Tongue Switch with Guard Locking & RFID Coding
Unlock signal (solenoid) apply +24V.dc
4 6 11/12 Safety output circuit
7 8 21/22 Safety output circuit
5 44 Guard open signal +24V.dc out
9 34 Unlocked signal +24V.dc out
ingress. Never attempt to repair any switch.
THESE INSTRUCTIONS FORM PART OF THE PRODUCT WARRANTY.
positively opened and the machine circuit is broken.
The KLTM-RFID and KLT-SS-RFID Safety Interlock switches are designed to fit to the leading edge of machine guard doors to provide robust
guard locking and provide a double tamper resistant interlock mechanism.
They are designed to provide robust position interlock detection for moving guards and will remain locked until the solenoid voltage is applied
to the switch. They can be used in conjunction with delay timers to provide the solenoid energise signal only after a pre-determined the time
has run down.
Operation:
The switch is rigidly mounted to the fixed frame of the guard or machine. The actuator is fitted to the moving part (frame) of the guard and is
aligned to the switch entry aperture. The mechanical tongue actuator profile is designed to match a cam mechanism within the switch head
and provides a not easily defeatable mechanical interlock. There is also an RFID coded actuator which aligns with a programmed receiver
inside the switch housing during closing of the guard. Only when both actuators are correctly aligned and the RFID coding is verified correctly
can the safety contacts close and allow the machine start circuit to be enabled. When the solenoid is energised the safety contacts are
Record any RFID codes as required by factory rules or with reference to any risk assessment for the particular application.
The risk assessment for the particular application should include the risk of spare actuators. Spare actuators should not be readily available and must be securely controlled.
The safety functions and mechanics must be tested regularly. For application where infrequent guard access is foreseeable, the system must have a manual function test to detect a possible
accumulation of faults. At least once per month for PLe Cat 3/4 or once per year for PLd Cat 3 (ISO13849-1). Where possible it is recommended that the control system of the machine
demands and monitors these tests, and stop or prevents the machine from starting if the test is not done.(see ISO14119). It is the responsibility of the user to ensure the correct overall
functionality of its systems and machines. IDEM, its subsidiaries and affiliates, are not in a position to guarantee all of the characteristics of a given system or product not designed by IDEM.
Installation:
1. Installation of all IDEM interlock switches must be in accordance with a risk assessment for the individual application.
If fitted, ensure access to at least one of the auxiliary release points. The switch can be positioned / shielded to prevent unintended actuation of the auxiliary release.
The release function is achieved by use of a tool and is to be used in exceptional circumstances. If used the release can be protected by use of a tamper coating to protect
against unintended operation. If operated this tamper protection must be restored.
Always fit the aperture plug to the unused entry aperture to prevent debris entering the switch mechanism.
4. The RFID code is factory set. For instances where replacement of the RFID actuator is required please contact IDEM via e-mail: technical@idemsafety.com.
5. The switch is supplied with removable conductor links fitted 41/42 and 31/32. If required by the control circuit these may be removed to offer independent monitoring of the
solenoid locking function or the actuator position.
6. After installation check operation of all control circuits and the locking function.
Every month: Check correct operation of all circuits and the Lock function. If the actuator shows signs of bending or the
switch head housing displays mechanical damage then remove and replace. IDEM will not accept responsibility for
failure of the switch functions if the installation and maintenance requirements shown in this sheet are not implemented.
Every 6 months: Isolate power and remove cover. Check screw terminal tightness and check for signs of moisture
Installation must only be carried out by competent personnel and in accordance with these instructions.
2. M5 (or appropriate) mounting bolts must be used to fix the switch and actuator mounting plates. The tightening torque to ensure reliable fixing is 4.0 Nm.
Tightening torque for the lid screws and cable glands must be 1.5 Nm to ensure the IP seal. The actuator entry position (Front or End) can be selected by using the internal
slide switch inside the switch cover (See Fig.1 on page 2). Do not mount adjacent switches or actuators closer than 100mm.
3. Always fit a mechanical stop to the guard to prevent damage to the front of the switch.
Always ensure correct alignment of actuator and handle with front apertures of the switch and guide. Use alignment guides to ensure that the actuator enters the switch
without interfering with the sides of the aperture.
