meter of the boiler.
To set up the ue inspection point, cut a Ø 21 mm hole in the ue exhaust pipe, and install the inspection point following the sequence provided.
Ø21 mm
29
Page 30
Instructions for the installer
3.13 ELECTRICAL CONNECTIONS
GENERAL RECOMMENDATIONS
Electrical safety of the appliance is only ensured when it is correctly connected to an ecient earthing system as specied by current safety standards: gas, water and heating system pipes are not suitable in any way whatsoever as earthing connections.
It is necessary to check this fundamental safety requirement; In case of doubt, have an accurate inspection of the electrical system carried out by profession­ally qualied personnel, as the manufacturer is not responsible for any damage caused by the lack of a earthing connection in the system. Have professionally qualied personnel make sure the electrical system is suit-
44
F1
55
TL
54
51
able for the maximum power absorbed by the appliance, as stated on the plate, making sure in particular that the section of the system's cables is suitable for the power absorbed by the appliance.
For the main power supply to the appliance, never use adapters, multiple sockets and/or extension leads.
The use of components involving use of electrical power requires some fundamental rules to be observed such as:
- do not touch the appliance with wet and/or moist parts of the body and/or barefoot;
- do not pull the electric cables;
- the appliance may not be used by children or unskilled individuals
A4
A3
Y3
123
A5
4
Y2
5
6
7
123
50
GND
A1
A2
4 3 2 1
12 11 10 9 8 7 6 5
Y2
Y1
2
1
4
5
6
123
33
00330914
Jp2
43
.
3
1
2
4
Y4
0
1
9
2
8
3
7
4
6
5
3
Y3
21 3
54 76
98 1 011 12 13 14
1
2
ATTENZIONE!
ATTENTION!
ACHTUNG! ATENCIÓN!
00330914
ATTENZIONE!
ATTENTION!
ACHTUNG!
E
38 38 38
BK
BK
LB
GY
RB
FL
FL
ATENCIÓN! ATTENTIE!
UPOZORNÌNÍ!
230 V
ATTENTIE!
UPOZORNÌNÍ!
230 V
KEY
DNALEIW
zH 05
V 032
D
Wiring
diagram
Description
33 Heat adjuster HSCP
38 BMM Burner management board
43 BCM 230 V power supply clamps
44 F1 Boiler pump
50 Fuse power supply 6.3 A
51 TLG
54 LTGL
55 Main boiler switch E Power supply distribution board FL Connection for ow switch
D Wieland power plug 230V - 50Hz
General manual reset limit thermostat (model 350)
Limit thermostat lamp TLG (model 350)
30
Page 31
230V
E8 - BCM
24V
ALIM.
Instructions for the installer
Danger! Electrical installation must only be carried out by an authorised company. Before setting up the connections or any operation on the electrical parts, always cut-o the electrical supply and make sure it cannot be accidentally re-connected.
e electrical supply to the boiler, 230 V - 50 Hz single phase, must be carried out on point A, included, with a H05VV-F (PHASE - NEUTRAL - GROUND) three­pole cable with a section between 0.75 mm and 1.5 mm. is connection must be set up by state of the art, as envisioned by regulations in force.
External probe connection
Remember that it is necessary to install a bipolar switch on the electrical supply to the boiler with a max distance between the contacts of 3 mm, easy to access, so that maintenance operations can be carried out quickly and safely.
ATTENTION!
Respect the PHASE and NEUTRAL polarity since ame detection is Phase Sensitive.
Connection TA - Clock (Optional)
NEVER remove the
Non rimuovere MAI
BCM jumper (Y2 11-12)
TA
12 11 10 9 8 7 6 5
Y2
il ponticello BCM (Y2 11-12)
4 3 2 1
Jp2
Y4
3
1
2
4
2 31
8 19
123
0
1
9
2
8
3
7
4
6
5
4
5
6
Set up on the terminal board, BCM (Y2 9-12) Remove only the jumper BCM (Y2 9-12)
Set up on the terminal board, BCM (Y2 6-7)
ATTENTION: Cables carrying a voltage of 230 V must travel separately from cables carrying a voltage of 24 V.
31
Page 32
one
Instructions for the installer
NOTE:
e boiler is provided with set-up to manage one direct ow and one storage tank. If Stemp. ACC is connected automatically, the DHW service is enabled, which will be managed as a priority compared to direct ow through the pumps shown below.
Alarm / signals contact (N.O. dry contact) Ext signal contact 0 - 10 V
Alarm
Jp2
signal
3
4
Y4
3
1
2
Y3
1
2
+
12 11 10 9 8 7 6 5
Y2
-
4 3 2 1
If other services (storage tanks, mixed zones, solar, etc.) are requested, it is necessary to purchase SHC multifunction modules to connect to the local bus for total temperature control management via HSCP (and UFLY).
e BCM relay contacts support pumps with max absorption of 4 A.
