IEC Vertical F*C, FHC, FXC, FVC Installation, Operation & Maintenance Manual

IEC Vertical F*C Series Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
BUILD YOUR REPUTATION ON OURS
IEC Vertical F*C Series Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
International Environmental Corporation Vertical F*C Series Fan Coil Installation, Operation, & Maintenance Manual
2
www.iec-okc.com
IEC Vertical F*C Series Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
Table of Contents
4 SECTION 1 – Introduction
4 Safety
5 SECTION 2 – Pre-Installation
Unpacking and Inspection
5 Prepare Jobsite for Unit Installation
5 Identify and Prepare Units
5 Protect Units from Damage
7 SECTION 3 – Installation
7 Place Units In Position
8 Cooling/Heating Pipe Connections
9 Field Piping Connections
10 Steam Drain Connections
10 Leak Testing
10 Refrigerant Coil Testing
10 Piping Insulation
10 Condensate Drain
11 Electrical Connections
12 Factory Installed Options
12 Condensate Overow switch
12 Standard Wiring Packages
15 Connecting Ductwork
16 Exposed Unit Finish Touch-up and Repaint
16 Make Final Preparations
16 SECTION 4 – Startup
17 Cooling/Heating System
17 Air Balance System
17 Water Balancing System
18 Water Treatment
18 Eco-telligent® Motor
19 Controls Operation
19 SECTION 5 – Service/Maintenance
General
19 Motor/Blower Assembly
20 Coil
20 Electric Resistance Heater Assembly
20 Electrical Wiring and Controls
21 Valves and Piping
21 Filters, Throwaway
21 Filters, Permanent
21 Drain
21 Replacement Parts
23 SECTION 6 – Equipment Startup Check List
23 Receiving and Inspection
23 Handling and Installation
23 Cooling/Heating Connections
23 Ductwork Connections
23 Electrical Conditions
23 Unit Startup
to improve its products. As a result, the design and specications
of each product may be changed without notice and may not be
as described herein. Please contact IEC for information regarding
current design and product specications. Statements and other
information contained herein are not express warranties and do not
form the basis of any bargain bet ween the parties but are merely IECs
opinion or commendation of its products. Manufacturers standard
limited warranty applies.
International Environmental Corporation Vertical F*C Series Fan Coil Installation, Operation, & Maintenance Manual
23 Motor
24 Appendix A
25 Appendix B
www.iec-okc.com
Adjustment of ICM AW4105
Adjustment of EVO/ECM-4SPD
3
IEC Vertical F*C Series Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
SECTION 1 – Introduction
International Environmental Corporation (IEC) fan coil units represent a prudent investment oering trouble­free operation and long service with proper installation, operation, and regular maintenance. The equipment covered by this manual is available with a variety of options and accessories. Always consult the approved unit submittals, order acknowledgement, and other manuals for specic details on unit options and accessories. Always follow proper procedures related to safety, handling, installation, operation, and servicing of mechanical equipment as the manufacturer assumes no responsibility for personal injury or property damage resulting from improper or unsafe practices during the handling, installation, service, or operation of any equipment.
Safety
IEC equipment is initially protected under the manufacturer’s standard warranty; however, this warranty is provided under the condition that the steps outlined in this manual for initial inspection, proper installation, commissioning, regular periodic maintenance, and everyday operation of the equipment be followed in detail. This manual should be fully reviewed and understood in advance of initial installation, startup, and any maintenance. Should any questions arise, please contact your local Sales Representative or the factory BEFORE proceeding.
Install approved Lock-Out/Tag-Out protection devices on ALL incoming power sources to equipment being installed or serviced prior to beginning any work. Always verify all incoming power sources are de-energized using an electrical multi-meter.
CAUTION: Never wear bulky or loose tting clothing when working on any mechanical
equipment. Gloves should always be worn for protection against sharp sheet metal edges, heat, and other possible injuries. Safety glasses or goggles should always be worn, especially when drilling, cutting, or working with refrigerants, lubricants or cleaning chemicals.
WARNING: Never pressurize any equipment beyond specied test pressures listed on the unit rating plate. Always pressure test with an inert uid or gas such as clear water or dry nitrogen to avoid possible damage or injury in the event of a leak or component failure during testing.
CAUTION: Always protect adjacent ammable
material when welding or soldering. Use a
suitable heat shield material to contain sparks or drops of solder. Have a re extinguisher readily available.
