IHP SF-HTSS, SV4.5HTSS, SV4.5-20SSWSK, SFKIT12-SS, SFKIT18-SS Installation Instructions Manual

...
HEARTH PRODUCTS
*34-5/16
(872)
Back wall of chase/enclosure (including any finishing materials)
a
8-3/16 (208)
b
NOTE: Venting requirements for rear vent applications in corner installations ­the horizontal vent length “a” to “b,” must not exceed 28” (711 mm)
*17-3/16
(437)
Inches
(millimeters)
*These dimensions occur when one 45 degree
elbow is connected directly to the appliance collar and the unit moved 1/2” (13 mm) into the room. This 1/2” movement is required to achieve a minimum of 5” (127 mm) in the F dimension.
*F = 5” (127 mm)
*24-1/4
(616)
33-1/8
(841)
*48-1/2
(1232)
CORNER FRAMING WITH SQUARE HORIZONTAL
TERMINATIONS (SV4.5HTSS)
SV4.5HTSS Termination
Framing should be constructed of 2x4 or larger lumber.
7 (178)
b
SV4.5HTS
Termination
CUS
KITS AND ACCESSORIES
Report No. F114-140
INSTALLATION INSTRUCTIONS FOR SV4.5HTSS, SV4.5-20SSWSK AND ALL DERIVATIONS OF THE SF-HTSS; SFKIT12-SS, SFKIT18-SS, SFKIT24SS, SFKIT26SS AND SFKIT48-SS KITS
Small Square Termination Kits
Cat. No Model Description
H5817 SV4.5-20SSWSK Small Square Termination, Horiz. 20" w/Sheild
94L10 SV4.5HTSS Small Square Termination, Horiz. - Rigid
H8915 SV4.5TK90SS Small Square Termination, Horiz. Kit w/90
GENERAL INFORMATION
Information provided here is supplemental to instructions provided with each fireplace and may, for the most part, be redundant to that information. The intent of this document is to provide complete instructions pertaining to the installation of the before-mentioned terminations, particularly any
f i r e - p a r t s . c o m
instructions that are exclusive to the installations of these terminations.
The SV4.5HTSS, SV4.5-20SSWSK and all derivations of the SF-HTSS; SFKIT12-SS, SFKIT18-SS, SFKIT24-SS, SFKIT36-SS, and SFKIT48-SS are intended for use ONLY with Innovative Hearth Products (IHP) 33”, 35” and select other Direct-Vent gas fireplaces listed as follows; DRC/ DRT-2033/2035, DRC/DRT-3033/3035, DRL3042, DRL6542, Aries 33/35, AriesCD 33/35, MPD33/35, MPD3328/3530, Gemini33/35, Rhapsody42, Sirius42, Envy35, Envy35CD, MHD35, MLDVTCD-35, SSDV-3328/3530, SDV35N, LMDV3328, LMDV-3530, MPLDV-30 and MPLDV-35, VeniceLightsTEN, VeniceLightsTEP, DRL4543TEN, DRL4543TEP series gas fireplaces.
These terminations MAY NOT be used with DRC/DRT-2040/2045, DRC/DRT-4040/4045, DRT40-ST/PF/CR/CL, DRC/DRT-3540/3545, DRC/DRT-3040/3045, DRT35ST/PF, DRL3054, DRL6554, Aries40/45, AriesCD40/45,Altair40/45, Envy40/45CD, Envy40CD/45CD, Eros35ST/PF, Gemini40/45, Libra40-ST/PF/CR/CL, Scorpio-35/40/45, ScorpioCD-35/40/45, MHD40, MPD Pro, MPD40/45, MPD4035/4540, MPD35ST/PF, Rhapsody 54, Sirius54, Spectra, EDV, ELDV and EDVST/ PF/CR/CL series gas fireplaces.
The terminations covered by this document seamlessly integrate with all the other components of the above mentioned fireplaces approved for use with these terminations, and when installed in accordance with the directions provided here and with each fireplace constitute a complete, approved and listed installation.
P/N 750204M REV. H 04/2018
Framing
Frame the fireplace in accordance with the instructions provided with the fireplace and refer to Figures 1, 4 and 5 for any dimensions applicable to the SV4.5HTSS, SF-HTSS terminations.