P. Coll - Pump Manifold (Primary ring) (Optional) P CH - Heating circuit pump (central heating circuit) P. Car DHW - Storage tank load pump
P. Coll.
2 31
5 64 7
98 10 11 12 13 14
123
0
1
9
2
8
3
7
4
6
5
4
5
6
Connect the cables as indicated (Y4 3-4) Connect the cables (Y4 7-8)
Connection Mod. P. Central Heating Modulating Pump (Optional)
3
1
2
12 11 10 9 8 7 6 5
Y2
4 3 2 1
4
Jp2
Y4
Connect the cables as indicated (Y4 1-2) Connect the cables as indicated (Y3 1-2-3)
Stemp. ACC. Storage Tank Temperature Sensor
If the storage tank temperature sensor
Se il sensore di temperatura accu-
is connected, the DHW is automatically
mulo viene collegato, automatica-
activated when the boiler is powered.
mente viene attivato il servizio sani-
e code (803) Srv (it is automatically
tario al momento dell'alimentazi
updated)
caldaia. Il par (803) Srv (viene automatica- mente aggiornato)
CCA.pmetS
DNG)-(
3
1
2
Jp2
4
Y4
12 11 10 9 8 7 6 5
Y2
4 3 2 1
Y3
Y3
3
1
2
3
1
2
Connect the modulation control cables as indicated (Y2 4-5). External power supply 230 V-50 Hz.
Connect the temperature sensor cables as indicated (Y2 6-8).
32
Page 33
Instructions for the installer
3.14 CONNECTION DIAGRAM
POWER SUPPLY, INAIL, MODULATION PUMP, EXTERNAL PROBE, FLOW SWITCH.
E
BK
1
C C CNC NC NO
1.1 (P. max.)
2
L1
PE
N
230 V 50 Hz
D
SAFE
1.3 (T.S.)
1.2 (P. min.)
NOT SUPPLIED
L1
PE
N
P.
mod.
SE
12 11 10 9 8 7 6 5
Y2
M
SS
N
4 3 2 1
L
IF-EXT. MIN 10-0V
3
4
Jp2
Y4
3
1
1
2
2
Y3
FL
FL
LEGENDA
Description 1 INAIL - SAFETY DEVICES 2 General electrical control panel (Not supplied) 4 BCM Connection clamps BCM E Power supply distribution board D Wieland power plug FL Terminals for ow switch SE External probe SMG Global ow probe P on_o Manifold pump connections (on_o) P mod Modulating pump connections
FL
4
21 3
4 5 6 7
0
1
9
2
8
3
7
4
6
5
123
4
5
6
98 1 011 12 131 4
33
Page 34
Instructions for the installer
2 ARES Tec connected in a set, managed by Cascade Manager.
E
BK
BK
1
C C CNC NC NO
1.1 (P. max.)
SAFE
1.3 (T.S.)
1.2 (P. min.)
PRIMARY LOOP
anello primario
2
L1
PE
N
L1
PE
N
E
230 V 50 Hz
D
IF-EXT. MIN 10-0V
P.
mod.
M
SS
N L
-SUBe
+SUBe
3
3
1
1
2
2
4
4 3 2 1
1211 10 9 8 7 6 5
Jp2
Y3
FL
FL
BK
FL
Y2
4
0
1
9
2
8
3
7
4
6
5
1
1.1 (P. max.)
Y4
0
1
9
2
8
3
7
4
6
5
4
5
6
123
SAFE
1.3 (T.S.)
C C CNC NC NO
21 3
98 101112 1314
1.2 (P. min.)
4 5 6 7
SMG
2
L1
PE
N
230 V 50 Hz
D
L1
PE
N
1211 10 9 8 7 6 5
FL
FL
FL
Y2
4
0
1
9
2
8
3
7
4
6
5
123
mod.
4
IF-EXT. MIN 10-0V
P.
M
SS
N L
-SUBe
+SUBe
3
3
1
1
2
2
4
4 3 2 1
Jp2
Y3
Y4
21 3 4 5 6
7
0
1
9
2
8
3
7
4
6
5
5
98 101112 1314
6
SE
5
CM 140
1211 10 9 8 7 6 5
Y2
Jp2
Y3
Y4
4
3
3
1
1
2
2
4
4 3 2 1
cascade
manager
3
3
6
4
4
7
1
1
2
2
5
)-(
+SUBe
V 42 +
R BK BR
4
5
123
24 V - DC
24 V - DC
2 31 4
65 7
0
1
9
2
8
3
7
4
6
5
98 101112 1314
6
34
Page 35
Instructions for the installer
Ares Tec connection 2 in battery controlled by Cascade Manager with Direct Zone plus Production of Domestic Hot Water.
anello secondario
SECONDARY LOOP
C
CH
Stemp.
ACC
P.
CH
P. Car.
DHW
L
3
3
1
1
2
2
4
4 3 2 1
12 11 10 9 8 7 6 5
Y2
Jp2
Y3
Y4
4
21 3
54 76
0
1
9
2
8
3
7
4
6
5
4
5
6
123
Note
Nota:
For conguration of boiler cascade management para-
in cascata, fare riferimento al manuale di installa-
meters, see the specic installation manual
98 1 011 121 314
caldaie
35
Note
Nota:
For installation with a single boiler, the above connec-
In caso di installazione con caldaia singola, i col-
tions will be made on the BCM board inside the boiler
scheda BCM interna alla caldaia.
