ILI DataLink GW1000 User Manual

GW1000
User’s Guide
Revision 1.04 – Mar 30, 2008
DataLink Technologies Gateways, Inc.
Website: www.datalink-networks.com
Tel : (604) 632-4278 / (866) 709-6390
Table of Contents
1.0 GW1000 General Operation & Applications................................................................. 3
2.0 Hardware Specifications ................................................................................................... 4
3.0 GW1000 Hardware Layout ................................................................................................ 5
4.0 Configuration........................................................................................................................ 6
4.1 Online Mode of Operation .......................................................................................................... 6
4.3 Restore Factory Defaults .......................................................................................................... 10
4.4 USB Driver Installation .............................................................................................................. 12
4.5 Firmware Upgrade ...................................................................................................................... 12
5.0 Switch and LED Indicator Functions ........................................................................... 16
6.0 GW1000 Wiring Diagrams ............................................................................................... 18
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
2
1.0 GW1000 General Operation & Applications
The GW1000 continues the functionality of the current DL2000/DL3000/DL3500 product line. In addition to having connectivity to Allen-Bradley’s DH+, and the RS232/422/485/USB capabilities of the DL3500, the GW1000 offers a 10/100 Base-T Ethernet connection. The ability to power the GW1000 from the USB communication link is also present, removing the sometimes cumbersome procedure of locating a DC power supply when using laptops or PC’s in the field.
The GW1000 has two communication ports. Channel A is designed to connect to your industrial Allen-Bradley DH+ network. Channel B is used to connect to your serial or USB device, the protocol depends on which model of the GW1000 you have ordered. Channel B has the capabilities of RS232C, RS422, RS485 and USB 2.0.
Configuration of the operating parameters is done quickly and easily via the Ethernet interface. Operational Firmware is also easily upgraded over the Ethernet interface. This allows for quick changes if you need to change your protocol.
Currently there are three standard GW1000 products available to allow access to Allen­Bradley’s DH+ network. Many other custom ASCII and serial protocols have been implemented to DH+ on the GW1000 platform.
Contact DataLink Technologies to see if the GW1000 is the correct device for your communication needs.
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
3
2.0 Hardware Specifications
2.1 Operating Specifications:
CHA can be configured DH+ with baud rates of 57.6, 115.2 and 230.4 KBaud
CHB has full RS232C, as well as both RS422-4 wire and RS485 2-wire modes.
CHB has the ability of being configured with asynchronous speeds up to 230.4 KBaud as well as the new Plug and Play Windows USB Interface.
Currently DF1, Modbus, and ASCII are the supported protocols. Custom protocols are easily implemented. Both CRC 16 and BCC error checking can be implemented; custom error checking can be added at the customer’s request.
Simple Parameter Configuration using Ethernet interface.
Configuration and Reset Pushbuttons to set up online configuration parameters and
perform a full Hardware Reset as well as a Restore to Factory Defaults option.
Operating Parameters are stored in non-volatile flash memory. The GW1000 firmware can be upgraded via the Ethernet interface.
Bi-Color (Green/Red) LED’s for each communication channel indicates activity and status. Green POWER LED indicates power on.
2.2 Physical Specifications:
Dimensions: 0.90" H x 4.65" D x 3.98" W (22.8mm x 118.3mm x 101.0mm) Weight: 0.44lbs (0.2kg) Installation: Plastic enclosure; Freestanding or DIN rail mounting with integrated clip Operating Environment: 32 to 122 °F (0 to 50 °C) Storage: -40 to 185°F (-40 to 85°C) Humidity: 5% to 95% non-condensing Power: 9-27V DC or standalone USB - 2.0 Watts
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
4
3.0 GW1000 Hardware Layout
This Section contains information on the physical position and purpose of the components of the GW1000.
Top side connectors
3-pin power – 3.81mm pitch removable screw terminal plug
3-pin A-B DH+ – 5.08mm pitch removable screw terminal plug
RJ45 Ethernet
Bottom side connectors (note: one connection is permitted at a time)
5-pin RS485/RS422 for CHB – 3.81mm pitch removable screw terminal plug
9 Pin D9M connector for CHB RS232C communications
USB connector for CHB
Front Panel Indicators
DH+ Status
Serial Status
Serial Receive (RX)
Serial Transmit (TX)
Ethernet Activity
Ethernet Link
Power
RESET and CONFIGure pushbuttons are accessible through openings in the top of the case as depicted on product label.
