IHP RC-S-MODMV Installation And Operation Instructions Manual

Page 1
Cat. No. H8862 MODEL: RC-S-MODMV
MODE
TIME
TIMER
SET
DOWN
UP
+
+
-
-
FAN
FLAME
ON
OFF
THERMO
X
ROOM
SET
AM PM
TIMER
FLAME
E
E
1
2
3
4
5
6
7
8
FAN
HI MED LOW OFF
9
INSTALLATION AND OPERATION INSTRUCTIONS
IF YOU CANNOT READ OR UNDERSTAND THESE INSTALLATION INSTRUCTIONS DO
NOT ATTEMPT TO INSTALL OR OPERATE
INTRODUCTION
This remote control system was developed to provide safe, reliable, user-friendly remote control system for gas heating appliances. The system can be operated manually from the transmitter.
TRANSMITTER
The transmitter operates on (2) AAA 1.5V batteries that are included. Install the AAA batteries supplied with the unit into the battery compartment. It is recommended that ALKALINE batteries always be used for this product. Be sure the batteries are
installed with the (+) and (-) ends facing the correct direction.
If the transmitter does not illuminate when you press any buttons, or you see nothing on the LCD screen, check the position of the batteries.
LIQUID CRYSTAL DISPLAY - LCD
1. Low Battery Indicator - Battery power is low, replace batteries within two weeks.
2. Timer - Time remaining before the system shuts off, must be programmed.
3. Mode - Indicates whether the system is ON, OFF, or in THERMO mode.
4. Set - Indicates the desired SET temperature when in THERMO mode.
5. Flame - Indicates burner/valve operational.
6. Clock - Indicates current time.
7. Room - Indicates current ROOM temperature.
8. ºF - Indicates degrees Fahrenheit (ºC indicates degrees Celsius).
9. Fan - Indicates the fan is ON, or is programmed to come ON.
MODE FUNCTION
To select an operational mode, press the MODE button on the transmitter.
ON - Turns the appliance ON, the ame icon will appear on the LCD screen. THERMO - Remote is in THERMO mode. OFF - Turns the appliance OFF, the ame will disappear from the LCD screen.
SETTING ºFAHRENHEIT / ºCELSIUS SCALE
The factory setting for temperature is degrees Fahrenheit (ºF). To change this setting to degrees Centigrade (ºC):
Remove battery cover on the back of the transmitter and locate the setting
Push the button once to enter temperature scale setting mode.
Use the up and down buttons to switch between the ºF and ºC.
Push the setting button again once again to set the displayed temperature
Repeat this procedure to switch back to ºF.
IHP: RC-S-MODMV
button in the top center of the battery compartment.
scale.
P/N 900258-00 Rev. B
+
SETTING BUTTON
-
REV. 1-8-15 Page 1
Page 2
THERMOSTAT FUNCTION
Press the MODE key until the LCD screen shows the word “THERMO” at the top of the screen.
To adjust set temperature, press the UP and DOWN but­tons until the desired temperature is reached. The tempera­ture range is 99ºF (32ºC) to 45ºF (6ºC).
If no button is pressed, the set temperature will automati­cally be accepted.
The ame icon will appear when the control calls for heat.
The ame icon will disappear when the appliance reaches
FLAME HEIGHT
This remote control system allows the user to control the height
of the ame when the gas valve is factory equipped with a ame
controller.
Press and release the ame button to change the ame from regular to HI.
When the ame is switched to HI, the word HI in a black box and
a second ame appears in the lower right hand corner of the LCD screen. When switched back to regular ame, they both
disappear.
its set temperature.
Press the MODE key to disengage the Thermo Mode.
SETTING THE TEMPERATURE SWING (TEMPERATURE DIFFERENTIAL)
The Thermo Mode on the transmitter operates the appliance whenever the room temperature varies a certain number of degrees from the set temperature. This variation is called the “SWING” or TEMPERATURE DIFFERENTIAL. The factory preset swing temperature is 2 ºF (1 ºC). To change the “Swing Setting:”
SETTING THE CLOCK
Hold the TIMER/TIME button for 3 seconds. The hour section of
the time should begin ashing.