Note
Nota:
Example diagram, consider the total nominal ow rate, any non-return valves (not supplied), moreover, the
nominale complessiva, eventuali valvole di non
eciency of the ow switches must be checked at each ow rate in modulation
-
lazione.
Page 36
Instructions for the installer
Wilo Stratos modulating Pump setting (Enable ext 0 - 10 V input).
NO
ON
OFF
10V
ON
10V
36
Page 37
Instructions for the installer
3.15 PRACTICAL CONNECTION DIAGRAM
2
50
E
Y1
A2
A1
DNG
al / to HSCP
-SUBe
+SUBe
V42+
123
1
RB
KB
R
123
7
6
5
Y2
4
Y3
A3
A4
GR eBUS+
142 3
PK eBUS-
BR BL BR BL
BK BL BR
BK OR
BL BL BR BR
BK
BK
BR YG BL
230 V
50 Hz
R
alla / to
BCM
(Y1)
A3
314
alla / to
BMM
1 MOD.
(Y1)
IG
TLG
(*)
LTLG
F 6.3A
+SUBeRB
-SUBeKB
R V42+
2
LB
GY
RB
GY
VM (R)
1
PF
SR
SR R
RS 1
PF
min.
LT 1
TL
SE
BK
KB
12 11 10 9 8 7 6
Y2
WHD.raC .P
.M.P.C
.RGNI-V01-0DNG
GOLANA.RGNI
CCA.pmetS
-V01-0
-SUBe
34 12
5
.lloC .P
HC.P
DNAMOC
DNAMOC
DNAMOC
AsubdoM
BsubdoM
+SUBe
4
Jp2
Y4
.MOC
CSU LANGISMRALLA
3
3
1
1
2
2
Y3
1° Mod.
VM (A)
LB
GY
RB
RB
BR
Y
LB
BL
1° Mod.
KP
BMM
BK BL BR OR
BR WH
WH WH R R WH WH
BR WH
L BL L BL L BL L BL
WH
E. RIL. 1
G
PK GR
YG BL
BR
BL BR YG
KEY
E. ACC. Ignition electrode E. RIL. Detection electrode SR Heating sensor (only 1° module) SR 1÷7 Local heating sensor PF Flue pressure switch (only 1° module)
PF min
Minimum ue pressure switch (only
1° module)
R
+ 20/40Vdc
BK
- 20/40Vdc eBUS+
BR
alla / to
alim. / supply (50)
A3
WH BR YG
2 31
Y1
4
5
6
123
4 5 6 7
0
1
9
2
8
3
7
4
6
5
98 10 1112 13 14
0
1
9
2
8
3
7
4
6
5
HSCP/
Uy
ermoregulation
SL Condensate level sensor (2° module) T. ACC. Ignition transformer TL Safety thermostat TL 1÷7 Local Safety thermostat VG Gas valve
MOD. 1
(POS . 0)
3
2
4
1
5
0
6
9
7
8
VM (A) Modulating fan power supply VM (R) Modulating fan adjustment/Det. SRR Global return sensor
BCM
SMG Global ow sensor S. temp.
ACC.
MOD. 2
(POS . 1)
3
2
4
1
5
0
6
9
7
8
Storage tank temperature sensor
BL BR YG
MOD. 3
(POS . 2)
2
1
0
9
8
3
4
5
6
7
SE Outdoor temperature sensor
37
Page 38
Instructions for the installer
Intermediate and Last
Module
BR
BL
3
2
4
1
0
6
9
7
8
Al / To conn.
4
A4 scheda alim. /
2
A4 power supply
T.ACC.
1
VM (A)
GY
RB
5
YG
R
LB
LB
VG
E. ACC. 1
mod.
1
FILTE R
R
RB
RB
VM
(R) 2-7
SR 2-7
SL
TL 2-7
VM (A)
VM (A)
BLUE BROWN
R
BLACK
GREEN
GREY
LB
GY
RB
LB
GY
RB
LIGHT BLUE
ORANGE PINK RED
YELLOW YELLOW / GREEN
RB
LB
VI
WHITE PURPLE
VIOLA
2° - 7° Mod.
KP
KP
G
MMB
BK BL BR OR
FL
BK
OR OR
BR WH
WH WH
BR WH L BL L BL
G
YG BL
BR
BL BR YG
T.ACC.
2 - 7
YG
VG
R
E. ACC. 2-7
mod.
2 - 7
. 2)
4
5
6
INGR. ANALOG. Analogue input GND 0-10V ING 0-10 V analogue input 0-10V C.P.M. Modulating Pump Control ALLARM SIGNAL Alarm Outlet Comm. P. COLL Boiler manifold pump control Comm. P. CH Central heating pump control
MOD. 4
(PO S. 3)
2
1
0
9
8
WH
E. RIL. 2 - 7
BL BR YG
MOD. 5
(PO S. 4)
3
4
5
6
7
3
2
4
1
5
0
6
9
7
8
MOD. 6
(PO S. 5)
2
1
0
9
8
MOD. 7
(PO S. 6)
3
4
5
6
7
3
2
4
1
5
0
6
9
7
8
BL BR
YG
mod.
