iLight SCI0405, SCI0410, SCI1205, SCI1210, SCI1220 Instruction Manual

Contents
2 Warning 3 Installation 5 Supply and load connections 7 iCAN Network 8 ASCII control messages 9 Typical system schematics 10 Service switches and LEDs 12 Specifications
- Inductive
- H F Ballast
- Power Switching
- Adaptive
- Trailing Edge
Instruction Manual
Read this document prior to installation
Source Controllers
INTELLIGENT CON TROLS
2 of 23
INTELLIGENT CON TROLS
Where?
Source Controllers (Racks) should be located in a ventilated dry location where the ambient temperature is within the operating range of the controller. When choosing the installation location take the following into account:
l  Depending on the size of the loads connected
to an Inductive or Adaptive Source Controller it will get warm. Adequate ventilation should be provided to ensure the ambient temperature does not rise above 40oC.
l  Allow adequate space for future maintenance
of the unit. Do not install in a location that will later be inaccessible.
l  Instal only on a vertical surface. l  Depending on Source Controller type and
the loads connected, Source Controllers can create noise. This is caused by electrical noise suppression components within the unit. The noise is a low level buzz that varies with the level of dimming. If noise of this type causes a problem, locate the Source Controller elsewhere.
Source Controllers require ventilation and have slots on all sides to allow for a convection flow of air through the unit. For this reason it is important to orientate the unit correctly and allow a minimum space between adjacent Source Controllers and other surfaces. A minimum of 100mm of free space should be left either side of a Source Controller or between adjacent Controllers.
IMPORTANT NOTE
Mounting the Source Controller in the wrong orientation, without proper ventilation or with inadequate airflow could result in overheating.
3 of 23
Installation Instructions
If a Source Controller is connecting to trunking of depth 50mm or less, then it may be coupled directly as shown below.
Leave 100mm of free space between other equipment, walls etc. either side
of the equipment.
If the trunking depth is greater than 50mm, installation of Source Controllers should be as shown below.
Typical installation for trunking less than 50mm depth. Source Controller connected directly to
trunking.
Typical installation where trunking depth is greater than 50mm. Controller connected to trunking using conduit couplers.
INTELLIGENT CON TROLS
4 of 23
Installation Instructions
Simply calculate the load for each channel, add all the loads together and this will be the size of the supply you require. Always calculate the supply assuming all channels working at full output simultaneously.
For a Source Controller being fed from a 3-Phase supply, calculate the load on each phase and fit externally to the Controller, a suitably rated 3-pole circuit breaker. Do not apply power until you are certain that a good Neutral connection is present at the Source Controller.
Sample supply requirement calculations:
Example 1 - Resistive loads connected to a 4 channel 5A Inductive Source Controller. (SCI0405S)
Channel 1 load is 300Watts Channel 2 load is 150Watts Channel 3 load is 1000Watts Channel 4 load is 500Watts Total connected load = 1950Watts
(All loads in this example are resistive or have unity power factor).
For the this example the minimum size of the supply required is: 1950W/230V = 8.5Amps
Therefore, the unit should be fed with a supply of at least 10Amps.
As the individual load channels are protected by 5Amp MCB’s a supply capable of delivering more than 10Amps could be used, but it is recommended that it should not exceed the rating shown on the label fitted inside the door.
Example 2 - Fluorescent lamps with dimmable HF ballasts connected to a 4 channel 10A High Frequency Ballast Source Controller. (SCH0410S)
Channel 1 load is 8 x 58 Watt tubes Channel 2 load is 16 x18 Watt tubes Channel 3 load is 10 x 26 Watt PL lamps Channel 4 load is 5 x 36 Watt tubes
Total connected load = 1192Watts
(All loads in this example have unity power factor).
For this example the minimum size of supply required is: 1192W / 230V = 5.18 Amps
Therefore the unit should be fed with at least 6 Amps supply.
How?
Remove the unit cover to gain access to the fixing holes.
Four screws hold on the cover of the Source Controller; two are visible from the front and two are visible only when the MCB cover door is opened. There is no need to remove the MCB door.
Four fixings holes are provided allowing for fixings up to 6mm diameter.
4 Channel version shown (SCI0405S)
Supply and Load Connections
Size of supply
The size of the supply required to the Source Controller is dependent on the power requirements of the loads connected to it.
(inside door)
(inside door)
INTELLIGENT CON TROLS
5 of 23
The diagram above shows the power supply connections to a single phase Source Controller. The Live supply is connected directly to one of the channel MCBs or Mains Isolator if fitted. These are factory fitted with a busbar linking them together. Do not remove the busbar or any other cables already connected to the MCBs or Isolator. The maximum supply cable size is 16mm2.
The Neutral supply cable is connected to the neutral busbar terminal (except in the case of a Source Controller fitted with Neutral disconnect circuit breakers, where connection is to the neutral busbar fitted to circuit breakers).
An earth connection must be made to the chassis, using the Earth stud. It is important that all supply and neutral connections are tight. There is also a diagram on the cover of the unit showing the connections.