Select the hour by pressing the UP and DOWN buttons. If you go past 12 o’clock the AM and PM will change.
Once the hour is selected, press and release the TIMER/TIME button again, and the minute section of the time should be
ashing.
Use the UP and DOWN buttons to scroll through the minutes.
Once the minutes are correct, press and hold the TIMER/TIME button for 3 seconds. The time is now set.
OPERATING THE FAN
This remote control system has the capability of operating a 110 VAC fan or blower system that may be included with you gas replace.
The fan will only operate when the transmitter in the ON or THERMO modes (THERMO or ON must be displayed on the LCD Screen).
To turn ON the fan, press the FAN button on your transmitter.
You can switch through the various positions by pressing the fan until the desired speed is obtained.
Your speed options are High, Medium, Low, and Off.
SETTING THE COUNTDOWN TIMER
This remote control system can operate with a built-in countdown timer when the transmitter is in the ON or THERMO modes (THERMO or ON must be displayed on the screen).
Press and release the TIMER button. The minimum 0:15 minute setting on the will begin to ash.
Press the UP or DOWN button on the transmitter to chose your countdown time. Available countdown times are 15 min, 30 min, 45 min, 1 hour to 9 hours (alternating every 30 min).
To initiate the countdown, simply press the SET button or wait 15 seconds for it to stop ashing. The appliance will turn off when the timer runs out.
RECEIVER
The remote receiver os powered by 110-120VAC. It plugs into a standard polarized duplex receptacle. The remote receiver has a
3-position slide switch for selecting the mode of operation ON/REMOTE/OFF
ON: will manually turn ON the appliance.
REMOTE: will allow use of handheld transmitter. If the system does not
respond to the transmitter on initial use, check the battery positions in the remote. If that does not work, see the LEARNING TRANSMITTER TO RECEIVER section.
OFF: will disable the remote receiver.
LEARN
FLAME
CONTROL
VALVE
GROUND
OFF REMOTE ON
It is suggested that the slide switch be placed in the OFF position if you will be away from your home for an extended period of time.
WARNING
This remote control system must be installed exactly as outlined in these instructions. Read all instructions completely before at­tempting installation. Follow instructions carefully during installation. Any modications of this remote control or any of its compo­nents will void the warranty and may pose a re hazard.
Do not connect any gas valve or electronic module directly to 110-120VAC power. Consult gas appliance manufacturer’s instruc­tions and wiring schematics for proper placement of all wires. All electronic modules are to be wired to manufacturer’s specica­tions.
The following wiring diagrams are for illustration purpose only. Follow instructions from manufacturer of gas valve and/or electronic module for correct wiring procedures. Improper installation of electric components can cause damage to electronic module, gas valve and remote receiver.
IHP: RC-S-MODMV
P/N 900258-00 Rev. B
REV. 1-8-15 Page 2
Page 3
OFF REMOTE ON
LEARN
GROUND
VALVE
FLAME
CONTROL
INSTALLATION
TERMINAL BLOCK
ON MILLIVOLT
GAS VALVES
TH
TP
TP
TH
THERMOPILE/
PILOT LIGHT
REMOTE
RECEIVER
Before installation make sure the remote receiver slide switch is in the OFF position. After installation be sure that the slide switch is moved to the REMOTE position.
MOUNTING THE REMOTE RECEIVER
HEARTH MOUNT
The remote receiver can be placed on the replace hearth or under the re­place behind the control access panel.
MAKE SURE THAT WHERE THE RECEIVER IS PLACED DOES NOT EXCEED 170ºF. IT WILL CAUSE DAMAGE TO THE PRODUCT.
Use the wires attached to the remote receiver to connect to the gas valve or the electric module.
Be sure that the connectors do not touch each other or other bare metal surfaces; this will cause the appliance to turn ON. The connectors may be wrapped with electrical tape to prevent this.
WIRING INSTRUCTIONS
A qualied electrician should install the remote control system.