3° - 7°
P. car DHW Storage tank load pump control COM. Common IG Main switch TLG General limit thermostat LTLG Limit thermostat lamp F Fuse
38
Page 39
Instructions for the installer
3.16 SYSTEM FILLING AND EMPTYING
ATTENTION! Do not mix the heating water with antifreeze or anti­corrosion substances at incorrect concentrations! This may damage the gaskets and cause noise to develop during operation. Immergas will not be held liable in case of damage caused to people, animals or property due to failure to observe the above.
Once all of the connections for the system have been set up, it is possible to ll the circuit.
EXAMPLE OF SYSTEM LOADING UNIT
To ll the system it is possible to set up a loading valve on the system's return pipe.
It can also be lled through the drain valve installed on the boiler return manifold.
e boiler is equipped with an emptying valve, positioned as indicated in the gure of parag. 2.2. is valve must never be used to empty the system, since all of the dirt contained in the system may accumulate in the boiler, jeopardising smooth operation. Accordingly, the system must be equipped with its own emptying valve, of a suitable size for the ow rate of the system.
LOADING
GRUPPO DI CARICAMENTO
UNIT
3.17 BOILER FROST PROTECTION
If the ow temperature (measured at the global ow NTC) should fall below 7°C the system pump starts operating. If the temperature drops any further (under 3°C), all modules are commissioned at the minimum power until the return temperature does not reach 10°C. is device protects the boiler only. In order to protect the system as well, it is necessary to add antifreeze liquid.
NB: e antifreeze liquid must be compatible with materials present in the entire system and tolerable for aluminium alloys.
39
Page 40
Instructions for the installer
3.18 CHECK THE ADJUSTMENT OF THE PRESSURE TO THE BURNER
ATTENTION!
All of the instructions below are provided for the exclusive use of authorised assistance personnel.
All boilers leave the factory calibrated and approved, nevertheless, if the calibration conditions need to be changed it is necessary to re-calibrate the gas valve.
ATTENTION!
Remove cap 2, attach the red cap 3 to the ue point 1. Place the CO2 analysis probe 4 in the hole on the cap. Once the measurement has been made, take the cap out and use the relative cap 2 to close the ue exhaust point back up.
A) Adjustment at maximum power.
- Unscrew the closing cap for ue exhaust analysis point.
- Place the analyser probe inside the ue analysis point.
- Make burner 1 operate at max power, following the procedure
illustrated below in "chimney sweep function " (100% CASC MANUAL).
- Make sure that the CO2 level falls within the values indicated in the
"Nozzle pressure" table.
- Possibly correct the value by turning adjusting screw "A" CLOCKWISE
to decrease it and COUNTER-CLOCKWISE to increase it.
B) Adjustment at minimum power.
- Make burner 1 operate at min power, following the procedure
illustrated below in "chimney sweep function " (10% CASC MANUAL).
- Make sure that the CO2 level falls within the values indicated in the
"Nozzle pressure" table.
- Possibly correct the value by turning adjusting screw "B" CLOCKWISE
to increase it and COUNTER-CLOCKWISE to decrease it.
1
2
3
4
MAXIMUM POWER ADJUSTING SCREW
MINIMUM POWER ADJUSTING SCREW
40
Page 41
Instructions for the installer
Follow this procedure to adjust the other modules as well.
If the measured ow rate is too low, make sure the supply and draining systems (the supply and draining pipes) are not obstructed. If they are not obstructed, make sure the burner and/or exchanger are not dirty.
C) Completing basic calibration.
- Check CO2 values at the minimum and maximum ow rate.
- Touch up if necessary.
For smooth operation, calibrate the CO2 values taking care to observe the values in the table.
- Close the cap for the ue inspection point back up.
NOTE: Do not force the adjusting screw limit switch limits.
When replacing the gas valve or having diculty with ignition:
Screw general adjusting screw "A" on clockwise until it stops, then unscrew by 7 revolutions. Check boiler ignition. If it does not start up unscrew screw "A" by one more revolution, then try to start it up again. If the boiler does not start up again, follow the operations described above until the boiler does start up again. At this point adjust the burner as previously illustrated.
Nozzles - pressures.
Frequently check the CO2 levels, especially at low ow rates.
ARES Tec
150 - 200
250 - 300 - 350
Type of
Gas
Nat. gas
(G20)
Nat. gas
(G25)
Propane
(G31)
Supply
pressure
(mbar)
20 7 - 1860 5880 9.1 9.1 80
25 9 - 1860 5880 9.1 9.1 80
37 7 - 1800 5460 10.8 10.8 80
Ø
Nozzles
(mm)
Diaphragm
Fan speed (rpm) CO2 levels (%)
Min. Max. Min. Max.