Supply & Load Cable Terminations
Connections to 3-Phase units are similar, except that live connections must be made to three sequential MCB’s. For example RED to MCB 1; YELLOW to MCB 2; BLUE to MCB 3. The MCBs are fitted on the supply side with a 3-phase busbar which distributes the incoming supply sequentially to all twelve breakers.
Load Cable Terminations
Load cables are connected to the column of terminal blocks located on the left hand side of a Source Controller. These terminals are labelled L1,E, N1 L2,E, etc… and will accept up to 6mm
2
cables.
It is important that each load circuit neutral is connected to the appropriate neutral terminal within the Source Controller. Failure to observe this could result in electrical interference affecting other equipment. Do not use a common neutral for multiple loads.
The Load terminals of 3 phase units are phase sequential as follows: L1 Phase 1 (R) L2 Phase 2 (Y) L3 Phase 3 (B) L4 Phase 1 (R) L5 Phase 2 (Y) L6 Phase 3 (B) . . . L11 Phase 2 (Y) L12 Phase 3 (B)
Note Adaptive dimmers (Source Controllers with
prefix SCA.....) are shipped in Switch mode,
and will be set (according to type of connected load) by the commissioning engineer. Please retain all information concerning the type of load transformers that are installed (for each dimmer channel), so as to assist this process.
WARNING: Meggers must not be used on any circuitry that is connected to iLight equipment. To avoid damage, load cables must be disconnected prior to any such testing.
HF Ballast Controllers - Connection of low voltage cables
(Applies only to Source Controllers with prefix SCH...) For each individual load circuit, there should be a pair of cables linking all ballast LV connections together (paying due attention to polarity), and terminating at the relevant connections in the Source Controller.
4 Channel inductive version shown
IMPORTANT:
Ensure that load cables are connected to the relevant type of Source Controller in accordance with iLight
project drawing (normally supplied with quotation). For example:
Source Controllers with part no. SCI..... are dimmers,
eg for tungsten or inductive loads.
Source Controllers with part no. SCI08..... are dual
units, incorporating four dimmers (O/P’s 1 to 4) and four O/P’s (5 to 8) with corresponding 0-10v (or DSI) connections for HF Ballasts.
Source Controllers with part no. SCH..... are HF
ballast controllers, eg for 0-10v fluorescent fittings.
Source Controllers with part no. SCS..... are switching
units, eg for non-dimmable luminaires.
Source Controllers with part no. SCA..... are adaptive
dimmers - eg where there is a mixture of inductive and capacitive loads.
Source Controllers with part no. SCT..... are trailing
edge dimmers - eg where “trailing edge” dimming is required on some circuits.
Supply Cable Terminations
INTELLIGENT CON TROLS
Networks and Connecting Control Cables
Network control cables should enter the Source Controller through the segregated route shown in the diagram below (A).
Ensure the CAT5 data cable is linked into all Source Controllers in this manner.
Segregation between Control Data cabling and power wiring should be maintained for safety and noise immunity. Control Data cabling should be run in separate or divided metal trunking or conduits. Where cables are run outside trunking or conduit then there should be 300mm separation between them, and where they cross they should do so at right angles.
Terminals for network and RS485 connections use two-part connectors allowing connections to be made outside of the Source Controller. Simply pull the connectors from the board
A Source controller is connected to other devices, control panels, Source Controllers, audio-visual systems and interfaces using the iCAN network or a RS485 data connection. The RS485 data connection is designed for use primarily with external systems and does not offer the full functionality and integrity that use of the iCAN network can provide. All other iLight products communicate with each other using the iCAN network. At no point should the RS485 and iCAN networks be joined together.
Ensure each low voltage pair is terminated at the connection corresponding to the associated mains pair - for example all ballasts which are fed with 230 volts from MCB 2 must have their low voltage cable terminated at 0V and DIM2.
If there is any doubt concerning which cable carries mains, this must be resolved (using a voltmeter) before connecting to the Source Controller. Connecting a mains potential cable to the Low Voltage terminals will damage the unit and invalidate warranty.
HF Ballast types:
The Source Controller is able to control either Analogue or DSI (digital) ballasts, with each channel individually configurable. This selection is normally made as part of commissioning, but it is also possible to “group configure” all outputs to one or other of the two standards. Source Controllers are ex-factory shipped set for Analogue ballasts. The procedure to alter this to DSI (for all channels) is:
Isolate the Source Controller. Locate the 3-way DIPswitches on the processor pcb. Move switch 1 to the ON position. Return power to the Source Controller. (to return to Analogue, reverse the above process)
Emergency Luminaires
Any luminaries that require a Permanent Live feed must be wired with an additional (identified) live cable, fed from the right-hand (protected) side of the relevant MCB. Install your Permanent Live cable together with the existing brown cable. Use only the MCB which relates to the circuit in question.
Additional Lighting Connections
Diagram shows typical connection of emergency lighting circuit and the entry point of the network control cable (A).