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
5
4.0 Configuration
4.1 Online Mode of Operation
Online Mode is the normal operating Mode of the GW1000. In this mode the Channels are configured and the GW1000 is ready to interface to your equipment.
Power on or a press of the Reset pushbutton automatically puts the GW1000 into Online mode.
4.2 Configuring the GW1000
Connect the GW1000 ethernet port to a switch or hub on the same network as your PC using a CAT5 network patch cord. Power on the GW1000 and wait 30 seconds for the bootup sequence to complete. Note the LAN LINK indicator LED should be on. From Windows, open a DOS command prompt window by clicking:
START All Programs Accessories Command Prompt
At the command prompt, type:
telnet 192.168.1.111 10000 (ENTER↵↵↵)
This will bring up the login screen for configuration. (note: if you have changed the default IP address of the GW1000, enter the new address. If you do not know the IP address programmed into the GW1000, first restore factory defaults.)
Welcome to Gateway 1000 Interface Configuration Utility 1.0 Serial Number: A000800042
login:
Type in the default login and password as: “Netsilicon” and “sysadm” respectively. Please note the login is case-sensitive.
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
6
The following is the main menu:
Hello Netsilicon
DataLink GW1000-DHP1:DF1 to DH+ Interface Main Menu. Build : 0803.1.11
1.) Modify IP Parameters
2.) Modify Password
3.) View/Modify Online Parameters
4.) Online Diagnostic Statistics
5.) Save and Reboot
6.) Quit without save
Enter Selection:
To access a menu item, press the corresponding number followed by ENTER.
1) Modify IP Parameters
To edit the IP Parameters, press “1” followed by ENTER. The following submenu is displayed.
Enter Selection: 1
IP Parameters:
1.) IP Address 192.168.1.111
2.) Subnet Mask 255.255.255.0
3.) Default Gateway 192.168.1.1
4.) Main Menu
To edit the IP address, press “1” ENTER followed by a new address and ENTER. Likewise, the Subnet Mask and Default Gateway can be set.
Enter Selection: 1 Enter IP address: 192.168.1.33 New IP address [192.168.1.33] accepted
IP Parameters:
1.) IP Address 192.168.1.111
2.) Subnet Mask 255.255.255.0
3.) Default Gateway 192.168.1.1
4.) Main Menu
Enter Selection:
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
7
Note: The new parameters will be written to memory upon returning to the main menu by pressing 4 ENTER↵↵↵.
2) Modify Password
The login password can be modified with main menu option 2.
Enter Selection: 2
Enter old password: ******
Enter new password: ******
Renter new password: ******
New password accepted
3) View / Modify Online Parameters
To edit the Online Parameters for DH+ port and serial port, from the main menu, press “3” followed by ENTER. The following submenu is displayed.
Enter Selection: 3
Online Parameters:
1.) Node Address Oct:1o, Hex:0x01, Dec:1
2.) DH+ Baud Rate 57.6 KBaud
3.) Serial Parameters
4.) DF1 Parameters
5.) Save Parameters and Exit
6.) Return to Main Menu
Enter Selection:
To edit the DH+ node address, press “1” ENTER↵, enter the two-digit octal value and press ENTER..
Enter Selection: 1
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
8
Enter new DH+ Node address (Octal):
To edit the DH+ baud rate, press “2” ENTER and select a value and press ENTER..
Enter Selection: 2
DH+ Speed: [57.6 KBaud]
1.) 57.6K Baud
2.) 115.2K Baud
3.) 230.4K Baud
4.) Autobaud Detection
5.) or <CR> Keep as Configured and Return to Online
Parameters Menu
To edit the parameters for the serial port, press “3” ENTER and the following submenu is displayed. Each of the parameters can be changed with corresponding submenus. To save the serial settings, press “7” ENTER↵.
Enter Selection: 3
Serial Parameters:
1.) Baud Rate 9600
2.) Parity NONE
3.) Data Bits 8
4.) Stop Bits 1
5.) Interface (RS232/422/485) RS232
6.) RS232 RTS/CTS Handshaking NONE
7.) Return to Online Parameters Menu
Enter Selection:
The following DF1 protocol parameters can be edited with option 4 and their associated submenus.
