37
Catalog Figure Ground Wire Dimensions - in. (mm)
Number Number Range L W H Hex Size
SGB-4+ 1 4 sol/str-14 sol/str 1.375 (34.9) 0.500 (12.7) 0.941 (23.9) 7/16
SGB-5+ 2 4 sol/str-14 sol/str 1.375 (34.9) 0.500 (12.7) 1.440 (36.6) 7/16
SGB-1/0 3 1/0 sol/str-14 sol/str 1.508 (38.3) 0.625 (15.9) 1.241 (31.5) 3/16
SGB-250 4 250kcmil-6 1.810 (46.0) 0.750 (19.1) 1.703 (43.3) 3/16
Dual Rated Lay-In Ground Lug
TYPE
SGB
Features
•
Manufactured from high strength 6061-T6 aluminum
alloy
•
Electro-tin plated
•
Lay-in feature
•
Exclusive Viritium®plating
•
Green color universal to identify ground
•
Serrations in conductor wire way
•
Unique clamp design
•
1/4” max frame thickness (SGB-4, SGB-5)
•
Meets ASTM B117-09
Benefits
•
Suitable for use with copper or aluminum
conductors
•
Provides low contact resistance
•
Provides ease of installation
•
Resists galvanic corrosion
•
Aids visual inspection
•
Cuts oxidation
•
No mounting hardware required, reusable
•
Mount to solar panel frames
•
Resistance to outdoor salt spray
All wire sizes, unless noted otherwise, are American Wire Gauge (AWG)
UL 467 for grounding and bonding. UL File E34440
+ UL2703 Recognized E354420 Vol. 1
DE-OX
®
oxide inhibitor is recommended for all aluminum terminations
Patented