Ignis gamma v 2.15 Quick Manual

1
2
IGNIS gamma v 2.15
Ignis gamma v2.15 is a microprocessor temperature regulator to control the central heating boiler with a solid fuel feeding screw. The Ignis gamma v2.15 controller with room sensor supports the preset room temperatures according to established time programs.
APPLICATION
The purpose of Ignis gamma v2.15 is automatic control of feeding screw, blower, central heating pump (CH pump) and feeding pump for tap water container (TW container).
FRONT PANEL
Controls:
feeding pump for TW container
CH pump
blower
feeding
parameter setting MENU ON/OFF
MENU navigation and parameter setting
MAIN DISPLAYS
controller operation status
current boiler temperature
current tap water temperature
current room temperature
boiler temperature setting
current day/hour
controller daytime
room temperature for daytime
The main displays operate changing in cyclic mode. The boiler temperature can be set on Display 1 using buttons and . The arrow we can use to change displays in manual mode. In 30 seconds the controller returns to its cyclic operation of changing displays.
Mo 12:35 Daily & 21,5*
- day
- day edition
- day selection
- copy to other day
- daytime
- hour selection
- enter the copy
- reset the day for introduced copy
Mo@ EDIT@ COPY#
Mo (! 7@ &21,0* ^^^^^^& &&&& @
Mo@ COPY
TO )Tu @
)Mo@^^^^^^&&&&&& &&&&&&&&====
OPERATION
The boiler is fired up in MANUAL MODE (f). To start MANUAL MODE press MENU and next use and .
When the feeder is started wait till coal is delivered to retort then stop the feeder and fire up the coal. The blower can be used during this operation with its whole range of power.
If there is fire in the whole retort, you can change operation mode into automatic. For this purpose press MENU and next - START. Operation status changes from STOP to FIRE UP. The blower is working with its maximum power and the feeder delivers coal regularly.
When the BURNING OUT TEMPERATURE (M) is exceeded controller starts HEAT.
If maximum and minimum power of the blower are different the quantity of delivered air and fuel decreases (feeder operation time is automatically reduced) as the temperature is drawing near the value preset by user and increases as the temperature is drawing away.
When the preset temperature is exceeded, the controller changes to HOLD mode. The feeder and blower begin periodical operation to keep fire on. Whereas, there is possibility to stop blower as in case of using the sawdust as solid fuel.
If the boiler temperature decreases, controller changes over to HEAT. If the boiler temperature drops below the value of BURNING OUT TEMPERATURE controller changes to STOP status. However controller cannot change to STOP, if the FIRE UP (F) time has not been completed since pressing START, that is setting of 1 hour - made by producer.
The controller operation can be stopped at any time by pressing - STOP. In STOP status the blower and feeder are stopped.
ROOM TEMPERATURES ROOM TEMPERATURES parameter (a) see page 3.
Controller keeps up the room temperature in three daytimes accordingly;
day period, night period, economy period.
The operator can set different room temperature for each of these periods. If the preset room temperature is exceeded the CH pump stops and controller changes to HOLD status.
Each day and hour can have any of those period set.
DAYTIME PROGRAM EDITION DAYTIME PROGRAM parameter(b) see page 3
& ^ =
display informs: Monday 00:00 - 05:59 night period 06:00 - 19:59 day period 20:00 - 23:59 economic period
holding or changes between copy daytime and an hour selection
!a@ ROOM TEMP. EDIT#
!b@TIME PROGRAMS
EDIT#
Blower [$ ! 30@% Feeding [#
!c@ WARM WATER
TEMP: 45)*
!d@ TIME DAY
12:30$ Fr#
HOUR:MINUTES
12:30
TEMP:!&@ &)21,0*
^ 18,0* = 17,0*
!e@ SEASON
WINTER)
!f@ MANUAL
$START$
TAP WATER PUMP (TW PUMP) OPERATION
TW pump starts when the boiler reaches TW PUMP START (H) temperature and keeps working till the container reaches WARM WATER (c) temperature. The following TW pump start occurs when the container temperature decrease is equal to TW HYSTERESIS (I). The pump will not start again if the boiler temperature is not at least 5°C higher than temperature of container (protection for the container against cooling due to over-cooled boiler).
RESETTING
The flickery arrows ! @ $, # and ) inform which button must be used to operate MENU and make any resetting.
and are for parameter changing and MENU navigation
and are for MENU navigation
Button enables the following returns to each previous displays till you are back on the MAIN DISPLAY. If the operator makes any modifications the controller will ask if those modifications are to be entered to memory. If there is no reaction during 1 minute, controller returns to MAIN DISPLAY and does not introduce any new data.
The other settings can be change after pressing MENU:
, ,
a) room temperature for each daytime
& -day period ^ -night period = -economic period
b) time programs
daytime for each day and hour daytime - hour , day (see
page 2)
c) tap water container temperature
d) hour setting display
day edition
and hour and minute setting
and active parameter selection
e) the season edition
WINTER - central heating and tap water pumps control
SUMMER - tap water pump control only
f) manual mode on
blower ON( )/OFF( ) feeder ON( )/OFF( ) and blower power increasing and decreasing
] [ ] [
MANUAL MODE
Manual mode enables the blower and feeding screw start and stop at any time. Manual mode is very useful at the firing up process if the feeding screw is empty.
