IDEX Health & Science VS-606V7 User Manual

VS-606V7 Series Instruction Manual
COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECT OR CONTROL)

PREFACE

YASKAWA ELECTRIC CORPORATION

General Precautions

• Some drawings in this manual are shown with the protective covers and shields removed, in order to describe detail with more clarity. Make sure all covers and shields are replaced before operating this product.
• This manual may be modified when necessary because of improvement to the product, modification, or changes in specifications. Such modifications are denoted by a revised manual No.
• To order a copy of this manual, if your copy has been damaged or lost, contact you YASKAWA representative.
• Y ASKAWA is not responsible for any modification of the product made by the user, doing so will void the warranty.
2
NOTES FOR SAFE OPERATION
Read this instruction manual thoroughly before installation, operation, maintenance or inspection of the VS-606V7. In this manual, NOTES FOR SAFE OPERATION are classified as “WARNING” or “CAUTION”.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury to personnel.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury to personnel and damage to equipment. It may also be used to alert against unsafe practices.
Even items described in may result in a vital accident in some situations. In either case, follow these important notes.
These are steps to be taken to ensure proper operation.
NOTE
CAUTION
3
Warnings for UL/cUL Marking
• Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON.
• The Inverter internal capacitor is still charged even after the power supply is turned OFF. To prevent electric shock, disconnect all power before servicing the Inverter. Then, wait at least one minute after the power supply is disconnected and all indicators are OFF.
• Do not perform a withstand voltage test on any part of the Inverter. This electronic equipment uses semiconductors and is vulnerable to high voltage.
• Do not remove the Digital Operator or the blank cover unless the power supply is turned OFF. Never touch the printed control board (PCB) while the power supply is turned ON. The Inverter is not suitable for use on a circuit capable of delivering more than
18,000 RMS symmetrical amperes, 250volts maximum (200V class units) or 18,000 RMS symmetrical amperes, 480volts maximum (400V class units).
CAUTION
(Ref. page)
Low voltage wires shall be wired with Class I Wiring.
. . . . . . . . . . . . . . . 22
4
RECEIVING
CAUTION
• Do not install or operate any inverter which is damaged or has missing parts.
Failure to observe this caution may result in personal injury or
equipment damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-16
MOUNTING
CAUTION
• Lift the cabinet by the cooling fin. When moving the unit, never lift by the plastic case or the terminal covers.
Otherwise, the main unit may be dropped causing damage to the unit.. . . . . . 18
• Mount the inverter on nonflammable material (i.e., metal).
Failure to observe this caution can result in a fire.. . . . . . . . . . . . . . . . . . . . . . 18
• When mounting units in an enclosure, install a fan or other cooling device (open chassis to keep the intake air temperature below 122°F (50°C).
Overheating may cause a fire or damage to the unit. . . . . . . . . . . . . . . . . . . . . 19
• The VS mini generates heat. For effective cooling, mount it vertically. Refer to the figure in “Mounting Dimensions” on page 18.
(Ref. page)
(Ref. page)
5
WIRING
WARNING
(Ref. page)
• Start wiring only after verifying that the power supply is turned OFF.
Failure to observe this warning can result in electric shock
or fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
• Wiring should be performed only by qualified personnel.
Failure to observe this warning can result in electric shock
or fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
• When wiring the emergency stop circuit, check the wiring thoroughly before operation.
Failure to observe this warning can result in personal injury. . . . . . . . . . . . . . 22
WARNING
(Ref. page)
• Make sure to ground the ground terminal according to the local grounding code.
Failure to observe this warning can result in electric shock
or fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
• For 400V class, to conform to CE requirements, make certain to ground the supply neutral.
Failure to observe this warning can result in electric shock
or fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6
CAUTION
• Verify that the inverter rated voltage coincides with the AC power supply voltage.
Failure to observe this caution can result in personal injury or fire.
• Do not perform a withstand voltage test of the inverter
It may cause semi-conductor elements to be damaged.
• To connect a braking resistor, braking resistor unit or braking unit, follow the procedures described in this manual.
Improper connection may cause a fire.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
• Make sure to tighten terminal screws of the main circuit and the control circuit.
Failure to observe this caution can result in a malfunction,
damage or a fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
• Never connect the AC main circuit power supply to output terminals U, V and W.
The inverter will be damaged and void the warranty. . . . . . . . . . . . . . . . . . . . 22
• Do not connect or disconnect wires or connectors while power is applied to the circuit.
Failure to observe this caution can result in personal injury.
• Do not change signals during operation
The machine or the inverter may be damaged.
(Ref. page)
7
OPERATION
WARNING
• Only turn ON the input power supply after replacing the digital operator/blank cover (optional). Do not remove the digital operator or the covers while current is flowing.
Failure to observe this warning can result in electric shock.
• Never operate the digital operator or dip switches when your hand is wet.
Failure to observe this warning can result in electric shock.
• Never touch the terminals while current is flowing, even during inverter stopping.
Failure to observe this warning can result in electric shock.
• When the fault retry function is selected, stand clear of the inverter or the load, since it may restart suddenly after being stopped.
(Construct machine system, so as to assure safety for personnel, even if the inverter should restart.) Failure to observe this
warning can result in personal injury.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
• When continuous operation after power recovery is selected, stand clear of the inverter or the load, since it may restart suddenly after being stopped.
(Construct machine system, so as to assure safety for personnel, even if the inverter should restart.) Failure to observe this
warning can result in personal injury.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
• Since the digital operator stop button can be disabled by a function setting, install a separate emergency stop switch.
Failure to observe this warning can result in personal injury.
• If an alarm is reset with the operation signal ON, the inverter restarts automatically. Only reset the alarm after verifying that the operation signal is OFF.
Failure to observe this warning can result in personal injury. . . . . . . . . . . . . . 27
(Ref. page)
8
OPERATION (Cont.)
CAUTION
(Ref. page)
• Never touch the heatsink or braking resistor, the temperature is very high.
Failure to observe this caution can result in harmful burns to the body.
• Since it is easy to change operation speed from low to high speed, verify the safe working range of the motor and machine before operation.
Failure to observe this caution can result in personal injury and machine damage.
• Install a holding brake separately if necessary.
Failure to observe this caution can result in personal injury.
• Do not change signals during operation.
The machine or the inverter may be damaged.
• All the parameters of the inverter have been preset at the factory. Do not change the settings unnecessarily.
The inverter may be damaged. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
MAINTENANCE AND INSPECTION
WARNING
(Ref. page)
• Never touch high-voltage terminals in the inverter.
Failure to observe this warning can result in an electrical shock. . . . . . . . . . 127
• Disconnect all power before performing maintenance or inspection. Then wait at least one minute after the power supply is disconnected and all LEDs and CHARGE LED are extinguished.
The capacitors are still charged and can be dangerous. . . . . . . . . . . . . . . . . . 127
9
WARNING
• Do not perform withstand voltage test on any part of the VS-606V7.
This electronic equipment uses semiconductors and is vulnerable
to high voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
• Only authorized personnel should be permitte d to perform maintenance, inspections or parts replacement.
[Remove all metal objects (watches, bracelets, etc.) before operation.] (Use tools which are insulated against electrical shock.)
Failure to observe this warning can result in an electrical shock. . . . . . . . . . 127
CAUTION
• The control PC board employs CMOS ICs. Do not touch the CMOS elements.
They are easily damaged by static electricity.
• Do not connect or disconnect wires, digital operator, connectors, or cooling fan while power is applied to the circuit.
Failure to observe this caution can result in personal injury. . . . . . . . . . . . . . 127
Others
WARNING
• Never modify the product.
Failure to observe this warning can result in an electrical shock or personal injury and will void the warranty.
(Ref. page)
(Ref. page)
(Ref. page)
10
WARNING DISPL AY
A warning label is displayed on the front cover of the inverter, as shown below. Follow these instructions when handling the inverter.
11

CONTENTS

NOTES FOR SAFE OPERATION . . . . . . . . . . . . . . . . . . . . 3
1. RECEIVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Checking the Name Plate . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2. IDENTIFYING THE PARTS . . . . . . . . . . . . . . . . . . . . . . 16
3. MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Choosing a Location to Mount the Inverter . . . . . . . . . . . . . .18
Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Mounting/Removing Components . . . . . . . . . . . . . . . . . . . . .20
4. WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Wiring Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Wire and Terminal Screw Sizes. . . . . . . . . . . . . . . . . . . . . . .23
Wiring the Main Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Wiring the Control Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Wiring Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
5. OPERATING THE INVERTER. . . . . . . . . . . . . . . . . . . . 28
Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Operating the Digital Operator. . . . . . . . . . . . . . . . . . . . . . . .30
LED Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Simple Data Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
6. PROGRAMMING FEATURES . . . . . . . . . . . . . . . . . . . . 39
Parameter Set-up and Initialization . . . . . . . . . . . . . . . . . . . .39
Using V/f control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Using Vector Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . .43
Switching LOCAL/REMOTE Modes . . . . . . . . . . . . . . . . . . .46
Selecting Run/Stop Commands. . . . . . . . . . . . . . . . . . . . . . .47
Setting Operation Condition . . . . . . . . . . . . . . . . . . . . . . . . .50
12
Selecting Stopping Method . . . . . . . . . . . . . . . . . . . . . . . . . .71
Building Interface Circuits with External Devices . . . . . . . . .73
Setting Frequency by Current Reference Input. . . . . . . . . . .83
Frequency Reference by Pulse Train Input. . . . . . . . . . . . . .85
Decreasing Motor Speed Fluctuation . . . . . . . . . . . . . . . . . .89
Motor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
Selecting Cooling Fan Operation. . . . . . . . . . . . . . . . . . . . . .92
Using MEMOBUS (MODBUS) Communications. . . . . . . . . .92
Using Parameter Copy Function . . . . . . . . . . . . . . . . . . . . . 116
Unit Selection for Frequency Reference Setting Display. . .125
7. MAINTENANCE AND INSPECTION . . . . . . . . . . . . . .127
Periodical Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127
Part Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127
8. FAULT DIAGNOSIS AND CORRECTIVE ACTIONS . . 129
9. SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
Standard Specifications (200V Class). . . . . . . . . . . . . . . . .139
Standard Specifications (400V Class). . . . . . . . . . . . . . . . .142
Standard Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Sequence Input Connection with NPN/PNP Transistor. . . .148
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150
Recommended Peripheral Devices. . . . . . . . . . . . . . . . . . .153
Parameter List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .167
CE Conformance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .167
13

1. RECEIVING

After unpacking the VS-606V7, check the following:
• V erify that the part numbers match your purchase order or packing slip.
• Check the unit for physical damage that may have occurred during shipping. If any part of VS-606V7 is missing or damaged, call for service immediately.
Checking the Name Plate
U.S. and Canadian Safety Standards for Types of 3-phase, 200VAC, 0.13HP (0.1kW)
INVERTER MODEL INPUT SPEC. OUTPUT SPEC. LOT NO. SERIAL NO.
MODEL
VS-606V7 SERIES
No. Type
A With digital operator (with volume) B Without digital operator
(with volume)
C With digital operator (with volume)
Note: Contact your YASKAWA representative
for the type without heatsink.
C I M R - V 7 A U 2 0 P 1
INVERTER
MASS
SOFTWARE
No. Applicable maximum motor output OP1 0.13 HP (0.1kW) OP2 0.25 HP (0.2kW) OP4 0.5 HP (0.4kW) OP7 1 HP (0.75kW) 1P5 2 HP (1.5kW) 2P2 3 HP (2.2kW) 3PO 4 HP (3.0kW) 3P7 5 HP (3.7kW) 5P5 7.5 HP (5.5kW) 7P5 10 HP (7.5kW)
No. Voltage Class
B 0.13 HP (0.1kW) 2 0.25 HP (0.2kW) 4 0.5 HP (0.4kW)
No. Specifications
U UL Specification (U.S .
Specification)
14
2 0 P 1 0
B Single-Phase 200VAC 2 Three-Phase 200VAC 4 Three-Phase 400VAC
No. Applicable maximum motor output OP1 0.13 HP (0.1kW) OP2 0.25 HP (0.2kW) OP4 0.5 HP (0.4kW) OP7 1 HP (0.75kW) 1P5 2 HP (1.5kW) 2P2 3 HP (2.2kW) 3PO 4 HP (3.0kW) 3P7 5 HP (3.7kW) 5P5 7.5 HP (5.5kW) 7P5 10 HP (7.5kW)
*1 Code No.s OP1 to 3P7 are IP20. Always remove both top and bottom covers
when using the 5P5 and 7P5 inverters as
open chassis types IP00. *2 NEMA 1 “OP1” to “3P7” are optional. NEMA 1 “5P5” and “7P5” are standard.
No. Protective structure
0 Ope n chassis
1 Enclosed wall-mounted
7 Open chassis (IP20)
(IP20, IP00) *1
(NEMA 1) *2
Top-closed type
15