Note
Control and network cables do not include the 0-10V or DSI control cables that are connected to controllable ballasts. The control cables to ballasts should be regarded as power cables and segregated from the CAN and RS485 cables that connect to the source controller.
6 of 23
Permanent Live
INTELLIGENT CON TROLS
Two sets of terminals are provided for the connection of iCANnet cables. Both iCAN terminals on the control board are connected in parallel.
The recommended cable to use for iCANnet is: CAT5 FTP such as RS part numbers 196-331 for 305m or 298-0885 for 1000m.
The Control Board paralleled iCANnet terminals are labelled with the recommended colours of the pairs in CAT5 cable to use. Orange pair +12V Blue/White CAN-H Blue CAN-L Green pair 0V Brown pair Shield
The structure of an iCAN network is shown in the diagram below.
In the above example, resistors should be fitted at the two ends of the network as marked with asterisks(*). The devices on an iCAN network may be wired in any order, but the network must be one continuous “daisy-chain”. Spurs are NOT permitted, as this is liable to result in communication problems.
Source Controllers and Control Panels are all shipped with a 120 ohm Termination resistor fitted on the iCANnet termination block. At all locations other than the two end-of-line positions, the resistors should be removed. Except where isolating Bridge Nodes are installed, every iCAN network requires two Termination resistors only.
iCANnet Connections
RS485 Control
The RS485 Control terminals are located adjacent to the iCAN network terminals.
The terminals to be used are labelled: RS485­ RS485+ 0V See the ASCII control message section on page 13.
RJ12 Connector
The Source Controller is fitted with an RJ12 socket to allow local connection of a handheld programmer or PC interface.
No connection should be made to the factory pins of the connector.
Alarm Input
An alarm input, designed for connection to a fire alarm system, is available on the same terminal block as the RS485 connections. The terminals to be used for an Alarm input are: 0V AL Any connection to this input MUST be volt free and have a cable length of less than 50 metres. Cabling for this input should be segregated from power wiring.
The default action that occurs when these terminals are linked is for every channel of the source controller to turn on to maximum output. It will then remain in this state, regardless of any other command received, until the link between the 0V and AL terminals is removed. Only when the alarm link is removed can levels be changed.
On an entire iCAN network only one fire alarm input is required.
7 of 23
INTELLIGENT CON TROLS
ASCII Control Messages
8 of 23
ASCII Control Messages provide a simple method of control for AV systems. This is done by sending a string of ASCII characters via the in-built RS485 serial port in the Source Controllers. The command is not case sensitive.
1.1 Message Syntax
The general form of the message is:
1.1.1 Start Character
Each message starts with the @ character The command is started receiving the @ character. If a command is incomplete when a new @ is received, the old command is discarded.
1.1.2 Command
The start character is followed by a two character command. Example: SS (select scene)
1.1.3 Parameters
After the command characters several characters define the parameters, such as the scene number, area number, and fade time. A colon delimits the values. If a colon is received after only 1 digit then a single digit value is assumed. <O: P</O:P
1.1.4 End Character
The command is ended with a carriage return, <cr> (13 dec). The # character can also be used.
1.3 Virtual Control Messages
Virtual control messages are used to control the system, and not individual devices. The message is transmitted across the iCANnet network to all other devices.
1.3.1 Command SS Select Scene
This message selects a scene in an area. The syntax is: @SSxx:Axx:Fxx<cr> SSxx defines the scene number, where xx is valid from 00 to 99. Scene 00 is OFF. Axx defines the Area Number, valid for 00 to 99. Fxx defines the Fade Time , valid for 00 to 99 for seconds.
1.3.2 Command SA Save Scene
This message saves the current levels to a scene in an area. The syntax is: @SAxx:Axx<cr> SAxx defines the scene number, where xx is valid from 00 to 99. Scene 00 saves to the current scene. Axx defines the Area Number, valid for 00 to 99.
1.3.3 Command RS Request Current Scene
This message requests the current scene number in an area. The syntax is: @RSxx<cr> RSxx defines the Area Number, valid for 01 to 99.
1.3.4 Command RE Report Current Scene
This message reports the current scene number in an area. The syntax is: @RExx:Axx<cr> RExx defines the Scene Number, valid for 01 to 99. Axx defines the Area Number, valid for 01 to 99.
1.3.5 Command SC Set Channel Level
This message sets the level of a channel in an area. The syntax is: @SCxx:Axx:Lxx:Fxx<cr> SCxx defines the channel number, where xx is valid from 00 to 99. Channel 00 affect ALL channels in an area. Axx defines the Area Number, valid for 00 to 99. Lxx defines the Level, valid for 00 to 99 in %, and FF for FULL (100%) Fxx defines the Fade Time , valid for 00 to 99 for seconds.
1.3.6 Command RC Request Channel Level
This message request the level of a channel in an area. The syntax is: @RCxx:Axx<cr> RCxx defines the channel number, where xx is valid from 00 to 99. Channel 00 requests ALL channels in an area. (use with caution). Axx defines the Area Number, valid for 00 to 99.