CAUTION: Always protect chilled and hot water
valve bodies, strainers, ball valves, and other
ow control related devices from heat caused by soldering or brazing processes by wrapping these devices in cold or damp rags.
WARNING: NO ATTEMPT SHOULD BE MADE TO HANDLE, INSTALL, OR SERVICE ANY UNIT WITHOUT FOLLOWING SAFE PRACTICES REGARDING MECHANICAL EQUIPMENT.
The equipment must always be properly supported. Temporary supports used during installation or service must be adequate to hold the equipment securely.
CAUTION: All power must be disconnected before any installation or service is attempted.
More than one power source may be supplied to a unit. Power to remote mounted control devices may not be supplied through the unit.
International Environmental Corporation Vertical F*C Series Fan Coil Installation, Operation, & Maintenance Manual
4
Safety should always be the rst priority when handling, installing, operating or servicing mechanical equipment. Always follow all safety codes, procedures and protocols.
Consult applicable local building codes and National Electrical Codes (NEC) for special requirements. Be alert to safety information: symbols, words such as DANGER, WARNING and CAUTION.
Improper installation, adjustment, service, maintenance, or use can cause explosion, re, electrical shock, or other conditions, which may result in personal injury or property damage. This product must be installed only by personnel with the training, experience, skills, and applicable licensing that makes him/her a qualied professional HVACR installer.
www.iec-okc.com
IEC Vertical F*C Series Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
SECTION 2 – Pre-Installation
Unpacking and Inspection
All units are carefully inspected at the factory throughout the manufacturing process under a strict detailed quality assurance program. All major components and sub­assemblies are carefully tested for proper operation and veried for full compliance with factory standards. Operational testing of some customer-furnished components such as DDC controls, pneumatic control valves and switches may be a possible exception.
Each unit is carefully packaged for shipment to avoid damage during normal transit and handling. Equipment should always be stored in a dry and covered place, and in the proper orientation as marked on the carton.
All shipments are made F.O.B. ex-factory and it is the responsibility of the receiving party to inspect the equipment upon arrival. Any obvious damage to the packaging and/or its contents should be recorded on the bill of lading and a claim led with the freight carrier.
Where local repairs or alterations can be accomplished, the factory must be fully informed of the extent and expected cost of those repairs before work is begun. Where factory operations are required, the factory must be contacted for authorization to return equipment and a Return Authorization Number will be issued. Unauthorized return shipments of equipment and shipments not marked with an authorization number will be refused. In addition, any claims for unauthorized expenses will not be accepted by the manufacturer.
Prepare Jobsite for Unit Installation
To save time and to reduce the possibility of costly errors, set up a complete sample installation in a typical room at the jobsite. Check all the critical dimensions such as eld piping, wiring, and duct connection to ensure they agree with job requirements. Refer to job drawings and product dimension drawings as required (See Figure 1 for sample drawing). Instruct all trades in their part of the installation. Should any discrepancies be discovered, contact your local representative before continuing with unit installations.
After determining the condition of the packaging exterior, carefully remove each unit from the carton and inspect for hidden damage. At this time, check to make sure that “furnished only” items such as switches, valves, thermostats, etc. are accounted for. Any hidden damage or missing components should be recorded and immediately reported to the carrier and a claim led. In the event a claim for shipping damage is led, the unit, shipping carton, and all packing must be retained for physical inspection by the freight carrier. All equipment shall be stored in the factory shipping carton with internal packing in place until installation.
At the time of receipt, the equipment type and arrangement shall be veried against the order documents. Should any discrepancy be found, the local Sales Representative shall be notied immediately so that proper action may be taken.
Should any questions arise concerning eld warranty repairs, the factory must be notied BEFORE any corrective action is taken.
Identify and Prepare Units
For each unit, conrm incoming and control power requirements match available power source. Refer to unit nameplate and wiring diagram.
1. Check all tags on unit to determine if shipping screws are to be removed. Remove screws as directed.
2. Rotate the fan wheel by hand to ensure that the fan is unrestricted and can rotate freely. Check for shipping damage and fan obstructions. Adjust blower wheel as required.
3. Perform “Dry Fit” of valve assembly that may be shipped unattached to unit coil assembly. Should any questions arise on fit up please contact your local representative immediately.
Protect Units from Damage
All equipment is designed and fabricated with robust materials and present a rugged appearance. Still, great care must be taken to assure that no force or pressure is applied to the coil, piping or drain stub-outs during handling.