2. IDENTIFYING THE PARTS

16
Main Circuit Terminal Arrangement
Terminal arrangement of the main circuit terminal differs depending on the inverter model.
The terminal arrangement for200/400V, 3-Phase input series 7.5/10 HP (5.5/7.5Kw) is shown below.
17

3. MOUNTING

Choosing a Location to Mount the Inverter
Be sure the inverter is protected from the following conditions:
• Extreme cold and heat. Use only within the ambient temperature range (for open
chassis type): 14 to 122°F (-10 to +50°C).
• Rain, moisture.
• Oil sprays , sp lashes.
• Salt spray.
• Direct sunlight. (Avoid using outdoors).
• Corrosive gases (e.g. sulfurized gas) or liquids.
• Dust or metallic particles in the air.
• Physical shock, vibration.
• Magnetic noise. (Example: welding machines, power devices, etc.)
• High humidity.
• Radioactive substances.
• Combustibles: thinner, solvents, etc.
18
aa
A
Mounting Dimensions
To mount the VS 606 V7, dimensions as shown below are required.
Voltage
200V Single - phase 3 - phase 400V 3 - phase
200V 3 - phase 400V 3 - phase
Max. Applicable
Motor Output
HP (Kw)
Less than
5 HP (3.7 Kw)
7.5 HP (5.5 Kw) More than 10 HP (7.5 Kw)
Length of A
More than
1.18in (30mm)
1.97in (50mm)
Caution!
1. The above dimensions are common for both open chassis type (IP00, IP20) and NEMA 1 type.
2. Always remove both top and bottom covers when using 200/400V, 5.5/7.5Kw (7.5/10 HP) as open chassis type.
19
Mounting/Removing Components
Removing and Mounting Digital Operator and Covers
NOTE:
Mount the inverter after removing the front cover, digital operator and terminal cover.
• Removing front cover
Use a screwdriver to loosen the screw on the front cover surface to direction 1 to remove it. Then press the right and left sides to direction 2 and lift the front cover to direction 3.
• Mounting front cover
Mount the front cover in the reverse order of the above procedure for removal.
• Removing terminal cover when “W”
(Width) dimensions are 4.25” (108mm),
5.51” (140mm), or 6.69” (170mm)
After removing the front cover, press the right and left sides to direction 1 and lift the terminal cover to direction 2.
.
• Removing terminal cover when “W”
(Width) dimensions are 7.09” (180mm)
Use a Screwdriver to loosen the screw on the terminal cover surface to direction 1 to remove it. Then press the right and left sides to direction 2 and lift the terminal cover to direction 3.
• Mounting terminal cover
Mount the terminal cover in the descending order of the above procedure for removal.
20
• Removing digital operator
After removing the front cover, lift the upper and lower sides (section A) of the right side of the digital operator to direction 1.
• Mounting digital operator
Mount the digital operator in the reverse order of the above procedure for removal.
• Removing bottom cover when “W” (Width) dimensions are 4.25” (108mm),
5.51” (140mm), or 6.69” (170mm)
After removing the front cover and the terminal cover, tilt the bottom cover to direction 1 with section A as a supporting point.
• Removing terminal cover when “W” (Width) dimensions are 7.09” (180mm)
After removing the terminal cover use a screwdriver to loosen the fastening screw to loosen the fastening screw to direction 1 to remove it.
• Mounting bottom cover
Mount the bottom cover in the reverse order of the above procedure for removal.
21

4. WIRING

• Wiring Instructions
(1) Always connect the power input terminals R/L1, S/L2, and T/L3 (R/L1, S/L2 for
single-phase) and power supply via a molded-case circuit breaker (MCCB). Never connect them to U/T1, V/T2, W/T3.
The single-phase (200V class) inverter can be connected to a 200V 3-phase input. However, when terminal T/L3 is connected to single-phase, never use the terminal for other purposes.
200V 3-phase Input Power Supply Specification Product CIMR-V7……2
Connect to R/L1, S/L2, T/L3 Connect to R/L1, S/L2 Connect to R/L1, S/L2, T/L3
(2) Connect the motor wiring to terminals U, V, and W on the main circuit output side
(bottom of the inverter).
(3) If the wiring distance between inverter and motor is long, reduce the inverter
carrier frequency. For details, refer to “Reducing motor noise or leakage current (n46)” on page 68.
(4) Control wiring must be less than 164ft(50m) in length and separate from the power
wiring. Use twisted-pair shielded wire when inputting the freque ncy signal
externally. (5) Tighten the screws on the main circuit and control circuit terminals. (6) Do not connect or disconnect wiring, or perform signal check while the power
supply is turned ON. (7) For 400V class inverters, make sure to ground the supply neutral to conform to CE
requirements. (8) A closed-loop connector should be used when wiring to the main circuit terminal. (9) Voltage drop should be considered when determining wire size.
Voltage drop can be calculated using the following equation:
Phase- to phase voltage drop (V) = √3 wire resistance (Ω/km) x wiring distance
(m) x current (A) x 10 Select a wire size so that voltage drop will be less than 2% of the normal rated
voltage.
Inverter Power Supply Connection Terminals
200V Single Input Power Supply Specification Product.
………
CIMR-V7……B
-3
………
400V 3-phase Input Power Supply Specification Product CIMR-V7……4
………
22
• Wire and Terminal Screw Sizes
1. Control Circuit
Tightening
M2
Torqu e
lb • in (N • m)
4.44 to 5.33 (0.5 to 0.6)
1.94 to 2.21
(0.22 to 0.25)
Model Terminal Symbol Screw
to
S1 to S7,P1, P2,SC,PC,R+,
MA, MB, MC M3
R-,S+,S-
,FS,FR,FC,AM,AC,RP
Common
all models
2. Main Circuit
200V Class 3-phase Input Series
Model Terminal Symbol Screw
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA20P1
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA20P2
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA20P4
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA20P7
R/L1,S/L2,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA21P5
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA22P2
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA24PO
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7*A25P5
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7*A27P5
M3.5
M3.5
M3.5
M3.5
M4
M4
M4
M5
M5
Note: The wire size is set for copper wires at 160°F (75°C)
Applicable size
mm twisted wire 0.5 to 1.25 single 0.5 to 1.25
twisted wire 0.5 to 0.75 single 0.5 to 1.25
Tightening
Torq ue
lb • in
(N • m)
7.1 to 8.88 (0.8 to 1.0)
7.1 to 8.88 (0.8 to 1.0)
7.1 to 8.88 (0.8 to 1.0)
7.1 to 8.88 (0.8 to 1.0)
10.65 to 13.31 (1.2 to 1.5)
10.65 to 13.31 (1.2 to 1.5)
10.65 to 13.31 (1.2 to 1.5)
22.19 (2.5)
22.19 (2.5)
Wire
Recommend
2
AWG
mm
20 to 16
0.75 18
20 to 16 20 to 18
0.75 18
20 to 16
size
2
AWG
18 to
18 to
18 to
18 to
14 to
14 to
14 to
14
14
14
14
10
10
10
Wire
Recommended
size
2
mm
214
214
214
214
214
3.5 12
5.5 10
Applicable
mm
0.75 to 2
0.75 to 2
0.75 to 2
0.75 to 2
2 to 5.5
2 to 5.5
2 to 5.5
5.5 to 8 10 to 8 8 8
5.5 to 8 10 to 8 8 8
size
2
AWG
AWG
Type
Shielded
wire or
equivalent
Type
600V vinyl-
sheathed
wire or
equivalent
23
200V Class Single-phase Input Series
Model Terminal Symbol Screw
Tightening
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AAB0P1
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AAB0P2
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AAB0P4
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AAB0P7
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AAB1P5
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AAB2P2
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMRV7AAB4PO
M3.5
M3.5
M3.5
M4
M4
M4
M5
M4
10.65 to 13.31
10.65 to 13.31
10.65 to 13.31
10.65 to 13.31
Note: The wire size is set for copper wires at 160°F (75°C) Note: Three-phase input is also available for 0.1 to 0.75kw of single-phase input
series.
Torq u e
lb • in
(N • m)
7.1 to 8.88 (0.8 to 1.0)
7.1 to 8.88 (0.8 to 1.0)
7.1 to 8.88 (0.8 to 1.0)
(1.2 to 1.5)
(1.2 to 1.5)
(1.2 to 1.5)
26.62 (3.0)
(1.2 to 1.5)
Applicable
size
2
mm
0.75 to 2
0.75 to 2
0.75 to 2
2 to 5.5
2 to 5.5
2 to 5.5
3.5 to 8
2 to 8
AWG
18 to
14
18 to
14
18 to
14
18 to
14
14 to
10
14 to
10
12 to
14 to
8
8
Recommended
mm
3. 5 12
5.5 10
3.5 12
5.5 10
5.5 10
400V Class 3-phase Input Series
Model Terminal Symbol Screw
Tightening
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA40P2
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA40P4
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA40P7
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA41P5
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA42P2 CIMR-V7AA43P0 R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7AA44PO R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7*A45P5 R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
CIMR-V7*A47P5 R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
M4
M4
M4
M4
M4
M4
M4
M4
M5
10.65 to 13.31
10.65 to 13.31
10.65 to 13.31
10.65 to 13.31
10.65 to 13.31
10.65 to 13.31
10.65 to 13.31
Note: The wire size is set for copper wires at 160°F (75°C)
Torq u e
lb • in
(N • m)
(1.2 to 1.5)
(1.2 to 1.5)
(1.2 to 1.5)
(1.2 to 1.5)
(1.2 to 1.5)
(1.2 to 1.5)
(1.2 to 1.5)
12.43 (1.4)
22.19 (2.5)
Applicable
size
2
mm
2 to 5.5
2 to 5.5
2 to 5.5
2 to 5.5
2 to 5.5
2 to 5.5
2 to 5.5
3.5 to 5.5
5.5 to 8
AWG
14 to
10
14 to
10
14 to
10
14 to
10
14 to
10
14 to
10
14 to
10
12 to
10
12 to
10
Recommended
mm
3.5 12
3.5 12
5.5 10
5.5 10
Wire
size
2
AWG
214
214
214
88
Wire
size
2
AWG
214
214
214
214
214 214
214
Type
600V vinyl-
sheathed
wire or
equivalent
Type
600V vinyl-
sheathed
wire or
equivalent
24
• Wiring the Main Circuit
L1 L2 L3
• Main circuit input power supply
Connect the power supply wiring to input terminals L1 (R), N/L2(S) and L3(T) [L1(R), N/L2(S) for single-phase specifications]. Never connect them to U/ T1, V/T2, W/T3, B1, B2, -, +1, or +2. Otherwise the inverter may be damaged. Single-phase voltage may be connected to inverter but do not use terminal T/L3 for any other purposes.
Single-phase (200V class, 0.75kW
NOTE
or less) voltage may be connected to terminal T/L3. Never use the ter­minal with other purposes.
• Grounding (Use ground terminal .)
Make sure to ground the ground terminal according to the local grounding code. Never ground the VS-606V7 in common with welding machines, motors, or other electrical equipment.
When several VS-606V7 units are used side by side, ground each unit as shown in examples. Do not loop the ground wires.
[Example of 3-phase 400V class, 0.37 inverters]
• Braking resistor connection (optional).
To connect the braking resistor, cut the protector on terminals B1 and B2.
To protect the braking resistor from overheating, install a thermal overload relay between the braking resistor and the inverter. This provides a sequence which shuts off the power supply, by a thermal relay trip contact.
Use this same procedure when connecting a braking resistor unit. Refer to page 104.
• Inverter output
Connect the motor terminals to U, V, W.
Wiring the main circuit termina ls
Pass the cables through wiring hole and connect. Be sure to mount the cover in its original position.
25
• Wiring the Control Circuit
Only basic insulation is provided for the control circuit terminal s. Additional insulation may be necessary in the end product.
• Control Circuit terminals
Pass the cable through wiring hole and connect. Be sure to mount all the covers on the original position.
* SW1 can be changed according to sequence input
signal (S1 to S7) polarity. 0V common: NPN side (factory setting) 24 common: PNP side Refer to pages 67 and 76 for SW2
Wiring the control circuit terminals
Screwdriver blade width
Insert the wire into the lower part of the terminal block and connect it tightly with a screwdriver.
Wire sheath strip length must be 0.22 in. (5.5mm).
26
Open the front cover and verify that the strip length is 0.22 in. (5.5mm)
• Wiring Inspection
After completing wiring, check the following:
• Wiring is properly connected.
• Wire clippings or screws are not left inside the unit.
• Screws are securely tightened.
• Bare wires in the terminal do not come in contact with other terminals. If the FWD (REV) run command is given during the operation reference selec-
NOTE
tion (n003=1) from the control circuit terminal, the motor will start automatically after the main circuit input power supply is turned ON.
27