1.3.7 Command RL Report Channel Level
This message reports the current level of a channel in an area. The syntax is: @RLxx:Axx:Lxx<cr> RLxx defines the Channel Number, valid for 01 to
99. Axx defines the Area Number, valid for 00 to 99. Lxx defines the Level, valid for 00 to 99 in %, and FF for FULL (100%)
1.3.8 Command CR Raise
This message increments the area by 1% level The syntax is: @CRxx:Axx <cr> CRxx defines the channel number, where xx is valid from 00 to 99. Channel 00 affect ALL channels in an area. Axx defines the Area Number, valid for 00 to 99.
1.3.9 Command CL Lower
This message decrements the area by 1% level The syntax is: @CLxx:Axx <cr> CLxx defines the channel number, where xx is valid from 00 to 99. Channel 00 affect ALL channels in an area. Axx defines the Area Number, valid for 00 to 99.
1.3.10 Command SF Stop Fade
This message stops fading in an area The syntax is: @SFxx:Axx <cr> SFxx defines the channel number, where xx is valid from 00 to 99. Channel 00 affect ALL channels in an area. Axx defines the Area Number, valid for 00 to 99.
1.3.11 Command TC Toggle Channel
This message toggles a channel state. The syntax is: @TCxx:Axx:Lxx:Fxx<cr> TCxx defines the channel number, where xx is valid from 00 to 99. Channel 00 affect ALL channels in an area. Axx defines the Area Number, valid for 00 to 99. Lxx defines the Level, valid for 00 to 99 in %, and FF for FULL (100%) Fxx defines the Fade Time , valid for 00 to 99 for seconds.
INTELLIGENT CON TROLS
Typical System Schematic
9 of 23
Commissioning
Please retain any Job-specific drawings or schedules relating to load connections at the Source Controllers. This information is required by the commissioning engineer to assist in configuration of the equipment.
When first energised after installation all Source Controllers will default to all channels being at 100% output.
Source Controllers can be energised without network cables being terminated.
If iCANnet cables are terminated after Source Controllers have been energised it should be noted that cables will be carrying low voltage signals and mis-connection of these could result in damage to other devices on the network.
Factory Set Source Controller Settings
All channels set to Area 1 Physical Channel No = Virtual Channel No Power Up Scene = Last Scene Selected (From factory last scene selected will be Scene 1 - all channels at 100%. Alarm Input set to operate with contact closing AL terminal to 0V.
Factory Set Scenes
Scene Level 1 100% 2 70% 3 50% 4 30% 5 80% 6 60% 7 40% 8 20%
INTELLIGENT CON TROLS
Service Switches and LEDs
10 of 23
These switches and LEDs are located at the base of the unit. The two service switches on the source controllers are used for the following:
l  Entering Diagnostic Mode. l  Putting the Source Controller in override
mode.
l  Sending a message to identify the device on
the network.
Sending a message to identify the device on the network. The LEDs indicate the following:
l  Normal operation. l  Message transmission and receipt. l  Override status
ICANnet error status will occur when a Source Controller is not connected to an iCAN network for any reason. Once either connected to a network of one or more other devices which are powered the error status will be removed. It is still possible to enter Diagnostic mode if a Source Controller is in iCANnet error status.
INTELLIGENT CON TROLS
General Specifications
11 of 23
INTELLIGENT CON TROLS
General Specifications
12 of 23
Key Features
l 128 scene memory. l Multiple choice of circuit protection. l Security door for MCB’s (where fitted). l Fail to full safety feature. l iCANnet™ inputs (10,000 node enabled). l Audio Visual port (RS485). l Alarm input. l CE mark compliant for all relevant standards. l Future proof with FLASH memory. l Designed and manufactured to ISO9000 standards. l Emergency Lighting Terminals.
Mechanical Data
Climate Range
l Temperature: - 20ºC to +40ºC. l Humidity: +5 to 95 % non-condensing.
Control Inputs
l Two sets of terminals for the iCANnet™ suitable
for CAT5 FTP.
l One RJ12 socket for the programming of iCANnet™. l One set of terminals for the Audio Visual port, RS485. l One set of terminals for alarm input.
Electrical Data
Terminal Sizes
l Loads, maximum cable size: 1 x 4 mm
2
or
2 x 2.5 mm2 per circuit.
l iCANnet cable size: 5 x 1mm
2
.
l Audio Visual Port: RS485 2 x 1mm
2
.
l Alarm input: 2 x 1mm
2
.
Memory
l FLASH memory to be able to upgrade firmware
EEPROM for 128 scene memory.
Fade Times
l 0.1 seconds to 60 minutes.
Mains Stabilisation
l 50:1.
Mains Isolators
Isolators are standard on the following Source Controllers SCH1210S & SCH1210N SCH1220S & SCH1220N SCS1210S & SCS1210N SCS1220S & SCS1220N SCI1205S & SCI1205N SCI1210S & SCI1210N SCI1220S & SCI1220SN See SCT1205S for details of isolator wiring.