Power at
ignition IG
(%)
41
Page 42
Instructions for the installer
3.19 EMERGENCY AND SAFETY OPERATIONS
G
F1
H
F
I
BCM e BCM board prevents the system from shutting down if management of the HSCP system or main boiler system are out of service (see the BCM manual).
A YELLOW LED = ashing (communication between BMM and BCM)
ok GREEN LED = on (Pump On) RED LED = on (Error Code detected) E HSCP Control panel F Only for ARES 350 Tec Light indicating the General Limit
ermostat TLG is on G Fuses: 1 = 6.3 A H Main Switch I Only for ARES 350 Tec When TLG General Limit ermostat comes on it cuts o power
to the boiler and light F comes on. To re-arm it, take o the cap and
press
AE
NOTE: the devices are positioned under the casing next to the control unit.
NOTE: the emergency function only switches the burners on in the boiler to 100% in ow. All system loads, including the manifold pump, must be controlled manually.
Condensate level sensor position
42
Page 43
Instructions for the installer
3.20 FIRST IGNITION
Preliminary checks.
First ignition must be carried out by professionally authorised company. Immergas will not be held liable in case of damage caused to people, animals or property due to failure to observe the above.
Danger! Prior to commissioning the appliance ll the trap through the ller hole and make sure the condensate is draining correctly. If the appliance is used with an empty condensate drain trap the danger of poisoning subsists following a ue gas leak.
Prior to commissioning the boiler it is advisable to make sure that:
- installation fulls the standard specications and requirements in
force for both the gas and electrical part;
- the supply of combustion air and the evacuation of ue exhaust are
carried out correctly in accordance with standard specications and requirements in force;
- the fuel supply system is sized for the boiler's ow rate and is equipped
with all of the safety and control devices required by regulations in force;
- the power supply for the boiler is 230V - 50Hz;
- the system has been lled with water (pressure gauge 0.8/1 bar with
the pump o);
- any cut-o dampers on the system are open;
- the required gas corresponds to the one used for boiler calibration:
otherwise have the boiler converted for use with the available gas (see section: "ADAPTATION FOR USE WITH OTHER GASES"); this operation must be carried out by authorised company in accordance with regulations in force;
- the gas supply valve is open;
- there are no gas leaks;
- the external main switch is engaged;
- the system safety valve on the boiler responds to operation and is
connected to the sewer drain;
- the condensate drain trap is lled with water;
- there are no water leaks;
- the conditions for aeration and minimum distances to carry out any
maintenance operations are fullled.
Switching the boiler on and o
To turn the boiler on and o read the manual for the HSCP regulator.
Information for the system manager
e individual in charge of the system must be instructed in the use and operation of the heating system, in particular:
- Supply the system manager with the "THE SYSTEM MANAGER'S INSTRUCTIONS FOR USE", as well as all other documents attached the appliance contained in the envelope in the packaging. e system
manager must keep this documentation safe so that it is available for future consultation.
- Inform the system manager of the importance of aeration vents and
the ue exhaust system, highlighting how essential they are and how it is strictly forbidden to change them.
- Inform the system manager of the requirement to check the system's water pressure, as well as operations to restore it.
- Inform the system manager on how to correctly regulate the temperature, control units/thermostats and radiators in order to save energy.
- Remember that it is compulsory to carry out regular maintenance on the system and measure combustion output (as per national law).
- If the appliance is sold or transferred to another owner or if the owner moves, leaving the appliance behind, always ensure the manual accompanies the appliance so that it may be consulted by the new owner and/or installer.
43
Page 44
Inspections and maintenance
INSPECTIONS AND
4
MAINTENANCE
4.1 INSTRUCTIONS FOR INSPECTION AND MAINTENANCE
Inspections and maintenance carried out to state of the art and at regular intervals, as well as the exclusive use of original spare parts, are of primary importance for smooth operation and to guarantee long boiler life. Annual maintenance of the appliance is compulsory, in accordance with Legislation in force.
Failure to carry out Inspections and Maintenance can cause material and personal damage.
For this reason we recommend stipulating an inspection or maintenance contract.
Inspection is required to determine the eective state of an appliance and compare it with the optimal state. is is carried out through measuring, checking, observing.
Maintenance is required to eliminate any deviation of the eective state from the optimal state. is is usually carried out through cleaning, setting and possibly replacing single parts that are subject to wear.
ese maintenance intervals are set forth by a specialist based on the
certied state of the appliance at the time of inspection.
Instructions for inspection and maintenance.
Only original spare parts must be used to ensure a long life for all of the functions of your appliance, and to avoid changing the conditions of the approved standard product.
Before proceeding with maintenance operations, always carry out the procedures described below:
- Turn o the mains switch.
- Separate the appliance from the electrical network using a separation device, with a contact opening of at least 3 mm (for ex. safety devices or power switches), and make sure it cannot be accidentally re­connected.
- Shut the gas cut-o valve upstream of the boiler.
- If necessary, and based on the work that needs to be carried out, close any cut-o valves on the heating ow and return.
