Installation instructions
T splitter
E70354
UK
80275345 / 00 06 / 2018

1 Preliminary note
Technical data, approvals, accessories and further information at
www.ifm.com.
1.1 Symbols used
► Instructions
→ Cross-reference
Important note
Non-compliance may result in malfunction or interference.
Information
Supplementary note.
2 Safety instructions
• Read this document before setting up the product and keep it during the entire
service life.
• The product must be suitable for the corresponding applications and
environmental conditions without any restrictions.
• Only use the product for its intended purpose (→ Functions and features).
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
• The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator.
• Installation, electrical connection, set-up, operation and maintenance of the
product must be carried out by qualified personnel authorised by the machine
operator.
• Protect units and cables against damage.
3 Functions and features
With the T splitter the AS-i voltage and external auxiliary voltage can be tapped via
the M12 socket (current rating 4 A).
2

4 Installation
► Disconnect power before installation.
► Remove protective cap for M12 socket when the plug is connected (→
Step 3).
AS-i
Step 1: Install lower part
► Choose a plane mounting surface.
UK
► Fix the lower part to the mounting
surface at the mounting holes (1).
► Insert the yellow AS-i flat cable (2)
into the cable duct "AS-i".
► Insert the black 24 V flat cable (3)
into the other cable duct.
If no additional power supply is
required:
► Instead of the 24 V flat cable
insert the supplied cable
dummy to close the unused
cable duct.
Step 2: Insert cable
3

Step 3: Fit upper part
► Place the upper part.
► Tighten the fixing screws (4)
alternately.Tightening torque 2.5
Nm.
► Remove protective cap from the
M12 socket (5) and fix the M12
connector on the cable using the
coupling nut. Tightening torque
0.5...0.8 Nm.
► Lay flat cable; straight for a
15 cm
Step 4: Lay flat cable
minimum of 15 cm.
► If necessary, use AS-i clips (6).
AS-i clips are not supplied with
the unit. Information at
www.ifm.com → Data sheet
E70354 → Accessories.
► Note on replacement:
Precisely use the pierced points of the
AS-i flat cable (7) or at least position
within the black seal (8) of the T
splitter.
Step 5: Replace T splitter
4

5 Electrical connection
The unit must be connected by a qualified electrician.
► Disconnect power.
► Connect the unit as follows:
Pin Connection
1 AS-i +
1
2 0 V
UK
4
2
5
3
3 AS-i 4 + 24 V
5 not connected
5