Isolators are NOT fitted to the following products 'D' (double pole) versions SCI0805S SCI0805N
Special order products that use different mechanics SCI0405 SCH0410 SCS0410 SCS0420 SCI0805T
All iLight Source Controllers have the following specifications:
INTELLIGENT CON TROLS
Inductive Source Controllers
Euro version
l Mains Cable Access: 12 x PG16 and 1 x PG29
knockouts.
l Control Cable Access: 1 x PG16 knockout.
SCI1220
l Weight: 18kg
UK version
l Mains Cable Access: 12 x 25 mm, 1 x PG29
knockouts.
l Control Cable Access: 1 x 25 mm knockout.
Euro version
l Mains Cable Access: 12 x PG16 and 1 x PG29
knockouts.
l Control Cable Access: 1 x PG16 knockout.
Electrical Data
SCI0405
l Maximum Load: 20 Amp single phase @ 40ºC. l Maximum Channel Current: 6 Amps. l Supply: 230 volts -/+ 10% 50/60 Hz.
(optionally, 127 volt 60 Hz).
l Protection: 4 x 6 Amp MCB’s type C, 6KA rated.
SCI0410
l Maximum Load: 40 Amp single phase @ 40ºC. l Maximum Channel Current: 10 Amps. l Supply: 230 volts -/+ 10% 50/60 Hz.
(optionally, 127 volt 60 Hz).
l Protection: 4 x 10 Amp MCB’s type C, 6KA rated.
SCI1205
l Maximum Load: 40 Amp single phase @ 40ºC. l Maximum Channel Current: 6 Amps. l Supply: 230 volts -/+ 10% 50/60 Hz.
(optionally, 127 volt 60 Hz).
l Protection: 12 x 6 Amp MCB’s type C, 6KA rated.
SCI1210
l Maximum Load: 40 Amp three phase @ 40ºC. l Maximum Channel Current: 10 Amps. l Supply: 415/230 volts -/+ 10% 50/60 Hz.
(optionally, 220/127 volt 60 Hz).
l Protection: 12 x 10 Amp MCB’s type C, 6KA rated.
SCI1220
l Maximum Load: 63 Amp three phase @ 40ºC. l Maximum Channel Current: 20 Amps. l Supply: 415/230 volts -/+ 10% 50/60 Hz.
(optionally, 220/127 volt 60 Hz).
l Protection: 12 x 20 Amp MCB’s type C, 6KA rated.
Load Types
l Incandescent 230 volt lamps. l Inductive Wire wound (allow for 10% transformer
losses).
l Leading edge electronic transformers. l Cold Cathode (Check the iLight™ help desk for details).
Minimum Load
l 20 watts per channel.
Dimmed Outputs SCI0405, SCI0410
l 4 x 40 Amp rated Triacs.
SCI1205, SCI1210, SCI1220
l 12 x 40 Amp Triacs.
Switched Outputs
l The Dimmed outputs may be configured as switches,
for non-dimmed loads. They require a minimum load of 30mA for them to latch. Before connecting Discharge lamps, consult with the iLight™ help desk.
Terminal Sizes
l Incoming supply, maximum cable size: 10mm
2
.
SCI0405S - Single pole SCI0405N - Neutral disconnect SCI0410S - Single pole SCI0410N - Neutral disconnect SCI0410D - Double pole SCI1205S - Single pole SCI1205N - Neutral disconnect SCI1210S - Single pole SCI1210N - Neutral disconnect SCI1210D - Double pole SCI1220S - Single pole SCI1220N - Neutral disconnect SCI1220D - Double pole
Common specifications as detailed on page 12 plus the following:
Key Features
SCI0405
l - 4 x 5 Amp fully rated Source Controller.
SCI0410
l - 4 x 10 Amp fully rated Source Controller.
SCI1205
l - 12 x 5 Amp fully rated Source Controller.
SCI1210
l - 12 x 10 Amp fully rated Source Controller.
SCI1220
l - 12 x 20 Amp Source Controller.
l Dims resistive, inductive and low voltage electronic
transformer loads (That are compatible with leading edge dimmers).
l Quiet operation.
Mechanical Data
SCI0405
l Weight: 4kg. l Mains Cable Access: 4 x 25 mm, 4 x PG16 and 1 x
PG21knockouts.
l Control Cable Access: 1 x 25 mm, 1 x PG16
knockouts.
SCI0410
l Weight: 7kg. l Mains Cable Access: 4 x 25 mm, 4 x PG16 and 1 x
PG21knockouts.
l Control Cable Access: 1 x 25 mm, 1 x PG16
knockouts.
SCI1205
l Weight: 10kg.
UK version
l Mains Cable Access: 12 x 25 mm, 1 x PG29
knockouts.
l Control Cable Access: 1 x 25 mm knockout.
Euro version
l Mains Cable Access: 12 x PG16 and 1 x PG29
knockouts.
l Control Cable Access: 1 x PG16 knockout.
SCI1210
l Weight: 18kg.
UK version
l Mains Cable Access: 12 x 25 mm, 1 x PG29
knockouts.
l Control Cable Access: 1 x 25 mm knockout.
