IFM Electronic SL5204 Installation Instructions Manual

Installation Instructions
Airflow monitor analogue
SL5204
UK
701793/00 07/2003
1 Function and features
The analog airflow monitor monitors airflows. It detects the flow velocity and con­verts it into an analog voltage signal.
Operating range: 2 m/s...30 m/s; Output signal: 1 V...10 V.
Ua [V]
10
9 8 7 6 5 4 3 2 1
2
4 6 8 10 12 14 16 18 20 22 24 26 28 30
v [m/s]
2 Mounting
Mount the airflow monitor by means of the mounting clamp provi-ded. Diameter of the mounting hole for the unit: 24 mm. If mounting is to be airtight, use the gaskets provided. The insertion depth depends on the diameter / side length of the pipe:
Diameter / side length = 180 mm: The arrow 1 must be flush with the mounting clamp.
arrow 1
Diameter / side length 100 mm: Max. distance of 30 mm between the arrow 2 on the unit and the mounting clamp.
arrow 1
2
180mm
arrow 2
max.
30mm
100mm