International Environmental Corporation Vertical F*C Series Fan Coil Installation, Operation, & Maintenance Manual
www.iec-okc.com
5
IEC Vertical F*C Series Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
STANDARD STAMPED SUPPLY GRILLE
5
E
(127)
2
(DIMENSION FROM MOUNTING HOLE)
(51)
2-1/2
(64)
9
(229)
9-1/2
(241)
3-3/4
25
(635)
1/2" (13) MTG. HOLES
(TYP. OF 4)
(102)
9-1/4
11-3/4
4
(235)
(298)
3-3/4
5
E
(95)
(127)
D
TOP VIEW
(229)
9-1/2
(241)
OPTIONAL CONTROL BOX SHOWN (STD BOX IS 2X4)
RETURN AIR OPENING
9
C
MOUNTING HOLES
B
A
REMOVABLE FRONT ACCESS PANEL
FRONT VIEW
CONTROL ACCESS DOOR STD. (2) (OPTIONS AVAILABLE)
(95)
1/4 TURN PANEL FASTENER TYP.
SUPPLY & RETURN WATER CONNECTIONS
DRAIN TROUGH
PLASTIC AUXILIARY 7X7 DRAIN PAN WITH 3/4" (19) MPT CONNECTION
4
(102)
(DIMENSION FROM INSIDE CASE LEG)
1" (25) FILTER
RETURN
AIR VENT
AIR
1-1/2
(38)
2-7/8
(73)
3/4 (19)
RIGHT SIDE VIEW
5-3/4
(146)
SUPPLY
AIR
8-1/4
(229)
(210)
9
REVISION HISTORY
REV
04/29/13
- 13-0801
05/22/13
A 13-0958 B 13-0981
05/24/13
06/05/13
C 13-1073 D 13-1843
09/03/13 09/11/14
E 14-1984
1-3/4
(45)
SEE TECHNICAL
CATALOG FOR
DIMENSIONAL DETAILS
16-1/8
(410)
14-1/2
(368)
4-1/2
(114)
ECNDATE
NOTES:
1. R.H. SHOWN, L.H. OPPOSITE.
2. ALL DIMENSIONS ± 1/4" (6).
3. PRODUCT SPECIFICATIONS ARE SUBJECT TO CHANGES WITHOUT NOTICE.
UNIT SIZE BA C D E
FXC FXC FXC FXC FXC FXC FXC FXC
02
41 (1041)
03 04
51 (1295)
05
06
61 (1549)
08
63 (1600)
10
77 (1956)
12
85 (2159)
22 (559)
32 (813) 32 (813) 42 (1067) 44 (1118) 58 (1473) 66 (1676)
DIMENSIONS-INCHES (MM)
23 (584) 17-1/4 (438) 3-1/8 (79) 23 (584) 17-1/4 (438) 3-1/8 (79)41 (1041) 22 (559) 33 (838) 26 (660)
33 (838) 26 (660) 3-3/4 (95)51 (1295) 12 43 (1092) 39 (991) 45 (1143) 39 (991) 59 (1499) 52-1/8 (1324) 67 (1702) 61 (1549)
Figure 1: Example of Submittal Drawing
Depending on the options and accessories, some units may contain delicate components that may be damaged by improper handling. Whenever possible, all units shall be maintained in an upright position, and handled by the chassis or as close as possible to the unit mounting-point locations. In the case of a full cabinet unit, the unit must be handled by the exterior casing. This is acceptable provided the unit is again maintained in an upright position, and no force is applied that may damage internal components or painted surfaces.
The equipment covered in this manual IS NOT suitable for outdoor installations. The equipment is never to be stored or
CLASSIC
TITLE
MODEL
FXC
CABINET
E
SHEETREVISION
OF
1
1
3-3/4 (95)
2-1/4 (57) 3-1/4 (83) 3-5/8 (92) 3-1/4 (83)
QUANTITY/UNIT
BLWR MOTOR
1 1 2
2 2 4 4
1 1 1
1 1 2 2
JOB NUMBER
JOB NAME
DRAWN BY
B. CHILDS
DRAWING NUMBER
I100-90017694
installed where it may be subjected to a hostile environment such as rain, snow, or extreme temperatures.
Before, during, and after installation, take specic care to prevent foreign material such as paint, plaster, and drywall dust from being deposited in the drain pan, on the motor or blower wheels and cooling/heating coils. Failure to do so may have serious adverse eects on unit operation, and in the case of the motor and blower assembly, may result in immediate or premature failure. All manufacturers warranties are void if foreign material is allowed to be deposited in the drain pan or on the motor or blower wheels of any unit. Some units and/or job conditions may require some form of temporary covering during construction.