13 of 23
INTELLIGENT CON TROLS
Inductive Source Controllers
14 of 23
SCI1205S
INTELLIGENT CON TROLS
RS485
RS485
oV
AL
Output Status LEDs
Load Terminals
Supply Earth Terminals
RJ12 iCANnet
Socket
Control Board
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
Supply & Load Cable entry knockouts
Control Cable entry knockouts
Service switches
and LEDs
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
Channel Circuit Breakers
MAINS IN
RS485 & Alarm
Terminals
iCANnet
Terminals
SCH0410
l Maximum Load: 40 Amp single phase @ 40ºC. l Maximum Channel Current: 10 Amps. l Supply: 230 volts -/+ 10% 50/60 Hz.
(optionally, 127 volt 60 Hz).
l Protection: 4 x 10 Amp MCB’s type C, 6KA rated.
SCH1210 - As 0410 but 3 phase + 12 x 10 Amp.
SCI0805
l Maximum Load: 40 Amp single phase @ 40ºC. l Maximum Channel Current: 5 Amps. l Supply: 230 volts -/+ 10% 50/60 Hz (same phase). l Protection: 1 x 20 Amp Double pole input MCB’s
type C, 6KA rated.
SCH1200
l Maximum Load: There is no load control. l Power switching is achieved by the DSI ballasts
themselves.
l Maximum Channel Current: Not applicable. l Supply: 1 x 230 volts -/+ 10% 50/60 Hz. l Protection: Thermal non resetting fuse.
SCH0410 Dimmed Outputs
l 4 x 1-10 volt at 0.1 Amp sink current per channel. l 4 x Tridonic DSI outputs (uses electronic power
switching in ballasts).
Switched Outputs
l 4 x 230 volt 10A (inductive or resistive).
SCH1210 Dimmed Outputs
l 12 x 1-10 volt at 0.1 Amp sink current per channel. l 12 x Tridonic DSI outputs (uses electronic power
switching in ballasts).
Switched Outputs
l 12 x 230 volt 10A (inductive or resistive).
SCI0805 Dimmed Outputs
l 4 x 1-10 volt at 0.1 Amp sink current per channel. l 4 x Tridonic DSI outputs (uses electronic power
switching in ballasts).
l 4 x 5 Amp inductive.
Switched Outputs
l 4 x 230 volt 5A (inductive or resistive).
SCH1200T Dimmed Outputs
l 12 x 0-10 volts at 0.1 Amp sink current per channel. l 12 x Tridonic DSI outputs (uses electronic power
switching in ballasts).
Switched Outputs
l None.
Terminal Sizes SCH0410, SCH1210, SCI0805
l Incoming supply, maximum cable size: 10mm
2
.
SI0805T
l Incoming supply, cable rated for 40 Amp or to
correspond to input supply voltage.
l Maximum cable size 10mm
2
.
SCH1200T
l Incoming supply, maximum cable size: 2.5mm
2
l Ballast output, maximum cable size: 12 pairs
2.5 mm2 per circuit.
SCH0410S - Single pole 4 channels SCH0410N - Neutral disconnect SCH0410D - Double pole SCH1210S - Single pole 12 Channels SCH1210N - Neutral disconnect SCH1210D - Double pole SCI0805T - Single pole - Dual unit SCI0805S - Single pole SCI0805N - Neutral disconnect SCH1200T - Terminals - 12 Channel, no relays
Common specifications as detailed on page 12 plus the following features:
Key Features
SCH0410S
l 40 Amp fully rated source controller.
SCH1210
l 120 Amp total box load on 4 circuits.
SCI0805
l 40 Amp total box load on 1 supply.
SCH1200
l A 12 channel device source controller.
l Suitable for both 0-10 volt analogue and DSI ballasts. l Quiet operation.
Mechanical Data
SCH0410
l Weight: 4kg. l Mains Cable Access: 4 x 25 mm, 4 x PG16 and 1 x
PG21knockouts.
l Control Cable Access: 1 x 25 mm, 1 x PG16
knockouts.
SCH1210
l Weight: 7.5kg.
UK version
l Mains Cable Access: 12 x 25 mm, 1 x PG29
knockouts.
l Control Cable Access: 1 x 25 mm knockout.
Euro version
l Mains Cable Access: 12 x PG16 and 1 x PG29
knockouts.
l Control Cable Access: 1 x PG16 knockout.
SCI0805
l Weight: 7.5kg. l Mains Cable Access: 4 x 25 mm, 4 x PG16 and 1 x
PG21knockouts.
l Control Cable Access: 1 x 25 mm, 1 x PG16
knockouts.
SCH1200T
l Weight: 3kg. l Mains Cable Access: 2 x 25 mm and 2 x PG16
knockouts.
l Control Cable Access: 1 x 25 mm and 1 x PG16
knockouts.
