IFM Electronic VSE150, VSE153, VSE151 Installation Instructions Manual

Page 1
Installation instructions
Diagnostic electronics
for vibration sensors
VSE150 VSE151 VSE153
80270678/00 10/2017
UK
Page 2
1 Functions and features
The diagnostic electronics has 2 analogue inputs and 4 dynamic inputs. These inputs can be used for process value monitoring, vibration monitoring, vibration diagnostics or analysis of other dynamic signals.
2 Symbols used
Instructions
Important note Non-compliance may result in malfunction or interference.
3 Installation
► Disconnect the system from power before installation.
► Mount the unit in a control cabinet with a protection rating of at least IP 54 to
ensure protection against accidental contact with dangerous contact voltages and against atmospheric influence. The control cabinet has to be installed in
accordance with local and national regulations. ► Mount the unit vertically on a DIN rail. ► Leave enough space between the unit and the top or bottom of the control
cabinet to enable air circulation and to avoid excessive heating.
3.1 Installation instructions
Electrostatic discharge The device contains components that can be damaged or destroyed by
electrostatic discharge.
► When handling the device, observe the necessary safety precautions against
electrostatic discharge (ESD) according to EN 61340-5-1 and IEC 61340-5-1. ► In order to dissipate electrostatic charges, the unit may only be operated on a
grounded DIN rail.
Page 3
UK
4 Electrical connection
The unit must be connected by a qualified electrician. The national and international regulations for the installation of electrical equipment must be adhered to.
► Disconnect the system from power and connect the unit.
4.1 Interfaces
LEDs
1
2
3
VSE150 VSE151 VSE153
1 1: Confi g: TCP/IP, IP address 192.168.0.1 (factory setting), parameter setting and
data interface (e.g. VES004)
2 IE 1: PROFINET IO IE 1: EtherNet/IP IE 1: Modbus TCP
3 IE 2: PROFINET IO IE 2: EtherNet/IP IE 2: Modbus TCP
Page 4
4.2 Wiring
18
17
20
19
14
13
16
15
22
21
24
23
6
5
8
7
2
1
4
3
10
9
12
11
Supply L- (GND) OU 1: switch/analog OU 2: switch
IN 1 (0/4...20 mA / pulse)
GND 1 IN 2 (0/4...20 mA / pulse)
GND 2
1
2
3
4
4
3
2
1
1
2
3
4
1
2
3
4
Supply L+ (24 V DC ±20 %)
Sensor 1
Sensor 2
Sensor 3
Sensor 4
Wiring of the sensors 1...4 (S1...S4) according to the connected unit
Sensor VSA IEPE/VSP 0...20 mA
S1 S2 S3 S4
09 16 20 24 BN: L+ (+ 9 V) not connected (n.c.) not connected (n.c.)
10 15 19 23 WH: signal IEPE + signal
11 14 18 22 BU: GND IEPE - GND
12 13 17 21 BK: test not connected (n.c.) not connected (n.c.)
Terminal 1 supply L+ When using an IEPE input 24 V + 20% (Integrated Electronics Piezo Electric)
5 Parameter setting
Parameter setting and configuration of the unit are exclusively made via the PC software VES004.
6 Technical data, approvals/standards
Detailed manuals, technical data, EC declaration of conformity, approvals and further information can be found at www.ifm.com.
Page 5
UK
7 Maintenance and disposal
The unit is maintenance-free.
► Dispose of the device including the battery in accordance with the national
environmental regulations.
8 Scale drawing
50
114,2
35
105,3
100,6