5. OPERATING THE INVERTER

Initial setting of control mode selection (n002) is set at V/f control mode.

Test Run

The inverter operates by setting the frequency (speed). There are three types of operation modes for the VS-606V7:
1. Run command from the digital operator (local pote ntiometer/digital setting).
2. Run command from the control circuit terminal.
3. Run command from communications (MEMOBUS communications). Prior to shipping, the drive is set up to receive run command and frequency reference
from the operator. Below are instructions for running the VS-606V7 using the digital operator JVOP-140 (with local potentiometer) or optional JVOP-147 (without local potentiometer. For instructions on operation, refer to page 37.
Operation reference or frequency reference parameters can be selected separately as shown below.
Name parameter
Operation Reference
Selection
Frequency Reference
Selection
N003 = 0 --- Enables operator RUN, STOP/RESET
= 1 --- Enables control circuit terminal run/stop = 2 --- Enables communications (MEMOBUS communications) = 3 --- Enables communication card (optional)
N004 = 0 --- E nables digital operator potentiometer
= 1 --- Enables frequency reference 1 (parameter 024) = 2 --- Enables voltage reference (0 to 10V) of control circuit terminal = 3 --- Enables current reference (4 to 20mA) of control circuit terminal = 4 --- Enables current reference (0 to 20mA) of control circuit terminal = 5 --- Enables pulse line reference of control circuit terminal = 6 --- Enables communications (MEMOBUS communications) = 7 --- Enables voltage reference (0 to 10V) of operator circuit terminal = 8 --- Enables current reference (4 to 20 mA) of operator circuit terminal = 9 --- Enables communication card (optional)
28
1.Turn ON the power supply. 6.00
2. Set parameter n004 to 1. 1
3.Set the following parameters. n019 : 15.0 (acceleration time) n020 : 5.0 (deceleration time)
4.F/R blinks. Select Forward or reverse run by pressing or key.
NOTE
5.Set the reference by pressing or key.
6. Press
Operation Steps
Examine the application. (Never select REV when reverse run is prohibited.)
RUN
Operator
Display
15.0
5.0
(Forward) or
(Reverse)
60.00 RUN
0.00 60.0 RUN
12-LED Display
FREF
PRGM
PRGM
F /R
Status
Indicator LED
RUN ALARM
RUN ALARM
RUN ALARM
RUN ALARM
FREF
ALARM
FOUT
ALARM
7. Press
STOP
to stop.
Status indicator lamp
: Blinking (Long Blinking)
: ON
60.0 00.0 RUN
Operation Check Points
• Motor rotates smoothly.
• Motor rotates in the correct direction.
• Motor does not have abnormal vibration or noise.
• Acceleration or deceleration is smooth.
• Current matching the load flows.
• Status indicator LED’s and digital operator display are correct.
FOUT
: Blinking
ALARM
:OFF
29

Operating the Digital Operator

All functions of the VS-606V7 are set by the digital operator. Below are descriptions of the display and keypad sections.
Digital Operator JVOP-140
30
Description of Status Indicator LED’s
RUN
There are two LED’s on the middle right section of the face of the VS-606V7. The inverter status is indicated by various combinations of ON, BLINKING and OFF
LED’s. RUN indicator and status indicator of the button have the same functions.
For details on how the status indicator LED’s function at inverter faults, refer to Section 8 “FAULT DIAGNOSIS AND CORRECTIVE ACTIONS” on page 126. If a fault occurs, the ALARM LED lights.
NOTE
The fault can be reset by turning ON the fault reset signal (or pressing key on the digital operator) with the operation signal OFF or by turning OFF the
power supply. If the operation signal is ON, the fault cannot be reset by the fault reset signal.
STOP RESET
31

LED Description

By pressing on the digital operator, each of the function LED’s can be selected.
The following flowchart describes each function LED.
If the VS-606V7 loses power while in one of these modes, it will return to this mode once power is restored.
32
Return to
Multi-Function monitor
• Selecting monitor
Press key. When is ON, data can be displayed by selecting monitor No.
[Example] Monitoring Output Voltage Reference
41
33
• Monitoring
Following items can be monitored by U-parameter
parameter
No.
U-01
U-02
U-03 U-04 Output voltage V Output voltage can be monitored.
U-05 DC voltage V Main circuit DC voltage can be monitored. U-06 Input terminal status*
U-07 Output terminal status*
U-08 Torque monitor %
U-09 Fault history (last 4 faults) — Last four fault history is displayed. U-10 Software No. — Software No. can be checked. U-11 Output power*
U-13 Cumulative operation time*
U-15 Data reception error*
U-16 PID feedback* U-17 PID input* U-18 PID output*
*1 The status indicator LED is not turned ON. *2 Refer to the next page for input / output terminal status. *3 The display range is from -99.9kW to 99.99kW. When regenerating. the output power will be displayed in units of 0.01kW when
-9.99kW or less and in units of 0.1kW when more than -9.99kW. When in the vector control mode, “----” will be displayed. *4 This function only applies to 200/400V class 7.5/10hp (5.5/7.5kW) inverters. *5 Displayed in units of 0.1% when less than 100% and in units of 1% when 100% or more. The display range is from -999% to 999%.
Name Description
Frequency reference
(FREF)*
¹
Output frequency
(FOUT)*
¹
Output current
(IOUT)*
¹
3
5
5
5
Frequency reference can be monitored.
Hz
(Same as FREF) Output frequency can be monitored.
Hz
(Same as FOUT) Output current can be monitored.
Hz
(Same as IOUT)
Input terminal status of control circuit terminals can be
2
monitored. Output terminal status of control circuit terminals can
2
be monitored. The amount of output torque can be monitored. When
V/f control mode is selected, “----” is displayed.
kW Output power can be monitored
Cumulative operation time can be monitored in units of
4
x10H
10H Contents of MEMOBUS communication data reception
4
error can be checked. (contents of transmission
register No. 003DH are the same) % Input 100(%) / Max. output frequency or equivalent % + 100(%) /+ Max. output frequency % + 100(%) /+ Max. output frequency
34
35
Fault history display method
When U-09 is selected, a four-digit box is displayed. The three digits from the right show the fault description, and the digit on the left shows the order of fault (from one to four). Number 1 represents the latest fault, and 2, 3, 4, in ascending order of fault occurrence.
(Example)
(Refer to page 126 for details.)
• Switching fault history Order of the fault history can be changed by or key.
• Clearing fault history Set parameter n001 to 6 to clear fault history. Display returns to n001 after completion of 6 setting.
Note: parameter initialize (n001 = 10, 11) clears the fault history.
Setting and referring parameters
36

Simple Data Setting

Digital setting (Refer to 5, OPERA T ING THE INVER T ER) and potentiometer setting are both available for simple accel/decel operation of the VS-606V7.
Frequency reference by analog voltage is set with initial setting (n004 = 1). For the model with digital operator (with potentiometer) JVOP-140, factory setting is set by frequency setting potentiometer (n004=0).
Following is an example in which the function LED’s are used to set frequency reference, acceleration time, deceleration time, and motor direction.
Data setting by frequency setting potentiometer
Operation Steps
1. Turn the potent iometer fully to the left. Then, tur n the power ON.
2. F/R blinks.
Select FWD/REV run using keys.
Never select REV when reverse run is
NOTE
prohibited.
Operator
Display
0.00
FOR or REV
12-LED Display
FREF
F/R
Status
Indicator LED
RUN ALARM
RUN ALARM
3. Press DSPL to blink FREF. Then press RUN. 0.00
4. Operates the motor by turning the potentiometer
to the right. (Frequency reference corresponds to the potentiometer position is displayed.)
If the potentiometer is switched rapidly,
NOTE
the motor also accelerates or decelerate s rapidly corresponding to the potentiometer movement. Pay attention
to load status and switch the
potentiometer movement.
Status indicator lamp
: Blinking (Long Blinking)
: ON
00.0 to
60.00 Minimum output frequency is
1.50Hz
FREF
FREF
: Blinking
RUN ALARM
RUN ALARM
:OFF
37
Notes
38

6. PROGRAMMING FEATURES

Factory settings of the parameters are shown as in the tables.

Parameter Set-up and Initialization

Parameter selection/initialization (n001)
The following table describes the data which can be set or read when n001 is set. Unused parameters among n001 to n179 are not displayed.
n001 Setting Parameter that can be set Parameter that can be referred 0 n001 n001 to n179 1 n001 to n049* n001 to n049 2 n001 to n079* n001 to n079 3 n001 to n119* n001 to n119 4 n001 to n179* n001 to n179 5 Not used 6 Fault history cleared 8,9,12,13 Not used 10 Initialize 11 Initialize (3-wire sequence)
* Excluding setting disabled parameters.
=
Refer to page 70.
NOTE
” appears on the LED display for one second and the set data returns to its initial values in the following cases:
(1) The set values of input terminal function selection 1 to 7 (n050 to n056) are the
same.
(2) The following conditions are not satisfied in the V/f pattern setting:
Max. output frequency (n011) > > Mid. output frequency (n014) >
Min. output frequency (n016) For details, refer to “Adjusting torque according to application” (V/f pattern set­ting) on page 38.
(3) If the following conditions are not satisfied in the Jump frequency setting:
Jump frequency 3 (n085)<
(4) If Frequency reference lower limit (n034) >
(n033)
(5) If motor rated current (n036) > (6) When n018 = 0 and n019 ~ n022 is set to a value greater than 600.0 sec, parameter
n018 will automatically be set to 1.
=
Max. voltage output frequency (n013)
Jump frequency 2 (n084)
<
Jump frequency 1 (n083)
Frequency reference upper limit
150% of inverter rated current
39