WIRING MILLIVOLT VALVES
Connect one wire from the remote receiver’s “valve” connection to the TH terminal on the gas valve.
Connect the other wire from the remote receiver’s “valve” connection to the TH/TP terminal on the gas valve.
MILLIVOLT SYSTEM CHECK
Ensure that the pilot ame is lit.
Slide the 3-position button on the remote receiver to the ON position. The main gas ame (i.e., the re) should ignite.
Slide the button to OFF. The main ame should extinguish (the pilot ame will remain on).
Slide the button to REMOTE, then press the ON button on the transmitter to change the system to on. The main
gas ame should ignite.
WIRING ELECTRONIC SPARK IGNITIONS
Take both switch/thermostatic wires from the Electronic Module, and connect them to the receiver wires using
I
ELECTRONIC SPARK SYSTEM CHECK
Slide the 3-position button on the remote receiver to the ON position. The spark electrode should begin sparking to ignite the pilot.
After the pilot ame is lit, the main gas valve should open and the main gas ame should ignite.
Slide the button to OFF. The main gas ame and pilot ame should both extinguish.
Slide the button to REMOTE, then select “ON” with the mode button on the transmitter to change the system to ON. The spark
electrode should begin sparking to ignite the pilot. After the pilot is lit, the main gas valve should open and the main gas ame
should ignite.
IHP: RC-S-MODMV
S
Electronic
Module
Switch
Wires
Piggyback
Connectors
P/N 900258-00 Rev. B
REMOTE
RECEIVER
the spade connectors.
NOTE: An adaptor may be necessary to
make the connection between the Electronic
Module and the Remote Receiver.
REV. 1-8-15 Page 3
Page 4
INSTALLING FLAME CONTROL SOLENOID
ALL STEPS REQUIRED FOR INSTALLATION OF THE FLAME CONTROLLER MUST BE DONE BY
A QUALIFIED GAS SERVICE TECHNICIAN
1. Using a athead screwdriver, remove and set aside the three pressure regulator mounting screws (A), pressure regulator tower (B), and spring diaphragm assembly (C) and keep them in a safe place. (See Figure 1)
2. Ensure the rubber gasket (D), which is pre-tted as part of the assembly (E), is properly positioned and install the new pressure regulator tower using the supplied screws (F). Tighten screws securely and remove cover screw (G). (See Figure 1)
3. LP INSTALLATIONS ONLY: Mark the location of the slot in the slotted nut
under cover screw (G). Using a athead screwdriver, turn the slotted nut exactly 2 full turns (720 degrees) clockwise.
4. Insert the correct plunger into the ame control solenoid (BLUE = NATU­RAL GAS, RED = PROPANE). (See Figure 2)
5. Ensure that the Flame Control Solenoid is disconnected from the remote
receiver box.
6. Screw the Solenoid on the to new regulator tower until it stops turning. Then tighten the jam nut. (See Figure 2)
7. Now take the blue wires (connected to the solenoid) and attach them to the orange wires (on the receiver). (See Figure 3)
CAUTION
TO ENSURE SAFE OPERATION, THE OUTLET PRESSURES ON BOTH
REGULAR AND HI FLAME LEVELS SHOULD BE CHECKED WITH A MA-
NOMETER IN ACCORDANCE WITH SPECIFICATIONS SUPPLIED BY THE
VALVE MANUFACTURER.
Fig. 1
Fig. 3
IHP: RC-S-MODMV
P/N 900258-00 Rev. B
Fig. 2
REV. 1-8-15 Page 4
Page 5
INSTALLING FAN/BLOWER
Plug 2 or 3 prong plug fan cord directly into the 3 prong polarized plug on back of the receiver. This receptacle receiver is rated at 110/120VAC, 3AMP.
Line cord
from fan
LEARN
FLAME
CONTROL
VALVE
GROUND
OFF REMOTE ON
COMMUNICATION - SAFETY - TRANSMITTER - (C/S - T/X)
This remote control has a COMMUNICATION –SAFETY function built into its software to ensure the transmitter and receiver are com­municating normally.