Once the maintenance work has been nished, always carry out the operations listed below:
- If necessary, open the heating ow and return
- Relieve and, if necessary, restore the pressure in the heating system.
- Open the gas cut-o valve.
- Re-connect the appliance to the electrical network and engage the mains switch.
- Make sure the appliance is water-tight, on the gas side and the water side.
OBLIGATION!
Wear protective gloves.
Scalding hazard!
Table of resistance values based on the heating probe (SR) and the heating return probe (SRR) temperature.
T°C 0 1 2 3 4 5 6 7 8 9
0 32755 31137 29607 28161 26795 25502 24278 23121 22025 20987 10 20003 19072 18189 17351 16557 15803 15088 14410 13765 13153 20 12571 12019 11493 10994 10519 10067 9636 9227 8837 8466 30 8112 7775 7454 7147 6855 6577 6311 6057 5815 5584 40 5363 5152 4951 4758 4574 4398 4230 4069 3915 3768 50 3627 3491 3362 3238 3119 3006 2897 2792 2692 2596 60 2504 2415 2330 2249 2171 2096 2023 1954 1888 1824 70 1762 1703 1646 1592 1539 1488 1440 1393 1348 1304 80 1263 1222 1183 1146 1110 1075 1042 1010 979 949 90 920 892 865 839 814 790 766 744 722 701
Relation between the temperature (°C) and nom. resistance (Ohm) of the heating probe SR and the heating return probe SRR. Example: At 25°C, the nominal resistance is 10067 Ohm At 90°C, the nominal resistance is 920 Ohm
Be careful during the maintenance operations.
44
Page 45
We urge you to have authorised company fulfil requirements regarding periodic maintenance checks.
Since dust is extracted from the inside, the resistance on the ue side, through the boiler, will increase, leading to a decrease in the heat load (and, consequentially, in the power). Prior to cleaning, check the heat load and the percentage of CO2. If the measured load (with a correct CO2 level) is within 5% of the value indicated in parag. 3.18, the boiler does not need to be cleaned. e operation must therefore be limited to cleaning the trap.
ATTENTION!
A drop in the heat load can be caused by an obstruction in the exhaust channel or air intake pipe. First of all make sure that this is not the cause.
If there is a drop in the heat load greater than 5%, check how clean the burner condensate-collection pan is. Also clean the trap.
First phase – Disassembly.
- Shut o the electrical and gas supplies making sure the valve is rmly
shut.
Inspections and maintenance
- Take out: all of the casings and act on the two closing hinges to take o the cover.
- Take out the rear casing clamping screw on the right and le side.
- Take out the side clamping screws (right/le side).
- Take out the closing plate clamping screws (ue exhaust output side) and take o the casing.
45
Page 46
Inspections and maintenance
- Unhook the fan chamber clamping spring (right/le side).
- Take out the red silicone pipes and then the fan chamber.
Cabling
- Take out the gas valve connector.
- Take out the fan connector.
- Unhook the cable clamps at the top of the boiler (DO NOT CUT).
46
Page 47
Element screws.
Inspections and maintenance
B
B
A
- Take out screws "A" from each element (with 13 mm socket key).
- Take out screws "B" (with 13 mm socket key / with 13 mm hex key) and take out the clamping plates.
- Take out the gas pipe clamping screws (right and le side).
- Take out the four screws, followed by the gas ange, using a 10 mm socket key.
47
Page 48
Inspections and maintenance
- Li the rear burner block slightly and take out 2 pins with a 4 mm hex key, until you reach holes "C".
- Place the pins in holes "D" to support the burner block.
- Li the burner block (front part).
48
Page 49
Aria compressa
Inspections and maintenance
Second phase – Cleaning.
- Take out the gaskets and burners.
- Dry clean the burners using compressed air and operating from the "ame side".
- Visually check the state of the welding on the angulars and burner mesh.
The burner gaskets must be replaced every time cleaning operations are carried out.
- Wash the combustion chamber with water being careful not to get the electrical cables wet.
- During this operation is necessary to make sure that the condensate exhaust pipe is always unobstructed so that the wash water does not leak out from the inspection opening.
- Blow the combustion chamber with compressed air to remove any dirt that is still attached to the studs.
- When the elements have been washed make sure that the condensate drain trap is unobstructed: clean if necessary.
- Inspect the exhaust evacuation pipe and the ue.
ird phase - Reassembly.
- Once the body and/or burners have been cleaned, put the burners back in their places.
- Put the new graphite gaskets in place.
Proceed in the reverse order for reassembly, being careful to tighten the screws that clamp the mixer unit/fans to the body, at a torque of 13 Nm.
ATTENTION IT IS NECESSARY TO CHANGE THE SEALING GASKETS ON EACH BURNER AT EVERY MAINTENANCE OPERATION.
- Prior to ignition, make sure the condensate drain trap is full of water.
- Before opening the gas supply valve make sure that the previously loosened gas tting is rmly tightened. In order to do so open the valve and check the seal using soapy water.
