ø30mm - TWTD Series |
Oiltight Switches & Pilot Devices |
|
|
<![endif]>Switches & Pilot Lights
<![if ! IE]><![endif]>Display Lights
<![if ! IE]><![endif]>Relays & Sockets
<![if ! IE]><![endif]>Timers
TWTD Series — Full Size NEMA Pushbuttons
TWTD Series: Heavy duty switches built to last
Key features include:
•Variety of button sizes up to 2 9/16” (65mm)
•Rugged construction includes chrome plated zinc locking ring die cast zinc mounting threads, screw mounted contact blocks
•LED or incandescent illumination
•Transformer or full voltage
•Transparent contact windows
•Slow make, double break self-cleaning contacts
•Modular construction for maximum fl exibility
•Double nickel plated terminal screws
•Available assembled or as sub-components
•NEMA 4x and IP65 watertight/oiltight panel
•Large M3.5 screw terminals with captive sems plate
The rugged series of TWTD switches offers both variety and durability in an attractive design.
With button sizes up to 2 9/16” (65mm), chrome plated zinc locking rings, die cast zinc mounting threads, steel anti-rotation rings, and self cleaning contacts, the TWTDs are here to stay.
The TWTD series also offers either LED or incandescent illumination in full voltage and transformer models.
Transparent contact windows allow the viewing of IDEC’s self cleaning slow- make/slow-break contacts.
Regardless of your switching needs, the TWTD series provides the kind of long lasting, industrial strength quality you’ve come to expect from IDEC.
UL Listed |
File No. LR48366 |
Ref No. 117617MC |
Certifi cate No. |
|
File No. E70646 |
2005010305145658 |
|||
|
|
<![endif]>Terminal Blocks
<![if ! IE]><![endif]>Circuit Breakers
610 |
www.idec.com |
Oiltight Switches & Pilot Devices |
ø30mm - TWTD Series |
|
|
Specifications
Conforming to Standards
Approvals
Operating Temperature
Vibration Resistance
Shock Resistance
Electric Shock Protection
Degree of Protection
Mechanical Life
Pollution Degree
(conforming to IEC60947-1)
EN60947-1, EN60947-5-1, VDE0660-200, UL508, CSA C22-2 No.14
CSA: pushbuttons and selector switches: A600 pilot lights and illuminated pushbuttons, direct supply pilot lights and illuminated pushbuttons with integral transformer (100/110, 115, 120, 200/220, 230, 240, 380, 400/440, 480V)
UL: pushbuttons and selector switches: A600 pilot lights and illuminated pushbuttons, direct supply pilot lights and illuminated pushbuttons with integral transformer (100/110, 115, 120, 200/220, 230, 240, 380, 400/440, 480V)
TÜV: pushbuttons and selector switches: A600=P600 (NO, NC)/Q600 (NO-EM, NC-LB) pilot lights and illuminated pushbuttons, direct supply pilot lights and illuminated pushbuttons with integral transformer (100/110, 115, 120, 200/220, 230, 240, 380, 400/440, 480V)
Operation: –25 to +50°C (without freezing) Storage: –40 to +70°C (without freezing)
10 to 55Hz, 98m/sec2 (10g) conforming to IEC6068-2-6 980m/sec2 (100g) conforming to IEC6068-2-7
Class 0 conforming to IEC60536
IP65 (from front of the panel) (conforming to IEC60529)
IP54 (key switches)
NEMA 1, 2, 3, 3R, 3S, 4, 4X, 5, 12, 13 (conforming to NEMA ICS6-110)
Momentary pushbuttons: 5,000,000 (900 operations per hour) All other switches: 500,000
3 for switches not using a transformer
2 for switches using a transformer
Mechanical-Electrical Specifications
AC-15: A600 or Ue = 250V, le = 3A (NO, NC, NO-EM, NC-LB)
Rated Operational Characteristics DC-13: P600 or Ue = 125V, le = 1.1A (NO, NC)
DC-13: Q600 or Ue = 125V, le = 0.9A (NO-EM, NC-LB)
Rated Insulation Voltage |
600V |
|
Rated Switching Overvoltage |
Less than 4kV, conforming to IEC60947-1 |
|
Rated Impulse Withstanding Voltage |
4kV for contact circuit |
|
2.5kV for lamp circuit |
||
|
||
Rated Thermal Current |
10 Amp |
|
Minimum Switching Capacity |
5 mA at 3V AC/DC |
|
Contact Operation |
Slow break NC or NO, self-cleaning |
|
|
Flush and extended pushbuttons—with 1NO or 1NC contact: 6.2±2N (momentary), |
|
Operating Force |
7.0±2N (maintained) |
|
|
Additional contacts—1NO or 1NC: +3.2N (momentary), + 3.3N (maintained) |
|
Terminal Referencing |
Conforming to CENELEC EN50005 |
|
Recommended Terminal Torque |
0.8 N m (7.1 in lb.) |
|
External Short-Circuit Protection |
10A 250V fuse conforming to IEC60269-1 |
|
Applicable Wire Size |
Minimum 1 x 22 AWG, max. 2 x 14 AWG or 1 x 12 AWG |
|
Contact Resistance |
Initial contact resistance of 50mΩ or less |
|
Contact Gap |
4mm (NO and NC) |
|
2mm (NO-EM and NC-LB) |
||
|
||
Lamp Ratings |
Incandescent: 1 W |
|
LEDs: 6V: 17mA, 12V: 11mA, 24V: 11mA, / 120, 240V: 10mA |
||
|
||
Maximum Inrush Current |
40 A (40 msec) |
|
Contact Material |
Silver |
Contact Ratings
Contact Ratings by Utilization Category IEC 60947-5-1 |
AC-15 |
(A600) |
|
DC-13 |
(P600) |
||
|
|||
|
|
||
Contact Ratings by Utilization Category |
|||
|
|
|
Operational Voltage |
24V |
48V |
50V |
110V |
220V |
440V |
|||
|
AC 50/60 Hz |
|
AC-12 Control of resistive loads & solid state loads |
10A |
— |
10A |
10A |
6A |
2A |
|
|
||||||||
|
|
AC-15 Control of electromagnetic loads (> 72VA) |
10A |
— |
7A |
5A |
3A |
1A |
|
Operation Current |
|
|
|||||||
|
|
DC-12 Control of resistive loads & solid state loads |
8A |
5A |
— |
2.2A |
1.1A |
— |
|
|
DC |
|
|||||||
|
|
DC-13 Control of electromagnets |
5A |
2A |
— |
1.1A |
0.6A |
— |
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
<![endif]>Lights Pilot & Switches
<![if ! IE]><![endif]>Lights Display
<![if ! IE]><![endif]>Sockets & Relays
<![if ! IE]><![endif]>Timers
<![if ! IE]><![endif]>Blocks Terminal
<![if ! IE]><![endif]>Breakers Circuit
USA: 800-262-IDEC |
Canada: 888-317-IDEC |
611 |