Using V/f Control Mode

Vector control mode is preset at the factory. Control mode selection (n002): 0: V/f control mode (initial setting) 1: Vector control mode
Adjusting torque according to application
Adjust motor torque by using “V/f pattern” and “full-range automatic torque boost”.
• V/f pattern setting Set V/f pattern by n011 to n017 as described below. Set each pattern when using a special motor (high-speed motor, etc.) or when requiring special torque adjustment of machine.
Be sure to satisfy the following conditions for the setting of n011 to n017.
n014 < n013 < n011
n016 < If n016 = n014 is set, the set value of n015 is disabled.
n016 n014 n013 n011 (frequency)
Parameters
No.
n011 Max. output frequency 0.1Hz 50.0 to 400.0Hz 60.0Hz n012 Max. voltage 1V
Max. voltage output frequency
n013
(base frequency)
n014 Mid. output frequency 0.1Hz 0.1 to 399.9Hz 1.5Hz n015 Mid. output frequency voltage 1V n016 Min. output frequency 0.1Hz 0.1 to 10.0Hz 1.5Hz n017 Min. output frequency voltage 1V
* 10.0V for 200V class 7.5/10hp (5.5/7.5kW)
20.0V for 400V class 7.5/10hp (5.5/7.5kW)
NOTE: Values with parentheses indicate 400V class.
Name Unit Setting range Initial Setting
1 to 255.0V
0.1Hz 0.2 to 400.0Hz 60.0Hz
(0.1 to 510.0V)
0.1 to 255.0V
(0.1 to 510.0V)
1 to 50.0V
(0.1 to 100.0V)
40
230.0V
(460.0V)
12.0V
(24.0V)
4.3V * (8.6V)
• Typical setting of V/f pattern Set the V/f pattern according to the application as described below . For 400V class, the voltage values (n012, n015, and n017) should be doubled. When running at a frequency exceeding 50Hz/60Hz, change the maximum output frequency (n011).
Note: Be sure to set the maximum output frequency according to the motor char-
acteristics
(Factory setting)
Increasing voltage of V/f pattern increases motor torque, but excessive increase may cause motor over excitation, motor overheat, or vibration.
Note: n012 is to be set to motor rated voltage.
41
Full-range automatic torque boost (when V/f mode is selected. n002=0)
Motor torque requirement changes according to load conditions. Full range automatic torque boost adjusts voltage of V/f pattern according to the requirement. The VS-606V7 automatically adjusts the voltage during parameter-speed operation as well as during acceleration. The required torque is calculated by the inverter. This ensures tripless operation and energy-saving effects.
Output voltage Torque compensation gain (n103) Required torque
×
• Operation
Normally, no adjustment is necessary for torque compensation gain (n103 factory setting: 1.0). An excessively high setting of torque compensation gain will res ult in motor over excitation, and possible inverter faults. If adjustments are necessary , adjust n103 in increments/decrements of 0.1 for optimization. When wiring distance between the inverter and the motor are long it may be necessary to increas e t he setting of n103. When motor generates vibration, decrease the setting of n103.
Adjustment of torque compensation time parameter (n104) and torque iron loss compensation parameter (n105) are normally not required.
Adjust torque compensation parameter under the following conditions:
• Increase setting when the motor generates vibration.
• Reduce setting when motor response is low.
42

Using Vector Control Mode

Setting the control mode selection (n002) can use a vector control mode.
n002=0: V/f control mode (factory setting)
1: Vector control mode
Precaution for voltage vector control application
Since vector control needs motor parameters, the YASKAWA standard motor parameters have been set at the factory prior to shipment. Therefore, when an inverter exclusive-use motor is used or when a motor of any other manufacturer is driven, the required torque characteristics or speed control characteristics may not be maintained because the parameters are not matched. Set the following parameters so that they can match the motor parameters.
No. Name Unit Setting range
n106 Motor rated slip 0.1Hz 0.0 to 20.0Hz
n107 Motor resistance per phase
n036 Motor rated current 0.1A
n110 M oto r no-load current 1%
Setting depends on inverter capacity.
=
0.001
(less than 10Ω)
0.01
(10Ω or more)
0.000 to 65.5
0 to 150% of inverter rated
current
0 to 99%
(100%=motor rated current)
Ω∗
Initial
Setting
150
To adjust for slip compensation gain (n111), induce load so that motor speed reaches target value. Increase or decrease the value by 0.1.
• When speed is less than target value, increase slip compensation gain.
• When speed is more than target value, reduce slip compensation gain. Adjustment of slip compensation gain time parameter (n112) is normally not
required. Adjust under the following conditions:
• Reduce the setting when response is low.
• Increase the setting when speed is unstable.
43
Select slip compensation status during regeneration
N113 Setting Slip Compensation during Regeneration
0Disabled 1 Enabled
Motor parameter calculation
The following shows an example of motor parameter calculation:
(1) Motor rated slip (n106)
×
120 motor rated frequency (Hz)
------------------- ----------------------------- --------------------------------- ----------- -
Number of motor pole
------------------ ------------------------------ --------------------------------- ------------------------------ ----------------------------- ------------------------------- -
=
120/Number of motor pole
(2) Motor resistance for one phase (n107)
Calculations are based on line-to-line resista nc e and insulation grade of the motor test report.
(E type insulation) Test report of line-to-line resistance at 75°C (
(B type insulation) Test report of line-to-line resistance at 75°C (
(F type insulation) Test report of line-to-line resistance at 115°C (
(3) Motor rated current (n036)
= Rated current at motor rated freque ncy (Hz) *1 (A)
*1
Motor rated speed (r/min)
) x 0.92 x 1/2
) x 0.92 x 1/2
) x 0.87 x 1/2
*2
(4) Motor no-load current (n110)
No-load current (A) at motor rated frequency (Hz)
--------------------------------------------------------------------------------------------------------- -
=
Rated current (A) at motor rated frequency (Hz)
*1 Base frequency (Hz) during rated output current.
*2 Rated speed (r/min) at base frequency during rated output current.
Set n106 (motor rated slip), n036 (motor rated current), n107 (motor resistance per phase) and n110 (motor no-load current) according to the motor test report.
When connecting a reactor between the inverter and the motor, set n108 to the value of n108 (motor leaking inductance) initial value + externally-mounted reactor inductance.
*1
×
100%
*1
Initial setting should be used unless a reactor is installed. Unless a reactor is connected, n108 (motor leakage inductance) does not have to be set
according to the motor.
44
V/f pattern during vector control
Set V/f pattern as follows during vector control. The following examples are for 200V class motors. When using 400V class motors, double voltage settings (n012, n015, n017).
When operating with frequency larger than 60Hz/50Hz, change only maximum output frequency (n011).
PARAMETER TORQUE VARIABLE OUTPUT
PARAMETER OUTPUT
= 50Hz
45

Switching LOCAL/REMOTE Modes

The following functions can be selected by switching the LOCAL or REMOTE mode. To select RUN/STOP commands or frequency reference, change the mode in advance depending on the following applications.
• LOCAL mode: Enabl es the digital operator for RUN/STOP commands and
• REMOTE mode: Enables operation reference selection (n003).
How to select LOCAL/REMOTE modes
FWD/REV run commands. Frequency reference can be set by local potentiometer or .
46

Selecting Run/Stop Commands

Refer to Switching LOCAL/REMOTE Modes (Page 44) to select either the LOCAL mode or REMOTE mode. Operation method (RUN / STOP commands, FWD / REV run commands) can be selected by the following method.
LOCAL Mod e
When Lo (local mode) is selected by digital operator ON mode, or when the LOCAL / REMOTE switching function is set and the input terminals are
turned ON, run operation is enabled by the or of the digital operator, and FWD/REV run is selected by ON mode (using or key).
REMOTE mode
• Select remote mode. The following two methods are used to select remote mode:
1. Select rE (remote mode) by
2. When the local / remote switching function is sele cte d by multi-function
input selection, turn OFF the input terminal to select remote mode.
• Select operation method by setting the parameter n003. n003 =0: Enables the digital operator (same with local mode)
=1: Enables the multi-function input terminal (see fig. below)
=3: Enables communication card (optional)
Below shows the example of three-wire sequence, (Refer to page 70.)
=2: Enables communications
• Example for using the multi-function input terminal as operation reference (two-wire sequence)
selection.
)
For example of three-wire sequence, refer to page 70
Note: When inverter is operated without the digital operator, always set the
parameter n010 to 0.
47
Operating (RUN /STOP commands) by communications
Setting parameter n003 to 2 in REMOTE mode can give RUN / STOP commands by communication (MEMOBUS communications). For the command by transmission, refer to page 89).
Selecting Frequency Reference
Frequency reference can be selected by the following methods.
Setting by operator
Select REMOTE or LOCAL mode in advance. For the method of selecting the mode, refer to page 44.
LOCAL mode
Select command method by parameter n008. n008 =0 : Enables the setting by potentiometer on digital operator.
=1 : Enables the digital set ting by digita l opera tor. (Initial Setting)
F ac t o r y s et t in g o f th e m o de l wi th d ig it a l o pe r at or ( wi th potentiometer) JVOP-140 is n008=0.
• Digital setting by digital operator
Input frequency while FREF is lit (press ENTER after setting the nume ric value). Frequency reference setting is effective when 1 (initial setting : 0) is set to
parameter n009 instead of pressing ENTER key. n009 =0 : Enables frequency reference setting by ENTER key.
=1 : Dis able frequency reference setting by ENTER key.
REMOTE mode
Select command method by parameter n004. n004 =0 : Enables frequency reference setting by potentiometer on digital
operator.
=1 : Frequency reference 1 (n024) is effective (Initial setting) Factory setting of the model with digital operator (with potentiometer)
JVOP-140 is n004=0 =2 : Voltage reference (0 to 10V) (See the figure on page 47) =3 : Current reference (4 to 20mA) (Refer to page 81) =4 : Current reference (0 to 20mA) (Refer to page 81) =5 : Pulse train reference (Refer to page 82) =6 : Communication (Refer to page 90) =7 : Voltage reference of digital operator circuit terminal (0-10) =8 : Current reference of digital operator circuit terminal (4-20mA) =9 : Communication card (optional)
48
Example of frequency reference by voltage signal
1)
49