Having the container filled with coal the feeding screw must be started and kept on till the coal appears in the retort.
Next the feeding screw must be stopped and the coal in retort partly fired up. Then the blower must be started on and its power set accordingly ( percent figure is given on the display). If the coal in retort is completely fired up the MANUAL mode must be stopped by pushing MENU and next - START.
SEQUENCE OF WIRES CONNECTION
TAP WATER FEEDING PUMP
CENTRAL HEATING PUMP
FEEDING SCREEW
BLOWER
EMERGENCY BLOWER BREAKER
POWER
ROOM TEMPERATURE SENSOR
BOILER TEMPERATURE SENSOR
FEEDER TEMPERATURE SENSOR
TAP WATER CONTAINER
TEMPERATURE SENSOR
WARRANTY
TMK (registered partnership) warrants 3 year product warranty for IGNIS gamma v2.15 controller. Warranty starts in the day of purchase and cannot be longer than 4 years since production date.
WARANTY CONDITIONS
The warranty is given under condition of the unit application in accordance with this instruction literally and general rules of the electronic units operation. TMK guarantees correct workmanship, high quality and reliability of the IGNIS gamma v2.15 controller. In case of any malfunction or defect due to the fault of manufacturer, TMK undertakes to repair it or replace the controller for a new one in term of 14 days since the fault product return to producer (personally or by post).
Warranty does not include any damage caused by fault of the user, especially due to mechanical failure, incorrect assembling, humidity or if the user fails to comply with general rules of electronic units operation.
DATE OF SALE …………………………
…………………………
Stamp and salesman signature
…………………………
MANUFACTURER ADDRESS
TMK sp.j. (registered partnership) Szosa Witkowska 105 62-300 Września, Poland
Tel./fax +48 61 437 97 60 mail: tmk@tmk.com.pl www.tmk.com.pl
MANUFACTURE DATE
!C@ OPER. TIME
HOLD: 10)s
!D@ BRAKE TIME
FOR HOLD: 30)m
!F@ FIRE UP
TIME: 60)m
!G@ CH PUMP ON
TEMP: 35)*
!H@ TW PUMP ON
TEMP: 30)*
!J@TW PUMP ON
NO )
!I@TW HYSTERESIS
TEMP: 3)*
!L@ BLOWER POWER
MAX: 100)%
!A@ OPER. TIME
HEAT: 10)s
!B@ BREAK TIME
HEAT: 30)s
!E@ BLOW TIME
MULTIPL: 2)
!K@
TW HEATING
BOILER>TW C +10)*
OPERATING SETTINGS
To enter the OPERATING MENU press MENU on MAIN DISPLAY and hold it 2 seconds.
A) Feeder operation time for HEAT - the boiler temperature
value.
below the setting
B) Feeder operation break time for HEAT
C) Feeder and blower operation time for HOLD - boiler temperature above the
setting value. The blower operation time can be increased by the blowing time multiplier (E)
D) Feeder and blower operation break time for HOLD
E) In f orma tion ho w m any tim e s the blo w er oper atio n t ime
is longer than feeder operation time at HOLD. It informs about the time necessary for blowing the fire after boiler operation break.
F) Time since t he controller operation START during which
the boiler is not OFF in spite of temperature decrease below the value of BURNING OUT TEMPERATURE .
G) CH pump start temperature
H) TW (tap water) feeding pump starting temperature
I) TW (tap water) container temperature decrease necessary to start the TW
pump.
J) TW (tap water) feeding pump priority towards CH (central heating) pump
K) Increasing the boiler temperature value while TW container is heating up if
this temperature is too low. The higher temperature setting the shorter heating up time.
L) Blower maximum power.
The blower power upper limit.
IGNIS gamma v 2.15
!M@ BLOWER POWER
MIN: 30)%
!T@ FACTORY SET
$RETURN$
!N@ BOILER OFF
TEMP: 35)*
!O@ FEEDER ALARM
TIME: 5)m
!P@ FEEDER ALARM
TEMP:100)*
!R@CH PUMP START SUMMER: 80)*
!S@KEEPING BOILER TEMP NO)
M) Blower minimum power.
The blower power lower limit.
N) The temperature limit below which controller makes the boiler OFF when
the FIRE UP TIME is completed.
O) The coal pushing time when the feeder alarm temperature is exceeded. (To
prevent the flashback from the boiler to coal container).
P) Feeder alarm temperature value. Exceeding this temperature the feeder
starts its operation to withdraw fire from feeder to the boiler. (To prevent the flashback from the boiler to coal container).
R) CH pump alarm temperature to start CH pump in SUMMER mode. When
this temperature value is exceeded CH pump starts working to cool down boiler. (To avoid boiling water in the boiler).
S) Parameter informing if in case of CH pump stop due to obtaining the preset
room temperature value,
i) boiler will obtain the preset boiler temperature and keep it ( on
display)
ii) boiler will be in HOLD status till CH pump start (NO on display)
YES
T) Return to the factory settings. Controller makes possible the return to
factory settings. After pressing the question concerning confirmation of your decision will appear.