International Environmental Corporation Vertical F*C Series Fan Coil Installation, Operation, & Maintenance Manual
6
www.iec-okc.com
IEC Vertical F*C Series Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
While the manufacturer is not involved in the design and selection of support methods and components, it shall be noted that unacceptable system operating characteristics and/or performance may result from improper or inadequate unit structural support. In addition, adequate clearance must be provided for service and removal of the equipment and its accessory components, consult local codes. See Figure 2 for minimum recommendation for clearances by manufacturer. Anchoring the equipment in place is accomplished by using the mounting points provided, and positioning the unit to maintain the drain pan on a LEVEL plane. Care must be taken to insure that the unit drain pan does not slope away from the outlet connection.
Vertical unit models FHC, FXC, FVC are designed to be oor mounted or otherwise supported from below, and bolted to the wall or oor structure through the mounting holes provided in the chassis. These units may be wall hung only when originally ordered from the factory for wall-mount applications.
The type of mounting device is a matter of choice; however, the mounting point shall always be that provided in the chassis or cabinet. Refer to the unit product drawings for hole mounting locations and sizes.
After mounting, the unit is then ready for the various service connections such as water, drain and electrical. At this time, verify that the proper types of service are actually provided to the unit. On units requiring chilled water and/or hot water, verify the proper line size and water temperature are available to the unit.
SECTION 3 – Installation
Place Units In Position
F*C UNITS
1. Select the unit location. Allow adequate space for free air circulation, service clearances, piping and electrical connections, and any necessary ductwork. For specific unit dimensions, refer to the submittal drawing for your model. Allow clearances according to local and national electric codes. See Figure 2 for basic minimum clearance recommendations.
2. Make sure the floor is able to support the weight of the unit. See Table 1 for nominal unit weight.
3. Ensure wall behind unit is smooth and plumb; if necessary, install furring strips on walls with irregular surfaces or mullions. Furring strips must be positioned behind mounting holes in unit (FHC, FXC, FVC units).
Fasteners, furring strips, and other seals (if required)
must be field-supplied.
4. Remove all wall and floor moldings from behind the unit.
5. Ensure FHC top panel (under window application) and FXC, FVC front panel has been removed from unit to obtain access to the four 0.75-in. mounting holes. Fasteners and other required hardware must be field­supplied.
6. Move unit into position. Ensure unit is level or slightly pitched towards drain to ensure proper drainage and operation.
Unit Size F*C 02 03 04 05 06 08 10 12
Nominal Air
Flow (cfm)
FHC 42 47 57 60 77 79 108 127
FXC 63 68 82 85 99 101 133 154
FVC 64 69 83 86 100 102 135 156
Coil Weight w/Water (Approx. lbs per row of coil)
FHC/FXC/FVC 0.4 0.5 0.6 0.8 1.0 1.1 1.8 2.1
Coils 5.7 7.4 7.6 11.6 14.5 15.1 24.5 27.7
FPI 12 FPI
Coil Face Area
(sq ft)
Motor (Qty)
FHC/FXC/FVC
Blower (Qty)
FHC/FXC/FVC
FHC/FXC/FVC
Qty 1 1 1 1 1 1 1 1
Supply Air
Duct Collar
Coil Supply and Return
Drain
Connection
Table 1: Nominal Unit Weight
200 300 400 500 600 800 1000 1200
Shipping Weight (lb)
0.8 1.0 1.1 1.6 2.0 2.1 3.6 4.2
1 1 1 1 1 1 2 2
1 1 2 2 2 2 4 4
Filters (Nominal Size (in.) (1-in. thick)
7¾ x
7¾ x
7¾ x
7¾ x
7¾ x
7¾ x
7¾ x
21¾
21¾
31¾
31¾
41¾
43¾
57¾
1-inch
Piping Connections (Sweat) (in.)
5/8” OD, 7/8” OD
3/4 MPT
x
65¾
International Environmental Corporation Vertical F*C Series Fan Coil Installation, Operation, & Maintenance Manual
www.iec-okc.com
7
IEC Vertical F*C Series Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
7. Adjust FHC, FXC, FVC units leveling legs so unit is level. See Figure 2. Unit must be level for proper operation and condensate drainage. (See Figure 5 for recommended connection methods/trapping)
8. Mounting unit: Reach into unit and attach unit to the wall using the 0.375-in. mounting holes (4)
Level Unit
12”
30” Minimum
per building code
±1/4”
1/2”
Minimum
in top panel; do not use any other locations. The four mounting holes and hanger slots with rubber grommets are NOT for balancing unit.