Electrical Data
Load Types
l 1-10volt HF Fluorescent, 100 per channel. l DSI & DALI Fluorescent Ballasts
SCH0410 & SCI0805, 32 / channel. 128 / unit SCH1210, SCH1220 & SCH1200T, 64 / channel; 128 / unit
l 0-10 volt Iris control 20K Ohm input). l 1-10 volt Multi-Load transformers 100 (control only).
HF Ballast Controllers
15 of 23
INTELLIGENT CON TROLS
HF Ballast Controllers
16 of 23
SCI0805S
SCH1200T
HF Control Connections
Option Switch
SCH0410S
INTELLIGENT CON TROLS
Channel Circuit Breakers
Load Terminals
Supply Earth Terminals
RJ12 iCANnet Socket
Load Terminals Supply Earth Terminals
HF Control Connections
Channel Circuit Breakers
HF Control Connections
Control Board
Option SwitchOption Switch
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
RS485
RS485
oV
AL
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
RS485
RS485
oV
AL
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
RS485
RS485
oV
AL
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
Mains Supply In
Supply & Load Cable entry knockouts
Supply & Load Cable entry knockouts
Control Cable entry knockouts
Control Cable entry knockouts
Service switches
and LEDs
Service switches
and LEDs
Service switches
and LEDs
Control Board
RJ12 iCANnet Socket
RJ12 iCANnet Socket
Control Board
MAINS IN
MAINS IN
RS485 & Alarm
Terminals
iCANnet
Terminals
RS485 & Alarm
Terminals
iCANnet
Terminals
RS485 & Alarm
Terminals
iCANnet
Terminals
SCS1210S - Single pole SCS1210N - Neutral disconnect SCS1220S - Single pole SCS1220N - Neutral disconnect
Common specifications as detailed on page 12 plus the following features:
Key Features
l Twelve channels of switching for resistive, inductive
or capacitive lighting loads.
l Quiet operation.
SCS1210
l 12 x 10 Amp fully rated switching Source Controller.
SCS1220
l 12 x 20 Amp Source Controller.
Mechanical Data
SCS1210, SCS1220
l Weight: 7.5kg.
UK version
l Mains Cable Access: 12 x 25 mm, 1 x PG29
knockouts.
l Control Cable Access: 1 x 25 mm knockout.
Euro version
l Mains Cable Access: 12 x PG16 and 1 x PG29
knockouts.
l Control Cable Access: 1 x PG16 knockout.
Switched Relay Controllers
17 of 23
Electrical Data
Load Types
l This unit is designed to work with most lighting load
types. Please consult with the iLight™ help desk for guidance on true load calculations. Care should be taken when specifying discharge lighting sources.
Switched Outputs
l This device uses 12 x 230 volt 20A (resistive and
inductive) relays.
Terminal Sizes
l Incoming supply, maximum cable size: 10mm
2
.
SCS1210
l Maximum Load: 40 Amp three phase @ 40ºC. l Maximum Channel Current: 10 Amps. l Supply: 415/230 volts -/+ 10% 50/60 Hz.
(optionally, 220/127 volt 60 Hz).
l Protection: 12 x 10 Amp MCB’s type C, 6KA rated.
SCS1220
l Maximum Load: 63 Amp three phase @ 40ºC. l Maximum Channel Current: 20 Amps. l Supply: 415/230 volts -/+ 10% 50/60 Hz.
(optionally, 220/127 volt 60 Hz).
l Protection: 12 x 20 Amp MCB’s type C, 6KA rated.
INTELLIGENT CON TROLS
SCS1210S
Switched Relay Controllers
18 of 23
INTELLIGENT CON TROLS
Output Status LEDs
Option Switch
Load Terminals
Supply Earth Terminals
RJ12 iCANnet
Socket
Control Board
Supply & Load Cable entry knockouts
Control Cable entry knockouts
Service switches
and LEDs
Channel Circuit Breakers
MAINS IN
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
RS485
RS485
oV
AL
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
RS485 & Alarm
Terminals
iCANnet
Terminals
SCA0410S - Single Pole SCA0410N - Neutral Disconnect SCA0410D - Double Pole SCA1210S - Single Pole SCA1210N - Neutral Disconnect SCA1210D - Double Pole
Common specifications as detailed on page 12 plus the following:
Key Features
SCA0410
l - 4 x 10 Amp fully rated Source Controller.
SCA1210
l - 12 x 10 Amp fully rated Source Controller.
l Auto Senses for load type, and suitable for resistive,
inductive and capacitive loads.
l Complete with iPROTECT™ lamp protection and auto
short circuit protection.
Mechanical Data
SCA0410
l Weight: 9kg. l Mains Cable Access: 4 x 25 mm, 4 x PG16 and
1 x PG21knockouts.
l Control Cable Access: 1 x 25 mm, 1 x PG16
knockouts.
SCA1210
l Weight: 18kg.
UK version
l Mains Cable Access: 12 x 25 mm, 1 x PG29
knockouts.
l Control Cable Access: 1 x 25 mm knockout.
Euro version
l Mains Cable Access: 12 x PG16 and 1 x PG29
knockouts.
l Control Cable Access: 1 x PG16 knockout.