SMALL SQUARE
Figure 1
1
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Vertical
Rise
SV4.5E90
Elbow
Horizontal / Inclined Run
SV4.5HTSS
Termination
Shown
*Ceiling
Firestop/Spacer
(SV4.5VF)
SV4.5L6/12/24/36/48
Vent Sections
Support Bracket Spacing Every 5 ft (1.52 m)
Support
Brackets
Building
Support
Framing
Ceiling
Fireplace
Exterior Wall
Exterior Wall
TYPICAL HORIZONTAL VENT INSTALLATION
Firestop/Spacer
SV4.5HTSS
Termination
Shown
Fireplace
*When using Secure Flex use
Firestop/Spacer (SF4.5VF)
Note: Adaptor SV4.5RCH or SV4.5RCHA must be used to attach the termination to the venting system. See Steps J and K.
HORIZONTAL (OUTSIDE WALL) TERMINATION SYSTEM
Figure 2, and Figures 7 to 1 3 and their associated Horizontal Vent Tables, illustrate the various hori­zontal venting configurations that are possible for use with these appliances. Secure Vent pipe applications are shown in these figures; Secure Flex pipe may also be used. A Horizontal Vent Table summarizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications. Both of these horizontal vent systems terminate through an outside wall. Building Codes limit or prohibit terminating in specific areas. Refer to the instructions provided with the fireplace.
Secure Vent SV4.5 direct vent system compo­nents are unitized concentric pipe components featuring positive twist lock connection.
A. Plan the vent run - Analyze the vent routing and determine the types and quantities of sections required 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (877 mm) and 46-1/2" (1181 mm) net section lengths are available. Make allowances for elbows as indicated in the instructions provided with the fireplace.
f i r e - p a r t s . c o m
Maintain a minimum 1" (26 mm) clearance to combustibles on the vertical sections. Clearances for the horizontal runs are; 3" (77 mm) on top, 1" (26 mm) on sides, and 1" (26 mm) at the bottom.
B. Frame exterior wall opening -
Locate the center of the vent outlet on the exterior wall. Cut and/or frame an opening, 10-1/2" x 12-1/8" (267 mm x 308mm) inside dimensions, about this center.
C. Frame ceiling opening - If the vertical route is to penetrate a ceiling, use plumb line to locate the center above the appliance. Cut and/or frame an opening, 10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center.
D. Attach vent components to appliance - To attach a vent component to the appliance collar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels on the collar. Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe elements with the same procedure.
Sealant and securing screws are not required.
2
Figure 2
NOTE: An elbow may also be attached to the
appliance collar. Attach in the same manner as you would a vent section.
E. Attach vent components to each other - Other vent sections may be added to the previ­ously installed section in accordance with the requirements of the vent tables. To add another vent component to a length of vent run, align the dimpled end of the component over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
F. Install firestop/spacer at ceiling - When using Secure Vent, use SV4.5VF firestop/ spacer at ceiling joists; when using Secure Flex, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (26 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
G. Support the vertical run sections -
On the vertical run, support the venting sys­tem every 8 feet (2.4m) above the fireplace vent outlet with field provided support straps (Plumber's tape). Attach the straps to the vent pipe and secure to the framing members with nails or screws.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
H. Change vent direction - At transition from or to a horizontal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow sections in a
clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections.
I. Continue installation of horizontal/inclined sections - Continue with the installation of the
straight vent sections in horizontal/inclined run as described in Step E. Install support straps every 5 ft. (1.52 m) along horizontal/inclined vent runs using conventional plumber’s tape. See Figure 2. It is very important that the
horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of 1/4" rise per foot (20 mm
per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
It is important to maintain the required clear­ances to combustibles: 1" (26 mm) at all sides for all vertical runs; and 3" (77 mm) at the top, 1" (26 mm) at sides, and 1" (26 mm) at the bottom for all horizontal/inclined runs.
J. Assemble vent run to exterior wall - If not
previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Step B.