-As a burner is being ignited, immediately check the seal between each single gas valve and relative premixing chamber.
- Perform a combustion analysis and check the parameters.
- Make sure that all of the previously opened gas pressure points are closed.
Compressed air
49
Page 50
Inspections and maintenance
4.2 PROGRAMMING THE OPERATION PARAMETERS
ATTENTION! Function reserved exclusively to Authorised Service Centres.
1 - SELECTION
3 - Device management SELECTION
Select with knob ‘‘C’’ and press key ‘‘A’’ in order to access the tech­nical programming area of each device (you must enter password 0000).
4 - SELECTION
Use knob ‘‘C’’ to select the symbol . Press ‘‘A’’. Wait for scanning.
2 - Device management SELECTION
e display shows the status and the active sections of the system: ( - = inactive / 1 active)
• HCM (BCM cascade controller)
• SHC (multifunction module) optional
• BMM (burner management board)
Select the module using knob ‘‘C’’ and conrm by pressing ‘‘A’ ’.
Select the parameter using knob ‘‘C’’. Press ‘‘A’’ (selec).
5 - MODIFICATION
Rotate knob ‘‘C’’ to edit the value. Press ‘‘A’’ (save).
50
Page 51
Inspections and maintenance
4.3 BMM. PARAMETERS
BMM parameters - ARES TEC 150 - 200 - 250 - 300 - 350
Code Symb. Description Unit Min Max Factory settings
31 HL CH#1: Minimum Setpoint °C 20 45 30
39 HH CH#1: Maximum Setpoint °C 50 90 95 322 Po Pump Post-circulation min. 0 10 5 309 St Application Code 0 619 IG Ignition Modulation % 0 100 80 314 Sb Standby Modulation % 0 100 26 319 FH Maximum Modulation % 0 346 FL Minimum Modulation % 0 488 Fb Fan 1 20 50 527 PU Fan: Pul./Rev 2 3 2
2590 bC Burner Power kW 1 1000 50
483 rP Gen: Temp. Max Dierential °C 0 50 30 622 FS Minimum Flow Sensor 0 1 1
34 HY Burner Hysteresis °C 5 20 5 336 Hs Temperature Gradient °C/min 1 30 10 353 Hp CH temperatures: Reg. Proportional % 0 50 25 354 HI CH temperatures: Reg. Integrative % 0 50 12 478 Hd CH temperatures: Reg. Derivative % 0 50 0 486 FP Fan speed: Reg. Proportional % 0 50 4 487 FI Fan speed: Reg. Integrative % 0 50 8 337 Fr Modulation gradient rpm 0 526 FM Fan: Absolute max speed giri/sec 50 120 100 777 AFC Burner air ow control 0 1 0 793 COC Chimney Obstruction Sens.: Enabled / Disabled 0 1 1 768 LG Min. Gas Pressure Sens. 0 1 0
100 100
30000
98 22
5280
51
Page 52
Inspections and maintenance
4.4 BCM. PARAMETERS
BCM parameters - ARES TEC 150 - 200 - 250 - 300 - 350
Code Symb. Description Unit Min Max Factory settings
803 Srv Services Enabled 16 27 19 483 rP Gen: Temp. Max Dierential °K 0,0 50,0 25
34 HY Burner Hysteresis °K 5,0 20,0 5,0
31 HL CH#1: Minimum Setpoint °C 20,0 40,0 35,0
39 HH CH#1: Maximum Setpoint °C 45,0 85,0 85,0 799 AC Input 0/10V 0 3 1 376 DI1 Programmable Input #1 0 2 3 322 Po Pump Post-circulation min. 1 10 5 341 PL Pump Minimum Control V 0 10 3 313 Pr Pump Maximum Control V 0 10 10 792 CHP CH: Max Modulation % 0 100 100 611 POT Gen: Err. Max. Parallel °K 0 30 5 612 POL Gen: Mod. Max. Parallel % 0 100 0 650 dL DHW: Minimum Setpoint °C 25,0 45,0 35,0 385 dH DHW: Maximum Setpoint 50,0 65,0 65,0 360 dt Storage tank adjustment 0 15 0 656 drT DHW: Temp. Request Dierential °K -20 20 4 657 drH DHW: Request Temp. Hysteresis °K 1 20 8 310 DpT DHW Pump: Postcirc. sec. 5 600 60 660 dbT DHW: Temp. Boiler Maximum °C 50,0 85,0 75,0
48 ChSet CH#1: Setpoint °C 20,0
64 ChPO1 CH#1: Parallel Supply 0 1 0 346 FL Minimum Modulation % 0 600 mB Burners: Min. Inserted 1 8 1 616 BSt Gen: Insertion Time sec. 30 900 120 613 BRt Gen: Removal Time sec. 30 900 120 336 HS Temperature Gradient °C/min 1 30 5 353 HP CH PID: Proportional °K 0 50 25 354 HI CH PID: Integrative °K 0 50 12 478 Hd CH PID: Derivative °K 0 50 0 816 MI ModBus Address 1 127 1 817 MT Timeout Modbus sec. 0 240 30 896 TU °Fahrenheit 0 1 0 309 St Application Code 0 1 0 368 VA1 Programmable Relay #1 0 1 0 369 VA2 Programmable Relay #2 0 1 1 771 PS Water Pressure Sensor 0 1 0 768 LG Min. Gas Pressure Sens. 0 1 0 793 COC Chimney Obstruction Sens. 0 2 0 622 FS Minimum Flow Sensor 0 1 0
85,0
100,0
85,0
25,0
52
Page 53
4.5 ERROR CODE
Inspections and maintenance
When the boiler detects a fault, the alarm symbol is displayed on the screen together with the relative error code and description.
