Installation Instructions
Airflow monitor analogue
SL5204
UK
701793/00 07/2003
![](/html/f8/f8c4/f8c46187c3173fd06a8b9678991b14487385f616e9f1307843ccac00e1a1f88e/bg2.png)
1 Function and features
The analog airflow monitor monitors airflows. It detects the flow velocity and converts it into an analog voltage signal.
Operating range: 2 m/s...30 m/s; Output signal: 1 V...10 V.
Ua [V]
10
9
8
7
6
5
4
3
2
1
2
4 6 8 10 12 14 16 18 20 22 24 26 28 30
v [m/s]
2 Mounting
Mount the airflow monitor by means of the mounting clamp provi-ded. Diameter of
the mounting hole for the unit: 24 mm. If mounting is to be airtight, use the gaskets
provided.
The insertion depth depends on the diameter / side length of the pipe:
Diameter / side length = 180 mm: The arrow
1 must be flush with the mounting clamp.
arrow 1
Diameter / side length ≤ 100 mm: Max.
distance of 30 mm between the arrow 2 on
the unit and the mounting clamp.
arrow 1
2
180mm
arrow 2
max.
30mm
≤ 100mm