Square Horizontal Termination- (SV4.5 HTSS)
Assemble the venting system to a point where the terminus of the last section is within 6" (152mm) to 9" (228mm) inboard of the exterior surface to which the termination is to be at­tached, see Figure 4. Attach Adaptor SV4.5RCH as shown in Figure 3.
*Firestop/Spacer (SV4.5HF) shown
on the exterior side of the wall. It
may also be installed on the
interior side.
SV4.5 HTSS Termination
Shown.
10-1/2"
(267 mm)
7"
(178)
5-1/8"
(130 mm)
12-1/8"
(308 mm)
NOTE: Centerline of Vent
Piping is NOT the Same as
the Centerline of the
Framed Opening.
6” to 48” Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Base of Appliance
3"
(77 mm)
1"
(26 mm)
Adaptor
SV4.5RCH or
SV4.5RCHA
*
NOTE: When using Secure Flex
use Firestop/Spacer SF4.5HF
See Fireplace
Installation Instructions
For Min. Distance to
Base of Appliance.
If the terminus of the last section is not within this distance, use the telescopic vent section SV4.5LA, as the last vent section for up to 15­3/4" (400mm). For distance greater than 15-1/4" (400mm) use adaptor SV4.5RCHA and refer to Table 1. This table lists venting components needed in addition to the termination adaptor. Also refer to the vent section length chart in the fireplace installation instructions manual for help on selecting additional vent sections.
Square Horizontal Termination ­(Kit No. SV4.5-20SSWSK)
Assemble the venting system to a point where the terminus of the last section is within 6" (152mm) to 21-1/4" (540mm) inboard of the exterior surface to which the termination is to be attached, see Figure 5. Attach Adaptor SV4.5RCHA as shown in Figure 3. Go to Step
It may be necessary to cut the excess length from the adaptor. Measure the distance from the last venting section to the exterior surface to which the termination is to be attached, see Figure 3. This is the total length the adaptor must be.
a) Separate the inner and outer pipes from the adaptor.
b) Mark the desired length of the outer pipe measured from the dimpled end towards the plain end.
c) Cut the excess material with sheet metal scissors or similar tool.
* To help minimize water infiltra­tion it is recommended that the Firestop/Spacer (SV4.5HF) be installed on the exterior side of the wall.
d) Proceed to mark the inner pipe using the
same dimension for the outer pipe, it is rec­ommended to add 1/4" to the length to aid in catching the mating pipe when inserting the termination.
L. Install Firestop/Spacer at exterior wall
- When using either of the square termina-
tions, install SV4.5HF (Secure Vent), or SF4.5HF (Secure Flex) firestop/spacer over the opening at the exterior side of the framing, long side up, with the 3" spacer clearance at the top as shown in Figure 3, and nail into place. (The Firestop/ Spacer may be installed over the opening at the interior side of the framing).
K for cutting to length instructions.
K. Attach Termination Adaptor ­Square Horizontal Termination Kit SV4.5HTSS (with short adaptor)
Attach adaptor SV4.5RCH (provided with the termination kit), to the vent section or telescop­ing vent section, elbow or appliance collar as shown in Figure 3, in the same manner as any SV4.5 vent component (refer to Step E).
Square Horizontal Termination Kit SV4.5-20SSWSK (with short adaptor)
f i r e - p a r t s . c o m
Attach adaptor SV4.5RCHA (provided with the termination kit No. SV4.5-20SSWSK), to the vent section or telescoping vent section, elbow or appliance collar as shown in Figure 3, in the same manner as any SV4.5 vent component (refer to Step E).
Figure 3 - Short Square Horizontal Termination (SV4.5HTSS)
Firestop/spacer (SV4.5HF) required, but not shown
Interior surface of finished wall
Maximum extent of vent run relative to exterior surface of framing
Last vent section (use telescopic vent section [SV4.5LA], if necessary)
Adaptor SV4.5RCH
Siding
*
Stucco
* To prevent water infiltration in wet environments, use a silicone sealant between the termination and the wall. High temperature sealant is not required.
