IFM Electronic E70588, E70600 Installation Instructions Manual

Installation instructions
Quad M12
E70588
Quad
E70600
UK
7390873/00 03/2014
1 Functions and features
With the Quad M12 module the AS-i voltage and external voltage can be tapped via the M12 socket (current rating 4 A). Pin connection of the M12 socket:
pin 1 AS-i +
12
5
4
3
pin 2 0 V pin 3 AS-i ­pin 4 + 24 V pin 5 functional earth
2 Installation
► Disconnect power.
2.1 Installation of the lower part
► Choose a plane mounting
surface. The entire bottom of the module must lie flat on the mounting surface.
► Screw the lower part onto the
mounting surface. To do so, use the mounting holes (1) and M4 mounting screws with washers M4 (not supplied with the device). Tightening torque
2.3...2.5 Nm.
► Place the profile seals (3) into the slots (2) of the module lower part. If
the module is at the end of the cable run, the blanking seals (4) must be used to ensure the IP 65 protection rating.
LINE 1
LINE 2
2