57
Electrical Characteristics
Nominal Short Circuit
UL Voltage
Catalog Per Mode AC Nominal Discharge Current Rating
Protection Rating (VPR)
Conduit
Number Phase System Surge Current Frequency Voltage Current (SCCR) L-L L-N L-G N-G Size (in.)
XE-050-1P1X-* 1 SINGLE 50 kA 50/60 Hz 100~140 V 20 kA 200 kA - 700 700 700 3/4
XE-100-1P1X-* 1 SINGLE 100 kA 50/60 Hz 100~140 V 20 kA 200 kA - 700 700 700 3/4
XE-050-1P2X-* 1 SINGLE 50 kA 50/60 Hz 220~280 V 20 kA 200 kA - 1200 1200 1200 3/4
XE-100-1P2X-* 1 SINGLE 100 kA 50/60 Hz 220~280 V 20 kA 200 kA - 1200 1200 1200 3/4
XE-050-1S1X-* 1 SPLIT 50 kA 50/60 Hz 120/240 V 20 kA 200 kA 1200 700 700 700 3/4
XE-100-1S1X-* 1 SPLIT 100 kA 50/60 Hz 120/240 V 20 kA 200 kA 1200 700 700 700 3/4
XE-050-3Y1X-* 3 WYE 50 kA 50/60 Hz 208Y/120 V 20 kA 200 kA 1200 700 700 700 3/4
XE-100-3Y1X-* 3 WYE 100 kA 50/60 Hz 208Y/120 V 20 kA 200 kA 1200 700 700 700 3/4
XE-050-3Y2X-* 3 WYE 50 kA 50/60 Hz 480Y/277 V 20 kA 200 kA 2500 1200 1200 1200 3/4
XE-100-3Y2X-* 3 WYE 100 kA 50/60 Hz 480Y/277 V 20 kA 200 kA 2500 1200 1200 1200 3/4
XE-050-3D1X-* 3 HI-LEG DELTA 50 kA 50/60 Hz 240D/120 V 20 kA 200 kA 1200/2000 800/1200 700/1200 700 3/4
XE-100-3D1X-* 3 HI-LEG DELTA 100 kA 50/60 Hz 240D/120 V 20 kA 200 kA 1200/2000 800/1200 700/1200 700 3/4
XE-050-3N4X-* 3 DELTA 50 kA 50/60 Hz 480 V 20 kA 200 kA 2000 - 1800 - 3/4
XE-100-3N4X-* 3 DELTA 100 kA 50/60 Hz 480 V 20 kA 200 kA 2000 - 1800 - 3/4
Surge Protective Device - Type 2
Series XE - Commercial & Industrial
TYPE
SPD
Features
•
Commercial & industrial surge protection,
up to 7 protection modes
•
Compact NEMA polycarbonate enclosure
•
Indicator LED, blue for proper operational status, red
to replace, optional audible alarm and relay contacts
•
Surge current strength up to 100 kA
•
UL 1283 electrical noise filter
•
UL 1449 Listed with advanced safety features
•
Ten year warranty
Benefits
•
Protects equipment downstream of electrical service entrance
•
Mounted outdoors or indoors external or internal to any electrical
panel, non-submersible
•
Easy monitoring of surge protection status
•
Withstands severe lightning strikes, 100 kA unit provides
extended service life
•
Protects critical commercial and industrial equipment
•
Product longevity in the most demanding environments
Tested and Certified:
Type 2 SPDs (filter) = UL 1449, UL 1283, CSA C22.2 No. 269.2-13, CSA C22.2 No. 8-13
Operating temperature range -40 to +150˚ F
Enclosure is rated to NEMA/UL Type 1, 2, 3, 3R, 3X, 4 and 4X
Type 2 = Permanently connected SPDs intended for installation on the load side of the
service equipment overcurrent device; including SPDs located at the branch panel
Add on option code to catalog number
*Indicates Package and option code- C or D
‡ Advanced UL 1283 rated electrical noise filter
Electrical
Option UL/CSA Indicator Audible Dry Relay Noise
Code Type LED Alarm Contact Filter‡
C 2
••
D 2
••• •
Lead wire size: 10 AWG