Ier MAXIMAT VK C Operating Instructions Manual

Operating Instructions
Compact Overfill Sensor, Float Type MAXIMAT VK C...
with integrated mesuring Transducer, DIBT Approval Z-65.11-355
:

Safety Precautions

Installation, initial start-up and maintenance may only be performed by trained personnel! All applicable European and national regulations regarding installation of electrical equipment must be adhered to.
The device may only be connected to supply power which complies with the specifications included in the technical data and on the serial plate!
The device must be disconnected from all sources of power during installation and maintenance work!
The device may only be operated under the conditions specified in the operating instructions!
Functions Description
The MAXIMAT VK C... compact overfill sensor is used as a fill­level limit switch for permanently installed containers used for the storage of non-flammable, water endangering liquids. It is equipped with three different output circuits:
A binary output for controlling a coupling relay, or the digital input of a PLC
A 0 to 20 mA current output for controlling an analogue input channel, e.g. a programmed logic controller (PLC)
Self-monitoring measuring circuit in combination with the MAXIMAT SHR C... measuring transducer with 2-wire connection
Note:
Only for liquids with density greater than 0.7g/cm³
The MAXIMAT VK C... compact overfill sensor is used also for oil, emulsion and other non-conductive liquids.
Technical Data
Supply power
24 V DC ± 10% With current limiting or 250 mA fuse recommended
Connected load
Approx. 3 W
Ambient temperature
-20 to +60
°
C
Container pressure
Atmospheric (0.8 to 1.1 bar)
Terminal housing
IP 65
Terminals
Screw terminals: IP 20 Max. wire cross-section: 2.5 mm²
Outputs
Binary output: +DO/-DO max. 20 mA / 24 V +AO / -AO 0 to 20 mA Output for MAXIMAT SHR C... measuring transducer
DIP Switch Operating Mode DIP1 DIP2 DIP3 DIP4
Binary output ON ON ON OFF Current output/PLC OFF OFF OFF OFF MAXIMAT SHR C OFF * OFF * OFF * OFF * * Default setting
Note:
Be sure to examine the DIP switch settings before switching supply power on!
Indicators
Run = LED illuminated
Green LED on the connector PCB:
Alarm / error = LED off
Measuring circuit for use with SHR C... transducer
Max. cable inductance: approx. 5 mH Max. cable capacitance: approx. 0.5 µF
Measuring circuit cable length
Max. 300 m Min. wire cross-section: 0.5 mm²
CE mark In accordance with low-voltage directive (73/23/EWG), EMC directive (89/336/EWG) and
EN 50 082-2:1995
EN 55 011 (class A):1998
DIBT Approval
Approval no. Z-65.11-355 for overfill sensors and leakage sensors in accordance with WHG §19
Note:
The accompanying “General Building Supervisory Approval no. Z-65.11-355” is an integral part of the operating instructions and all stipulations contained therein must be adhered to!
SU0213.DOC 06/03 © IER Eberhard Henkel GmbH Sheet 1
Operating Instructions: MAXIMAT VK C Compact Overfill Sensor, Float Type
Electrical connection:
MAXIMAT VK C... binary output to coupling relay
MAXIMAT VK C... current output to PLC analogue input

Adjustment Instructions

The maximum allowable fill-level of any given tank can be determined, for example, in accordance with TrbF 280 no.
2.2. Triggering level A is then calculated in accordance
with attachment 1, or the approval guidelines for overfill inhibitors (ZG-ÜS). Dribbling quantities and switching delay times must be taken into consideration. Switching delay time can be adjusted at the MAXIMAT SHR C measuring transducer within a range of 0.3 to 3 seconds.
Installation length L determines the fill-level monitor’s triggering point. Dimensions are calculated as follows: H = tank height A = triggering level B = connector E = immersion depth, table E S = triggering point
L = H - A + B + E + 3 S = L - E – 3
MAXIMAT VK C... to MAXIMAT SHR CS measuring transducer
MAXIMAT CK C… to MAXIMAT SHR C19 transducer
Guide tubes included with MAXIMAT VK.3L and MAXIMAT VK.4L adjustable level monitors are supplied 50 mm longer than dimension L, so that the fill-level monitor can be adapted to correspond to triggering level A during installation. It is thus possible to readjust dimension L. After the triggering point has been set, the locking screws are tightened and sealed against tampering. Due to the fact that this seal is not removed during periodic testing, dimension L is always fixed, i.e. no readjustment is necessary
SU0213.DOC 06/03 © IER Eberhard Henkel GmbH Sheet 2
Loading...