Enter Selection: 4
DF1 Protocol Parameters:
1.) Error Checking Mode BCC
2.) Duplex Protocol FULL
3.) PASS/EXECUTE Diagnostics PASS
4.) Return to Online Parameters Menu
Enter Selection:
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
9
Note: To save the values and exit, press “5” from the Online Parameters menu: “Save Parameters and Exit.”
4) Online Diagnostic Statistics
An online diagnostics menu is provided for troubleshooting purposes.
Enter Selection: 4
Online Diagnostics Statistics and Counters
1.) DH+ Diagnostic Counters
2.) DF1 Diagnostic Counters
3.) Return to Main Menu
Enter Selection:
4.3 Restore Factory Defaults
To restore factory defaults, connect the GW1000 to a PC using either a USB or RS232 connection. If using USB, first install USB drivers as explained in “USB Driver Installation”. Using a terminal program such as “Hyperterminal” included with Microsoft Windows, configure a connection to the RS232 port on the PC (typically COM1 or COM2) or the virtual COM port assigned by the USB driver. This setting is under File Properties menu. Press “Configure” and select baud rate of 57.6 Kbaud, 8 data bits, no Parity, 1 stop bit, flow control: none.
Power on the GW1000 by connecting power supply or USB cable.
Wait 30 seconds for the bootup sequence to complete
In the Hyperterminal program, select Call Call to connect to the selected COM
port.
Through the window in the side of the GW1000 case, press the “Config” button with a paperclip or small screwdriver. The config button should be pressed for one second and then released.
The following screen is displayed
PLATFORM: ns7520_a_esp BSP Library Built on: Mar 30 2008 11:25:37 APPLICATION: DataLink GW1000-DHP1 : DF1 to DH+ Interface Application Built on: Mar 30 2008 11:26:31
-----------------------------------------------------------------
NETWORK INTERFACE PARAMETERS: IP address on LAN is 192.168.1.111 LAN interface's subnet mask is 255.255.255.0
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
10
IP address of default gateway to other networks is 192.168.1.1 HARDWARE PARAMETERS:
GW1000's serial number is A00800333 GW1000's Ethernet MAC Address is 00:50:C2:89:F0:29 After board is reset, start-up code will wait 5 seconds Default duplex setting for Ethernet connection: default ONLINE DH+ PARAMETERS: Serial DF1/Config channel will use a baud rate of 57600 DH+ Node address is 22 Octal. DH+ baud Rate is 57600 Baud. DF1 Parameters: Full Duplex Operation, and BCC Error Checking.
-----------------------------------------------------------------
Press any key in 5 seconds to change these settings.
Press a key…
Press A to Accept the settings, or M to Modify?
Press “M” followed by ENTER to modify settings…
Enter the root password:
At the password prompt, type “Netsilicon”. Note password is case-sensitive…
Reset configuration to default values [N]?
Type “Y”, ENTER to restore settings to default values, then press ENTER at each prompt to accept default values, or enter desired new values followed by ENTER
For each of the following questions, you can press <Return> to select the value shown in braces, or you can enter a new value.
ETHERNET INTERFACE SETTINGS:
Obtain IP settings automatically using DHCP for this interface [N]? IP address [192.168.1.111]? Subnet mask [255.255.255.0]? Gateway address [192.168.1.1]?
This interface must have a unique MAC address. Ethernet MAC Address [00:40:9D:43:35:97]? Ethernet duplex setting (default, full, half)? [default]
SERIAL CONSOLE PORT SETTINGS:
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
11
Set the baud rate of the serial console port [57600]? 9600, 19200, 38400, 57600, 115200
SECURITY SETTINGS:
Would you like to update the Root Password [N]? Would you like to update the Administrator 'admin' Password [N]?
MISCELLANEOUS SETTINGS:
Each development board must have a unique serial number Set the board's serial number[A00800333]?
How long (in seconds) should CPU delay before starting up [5]?
Saving the changes in NV memory...
Default Settings
DF1 protocol: 9600 Baud, 8 Bits, No Parity, BCC Checksum
DH+ defaults
57.6 KBaud
Node address: 1 octal, 0x01 hex, decimal 1
4.4 USB Driver Installation
The USB driver is provided by Future Technology Devices International Ltd. Please see the Windows_XP_Installation_Guide.pdf in the Documentation folder on the CD included with the GW1000. The USB driver version on the CD is “CDM 2.02.04 WHQL Certified.” See section “2.1 Installing CDM drivers” on page 4. For reference, the document is also available here…
http://www.ftdichip.com/Documents/InstallGuides/Windows_XP_Installation_Guide.pdf
4.5 Firmware Upgrade
Firmware upgrade is accomplished using the ethernet interface and a web browser. Connect the GW1000 ethernet port to an ethernet port on the same network as your PC using a CAT5 network patch cord to a network hub or router. Open a web browser such as Microsoft Internet Explorer or Mozilla Firefox, power on the GW1000 and wait 30 seconds for bootup sequence to complete. Note the LAN LINK indicator LED should be on.