Figure 4 - 6" to 9-1/4" Wall Thickness, SV4.5HTSS Terminations
SV4.5HTSS Small square termination shown
Minimum wall thickness 6" (153 mm)
Maximum wall thickness 9-1/4" (235 mm)
Exterior surface of siding
Exterior surface of framing
6 to 9-1/4" (153–235 mm)
Cut termination collar and adaptor for wall thickness < 6" (153 mm)
SV4.5HTSS Small square termination shown
1-1/4" Maximum recess of square termination into exterior finishing material
Firestop/spacer (SV4.5HF) required, but not shown
When using Secure Flex, use firestop/spacer SF4.5HF
For wall thickness, refer to
Table 1
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Cut termination collar and adaptor for wall thickness < 9" (229 mm)
Interior surface of finished wall
Maximum extent of vent run relative to exterior surface of framing
Last vent section (use telescopic vent section [SV4.5LA], if necessary)
Termination securing screw
Siding
*
Stucco
* To prevent water infiltration in wet environments, use a silicone sealant between the termination and the wall. High temperature sealant is not required.
SV4.5HTSS Square termination shown
Minimum wall thickness 9" (229 mm)
Maximum wall thickness 21-1/4" (540 mm)
Exterior surface of siding
Exterior surface of framing
9 to 21-1/4" (229–540 mm)
SV4.5HTSS Square termination shown
1-1/4" Maximum recess of square termination into exterior finishing material
Firestop/spacer (SV4.5HF) required, but not shown
When using Secure Flex, use firestop/spacer SF4.5HF
Figure 5 - 9" to 21-1/4" Wall Thickness, SV4.5-20SSWSK Terminations
3
*Wall Firestop/Spacer
(SV4.5HF)
28” (711 mm)
Maximum
NOTE: In applications where the wall thickness is less than 6” (152 mm), field shortening of the termination collar and adaptor may be required.
SV4.5HTSS Termination Shown
20” (508 mm)
Maximum
*When using Secure Flex,
use Firestop/Spacer
(SF4.5HF)
*Wall Firestop/Spacer
(SV4.5HF)
28” (711 mm)
Maximum.
NOTE: It may be necessary to cut the termination collar and adaptor in some applications.
10-1/2” to 20”
(267 to 508 mm)
12” Vent Section
(SV4.5L12)
*When using Secure flex,
use Firestop/Spacer
SF4.5HF)
M. Install the desired termination -
1. Install the short square termination (SV4.5HTSS) - For the last step , from outside
the exterior wall, slide the collars of the ter­mination into the adaptor (see Figure 4) until the termination seats against the exterior wall surface to which it will be attached. Orient the housing of the termination with the arrow pointed upwards. Secure the termination to the exterior wall.
The horizontal termination must not be recessed into the exterior wall or siding by more than the
1-1/4" (32 mm) as shown in Figure 4.
2. Install the square termination (SV4.5HTSS)
- For the last step , from outside the exterior wall,
slide the collars of the termination onto the last vent section (see Figure 5) until the termination seats against the exterior wall surface to which it will be attached.
Orient the housing of the termination with the arrow pointed upwards. Secure the termination to the exterior wall. The horizontal termination
must not be recessed into the exterior wall or siding by more than the 1-1/4" (32 mm) as
shown in Figure 5.
**NOTE: To prevent water infiltration in wet
environments, we recommend the use of a silicone sealant between the termination and the wall. (Refer to Figure 4 and Figure 5).
HORIZONTAL VENT FIGURES/TABLES
Venting Components Required for Various exterior
Wall Thicknesses*, When Using the Small Square Termination
(SV4.5HTSS)
Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only 6 to 9-1/4" (153 to 235)
Termination Kit and 6" Vent Section (SV4.5L6)
Termination Kit and 12" Vent Section (SV4.5L12)
Termination with 20" adaptor SV4.5RCHA
f i r e - p a r t s . c o m
Termination Kit and Telescop­ic section (SV4.5LA) and 6" vent section (SV4.5L6)
* NOTE: See Figure 7 for wall thickness range reductions
Table 1
when using SV4.5HTSS terminations.