Electrical Data
SCA0410
l Maximum Load: 40 Amp single phase @ 40ºC. l Maximum Channel Current: 10 Amps. l Supply: 230 volts -/+ 10% 50/60 Hz.
(optionally, 127 volt 60 Hz).
l Protection: 4 x 10 Amp MCB’s type C, 6KA rated.
SCA1210
l Maximum Load: 40 Amp three phase @ 40ºC. l Maximum Channel Current: 10 Amps. l Supply: 415/230 volts -/+ 10% 50/60 Hz.
(optionally, 220/127 volt 60 Hz).
l Protection: 12 x 10 Amp MCB’s type C, 6KA rated.
Load Types
l Incandescent 230 volt lamps. l Low voltage inductive lamps (wire wound or
electronic).
l Low voltage electronic (capacitive). l Cold Cathode (Check the iLight™ help desk for
details).
Minimum Load
l 20 watts per channel.
Dimmed Outputs
l 2 x 45 Amp FET’s per circuit.
Switched Outputs
l The Dimmed outputs may be configured as switches,
for non-dimmed loads. They require a minimum load of 30mA for them to latch.
Terminal Sizes SCA0410, SCA1210
l Incoming supply, maximum cable size: 10mm
2
.
Adaptive Source Controllers
19 of 23
INTELLIGENT CON TROLS
Adaptive Source Controllers
20 of 23
SCA1210S
INTELLIGENT CON TROLS
Trailing Edge Source Controllers
Electrical Data
SCI0405
l Maximum Load: 20 Amp single phase @ 40ºC. l Maximum Channel Current: 6 Amps. l Supply: 230 volts -/+ 10% 50/60 Hz.
(optionally, 127 volt 60 Hz).
l Protection: 4 x 6 Amp MCB’s type C, 6KA rated.
SCI1205
l Maximum Load: 40 Amp single phase @ 40ºC. l Maximum Channel Current: 6 Amps. l Supply: 230 volts -/+ 10% 50/60 Hz.
(optionally, 127 volt 60 Hz).
l Protection: 12 x 6 Amp MCB’s type C, 6KA rated.
Load Types
l Incandescent 230 volt lamps. l Capacitive loads l Trailing edge electronic transformers.
Minimum Load
l 20 watts per channel.
Dimmed Outputs SCT0405
l 4 x 19 Amp rated Transistors.
SCT1205
l 12 x 19 Amp rated Transistors.
Switched Outputs
l The Dimmed outputs may be configured as switches,
for non-dimmed loads. They require a minimum load of 30mA for them to latch. Before connecting Discharge lamps, consult with the iLight™ help desk.
Terminal Sizes
l Incoming supply, maximum cable size: 10mm
2
.
SCT0405S - Single pole SCT0405N - Neutral disconnect SCT0405D - Double pole SCT1205S - Single pole SCT1205N - Neutral disconnect SCT1205D - Double pole
Common specifications as detailed on page 12 plus the following:
Key Features
SCT0405
l - 4 x 5 Amp fully rated Source Controller.
SCT1205
l - 12 x 5 Amp fully rated Source Controller.
l Dims resistive, capacitive and low voltage electronic
transformer loads.
l Quiet operation.
Mechanical Data
SCT0405
l Weight: 4kg. l Mains Cable Access: 4 x 25 mm, 4 x PG16 and 1 x
PG21knockouts.
l Control Cable Access: 1 x 25 mm, 1 x PG16
knockouts.
SCT1205
l Weight: 10kg. l Mains Cable Access: 12 x 25 mm, 1 x PG29
knockouts.
l Control Cable Access: 1 x 25 mm knockout.
21 of 23
INTELLIGENT CON TROLS
Trailing Edge Source Controllers
22 of 23
SCT1205S
INTELLIGENT CON TROLS
RS485
RS485
oV
AL
Channel Circuit Breakers
Option Switch
Load Terminals
Supply Earth Terminals
RJ12 iCANnet
Socket
Control Board
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
Supply & Load Cable entry knockouts
Control Cable entry knockouts
Service switches
and LEDs
+12V
Orange Pair
CAN-H
Blue/White
CAN-L
Blue
0V
Green Pair
SHIELD
Brown Pair
Isolator
MAINS IN
RS485 & Alarm
Terminals
iCANnet
Terminals
23 of 23
iLight Unit 4 Enterprise Centre Penshurst Tonbridge Kent TN11 8BG
T +44 (0)1892 870072 F +44 (0)1892 870074 E service@iLight.co.uk www.iLight.co.uk
ILIGHT™, iCAN™, iCanTools™, iCANnet™, iPROTECT™ are registered trademarks of Cooper Controls Limited. All servicing must be referred to iLight - Cooper Controls Limited. This equipment is designed for professional lighting control, and is unsuitable for any other purpose. Cooper Controls Limited reserves the right to make changes to the equipment described in this handbook without prior notice. Errors and omissions excepted (E&OE)
Part No.: 7385000 Issue 10 January 2008
INTELLIGENT CON TROLS
Loading...