NOTE: For any unit without a return-air duct connection,
applicable installation codes may limit unit to installation in single story applications only.
1/2”
Minimum
Side View Front View
Figure 2: Clearance recommendations.
valve packages may be shipped loose with the equipment.
Cooling/Heating Pipe Connections
CAUTION: Residues and loose particles resulting from manufacturing and eld piping
In these cases, perform a dry t of the assemblies to ensure proper alignment and access to the assembly components can be utilized for maintenance and service.
techniques such as joint compounds, soldering ux, and metal shavings may be present in the unit and the piping system. Give special consideration to system cleanliness when connecting to solar, domestic or potable water systems.
If coil and valve package connections are made with a sweat or solder joint, verify that no components in the valve package are subjected to a high temperature which may damage seals or other materials. Do not allow valve bodies to exceed 300°F. Protect all valve and water control
Thoroughly review submittals and product literature detailing unit operation, controls, and connections BEFORE
assemblies with wet or damp rag wrapped around the body during the soldering/brazing process.
beginning the connection of the various cooling and/or heating mediums to the unit.
Many two position electric control valves, depending on valve operation, are provided with a manual opening lever.
All accessory valve packages shall be installed as required, and check all service valves for proper operation. At times,
Place this lever in the open position during all soldering or brazing operations.
International Environmental Corporation Vertical F*C Series Fan Coil Installation, Operation, & Maintenance Manual
8
www.iec-okc.com
IEC Vertical F*C Series Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
Mating
Hole
Step 1: Rotate actuator counter clockwise approximately 30 degrees.
Manual Operating
Lever
General Close-O (G)
Taco Line Voltage
Locking Post
Schneider Erie
Release Button
Stem
B
A
Release
Button
High Close-O (H)
Step 2: Move actuator upward 3/4” to disengage.
Manual
Operating Lever
Mating
Hole
The supply and return connections are marked on the coil stub outs and the valve package, with an “S” meaning supply or inlet and “R” meaning return or outlet indicating uid ow direction to and into the coil. Blue letters mark the chilled water connections and Red letters mark the hot water or steam connections.
In the case of eld-installed valves and piping, install the chilled water valve cluster (or expansion valve on DX units) in such a way that any dripping or sweating caused from condensation is contained in the drain pan or other device such as an optional extended drain pan or factory drip lip. Factory drip lips are eld installed and may be packaged separately from the unit. Factory supplied cooling coil valve packages will be arranged to locate as much of the package as possible over a standard drip lip. Some eld congurations may require additional insulation be applied to the exposed water piping to prevent condensation from dripping into areas not directly above the auxiliary drain pans.
If none of the above factory accessories are provided with the units, simple ashing may be used to carry moisture into the unit drain pan.
Field Piping Connections
Taco Zone Sentry
Step 1: Push in and hold release clip at the front of the actuator.
Figure 3: Valve and Lever–Pop-Top Installation
If the valve package connection at the coil is a union, the coil side of the union must be prevented from twisting (“backed up”) during tightening to prevent damage to the coil tubing. Do not over tighten the union preventing distorting (“egg shaping”) of the union seal surface and destroying the union.
International Environmental Corporation Vertical F*C Series Fan Coil Installation, Operation, & Maintenance Manual
Step 2: Move actuator away from the valve body approximately 3/4” to disengage locking posts and stem.
Locking Post
www.iec-okc.com
To chilled water coil: IECs innovative design incorporates 3/8” copper tubing inside and stubbing out of the coil. To facilitate ease of connecting to eld supplied ½” hydronic tubing, there is a 3/8” to 1/2” swedge adaptor installed on both the supply and return water tube connections to the coil. Care must be taken when soldering the eld supplied tubing to this connection.
The use of solder with a ow or initial melting point below 500°F is recommended to make these connections. Local codes and/or building specications should always be consulted to ensure solder being used is compliant with current building standards. When making soldering connections, use a wet rag as a heat sink around the factory adaptor to prevent overheating of this joint. See Figure 4. After soldering, use the wet rag to quench the eld and factory connections at this tting.
9
Loading...
+ 19 hidden pages