iLumin SC-UN Technical Data

Technical Data
iLumin
INS #
SC-UN – Universal Source Controllers
Catalog# Prepared by
Project Date
Comments Type
Overview
The Universal Source Controller line of lighting control panels set a new standard in architectural lighting control. Each Source Controller contains individual control cards that are the industry’s only “true universal” by controlling most load types without interface or multiple cards. In addition, each panel has onboard Ethernet, A/V interface, Contact Closure, DMX input, voltage sensing, real-time individual circuit power metering, and Phase Sense™ technology designed to ensure control even during individual phase failure.
Features
6, 12, and 24 circuit variants
Forward Phase triac slow rise-time dimmer engine. Capable of withstanding repetitive inrush current of 50 times operating current without impacting lifetime of dimmer or relay.
Positive air-gap off per circuit
Single or three phase versions
Continuous duty, thermal magnetic SWD rated breakers for each circuit
Bypass per circuit for manual override and providing construction site lighting
Voltage and frequency compensation to maintain light level during supply fluctuations
Real-time power metering for each circuit, phase, and the total panel
Live feed per circuit, via breaker, for emergency lighting connection
7.6in.
(193 mm)
27.8 in.
(707 mm)
56.7in. (1440 mm)
7.6 in.
(193 mm)
20.3 in.
(517 mm)
56.7in. (1440mm)
7.6in.
(193 mm)
20.3 in.
(517 mm)
37.2 in. (945 mm)
6 Channel
6 Circuit
12 Circuit
24 Circuit
7.6in.
(193 mm)
27.8 in.
(707 mm)
56.7in. (1440 mm)
18 & 24 Channel
24 Circuit
July 2015
SC-UN – Universal Source Controllers
Specifications
Mechanical No regular maintenance requirements due
to natural convection cooling, i.e. no fans or filters
Single circuit dimmer card
Wall mounted design
Programming An LCD graphical user interface and keypad
for ease of programming and configuration. The interface can be used for programming single area systems there is no need to use a PC. The GUI also allows programming of the astronomical timeclock.
Interfacing All SC-UN Source Controllers have RS485
and Ethernet over UDP connections to allow for control by third party systems (Building Management System, Audio/Visual, etc.) through the use of open protocol ASCII message commands
Two contact closure inputs for integration with auxiliary equipment and emergency lighting input
DMX512 input for control by entertainment systems
Power metering information is available via Ethernet over UDP through the use of open protocol ASCII message commands
Standards
Dimensions
(Inches/mm)
Load Types
Incandescent
Magnetic and Forward Phase electronic low voltage - Factory Approved Transformer only.
Neon / cold cathode
Non-dim (switched)
Analog fluorescent ballast control
− 2-wire fluorescent loads
− 3-wire fluorescent loads (Lutron ECO-10 and Hi-Lume)
− 4-wire fluorescent loads, 0-10 VDC Isolated (40 µA max per circuit leakage to line)
Each 0-10V output supports up to 50 ballasts/drivers that draw the standard 2mA each