IFM Electronic DF2210, DF2208, DF2212, DF2216, DF2214 Installation Instructions Manual

...
Installation instructions
Electronic circuit breakers, IO-Link
for the 24 V DC secondary circuit
DF21xx DF22xx
UK
80278886 / 00 10 / 2018
This document applies to the DF21xx supply modules and the DF22xx circuit protection modules.
Read this document before use to familiarise yourself with operating conditions, installation and operation. Keep this document during the entire duration of use of the device.
WARNING
Adhere to the warning notes and safety instructions (→ 2 Safety instructions).
The devices are not suitable for battery-backed applications.
2 Safety instructions
The devices are intended for use with a 24 V DC safety extra-low voltage.
A wrong connection to voltage which is higher and/or not safely isolated may lead to damage or conditions which are dangerous to life.
Use the supply module only with the matching circuit protection modules.
Observe the technical data of the circuit protection modules used.
The devices must be installed, connected and put into operation by a qualified electrician.
Adhere to the national regulations regarding the installation and selection of cables.
Do not mount the devices and do not actuate the contact levers while live.
Supply the devices with energy only after they have been properly installed.
After triggering a circuit protection module and before power on again, remove
the cause of triggering (short circuit or overload).
Check the devices for damage prior to installation. Faulty devices must not be used.
In case of malfunction of the unit or queries, please contact the manufacturer. Any tampering with the device can seriously affect the safety of operators and machinery.This is not permitted and leads to the exclusion of any liability and
warranty claims.
2
3 Installation
123
4
► Mount the devices on a 35 mm rail.
Example DF22xx circuit protection module 1: rail
2: contact lever 3: installation area 4: operating area
4 Electrical connection
► Dimension cables according to input and output current. ► Insert wires directly into the terminals as shown on the device label.
Art. no. Terminals Potential Cross-
section
[mm²]
DF21xx 24 V DC supply 0.5...10 18
0 V 0.14...2.5 8...10
Stripping
length
[mm]
UK
L+, C/Q, L- IO-Link 0.25...0.5 6
DF22xx O1 or O1/O2 current outputs 0.14...2.5 8...10
To disconnect press the orange pusher using a suitable tool. To open the push-in terminals IO-Link use a 2 mm wide micro screwdriver.