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
12
In the browser address bar, type 192.168.1.111 and press ENTER. (note: if you have changed the default IP address of the GW1000, enter the new address in the address bar. If you do not know the IP address programmed into the GW1000, first restore factory defaults.) In the “User Name” field, type “root”. In the Password field, type “Netsilicon”. (note: password is case-sensitive.)
Click OK and the home page will be displayed. The current software version is displayed in the lower right of the screen.
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
13
Click “Upload Firmware
Click Browse or type the location of the new firmware file. (note: the firmware image filename must not be edited. The filename must be image.bin. If you have multiple versions of firmware files, they must each be stored in a different folder on your computer.) Click Upload. Please wait two minutes until you see the “Upload Successful” message. On rare occurrences, the browser program may timeout before a successful response is received. In this case, wait an extra minute to make sure the upload has taken place, repower the GW1000, and login as explained above. Examine the firmware release number in the lower right of the screen to check the version has been updated.
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
14
To finalize firmware update, you must cycle power on the GW1000.
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
15
5.0 Switch and LED Indicator Functions
5.1 Switch Functions
The Reset pushbutton will perform a complete hardware reset of the GW1000. It is identical to a complete power cycle and will cause the GW1000 to go through its LED start-up sequence.
The Configure pushbutton takes the GW1000 out of On-Line operation mode and allows the user to restore factory default settings.
5.2 Indicator Functions
5.2.1 Power-Up and Reset Sequence
On Power-up or after the Reset button has been pressed the GW1000 executes a self-diagnostic check of the RAM and flash firmware. The correct LED indicator sequence to show the GW1000 is functioning properly is as follows: After all LEDS go out.
LED STATUS
Power Green Continuously Serial Tx Brief green flash then off Serial Rx Green for 3 seconds then off Status Red for 10 seconds then Green 1 second, then off DH+ Green 1 second, Red 1 second, then flashing green for offline,
solid green for online.
After this sequence the GW1000 goes into the On-line mode of Operation. The LED indicators will behave in the way defined by the GW1000 model used. Normally, all LEDS will be off waiting for communication on its channels.
5.2.2 Normal On-line Operation
The following is a description of the normal operation of the Channel LEDs on the GW1000. Custom products operation will differ from the following:
LED Description of Operation
Power Green Indicates Power is being supplied to the GW1000.
Serial Tx, Flashes GREEN when a Character is Received or & Serial Rx Transmitted. If Characters are being received or transmitted
rapidly, the LED might appear on SOLID.
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
16
Status Flashes RED for 0.5 seconds if a NAK is received or transmitted in
DF1 protocol or if all serial communication buffers are full. Flashes GREEN for 0.5 seconds if Good DF1 packets are being sent. If Characters are being received or transmitted rapidly, the LED might appear on SOLID.
DH+ Flashes RED if a Duplicate DH+ node address is already on the
network. Flashes GREEN when soliciting for stations to create a new network or DH+ cable is not connected. Alternately flashes RED and GREEN if in DH+ autobaud detection mode and listening to the network to determine the baud rate to use.
5.2.3 Off-Line Modes
The following table describes the meaning of LED patterns in the different Off­Line modes of operation.
LED Pattern Description of Operation
DH+ and Status Offline configuration of parameters mode from the serial
menu: Solid GREEN, Rest OFF
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
17
6.0 GW1000 Wiring Diagrams
6.1 Online Cable GW1000-CHA DH+
GW1000-CHA DH+ Other DH+ Nodes
Note: Clear & Blue might have to be swapped depending on existing DH+ wiring
6.2 Configuration Cable/Online Cable GW1000-CHB RS-232 – No Handshaking
GW1000 – CHB PC/OEM Equipment
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
18
6.3 Online Cable GW1000-CHB RS-232 – With RTS/CTS Handshaking
GW1000-CHB PC/OEM Equipment
DataLink Technologies Gateways, Inc. Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
19
Loading...