Setting Operation Conditions

Reverse run prohibit (n006)
“Reverse run prohibit” setting does not accept a reverse run command from the control circuit terminal or digital operator. This setting is used for applications where a reverse run command can cause problems.
Setting Description
0 Reverse run enabled 1 Reverse run disabled
Multi-step speed selection
By combining frequency reference and input terminal function selections, up to 16 steps of speed can be set.
8-step speed change
n003=1 (operation mode selection) n004=1 (Frequency reference selection) n024=25.0Hz (Frequency reference 1) n025=30.0Hz (Frequency reference 2) n026=35.0Hz (Frequency reference 3) n027=40.0Hz (Frequency reference 4) n028=45.0Hz (Frequency reference 5) n029=50.0Hz (Frequency reference 6) n030=55.0Hz (Frequency reference 7) n031=60.0Hz (Frequency reference 8)
When all multi-step speed inputs are
NOTE
open, frequency reference selected by parameter n004 (frequency reference selection) becomes effective.
Only when multi-step speed input ref. 1 is closed and n077=1, the effective frequency reference becomes the CN2 analog input signal.
n054=6 (Multi-function contact input terminal 5) n055=7 (Multi-function contact input terminal 6) n056=8 (Multi-function contact input terminal 7) n053=1
n050=1 (Input terminal S1 ) Initial Setting n051=2 (Input terminal S2 ) Initial Setting n052=3 (Input terminal S3) Initial Setting n053=5 (Input terminal S4 ) Initial Setting n054=6 (Input terminal S5 ) Initial Setting n055=7 (Input terminal S6 ) Initial Setting n056=10 (Input terminal S7 ) Change the Setting to 8
50
Additional settings for 16-Step speed operation Set n120 ~ n127 to frequency reference 9-16. A multi-function input must be set to multi-step speed reference 4 (n050 ~ n056 = 9).
Operating at low speed
By inputting a jog command and then a forward (reverse) run command, opera tion is enabled at the jog frequency set in n032. When multi-step speed references 1, 2, 3 or 4 are inputted simultaneously with the jog command, the jog command has priority.
Parameter No. Name Setting
n032 Jog freque ncy reference Factory setting : 6.00Hz
n050 to n056 Jog command Set to “10” for any parameter.
51
Adjusting speed setting signal
To provide frequency reference by analog input of control circuit terminal FR and FC, the relationship between analog input and frequency reference can be set.
FREQUENCY REFERENCE
(a) Analog frequency reference gain (n060)
The frequency reference provided when analog input is 10V(20mA) can be set in units of 1%. (maximum output frequency n011=100%)
Factory setting : 100%
(b) Analog frequency reference bias (n061)
The frequency reference provided when analog input is 0V (4mA or 0mA) can be set in units of 1%. (Maximum output frequency n011=100%)
Factory setting : 0%
Typical setting
52
•To operate the inverter with frequency reference of 0% to 100% at 0 to 5V input
•To operate the inverter with frequency reference of 50% to 100% at 0 to 10V input
53
Adjusting frequency upper and lower limits
• Frequency reference upper limit (n033) Sets the upper limit of the frequency reference in units of 1%. (n011: Maximum output frequency = 100%) Factory setting: 100%
• Frequency reference lower limit (n034) Sets the lower limit of the frequency reference in units of 1%. (n011: Maximum output frequency = 100%) When operating at frequency reference 0, operation is continued at the frequency reference lower limit. However, when frequency reference lower limit is set to less than the minimum output frequency (n016), operation is not performed. Factory setting: 0%
Using two accel/decel times
*When “deceleration to a stop” is selected (n005=0).
By setting “Multifunction Input Selection” (either of n050 to n056) to “11 (accel/decel time select)”, accel/decel time is selected by turning ON/OFF the accel/ d ecel tim e select (terminal S1 to S7).
At OFF : n019 (accel time 1)
n020 (decel time 1)
At ON : n021 (accel time 2)
n022 (decel time 2)
54
No. N am e Unit Setting Range Initial setting n019 Accel time 1 n020 Decel time 1 10.0s n021 Accel time 2 10.0s n022 Decel time 2 10.0s
Refer to
n018
setting
Refer to n018
setting
10.0s
n018 setting
No. Unit Setting Range
n018
Notes: Parameter n018 can be set during stop. If the numeric value exceeded 600.0 sec. is set for the accel/decel time when n018 = 0 (in units of 0.1 sec.). “1” cannot be set to n018.
• Accel time Set the time needed for output frequency to reach 100% from 0%.
0.1s 0.0 - 999.9s (999.9s or less)
0
1s 1000 - 6000s (1000s or more)
0.01s 0.00 - 99.99s (99.99s or less)
1
0.1s 100.0 - 600.0s (100s or more)
• Decel time Set the time needed for output frequency to reach 0% from 100%.
(Maximum output frequency n011 = 100%)
Automatic restart after momentary power loss (n081)
When parameter n081 is set to 1 or 2, operation automatically restarts even if momentary power loss occurs.
Setting. Description
0 Continuous operation after momentary power loss not provided.
Continuous operation after power recovery within momentary
1*
power loss ride thru time 0.5s. Continuous operation after power recovery (Fault output not
2*
=
* Hold the operation command to continue the operation after recovery from a momentary power
= When 2 is selected, the inverter restarts if power supply voltage recovers while the control power
provided)
loss.
supply is held. No fault signal is output.
55
Soft-start characteristics (n023)
To prevent shock at machine start/stop, accel/decel can be performed in S-curve pattern.
Setting S-curve characteristic time
0 S-curve characteristic not provided 1 0.2 second 2 0.5 second 3 1.0 second
Note: The S-curve characteristics time is the time from accel/decel rate 0 to a reg-
ular accel/decel rate determined by the set accel/decel time.
The following time chart shows FWD/REV run switching at deceleration to a stop.
56
Torque detection
If an excessive load is applied to the machine, the resultant output current increase can be compared to the threshold setting of parameter n098, then output alarm signals to multi-function output terminals MA, MB, P1 and P2.
To output an overtorque detection signal, set output terminal function selection n057 to n059 to “overtorque detection” [Setting:6 (NO contact) or 7 (NC contact)].
Overtorque detection release width (hysterisis) is set at approx. 5% of inverter rated current.
57
Overtorque detection function selection 1 (n096)
Setting Description
0 Overtorque detection not provided
Detected during parameter-speed running,
1
and operation continues after detection. Detected during parameter-speed running,
2
and operation stops during detection. Detected during running,
3
and operation continues after detection. Detected during running,
4
and operation stops during detection.
(1) To detect overtorque at accel/decel, set to 3 or 4. (2) To continue the operation after overtorque detection, set to 1 or 3.
During detection, the operator displays “ ” alarm (blinking).
(3) To halt inverter by a fault at overtorque detection, set to 2 or 4. At detection, the
operator displays “ ” fault (ON).
• Overtorque detection level (n098) Sets the overtorque detection current level in units of 1%. (Inverter rated current = 100%) When detection by torque is selected, motor rated torque becomes 100%. Factory setting: 160%
• Overtorque detection time (n099) If the time when the motor current exceeds the overtorque detection current level (n098) is longer than overtorque detection time (n099), the overtorque detection function operates. Factory setting: 0.1sec.
• Overtorque detection function selection 2 (n097) When vector control mode is selected, overtorque detection can be performed either by output current or by output torque. When V/f control mode is selected, n097 setting becomes invalid, and overtorque is detected by output current.
Setting Description
0 Detected by output torque 1 Detected by output current
58
Frequency detection (n095)
Effective when either of output terminal function selections n057, n058 or n059 are set to “frequency detection” (setting: 4 or 5). “Frequency detection” turns ON when output frequency is higher or lower than the frequency detection level (n095).
• Frequency detection1 Output frequency > Frequency detection level n095
(Set either of n057, n058 or n059 to “4”.)
• Frequency detection2 Output frequency <
Frequency detection level n095
(Set either of n057, n058 or n059 to “5”.)
59
Jump frequencies (n083 to n086)
This function allows the prohibition or “jumping” of critical frequencies so that the motor can operate without resonance caused by machine systems. This function is also used for dead band control. Setting the value to 0.00Hz disables this function.
Set prohibited frequency 1, 2 or 3 as follows:
n083 > n084 > n085 If this condition is not satisfied the
inverter displays for one second and restores the data to original settings.
Operation is prohibited within jump frequency range. However, motor operates smoothly (without jumping) during accel/decel.
Continuing operation by automatic fault reset (n082)
Sets the inverter to restart and reset fault detecti on af ter a fault occurs. The number of self-diagnosis and retry attempts can be set at n082 up to 10. The inverter automatically restarts after th e following fa ults occur:
• OC (over current)
• OV (over voltage) The number of retry attempts are cleared to 0 during the following cases: (1) If no other fault occurs within 10 minutes after retry (2) When the fault reset s igna l is ON after the fa ult is det ect ed (3) Power supply is turned OFF
60
Cumulative Operation Time Selection (n087)
Setting Description
0
1
(Counts the el apsed time that there is an inverter output.)
Inverter power -o n t im e
(Counts the elapsed time that there is an inverter output)
Inverter running time
Cumulative operation time setting. Inverter operating time set with parameter n087 is accumulated by the unit of 10H. Accumulation starts from the time set with parameter n08 8.
Parameter No. Name Unit Setting Range
n088 Cumulative operation 1 = 10H 0 to 6550 (65500H) 0 (H)
Initial
Setting
Installed Braking Resistor Overheating protection Selection (n165) Set 0 when braking resistor is not connected.
Setting Description
0 Over heating protection is not provided 1 Overheating protection is provided
61
Input / Output Open Phase Protection
Parameters
No.
n166
n167
n168
n169
Name Unit
Input open-phase
detection level
Input open-phase
detection time
Output open-phase
detection level
Output open-phase
detection time
*1 0% setting - no detection *2 0.0 sec setting - no detection
• Recommended set values: 7% for n166 10sec. for n167
5% for n168
0.2sec. for n169
Setting Range
0 to 100% *1
1%
1 sec. 0 to 255 sec. *2 0 sec.
1%
0.1 sec. 0.0 to 2.0 sec *2 0.0 sec.
400.0V/100%
(for 200V class)
800.0V/100%
(for 400V class)
0 to 100% *1
Inverter rated output
current value/100%
Initial
Setting
0%
0%
62
• Speed search command
Restarts a coasting motor without stopping it. This function enab les smooth switching between motor commercial power supply operation and inverter operation.
Set input terminal function selection (n050 to n056) to “14” (search command from maximum output frequency) or “15” (search command from set frequency).
Build a sequence so that FWD (REV) run command is input at the same time as the search command or after the search command. If the run command is input before the search command, the search command becomes disabled.
• Time chart at search command input
Set declaration time during a speed search at parameter n101. Speed search starts when inverter output current This function applies to the 200/400V class 7.5/10hp inverters.
speed search operation level.
>
63
Holding accel/decel temporarily
To hold acceleration or deceleration, input accel/decel hold command. The output frequency is maintained when the accel/decel hold command is input during acceleration or deceleration.
When the stop command is input during accel/decel prohibition command input, accel/ decel hold is released and operation ramps to stop.
Set multi-function input terminal selection (n050 to n056) to 16 (accel/decel hold command).
64
Using frequency meter or ammeter (n066)
Selects the function to be monitored at analog output terminals AM-AC.
Setting Description
0 Output frequency 1 Output current 2 Main circuit DC voltage 3 Torque monitor 4 Output power 5 Output voltage reference
In initial setting, analog voltage of approx. 10V is output when output frequency (output current) is 100%.
Calibrating frequency meter or ammeter (n067)
Used to adjust analog output gain.
Set the analog output voltage at 100% of output frequency (output current). Frequency meter displays 0 to 60Hz at 0 to 3V.
10V
n067 Setting
×
0.30
3V
=
Output frequency becomes 100% at this value
65
Using analog output (AM-AC) as a pulse train signal output (n065)
Analog output AM-AC can be used as a pulse train output (output frequency monitor). Set n065 to 1 when using pulse train output.
Parameters No. Name Unit Setting range Initial Setting
n065 Monitor output type selection 1 0,1 0
n065 setting
n065 Setting
0 Analog monitor output 1
Pulse train signal can be selected by setting n150.
n150 Setting Description
0 1440Hz / Max. frequency (n011) 1 1F: Output frequency x 1
6 6F: Output frequency x 6 12 12F: Output frequency x 12 24 24F: Output frequency x 24 36 36F: Output frequency x36
At the factory setting the pulse of 1440Hz can be output when output frequency is 100%
Pulse monitor output can be adjusted with the parameter n067.
Pulse monitor output
(Output frequency monitor)
66
Peripheral devices must be connected according to the following load conditions
NOTE
when using pulse monitor output. The machine might be damaged when the con­ditions are not satisfied.
Used as a sourcing output
Output voltage
VRL (V)
+5V 1.5 kΩ or more +8V 3.5 kΩ or more +8V 10 kΩ or more
Load impendance
(k
Ω)
Used as a sinking input
External power supply (V) +12VDC+5%
Sinking current (mA) 16mA or less
67
Reducing motor noise leakage current (n080)
Set inverter output transistor switching frequency (carrier frequency).
Setting Carrier Frequency (kHz)
7 12 fout (Hz)
8 24 fout (Hz)
9 36 fout (Hz)
12.5(kHz)
25.0(kHz)
37.5(kHz)
4 10.0 (kHz)
Metallic Noise
from Motor
Higher
audible
Setting values 7, 8, or 9 multiplies output frequency according to output frequency value.
Not
Noise and Current
Leakage
Smaller
Larger
fout = OUTP UT FREQUENCY
fou t = OU T P UT FREQUENCY
fou t = O U T PUT FREQUENCY
68
Reducing Mo tor Noise or Leakage Current (n080)
Frequency setting varies according to inverter capacity (kVA).
Voltage Class (V)
200
Single-phase 3-
phase
400
3-phase
Capacity
(kW)
0.1 4 10kHz 0.8
0.2 4 10kHz 1.6
0.4 4 10kHz 3.0
0.7 4 10kHz 5.0
1.5 3 7.5kHz 8.0 7.0
2.2 3 7.5kHz 11.0 10.0
3.7 3 7.5kHz 17.5 16.5
5.5 3 7.5kHz 25 23
7.5 3 7.5kHz 33 30
0.2 3 7.5kHz 1.2 1.0
0.4 3 7.5kHz 1.8 1.6
0.7 3 7.5kHz 3.4 3.0
1.5 3 7.5kHz 4.8 4.0
2.2 3 7.5kHz 5.5 4.8
3.0 3 7.5kHz 7.2 6.3
3.7 3 7.5kHz 8.6 8.1
5.5 3 7.5kHz 14.8 *
7.5 3 7.5kHz 18 17
(1) Reduce continuous output current when changing carrier frequency to
4 (10kHz) for the 200V class (1.5 W or more) and 400V class invert-
Initial Setting Maximum
Carrier
Setting
Frequency
Continuous
Output Current
(A)
ers. Refer to the table above for the reduced current.
[Operation Condition]
•Input power supply voltage : 3-phase 200 to 230 V (200V class) Single-Phase 200 to 240V (200V class)
3-Phase 380 to 460V (400V class)
•Ambient temperature: 14 to 122ºF (-10 to +50ºC) (Protection structure: open chassis type
IP20)
(2) If the wiring distance is long, reduce the inverter carrier frequency as
described below
Reduced
Current (A)
Wiring Distance between
Inverter and Motor
Carrier frequency
(n080 setting )
Up to 50m Up to 100m More than 100m
10kHz or less
(n080=1, 2, 3, 4, 7, 8, 9)
5kHz or less
(n080=1, 2, 7, 8, 9)
2.5kHz or less
(n080=1, 7, 8, 9,)
69
(3) Set carrier frequency (n080) to either 1, 2, 3, 4 when using vector con-
trol mode. Do not set to 7, 8, or 9.
(4) Carrier frequency is automatically reduced to 2.5kHz when reducing
carrier frequency selection at low speed (n175) is set to 1 and the fol­lowing conditions are satisfied:
Output frequency < 5 Hz Output current > 110%
Factory setting : 0 (Disabled)
Operator stop key selection (n007)
Selects processing when STOP key is pressed during operation either from multi-func­tion input terminal or communications.
Setting Description
STOP key effective when running either from multi-function input terminals or communications. When STOP key is pressed, the inverter stops according to the setting of the parameter n005.
0
At this time, the digital operator displays “ “ alarm (blinking). This stop command is held in the inverter until both forward and reverse run commands are open, or until run command from communications becomes zero.
STOP key is ineffective when running either from multi-function input terminals or
1
communications.
70
Selecting stopping method (n005)
Selects the stopping method suitable for application.
Setting Description
0 Decel eration to sto p 1 Coast to stop
• Deceleration to stop Example: when accel/decel time 1 is selected
.5
.0
* When frequency reference is changed during running.
Upon termination of the FWD (REV) run command, the motor decelerates at the decel rate determined by the time set to decel time 1 (n020) and DC injection braking is applied immediately before stop. DC injection braking is als o applie d when the motor decelerates by setting frequency reference lower than minimum output frequency (n016) with FWD (REV) run command ON.
If the decel time is short or the load inertia is large, over voltage (OV) fault may occur at deceleration. In this case, increase the decel time or install a optional braking resistor.
Braking Torque: Without braking resistor: Approx. 20% torque of motor rating
With braking resistor: Approx. 150% torque of motor rating
71
• Coast to stop Example: when accel/decel time 1 is selected
* When frequency reference is changed during running.
Upon removal of the FWD (REV) run command, the motor starts coasting.
Applying DC injection braking
• DC injection braking current (n089) Sets DC injection braking current in units of 1%. (Inverter rated current=100%)
• DC injection braking time at stop (n090) Sets the DC injection braking time at stopping in units of 0.1 second. When the setting of n090 is 0, DC injection braking is not performed but inverter output is shut OFF at the timing of DC injection braking start.
When coasting to a stop is specified in stopping method selection (n005), DC injection braking at stop does not operate.
72