For applications with a run down time after removing power, ensure that the correct timing allowance has been made before the solenoid is energised.
KLTM-RFID & KLT-SS-RFID Operating Instructions
M23 12 way
Male Plug
(Pin view from Switch)
Switch Circuit

Tongue Switch with Guard Locking & RFID Coding
Guard Closed + Misalligned / Wrong Actuator
Alternate Flashing Green/Yellow
Special Instruction: RFID actuator
24Vdc 200mA max. switching.
Auxiliary Circuits (34 & 44)
Classification and coding level
Actuator insertion distance for assured locking
Actuator entry minimum radius
KLT-SS-RFID: Stainless Steel 316
Mechanical Actuator Material
IP69K S/Steel versions only).
Mechanical Life Expectancy
x 106 cycles at 100mA load
Excursion: 0.35mm, 1 octave/min
Corresponds to 4.8% of SIL3
Characteristic data according to EN ISO13849
If both channels are used in
Note: The Diagnostic coverage could
Information with regard to UL 508: Type 1 enclosure.
To request this datasheet in other languages please contact
NE PAS DESACTIVER, MODIFIER, RETIRER, OU
Fig. 1. Entry Selector Switch
WARNING:
AVERTISSEMENT:
DO NOT DEFEAT, TAMPER, OR BYPASS THE
SAFETY FUNCTION. FAILURE TO DO SO CAN
RESULT IN DEATH OR SERIOUS INJURY.
CONTOURNER CETI INTERVERROUILLAGE IL
PEUT EN RESULTER DES BLESSURES
GRAVES DU PERSONNEL UTILISATEUR
Original Instructions
Um dieses Datenblatt in Deutscher Sprache wenden Sie sich bitte anfordem info@idemsafety.com
Pour obtenir cette fiche en Francais, veuillez contacter info@idemsafety.com
Para solicitor esta hoja de datos en Espanol, por contacto con info@idemsafety.com
In the event that a Fault condition requires reset, follow the reset instructions:
1) Turn off all power to the switch and open the guard.
2) Remove the switch cover.
3) Using a 2mm terminal screwdriver hold down the RESET button inside the switch housing and turn on the switch
power (see Fig.2).
4) Release the RESET button, the yellow LED will flash, close the guard and the yellow LED will turn steady yellow.
(If yellow LED continues to flash check for mechanical fault (e.g. damaged actuator or switch head)).
5) Turn power off and then on, the green LED will illuminate.
6) Re-fit the switch cover.
7) Open and close the guard ensuring all safety functions are correct –refer to any risk assessment for the particular
guard application.
Standards : IEC60947-5-1 IEC60947-5-3 ISO14119 ISO13849-1 IEC62061 UL508
Entry Selector Switch
Select Front or End sensing. (See Fig 1)
FRONT Entry
END Entry
this way.
FRONT
RESET button
(If required press and hold using a 2mm
terminal screw driver)
Safety Classification for Guard Position monitoring.
Characteristic data according to IEC62061 (used as a subsystem)
Connection example to SCR31-42-TD-i Safety Relay (Timed delay to solenoid)
PFH (1/h)
Performance Level e
Diagnostic Coverage DC
Maximum temperature 40°C.
Use 16-28AWG copper conductors (rated 90°C). Terminal Torque 6 lb ins. (0.7Nm).
Intended for same polarity use. Safety Circuits (11-12 & 21-22) 24V.dc 200mA max.
Use one polymeric conduit connection. Not suitable for connection to rigid metal conduit.
(Earth bonding terminal inside enclosure if required – use 16-12AWG conductors).
10
1
conjunction with a SIL3/PLe control
device.
(High)
be reduced to lower than PL e if
multiple interlocking switches are
connected in series.
IDEM SAFETY SWITCHES Ltd., 2 Ormside Close, Hindley Industrial Estate, Hindley Green, Wigan, WN2 4HR UK. Tel: +44 (0)1942 257070 Fax.: +44 (0)1942 257076
IDEM (USA) 4416 Technology Drive, Fremont, CA 94538 Tel:510-445-0751 Fax:1866-431-7064 email: sales@idemsafety.com Web: www.idemsafety.com
Doc.102540 Jan 18