In all operating modes, the transmitter sends an RF signal every fteen minutes to the receiver indicating that the transmitter is within
the normal operating range of 20-feet. Should the receiver NOT receive this signal, the receiver will begin a 2-hour countdown. If the receiver does not receive a signal from the transmitter in 2 hours, the receiver will shut off the appliance. The receiver will then emit a series of rapid “beeps” for a period of 10 seconds. Then after 10 seconds of rapid beeping, the receiver will continue to emit a single “beep” every 2 seconds until a transmitter MODE Button is pressed to reset the receiver.
AUTO SHUT DOWN
This remote control has an auto shut down feature incorporated into its system. When the transmitter mode is in the ON position, the appliance will only run for 9 hours. After that it will shut down. To reactivate the appliance, press the MODE button.
CP (CHILDPROOF) FEATURE
This remote control includes a childproof feature that allows the user to “lock-out” operations from the transmitter.
To activate and de-activate the childproof feature, press and hold the SETTING button behind the battery cover, for 5 seconds
(SEE The letters “CP” will briey appear on the LCD screen when childproof mode is activated).
“CP” will appear on the LCD screen if any button is pressed while childproof mode is engaged.
When this mode is engaged, all auto settings go on without interruption (like thermostat). Only manual functions are prevented.
TRANSMITTER WALL BRACKET
The transmitter can be hung on a wall using the clip provided.
Wood - Drill 1/8’’ pilot holes and install with screws provided.
Plaster/Wallboard - Drill 1/4’’ holes, tap anchors in with hammer, then install with the screws provided.
Slide Transmitter down into holder
BATTERY LIFE
Life expectancy of the alkaline batteries in the transmitter should be at least 12 months. Check and replace all batteries:
Annually.
When operating range becomes reduced.
When transmissions are not received by the remote receiver..
If the hand held transmitter batteries measure less than 2.4 volts (Both batteries in combination).
IHP: RC-S-MODMV
P/N 900258-00 Rev. B
REV. 1-8-15 Page 5
Page 6
LEARNING TRANSMITTER TO RECEIVER
This transmitter has one of 1,048,576 unique security codes. It may be necessary to program the remote receiver to “learn” the security
code of the transmitter upon initial use, if batteries are replaced, or if using a replacement transmitter.
Make sure the receiver’s slide switch is in the REMOTE position.
Press and release the LEARN button on the receiver.
When you hear the “Beep”, press and hold the MODE button for about 2 seconds on the transmitter.
If you not hear a beep after you press the LEARN button, check the power cord from the receiver and ensure it is plugged in and has power.
You will then hear a series of beeps that indicate that your new transmitter has been accepted by the receiver.
TROUBLE SHOOTING
If you encounter problems with your replace system, the problem may be with either the replace itself or with the remote. Review the replace manufacturer’s operation manual to make sure all connections are properly made. Then check the operation of the
remote in the following manner:
Make sure all batteries are correctly installed in the transmitter. Also check that the batteries are fully charged.
Check batteries in transmitter to make sure contacts are touching (+) and (-) ends of battery. Bend metal contacts in for tighter t.
Be sure receiver and transmitter are within 20 to 25-foot operating range.
Keep receiver from temperatures exceeding 170º F.
If receiver is installed in a tightly enclosed metal surrounding, the operating distance will be shortened.
Make sure the hand-held transmitter and remote receiver are communicating properly (see LEARNING TRANSMITTER TO RECEIVER section).
FCC REQUIREMENTS
NOTE: THE MANUFACTURER IS NOT RESPONSIBLE FOR ANY RADIO OR TV INTERFERENCE CAUSED BY UNAUTHORIZED MODI-
FICATIONS TO THE EQUIPMENT. SUCH MODIFICATIONS COULD VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you
purchased the product. If you cannot locate the dealer/distributor, then you must notify IHP in writing. IHP must be
notied of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to the IHP
Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210 or
visit our website at www.IHP.us.com
IHP: RC-S-MODMV
P/N 900258-00 Rev. B
REV. 1-8-15 Page 6
Loading...