CODE DESCRIPTION obtained from BMM REMEDIES
01
04
05
06
10
11
12
14
15
SAFETY THERMOSTAT
Safety thermostat intervention
BLOCK
No gas or burner ignition failure
NO FLAME DURING OPERATION.
HIGH TEMPERATURE
Boiler temperature too high
INTERNAL FAULT
Flame detection before ignition (parasite ame)
CENTRAL HEATING SENSOR
Central heating sensor fault
RETURN PROBE (if applicable) Sensor (SRR)
INSUFFICIENT WATER CIRCULATION
Insucient primary circuit water circulation (∆t > 40° C)
Press the release button on the panel and/or check if the thermostat and its connec­tions are not disconnected. Make sure the INTC switches are closed (position 1)
Check gas supply or correct operation of the detection/ignition electrode(4-5).
Check detection electrode
Check pump operation and, if necessary, clean the heat exchanger (9 )
Check eciency of the sensor (see Res/Temp table) (Par. 4) or its connections.
Check the wiring; if necessary, replace the sensor (15)
Check pump operation and its speed - remove any obstructions in the central heating system
It is possible to reset the boiler by pressing “A” from HSCP or RESET from BCM
( Num ) = see key Par. 2.2
16
20
24
HEAT EXCHANGER FREEZING ( 9 )
Heat exchanger freezing detection. If the cen­tral heating sensor detects temperature below 2° C, burner ignition is prevented until the sensor detects temperature above 5°C.
PARASITE FLAME
Flame detected aer the burner is switched o
SPEED OUT OF CONTROL
Fan speed alteration; the speed is not reached.
Disconnect electric power supply, close the gas cock, and carefully defrost the heat exchanger.
Check the wiring and any leaks from the gas valve (2), replace the Gas valve if necessary
Check operation of the fan (18) and the connections
53
Page 54
Inspections and maintenance
SPEED OUT OF CONTROL
26
28
29
30
32
Fan speed alteration; the speed is higher than what is requested.
CLOGGED DRAINS Stop
WATER IN THE COMBUSTION CHAM BER
Stop
DEFAULT PARAMETERS Alteration of default settings or any electro­magnetic interferences.
Line voltage below 80% of the nominal value. Wait for the line’s voltage to reach > 85% of the nominal value.
Check operation of the fan (18) and the connections
Check Chimneys / Check Drain Trap.
Check the combustion chamber / check the drain trap.
Press the release key, if the fault persists, replace the board
Correction: if the line voltage < 190Vac: the line’s voltage is way below the mini­mum limit, otherwise line errors of the monitor: replace BMM
40
CODE
17
18
19
37
38
56
57
58
93
e error codes are displayed in the info row of the remote panel and also remain if the fault was temporary. erefore, you must always reset to eliminate the “Alarm” from the display.
FL INTERVENTION insufficient water circulation Stop
DESCRIPTION obtained from HCM
(BCM)
HEAT EXCHANGER FREEZING ( 9 ) stop eect
MAXIMUM PROTECTION ∆T FLOW RETURN
stop eect FLOW OVERHEATING.
It is activated when the ow temperature is > 95. It is automatically restored when the temperature is < 80.
Eect: Stop burner, Pump on DEFECTIVE PARAMETERS
MEMORY Flame Block
DEFAULT PARAMETERS CORRUPTED by electromagnetic interferences stop
REMOTE CONTROL WAS NOT DE TECTED Flame Block
BMM BOARD NOT DETECTED stop
FLOW SENSOR Stop
ISPESL SAFETY INTERVENTION Stop
Water circulation control
REMEDIES
Try to Reset for the system to automatically activate the antifreeze function and thus may only be a warning.
Circulation control, check installation (Only with return probe installed).
Circulation control.
Contact support service.
Contact support service.
Check electrical connections e-BUS1
Check electrical connections BMM e-BUS1
Connect a new sensor if the code disappears, replace the sensor or check the electrical connections
Check the safety devices, manual reset aer releasing single safety devices
54
Page 55
55
Page 56
immergas.com
Immergas S.p.A. 42041 Brescello (RE) - Italy Tel. 0522.689011 Fax 0522.680617
Certied company ISO 9001
is instruction booklet is made of ecological paper Cod. 1.042909ENG - rev. ST.003938/000 - 12/18 - Inglese per IRLANDA (IE)
Loading...