10-3/4 to 14 (273 to 356)
16-3/4 to 20 (426 to 508)
9" (229 mm) to 21-1/4" (540 mm)
11-3/4 to 20 (299 to 508)
NOTE: Secure Vent® components (rigid vent pipe and terminal) are shown in the figures; Secure Flex® components (flexible vent pipe and terminal) may also be used.
NOTE: SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible wall.
NOTE: Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting figures for 90 elbows, must be followed if 45 degree elbows are used.
NOTE: It is very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of 1/4" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
WARNING
Under no circumstances, may separate sections of con­centric flexible vent pipe be joined together.
See Table 1 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Figure 6 -
4
Rear Vent - NO ELBOWS - with SV4.5HTS-2 SQUARE OR SV4.5HTSS SHORT SQUARE TERMINATION
Figure 7 -
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Rear Vent - NO ELBOWS - with SV4.5HTSS LONG SQUARE TERMINATION
HORIZONTAL VENT FIGURES/TABLES (CONTINUED)
H
*Wall Firestop/Spacer
(SV4.5HF)
V
*When using Secure Flex®, use Wall Firestop/Spacer SV4.5HF
AELBAT
wobleeerged09en0=V
.xaM)m419.0(teef3=H
Vm
f)
1)
1)
2)
H
V
*Wall Firestop/Spacer
(SV4.5HF)
**Ceiling Firestop/Spacer
(SV4.5VF)
*When using Secure Flex,
use Wall Firestop/Spacer
SF4.5HF.
**When using Secure Flex, use Ceiling
Firestop/Spacer SF4.5VF.
Vm
HH
f)
1)
1)
2)
H
1
V
H
*Wall
Firestop/Spacer
(SV4.5HF)
**Ceiling
Firestop/Spacer
(SV4.5VF)
*Wall
Firestop/Spacer
(SV4.5HF)
*When using Secure
Flex, use Wall
Firestop/Spacer
SF4.5HF.
**When using Secure
Flex, use Ceiling
Firestop/Spacer
SF4.5VF.
Refer to Table 1 for an aid in venting component selection for a particular range of exterior wall thicknesses when using the square (SV4.5HTS-2) or small square (SV4.5HTSS).
Short Square Termination (SV4.5HTSS) shown; SV4.5-20SSWSK and SV4.5HT-2 may also be used.
Figure 8 - Top Vent - ONE 90 DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE
ELBATB
muminiM
teef)m(tee
1)503.0(5)25.1(
2)16.0(0
3)419.0(5
f i r e - p a r t s . c o m
4)22.1(0
umixaMH
m(
1)503.0(2)016.0(5)25.1(
1.3(
56.4(
2.6(
2)016.0(4)22.1(0
3)419.0(6)68.1(5
4)22.1(8)84.2(0
.xaM)m4.21(teef04=H+V
.xaM)m2.6(teef02=H
Refer to Table 1 for an aid in venting component selection for a particular range of exterior wall thicknesses when using the square (SV4.5HTS-2) or small square (SV4.5HTSS).
Short Square Termination (SV4.5HTSS) shown; SV4.5-20SSWSK and SV4.5HT-2 may also be used.
Refer to Table 1 for an aid in venting component selection for a particular range of exterior wall thicknesses when using the square (SV4.5HTS-2) or small square (SV4.5HTSS).
Short Square Termination (SV4.5HTSS) shown; SV4.5-20SSWSK and SV4.5HT-2 may also be used.
muminiM
teef)m(teef)m(tee
H+H+V
1
H+H
1
CELBAT
umixaM
+H
1
m(
1.3(
56.4(
2.6(
.xaM)m4.21(teef04=
.xaM)m84.2(teef8=H
.xaM)m2.6(teef02=
mumixaM
Figure 9 - Top Vent - ONE 90 DEGREE ELBOW -
ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
Figure 10 - Rear Vent - TWO 90 DEGREE ELBOWS
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
HORIZONTAL VENT FIGURES/TABLE (CONTINUED)
DELBAT
VM
MUMINI
H+H
1
mumixaM
teef)m(teef)m(
1)503.0(5)25.1(
2)016.0(01)1.3(
3)419.0(51)56.4(
4)22.1(02)2.6(
H+H+V
1
.xaM)m4.21(teef04=
H+H
1
.xaM)m2.6(teef02=
EELBAT
muminiMVmumixaMH
H+H
1H+2
mumixaM
teef)m(teef)m(teef)m(
1)503.0(2)016.0(5)25.1(
2)016.0(4)22.1(01)1.3(
3)419.0(6)68.1(51)56.4(
4)22.1(8)84.2(02)2.6(
H+H+V
1H+2
.xaM)m4.21(teef04=
.xaM)m84.2(teef8=H
H+H
1H+2
.xaM)m2.6(teef02=
V
H
**Ceiling Firestop/Spacer
(SV4.5VF)
*Wall Firestop/Spacer
(SV4.5HF)
*When using Secure Flex, use Wall Firestop/Spacer
SF4.5HF.
