9.3 Set output signals
9.3.1 Set output functions
► Select [OU1] and set the switching function:
- [Hno] = hysteresis function/NO�
- [Hnc] = hysteresis function/NC�
- [Fno] = window function/NO�
- [Fnc] = window function/NC�
► Select [OU2 ] and set the analogue function:
- [I] = current signal proportional to pressure 4…20 mA�
- [InEG] = current signal proportional to pressure 20…4 mA�
9.3.2 Set switching limits
► Select [SP1] and set the value at which the output switches�
► Select [rP1] and set the value at which OUT1 switches off�
rP1 is always smaller than SP1� The unit only accepts values which are
lower than SP1�
9.3.3 Scale analogue value for OUT2
► Set the minimum pressure requested in the system�
► Touch [Mode/Enter] until [tASP] appears�
► Touch [Set] and keep it touched�
> Current setting value flashes�
► Release [Set] when the display stops flashing�
> New setting value is displayed�
► Touch [Mode/Enter] briefly�
> The current system pressure is defined as start value for the analogue
signal�
► Set the maximum pressure requested in the system�
► Touch [Mode/Enter] until [tAEP] appears�
► Touch [Set] and keep it touched�
> Current setting value flashes�
► Release [Set] when the display stops flashing�
> New setting value is displayed�
► Touch [Mode/Enter] briefly�
> The current system pressure is defined as end value for the analogue
signal�
ASP / AEP can only be set automatically within defined limits (→ 12�1 Setting ranges)�
If automatic setting is carried out at an invalid pressure value, [UL] or [OL] is displayed�
After acknowledgement by [Mode/Enter] [Err] flashes, the ASP value / AEP value is not
changed