Building Interface Circuits with External Devices

Using input signals
Multi-function input terminal S1 to S7 functions can be changed when necessary by setting parameters n051 or n052 respectively. The same value cannot be set to different parameter settings.
Setting Name Description Ref.
0 1 2
3 External fault (NO contact input) 4 External fault (NC contact input)
5Fault Reset 6 Multi-step speed reference 1 50
7 Multi-step speed reference 2 50 8 Multi-step speed reference 3 50
9 Multi-step speed reference 4 50 10 JOG command 51 11 Accel/Decel time select 54
12 13 14 15
16 Accel/decel hold command 64 17 LOCAL/REMOTE selection 46
18 19 20 21 22
23 PID Control cancel 114 24 PID integral reset 114
26 Inverter overheat prediction OH3 25 PID intregal hold 114
34 UP/DOWN command 35 Self-test
* Numbers 1 to 7 are displayed in q corresponding to the terminal number S1 to S7 respectively.
FWD/REV run command
(3 wire sequen ce selection)
Forward run
(2 wire sequen ce selection)
Reverse run
(2 wire sequen ce selection)
External baseblock
(NO contact input)
External baseblock
(NC contact inp ut )
Search command from
maximum frequency
Search command from
set frequency
Communication/control circuit
terminal selection
Emergency st op fault
(NO contact input)
Emergency stop alarm
(NO contact input)
Emergency st op fault
(NC contact inp ut )
Emergency stop alarm
(NC contact inp ut )
Setting enabled only for n052 74
Inverter stops by external fault signal in put
Digital opera tor display is
Resets the fault. Fault reset not
effective with the run signal ON.
Motor coast to a stop by this
Digital operator display is
Inverter stops by emergency stop signal input according to stopping method selection (n005). When frequency coasting to a stop (n005 is set to 1) method is selected, inverter coasts to a stop according to decel time setting 2 (n022).
Digital operator display is (lit at fault, blinking at alarm).
“ (Blinking) is displayed on the digital operator by signal input
Setting enabled only for Setting enabled only for
signal input.
bb.
Speed search
reference signal
sRp
n056 (terminal S7) n056 (terminal S7)
EFD
45 45
.*
50
– 63 63
78
75
114
73
Initial setting
No. Terminal Initial Setting Function n050 S1 1 Forward run command (2-wire sequence) n051 S2 2 Reverse run command (3-wire sequence) n052 S3 3 External fault n053 S4 5 Fault reset n054 S5 6 Multi-step speed reference 1 n055 S6 7 Multi-step speed reference 2 n056 S7 10 JOG command
Terminal function at 3-wire sequence selection
When 0 is set at the terminal S3 (n052), terminal S1 becomes run command, terminal S2 becomes stop command, and terminal S3 becomes FWD/REV ru n comma nd.
• LOCAL/REMOTE select (setting: 17) Select operation reference either by the digital operator or by the settings of operation method selection (n003) and frequency reference selection (n004). LOCAL/REMOTE select is available only during stop.
Open: Run according to the setting of run command selection (n003) or
frequency reference selection (n004)
Closed: Run by frequency reference and run command from the digital operator.
74
(Example:)Set n003 = 1, n004 = 2, n008 = 0. Open: R un by frequency reference from multi -funct ion input terminal FR and
run command from multi-function input terminals S1 to S7.
Closed: Run by potentiometer frequency reference and run command from the
digital operator.
• UP/DOWN command (setting: n056 = 034) With the FWD (REV) run command entered, accel/decel is enabled by inputting the UP or DOWN signals to multi-function input terminals S6 and S7 without changing the frequency reference, so that operation can be performed at the desired speed. When UP/DOWN commands are specified by n056, any function set to n055 becomes disabled; terminal S6 becomes an input terminal for the UP command and terminal S7 for the DOWN command.
Multi-function Input Terminal S6 (UP command) Multi-function Input Terminal S7 (DOWN command) Operation Status Accel Decel Hol d Hold
Closed Open Open Closed
Open Closed Open Closed
75
Time Chart at UP/DOWN Command Input
76
Notes: (1) When UP/DOWN command is selected, the upper limit speed is set regardless of frequency
reference.
Upper limit speed = Maximum output frequency (n011)
(2) Lower limit value is either minimum output frequency (n016) or frequency reference lower limit
(n034) (whichever is greater).
(3) When the FWD (REV) run command is input, operation starts at the lower limit speed without an
UP/DOWN command.
(4) If the jog command is input while running by the UP/DOWN command, the jog command has
priority.
(5) Multi-step speed reference 1 to 4 is not effective when UP/DOWN command is selected. Multi-
step speed reference is effective during running in hold status.
(6) When “1” is set for HOLD output frequency memory selection (n100), output frequency can be
recorded during HOLD.
Setting Description
0 Output frequency is not recorded during HOLD. 1
x Frequency reference upper limit (n033)/100
When HOLD status is continued for 5 seconds or longer, the output frequency during HOLD is recorded and the inverter restarts at the recorded frequency.
77
Communication/multi-function input terminal selection input (setting: 18)
Operation can be changed from communication command, or from multi-function
input terminal or digital operator command. Run command from communication and frequency reference are effective when
multi-function input terminal for this setting is “closed (regis te r No. 0001H, 0002H).” Run command in LOCAL/REMOTE mode and frequency reference are effective when “Open.”
Using multi-function analog input (n077, n078, n079)
The input analog signal (0 to 10V or 4mA to 20mA) for the CN2 terminal of the JVOP-140 digital operator can be used as an auxiliary function for the main speed frequency reference input to the control circuit terminals (FR or RP). Refer to the
block diagram on page 111 for details of the input signal.
When using the signal for the CN2 terminal of the JVOP-140 digital operator’s
NOTE
a multi-function analog input, never use it or the target value or the feedback value of PID control. (PID control is disabled when n128 is set to 0.)
Multi-function input selection (n077)
No. Name Unit
n077
Multi-function
input selection
_ 0 to 4 0
Setting Range
Initial
Setting
78
n077 setting
Setting Name Description
0 Disabled The multi-function input is disabled
Auxiliary frequen c y reference (FREF2)
1
Frequency reference gain
2
(FGAIN) Frequency reference (FBIAS)
3
4 Frequency detection
When frequency reference 2 is selected in multi-step speed reference, the input analog signal for the CN2 terminal becomes the frequency reference. The n025 setting becomes invalid. Note: Set frequency reference gain to n068 or n071, and frequency reference bias to n069 or no72.
Provides gain to main frequency reference. Set the FGAIN to parameter n60 or n074 and the FBIAS
to parameter n061 or n075 for the main speed frequency reference. Then, add the FBIAS to the resulting frequency reference. The amount of the FBIAS to be added is set to n79. Add the VBIAS to the output voltage after V/f conversion.
79
Analog input level
Frequency reference gain (n077=2)
Auxiliary frequency reference (n077=1)
FREF2
Frequence reference bias (n077=3) Output voltage bias (n077=4)
FGAIN
for 400V class inverters.
The VBIAS value to be added is doubled
80
Multi-function analog input signal selection (n078)
Parameter No. Name Unit
0 = Digital operator terminal
n078
Multi-function analog input signal selection
(voltage: 0 to 10V)
_
1 = Digital operator terminal (current: 4 to 20mA)
Setting Range
Initial
Setting
0
Frequency reference bias setting (n079)
Parameter No. Name Unit
Frequency reference bias
n079
setting
%
100% / Max. output frequency
Setting Range
0 to 50 (n011)
Initial
Setting
10
81
Using output signals (n057, n058, n059)
Multi-function output terminal MA, MB, P1 and P2 functions can be changed when necessary by setting parameters n057, n058, and n059.
• Terminal MA and MB functions: Set to n057
• Terminal P1 function: Set to n058
• Terminal P2 function: Set to n059
Setting Name Description Re f page
0 Fault Closed when inverter fault occurs. – 1 In operation
2 Agreed frequency
3 Zero speed 4 Frequency detection Output frequency
5 Frequency detection Output frequency
Overtorque detection
6
(NO contact output) Overtorque detection
7
(NC contact output) 10 Minor Fault Closed when the alarm is indicated. – 11 Base blocked Closed when the inverter output is shut off.
12 Operation mode
13 Inverter operation ready 14 Fault restart Closed during fault retry
15 In UV Closed when undervoltage is detected. – 16 In reverse run Closed during reverse run. – 17 In speed search Closed when inverter conducts speed search.
Data output from 18
communication 19 PID feedback loss Closed during PID feedback loss 109
Frequency reference is 20
missing
Inverter overheat prediction 21
OH3
Closed when either FWD/REV command is input or voltage is output from the inverter. Closed when setting frequency agrees with inverter output frequency. Closed when inverter output frequency is less than minimum output frequency.
Closed when “LOCAL” is selected by LOCAL/REMOTE selection. Closed when inverter fault is not detected, and operation is ready.
Operates multi-function output terminal independently from inverter operation (by MEMOBUS communication).
Closed when frequency reference is missing – Closed when overheat prediction is input. Digital
operator display is “OH3 (blinking).”
frequency detection level (n095) 56
frequency detection level (n095) 56
—55
—55
79
89
82