**When using Secure Flex,
use Ceiling Firestop/Spacer
SF4.5VF.
H
2
H
1
Hm
f)
1)
1)
2)
1
1
V
H
H
1
V
1
*Wall Firestop/spacer
(SV4.5HF)
**Ceiling Firestop/spacer
(SV4.5VF)
*Wall Firestop/spacer
(SV4.5HF)
**When using Secure flex, use Ceiling Firestop/spacer
SF4.5VF.
*When using Secure Flex,
use Wall Firestop/spacer
SF4.5HF.
Refer to Table 1 for an aid in venting component selection for a particular range of exterior wall thicknesses when using the square (SV4.5HTS-2) or small square (SV4.5HTSS).
*Wall Firestop/Spacer
(SV4.5HF)
H
H
1
V
Short Square Termination (SV4.5HTSS) shown; SV4.5-20SSWSK and SV4.5HT-2 may also be used.
Figure 11- Top Vent - TWO 90 DEGREE ELBOWS
*When using Secure Flex,
use Wall Firestop/Spacer
SF4.5HF.
**When using Secure
Flex, use Ceiling
Firestop/Spacer
SF4.5VF.
*Wall Firestop/Spacer
(SV4.5HF)
**Ceiling
Firestop/Spacer
(SV4.5VF)
f i r e - p a r t s . c o m
Refer to Table 1 for an aid in venting component selection for a particular range of exterior wall thicknesses when using the square (SV4.5HTS-2) or small square (SV4.5HTSS).
Short Square Termination (SV4.5HTSS) shown; SV4.5-20SSWSK and SV4.5HT-2 may also be used.
Figure 12 - Rear Vent - THREE 90 DEGREE ELBOWS
VM
MUMINI
teef)m(tee
1)503.0(5)25.1(
2)016.0(0
3)419.0(5
4)22.1(0
Refer to Table 1 for an aid in venting component selection for a particular range of exterior wall thicknesses when using the square (SV4.5HTS-2) or small square (SV4.5HTSS).
Short Square Termination (SV4.5HTSS) shown; SV4.5-20SSWSK and SV4.5HT-2 may also be used.
Figure 13 - Top Vent - THREE 90 DEGREE ELBOWS
6
H+H
1
V+V
H+H+
FELBAT
umixaM
m(
1.3(
56.4(
2.6(
.xaM)m2.6(teef02=
.xaM)m4.21(teef04=
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5" (127 mm)
Radius Minimum
SF-12 or SF-18 Flexible Vent Section
VERTICAL OR HORIZONTAL VENTING USING SECURE FLEX® KITS AND COMPONENTS
Secure Flex® venting kits and components may
be used in any venting application where rigid
Secure Vent® (SV4.5) direct vent components
can be used. All restrictions, clearances and allowances that pertain to the rigid piping apply to the flexible venting. Secure Flex kits may
not be modified; also, under no circumstances may separate sections of flex pipe be joined together. Secure Flex kits may be added to the end of a vent run made up of rigid Secure Vent (SV4.5) vent sections provided that doing
so does not violate any of the venting length, height, routing, horizontal to vertical ratio re­quirements or clearance considerations detailed in this manual.