Setting Frequency by Current Reference Input

When setting frequency by inputting current reference (4 -20mA or 0-20mA) from the control circuit terminal FR, switch the DIP switch SW1 on the control circuit board to “I” side.
SW1 is accessed by removing the digital operator.
Never input voltage reference to control circuit terminal FR when DIP switch
NOTE
SW2 is switched to “I” side. This could damage the inverter.
Initial setting of multi-function output terminal
No. Terminals Initial Setting n057 MA, MB 0 (fault) n058 P1 1 (in operation) n059 P2 2 (Frequency agreed)
83
Current reference selection
After changing DIP switch (V/I switch of SW2) to the “I” side, PRESS on the digital operator, then set the following parameters.
Current reference (4-20mA) parameter n004=3 Current reference (0-20mA) parameter n004=4
Press the digital operator keys to run or stop the inverter. Switch run and stop direction by setting F/R LED.
Set frequency by the analog current signal [0-100% (max frequency)/4-20mA] connected to the control circuit terminal.
Set run/stop and FWD/REV run with switching device connected to the control circuit terminal.
Multi-function input terminals S1 and S2 are set to Forward run / STOP (n050 = 1) and Reverse run/stop (n051 = 2) respectively.
Set frequency by the analog current signal [0-100% (max. frequency)/4-20mA] connected to the control circuit terminal.
Frequency reference gain (n060)/bias (n061) can be set even when current reference input is selected. For details, refer to “Adjusting frequency setting signal” on page 81.
PRGM
84

Frequency Reference by Pulse Train Input

Frequency reference can be set by pulse train input from the multi-function input terminal.
• Input pulse specifications
• Low-level voltage: 0.8V or less
• High-level voltage: 3.5 to 32V
• Duty Cycle: 30 to 70%
• Pulse frequency: 0 to 33 kHz
• Frequency reference method Frequency reference is a value obtained by multiplying the ratio of the maximum input pulse frequency and actual input pulse frequency by the maximum output frequency.
Input pulse frequency
Reference freq
-----------------------------------------------------------------------------------------------------------------
=
Minimum pulse train frequency (n149) 10
×
max output frequency (n011)
×
Run/stop and FWD/REV can be selected by a switch connected to the control circuit terminal.
Frequency setting can be set by pulse train input signal [0 to 100% (maximum frequency)/0 to 33kHz] connected to the multi-function input terminal.
Parameter
No. n003 Run command selection 1 0 to 2 0 n004 Frequ enc y reference selection 1 0 to 6 0
n149 Pulse train input scaling 1=10Hz 1
Name Unit Setting range Initial Setting
100 to 3300
(33kHz)
2500
(25kHz)
85
Preventing Motor from Stalling (Current Limit)
Automatically adjusts the output frequency and output current according to the load to continue operation without stalling the motor.
• Stall prevention (current limit) level during acceleration (n093) Sets the stall prevention (current limit) level during acceleration in units of 1% (Inverter rated current = 100%).
Factory setting: 170% A setting of 200% disables the stall prevention (current limit) during acceleration.
During acceleration, if the output current exceeds the value set for n093, acceleration stops and frequency is maintained. When the output current goes down to the value set for n093, acceleration starts.
* Stops the acceleration to prevent the motor
from stalling.
† Release width (hysteresis) of stall prevention
during accel is approx. 5% of inverter rated current.
In the constant horsepower area [output frequency > max. voltage output frequency (n013)], the following equation automatically decreases the stall prevention (current limit) level during acceleration, but the stall prevention level will never go below 40% of n093.
86
• Stall prevention (current limit) level during running (n094) Sets the stall prevention (current limit) level during running in units of 1% (Inverter current = 100%).
• Factory setting: 160%
A setting of 200% disables the stall prevention (current limit) during running. If the inverter is at speed agree and output current exceeds the value set for n094 for
longer than 100msec, deceleration starts. Deceleration continues until the output current falls below the value set for n094.
When this occurs, the inverter will accelerate back up to the set frequency. Stall prevention accel/decel settings during operation are set either by accel time 1
(n019) and decel time 1 (n020), or accel time 2 (n021) and decel time 2 (n022).
* Decreases frequency to prevent the motor
from stalling.
† At acceleration start, output hysteresis is
approx. 5% of inverter rated current.
Stall prevention during operation
• Stall prevention automatic decrease selection (n115) The stall prevention level can be increased automa tica lly in the pa rame te r output
range.
Parameter
No.
n115
Name Unit Setting Range
Stall prevention automatic decrease selection
-
0=Disabled 1=Enabled
Initial
Setting
0
87
n115 setting
Setting Function
0 The stall prevention level becomes the level set for the parameter n094 in all frequency areas
The following shows that the stall prevention level is automatically decreased in the parameter output range (Max. frequency>Max. voltage output frequency). The lower limit is 40% of the set value of n094.
1
• Accel/decel time selection during stall prevention (n116)
With this function, acceleration/deceleration time when moving to prevent stalling
during operations can be assigned to the two parameters, n021 and n022.
Parameter
No.
n116
Name Unit Setting Range Initial Setting
Accel/decel time selection during stall prevention
-
0=Disabled 1=Enabled
n116 setting
Setting Function
0 Accel/decel time is set by accel/decel time 1or 2. 1 Accel/decel time is fixed at accel/decel time 2(n021, n022)
• Stall prevention (current limit) function during accelerati on (n092)
To prevent over voltage during deceleration, the inverter automatically extends the
deceleration time according to the value of the main circuit DC voltage. When using an optional braking resistor, set n092 to 1.
Setting
88
Stall prevention (current limit) during
0 Provided 1 N o t provided (when braking resistor is mounted
deceleration
0

Decreasing Motor Speed Fluctuation

Slip compensation (When V/f control mode n002=0)
As the load becomes larger, motor speed is reduced and motor slip value is increased. The slip compensating function controls the motor spe ed at a parame te r value even if the load varies.
When inverter output current is equal to the motor rated current (n036), the compensation frequency is added to the output frequency.
Compensation frequency Motor rated slip (n106)
Related Parameters
Parameters
No.
n036 Motor rated current 0.1A 0 to 150% of inverter rated current *
n111 Slip compensation gain 0.1 0.0 to 2.5 0.0
n110 Motor no-load current 1% 0 to 99% (100% = Motor rated current n036) *
Slip compensation primary
n112
delay time
n106 Motor rated slip 0.1Hz 0.0 to 20Hz *
* Differs depending on inverter capacity.
Notes: 1. Slip compensation is not performed in the following condition:
Output frequency < minimum output frequency (n016).
2. Slip compensation is not performed during regeneration.
3. Slip compensation is not performed when motor rated current (n036) is set to 0.0A.
=
Output current Motor no-load current (n110)
---------------------------------------------------------------------------------------------------------------------------------------------------
×
Electronic thermal reference current (n036)
×
Slip compensation gain (n111)
Name Unit Setting Range
0.0 to 25.5s
0.1s When 0.0s is set, delay time becomes 2.0s.
Motor no-load current (n110)
Initial
Setting
2.0s
89

Motor Protection

Motor overload detection
The VS-606V7 protects against motor overload with a built-in electronic thermal overload relay.
• Motor rated current (electronic thermal reference current, n036) Set to the rated current value shown on the motor nameplate.
Note: Setting to 0.0A disables the motor overload protective function.
• Motor overload protection selection (n037, n038).
n037 Setting Electronic Thermal Characteristics
0 Applied to general-purpose motor 1 Applied to inverter duty motor 2 Electronic thermal overload protection not provided
Parameters
No.
n038
The electronic thermal overload function monitors motor temperature, based on inverter output current and time, to protect the motor from overheating. When electronic thermal overload relay is enabled, an “ ” error occurs, shutting OFF the inverter output and preventing excessive overheating in the motor. When operating with one inverter connected to one motor, an external thermal relay is not needed. When operating several motors with one inverter, install a thermal relay on each motor.
Name Unit Setting Range Initial Setting
Protection parameter selection
1min 1 to 60min 8min
90
• General-purpose motor and inverter duty motor Induction motors are classified as general-purpose motors or inverter motors, based on their cooling capabilities. Therefore, the motor overload function operates differently between these two motor types.
Example of 200V class motor
Cooling Effect Torque Characteristics
Effective when operated at 50/60Hz from commercial power supply
General-purpose Motor
Base Frequency 60Hz
(V/f for 60Hz, 220V Input Voltage)
For low-speed operation, torque must be limited in order to stop motor temperature
Effective even when operated at low speed (approx. 6Hz)
Inverter Motor
rise.
Electronic Thermal overload
error (motor
overload protection) occurs when continuously operated at 50/60Hz or less at 100% load.
Electronic thermal overload protection not activated even when continuously operated at 50/60Hz or less at 100% load.
Base Frequency 60Hz
(V/f for 60Hz, 220V Input Voltage)
Use an inverter motor for continuous operation at low speed.
91

Selecting Cooling Fan Operation

In order to increase lifetime, the cooling fan can be set to operate only when inverter is running.
n039 = 0 (factory setting) : Operates only when inverter is running.
(Continuous operation for 1 minute after inverter is stopped.)
1 : Operates with power ON.
Using MEMOBUS (MODBUS) Communications
Serial transmission is available with VS-606V7 using programmable controller (MEMOCON series) and MEMOBUS.

MEMOBUS (MODBUS) communications

MEMOBUS system is composed of a single master (PLC) and slaves (1 to 31 VS-606V7 units). Communication between master and slave (serial communication) is controlled according to the master program with the master initiating communica tion a nd the slave responding. The master sends a signal to one slave at a time. Each slave has a pre-registered address No., and the master specifies the number and conducts signal communication. The slave receives the communications to carry out designated functions and reply to the master.
Communications specifications
Interface RS-422, RS485 Synchronization Asynchronous (Start-stop synchronization)
Communication parameters
Communication protocol Max. number of inverters that can be connected
92
Baud rate: Selected from 2400/4800/9600/19200 bps Data length: 8bit fixed Parity: Selected from even/odd/none Stop bits: 1bit fixed
MEMOBUS (MODBUS) (RTU mode only)
31 units (When using RS-485
Communic at i ons connect i on terminal
Use the following S+, S-, R+ and R- terminals for MEMOBUS communications. Change the termination resistor as shown below.
At RS-422, RS-485 communications: Turn ON SW2 ON/OFF switch of only the inverter at the termination viewed from the PLC.
Notes: 1. Separate the wiring for communication from the
main circuit wiring or other power lines.
2. Use shielded cables for communication wiring; connect the shielded sheath to the ground terminal and terminate the other end to prevent it from being connected (to prevent noise malfunction).
3. When communication is performed through RS-485, connect S+ and R+, S- and R- terminals outside the inverter as shown right side.
Procedure for communications with PLC
The following shows the procedure for communications with PLC. (1) Connect the communication cable between the PLC and the VS-606V7 with the
power supply turned OFF. (2) Turn the power ON. (3) Set the parameters (n151 to n157) required for communication by using the digital
operator. (4) Turn the power OFF once to verify that the digital operator displays have been
completely erased. (5) Turn the power ON again. (6) Communications with the PLC starts.
93
Setting necessary parameters for communication
Communication related parameter s must be set for PL C com munica tion. parameters n151 to n157 cannot be set during communication. Always set them prior to performing communication.
Parameter Name Description
n003 Run command selection
Frequency reference
n004
selection
Timeover detection selection Monitors transmission time
n151
between the receiving the correct data from the PLC (Timeover: 2 sec)
Communication frequency
n152
Reference monitor unit selection
n153 Slave address Setting range: 0 to 32* 0
n154 Baud rate selection
n155 Parity selection
n156 Sending waiting time Setting limit: 10 ms to 65 ms setting unit: 1 ms 10 ms n157 RTS control
0 : operator 1 : control circuit terminals 2 : communication 3 : communication card (optional) 0 : Local potentiometer (digital operator) 1 : frequency ref. 1 (n024) 2 : control circuit terminals (voltage 0 to 10V) 3 : control circuit terminals (current 4 to 20mA) 4 : control circuit terminals (current 0 to 20mA) 5 : pulse train 6 : MEMOBUS communication (Register No. 000211) 7 : operator circuit terminals (voltage 0 to 10V) 8 : operator circuit terminals (current 4 to 20mA) 9 : communication card (optional)
0 : timeover detection (free run stop) 1 : timeover detection (coasting to a stop with speed
reduction time 1)
2 : timeover detection (coasting to a stop with speed
reduction time 2)
3 : timeover detection (continuous operation, warning
display) 4 : timeover detection not provided 0 : 0.1Hz 1 : 0:0.1Hz 2 : 30000/100% (30000 = max. output frequency) 3 : 0.1%
0 : 2400 bps 1 : 4800 bps 2 : 9600 bps 3 : 19200 bps 0 : even parity 1 : odd parity 2 : no parity
0 : RTS control 1 : no RTS control (RS-422A 1 to 1 communication)
Initial
Setting
0
0
0
0
2
0
0
* The slave does not respond to the command from the master when set to 0. Monitoring run status from the PLC, setting/referencing of parameters, fault reset and
multi-function input reference can be done regardless of run command or frequency reference selection.
Multi-function input reference fr om PLC be come s OR with input comm a nds from S1 to S7 multi-function input terminals.
94
Message format
Slave address
Function code
Data
Error Check
For communications, the master (PLC) sends a command to the slave (VS-606V7) and the slave responds to it. The configuration for sending and receiving is as shown to the right. The length of the data varies according to the contents of commands (functions).
The interval between messages must be maintained at the following amount.
VS-606V7 VS-606V7 VS-606V7
• Slave address: Inverter address (0 to 32). Setting to 0 indicates simultaneous broadcasting. The inverter does not respond to the command from the master.
• Function code: Command codes (See below).
Function
Code
01H 08H Loop back test 8888 10H
Function
Reading holding resistor contents
Write in several
holding resistors
Reference Message Response Message
Minimum (Byte) Maximum (Byte) Minimum (Byte) Maximum (Byte)
88737
11 41 8 8
• Data: Composes a series of data by combining holding register numbers (test codes for loop-back numbers) and their data. Data length depends on the contents of the commands.
• Error check: CRC-16 (Calculate the value by the following method.)
1. The default value at calculation of CRC-16 is normally 0. In the MEMOBUS system, change the default to 1 (all 1 to 16-bit).
2. Calculate CRC-16 assuming that the loop address LSB is MS B and the last data MSB is LSB.
3. Also calculate CRC-16 for a response message from the slave and refer it to CRC-16 in the response message.
95
Read out holding register contents [03H]
Reads out the contents of the holding registers with the continuous numbers for the specified quantity. The contents of holding register is divided into the upper 8 bits and the lower 8 bits. They become the data items in response message in the order of numbers. Example: Reads out status signal, fault contents, data link status and frequency reference from the VS-606V7 (slave 2).
Reference message
(at normal operation) Slave address 02H Function code 03H
Start number
Quantity
CRC-16
Upper 00H Lower 20H Upper 00H Lower 04H Upper 45H Lower F0H
(For error code 03H, refer to
page 99.)
Response message
(at normal operation) Slave address 02H Function code 03H
Number of data* 08H
First holding resistor Next holding resistor
Next holding resistor Next holding resistor
CRC-16
Upper 00H Lower 65H Upper 00H Lower 00H Upper 00H Lower 00H Upper 1H Lower F4H Upper AFH Lower 82H
Reference message (at fault occurrence)
Slave address 02H
Function code 83H
Error code 03H
CRC-16
Upper F1H Lower 31H
* Twice as much as the number of reference message.
Example of loop-back test [08H]
Command message is returned as a response message without being changed. This function is used to check transmission between the master and the slave. Any arbitrary values can be used for test codes or data. Example: Loop-back test of slave 1 and VS-606V7
Reference message
(at normal operation) Slave address 01H Function code 08H
Start number
Quantity
CRC-16
Upper 00H Lower 00H Upper A5H Lower 37H Upper DAH Lower 8DH
96
Response message
(at normal operation) Slave address 01H Function code 08H
Start number
Quantity
CRC-16
Upper 00H Lower 00H Upper A5H Lower 37H Upper DAH Lower 8DH
Reference message
(at fault occurrence) Slave address 01H Function code 89H
Error code 01H
CRC-16
Upper 86H Lower 50H
Writing to several holding registers [10H]
Specified data are written into the several specified holding registers from t he specified number, respectively. Written data must be arranged in a command message in the order of the holding register numbers: from upper eight bits to lower eight bits.
Example: Set forward run at frequency reference 60.0 Hz to slave 1 VS-606V7 from the PLC.
Reference message
(at normal operation)
Slave address 01H
Function code 10H
Start number
Quantity
First Data
Next data
CRC-16
Upper 00H Lower 01H Upper 00H Lower 02H
Number of data* 04H
Upper 00H Lower 01H Upper 02H Lower 58H Upper 63H Lower 39H
* Sets twice as large as the actual number.
Response message
(at normal operation) Slave address 01H Function code 10H
Start number
Quantity
CRC-16
Upper 00H Lower 01H Upper 00H Lower 02H Upper 10H Lower 08H
Reference message
(at fault occurrence) Slave address 01H Function code 89H
Error code 01H
CRC-16
Upper 86H Lower 50H
97
Data
• Reference Data (available to read out/write in)
Register No. bit Description
0000H Reserved
0001H
0002H Frequency reference (unit : n152) 0003H V/f gain (1000/100%) Setting range : 2.0% ~ 200.0%
0004H-
0008H
0009H
000AH-
001FH
Note: Write in “0” for unused bit. Never write in data for the reserved register.
• Simultaneous Broadcasting Data (available only for write in)
Register No. bit Description
0001H
0002H
Bit signals not defined as the broadcast operation signals are used as the local station data signals.
0 Run command 1 : Run 0 : Stop 1 Reverse run 1 : Reverse run 0 : Forward run 2 External fault 1 : Fault (EFO) 3 Fault reset 1 : Reset command 4 Multi-function input reference 1 (Function selected by n050) 5 Multi-function input reference 2 (Function selected by n051) 6 Multi-function input reference 3 (Function selected by n052) 7 Multi-function input reference 4 (Function selected by n053) 8 Multi-function input reference 5 (Function selected by n054) 9 Multi-function input reference 6 (Function selected by n055)
A Multi-function input reference 7 (Function selected by n056)
B-F (Not used)
Reserved
Multi-function output reference 1
0
(Effective when n057=18) Multi-function output reference 2
1
(Effective when n058=18) Multi-function output reference 3
2
(Effective when n059=18)
3-F (Not used)
Reserved
0 Run command 1 : Run 0 : Stop 1 Reverse run 1 : Reverse run 0 : Forward run 2 (Not used) 3 (Not used) 4 External fault 1 : Fault (EFO) 5 Fault res e t 1 : Fault reset comman d
6-F (Not used) 30000/100% fixed unit (Data is converted into 0.01 Hz inside the inverter, and fractions are rounded off.)
( 1 : MA “ON” 0 = MA “OFF” ) ( 1 : P1 “ON” 0 = MA “OFF” )
( 1 : P2 “ON” 0 = MA “OFF” )
98
• Monitor Data (available only for read out)
Register No. bit Description
0020H
0021H
0022H
0023H Frequency reference (Unit : n152) 0024H Output frequency (Unit : n152)
0025H-026H (Not used)
0027H Output current (10/1A) 0028H Output voltage reference (1/1V)
0029H
0 Run command 1 : Run 0 : Stop 1 Reverse run 1 : Reverse run 0 : Forward run 2 Inverter operation ready 1 : Ready 0 : Not ready 3 Fault 1 : Fault 4 Data setting error 1 : Error 5 Multi-function output 1 (1 : MA ON 0 : MA OFF)
Status signal
6 Multi-function output 2 (1 : P1 ON 0 : OFF) 7 Multi-function output 3 (1 : P2 ON 0 : OFF)
8-F (Not used)
0 Over current (OC) 1 Over voltage (OV) 2 Inverter overload (OL2) 3 Inverter overheat (OH) 4 (Not used) 5 (Not used) 6 PID Feedback loss (FbL) 7 External fault (EF, EFO) Emergency stop (STP) 8 Hardware fault (Fxx) 9 Motor overload (OL1)
Fault description
A Overtorque detection (OL3) B (Not used) C Power loss (UV1) D Control power fault (UV2) E MEMOBUS communications timeover (CE) F Operator connection (OPR) 0 Data write in 1 (Not used) 2 (Not used) 3 Upper/lower limit fault 4 Consistency fault
Data link status
5-F (Not used)
0 Load short circuit (SC) 1 Ground fault (GF) 2 Input open phase (PF) 3 Output open phase (LF) 4 Installed type braking resistor overheat 5 Braking transistor fault (RR)
Fault contents
6-F Not used
99
Register No. bit Description
002AH
002BH
002CH
002DH
0 Operator stop (STP) 1 Sequence error (SER) 2 FWD - REV command simulation input (EF) 3 External baseblock (BB) 4 Overtorque detection (OL3) 5 Cooling fin overheat (OH) 6 Main circuit overvoltage (OV) 7 Main circuit undervoltage 8 Cooling fan fault (FAN) 9 Communication error
Alarm Contents
A Option card communication error (BUS) B Not used C Inverter overheat prediction (OH3) D PID feedback loss (FBL) E Emergency stop (STP) F Communication waiting (CALL) 0 Terminal S1 1 : Closed O : Open 1 Terminal S2 1 : Closed O : Open 2 Terminal S3 1 : Closed O : Open 3 Terminal S4 1 : Closed O : Open 4 Terminal S5 1 : Closed O : Open 5 Terminal S6 1 : Closed O : Open
Sequence input
6 Terminal S7 1 : Closed O : Open
7-F (Not Used)
0 Run 1 : Run 1 Zero - speed 1 : Zero - speed 2 Frequency agreed 1 : Agreed 3 Minor fault (Alarm is indicated) 4 Frequency detection 1 1: Output frequency 5 Frequency detection 2 1 6 Inverter operation ready 1 : Ready 7 Undervoltage detection 1 : Under Voltage detection 8 Baseblock 1 : Inverter output base block
9 Frequency reference mode
Inverter status
A Run command mode B Overtorque detection 1 : Detection or overtorque fault
C (Not used) D Fault restart E Fault (Including MEMOBUS communications timeover) 1 : Fault F MEMOBUS communications timeover 1 : Timeover 0 MA “ON” 1 : Closed 0 : Open 1 P1 “ON” 1 : Closed 0 : Open 2 P2 “ON” 1 : Closed 0 : Open
(Not used)
3-F
:
1 : Other than communications 0 : Communications 1 : Other than communications 0 : Communications
Output frequency
(n095)
(n095)
100
Loading...