Secure Flex kits come with an included adaptor that can be fitted to the appliance collar or the inclined channel end of the last Secure Vent (SV4.5) vent section in a rigid system in the exact same fashion as any other Secure Vent section. Align the dimpled end of the adaptor over the previously installed section or appliance collar, adjusting the radial alignment until the four locking dimples of the adaptor are aligned with the inlets of the four incline channels of the last vent section or collar. Push on the
f i r e - p a r t s . c o m
adaptor until it fully engages, then twist the adaptor clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
Attach the flexible vent to the adaptor as fol­lows (see also Figure 14):
A. Install the Inner Flex Pipe -
1. Install the small gear clamp loosely around
the inner flexible vent pipe, push it back out of the way.
2. Apply a bead of Mill-Pac Black (700°F) high temperature sealant - Catalog No. 10K81)
to the inner adaptor collar, approximately 1/2 inch from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slide the inner flex pipe over the adaptor col-
lar. Ensure the flexible vent pipe completely engages the adaptor collar to a distance of 1-3/4 inches from the end, and that it is free from damage or tears.
5. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor inner collar approximately 3/4 inch from the end of the flex.
6. Install three screws 120 degrees apart through the flexible vent pipe and into the adaptor collar just below the gear clamp to provide additional security to the connection.
NOTE: OUTER PIPE IS PULLED AWAY TO SHOW THE DETAIL OF THE INNER PIPE
Apply ONLY MIL-PAC BLACK HIGH TEMPERATURE SEALANT (Catalog No. 10K81) to the outside surface of both collars of the adaptor (be especially careful to fill the grooves of the outer collar to be covered by the flexible pipe) and slide flexible pipe over inner and outer adaptor collars.
1-3/4” (44 mm)
Flexible Pipe and
Adaptor Outer Collar Overlap
Adaptor
(SV4.5RF)
Figure 14
Attach Adaptor to Appliance
Collar, or Secure Vent Sections
B. Install the Outer Flex Pipe -
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out of the way.
2. Apply a bead of Mill-Pac Black (700°F) high temperature sealant - Catalog No. 10K81)
to the outer adaptor collar; to the grooves of the collar which extend approximately 1" from the end and to the flat surface, approximately 1-3/8" from the end.
3. Pull and extend the outer flexible vent pipe.
4. Slide the outer flex pipe over the adaptor col-
lar. Ensure the flexible vent pipe completely engages the adaptor collar to a distance of 1-3/4 inches from the end, and that it is free from damage or tears.
5. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor outer collar approximately 3/4 inch from the end of the flex.
6. Install three screws 120 degrees apart through the flexible vent pipe and into the adaptor collar just below the gear clamp to provide additional security to the connection.
C. Route Flex Vent - Ensure that the flex vent is properly routed to provide the required clearance. Do Not allow the flexible vent to bend in a radius tighter than 5" (127 mm). Refer to Figure 15. Support horizontal sections of flex with metal straps at 2 foot (0.61 m) intervals.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
FLEX VENT
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
GEAR CLAMPS
1-3/4” (44 mm)
Flexible Pipe and
Adaptor Inner Collar Overlap
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
D. Install Firestop/Spacers at ceilings and walls - When Secure Flex penetrates a wall or ceiling, a firestop/spacer is required: use the SF4.5 VF firestop/spacer for ceilings and the SF4.5 HF firestop/spacer for walls. See the appropriate sections and figures shown throughout the vent­ing section for their installation requirements.
Figure 15
E. Attach Flex Vent to Termination - Secure Flex components can be purchased separately and attached to bulk lengths of Se­cure Flex flexible tubing cut to size at the job
site. Secure the flexible vent to the Secure Flex terminations in the same manner (see Figure
14) as it was attached to the adaptor.
NOTE: Secure Flex vent must be attached to Secure Flex terminations only. DO NOT substitute Secure Vent terminations or the Secure Vent adaptor for Secure Flex compo­nents. The collars of Secure Flex terminations and adaptors have a different circumference than that used with the Secure Vent pipe. Additionally, Secure Flex components have an extended length center tube for use in attaching the flexible vent.
7
f i r e - p a r t s . c o m
IHP reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2005 Innovative Hearth Products
8
P/N 750204M REV. H 04/2018
1769 East Lawrence Street • Russellville, AL 35654
Loading...