1: For protection against surge noise on DC power supply types (FL1F-H12RCE/B12RCE, FL1F-H12SCD, FL1F-H12RCA/B12RCA), use surge absorbers,
noise cut transformers or noise filters. Use of a surge protection device (DEHN + SÖHNE GmbH + Co, BVT AD 24 Part No. 918 402) is recommended.
2: Tightening torque 0.5 to 0.6N·m
Horizontal Mounting
Vertical Mounting
1
0 to 55°C (no freezing)
0 to 55°C (no freezing)
–40 to +70°C (no freezing)—
10 to 95% (no condensation)IEC60068-2-30
795 to 1080hPa—
No corrosive gas—
IP20—
5 to 8.4Hz, amplitude 3.5mm
8.4 to 150Hz, acceleration 9.8m/s²
147m/s²IEC60068-2-27
0.3mIEC60068-2-32
Limit class B Group 1
8kV air discharge
6kV contact discharge
Field Strength:
1V/m a nd 10V/m
2kV (power line)
2kV (I/O signal line)
1kV (power line) normal
2kV (power line) common
2.5mm ² (one wire)
1.5mm² (two wires)
Finger-safe type
2
Cold: IEC60068-2-1
Hot: IEC60068-2-2
IEC60068-2-6
EN 550 11/A
EN55022/B
EN50081-1
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
—
—
PRODUCT DESCRIPTION
With an ever-changing market and
tough competition, you need an edge to
stay on top. This sixth-generation IDEC
SmartRelay meets your demands from all
small-scale applications by offering more
powerful hardware, a new display and full
communication options via Ethernet.
BASE MODULE HIGHLIGHTS
Embedded RJ45 Ethernet Port
• Remote program download, upload and
monitor
• Integrated web server for remote
monitoring and control
Micro SD Card
• Equipped with micro SD slot for program
storage, transfer and data logging
• No need for a special memory cartridge
Data Logging
• Up to 20,000 lines in a file with a maximum
of 50 files can be stored in the Micro SD
Memory card
Integrated Web Server
• Easily monitor and control web pages with
no HTML knowledge
• Instant monitoring and control using
standard web browser like Chrome, IE and
Firefox
• View and control I/O status, timer,
counters, analog set point and more
There's an App for that!
• Download iOS and Android App for free
• Using the SmartRelay App, users can view
and control any I/O status, timer, counters,
and analog set point anywhere and at any
time
1:N Communication
• FL1F SmartRelays now have the capability
to communicate with each other over an
Ethernet network
• Up to 16 FL1F SmartRelays can be
configured on the network
R
USC
1
TEXT DISPLAY PANEL HIGHLIGHTS:
New and improved LCD display
• Improved display with 6 lines and 20 characters per line, more than twice as many characters as before
• Selectable white, amber or red backlighting for optical emphasis on alarms and events
Two RJ45 Ethernet ports
• Use a standard Ethernet cable to the connect FL1F base module to the Text Display Panel. A special cable is not required.
• Provide different ways to connect
TEXT DISPLAY SPECIFICATIONS
Text Display General Specications
ItemSpecicationsStandard
Horizontal
Operating
Temperature
Storage/Transportation Temp.
Relative Humidity
Atmospheric Pressure
Operating Condition
Degree of Protection
Vibration Resistance
Shock Resistance
Drop Test (packaged)
Emissions
Electrostatic Discharge
Immunity
Radiation Field Immunity
Fast Transient Burst
Surge Immunity
(FL1F-H12RCC, FL1F-B12RCC only)
Communication Cable
Terminal Style
1 For protection against surge noise on DC power supply types (FL1F-H12RCE/B12RCE, FL1F-H12SCD, FL1F-
H12RCA/B12RCA), use surge absorbers, noise cut transformers, or noise filters. Use of a surge protection device
(DEHN + SÖHNE GmbH + Co, BVT AD 24 Part No. 918 402) is recommended.
2 Tightening torque 0.5 to 0.6N·m
Mounting
Vertical
Mounting
1
0 to 55°C (no freezing)
0 to 55°C (no freezing)
Cold: IEC60068-2-1
Hot: IEC60068-2-2
–40 to +70°C (no freezing)—
10 to 95% (no condensation) IEC60068-2-30
795 to 1080hPa—
No corrosive gas—
IP20—
5 to 8.4Hz, amplitude
3.5mm
8.4 to 150Hz, acceleration
2
9.8m/s
2
147m/s
IEC60068-2-6
IEC60068-2-27
0.3mIEC60068-2-32
EN 55011/A
Limit class B Group 1
EN55022/B
EN50081-1
8kV air discharge
6kV contact discharge
Field Strength:
1V/m and 10 V/m
2kV (power line)
2kV (I/O signal line)
1kV (power line) normal
2kV (power line) common
2.5mm2 (one wire)
1.5mm2 (two wires)
Finger-safe type
2
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
—
—
Text Display General Specications Cont.
Dimensions (W × H × D)
Weight (approx.)
Installation
Keyboard
Display
128.2 × 86 × 38.7 mm
220g
Panel cut-out using mounting clips
Membrane keypad
FSTN graphic display
(W × H: 160 × 96 dots)
LED backlight (White, Amber, Red)
Font type
Displayable string
English, Spanish, Russian, Chinese, Italian, Turkish,
German, Dutch, French, Japanese
1 screen 6 lines × 20 columns
Power Supply Specications
Power Voltage
Allowable Voltage Range
Allowable Voltage Frequency
Power Consumption
Data Transmission Rate
24V AC/DC
12V DC
20.4 to 26.4V AC
10.2 to 28.8V DC
47 to 63Hz
12V DC: 145mA (Typ.)
24V DC: 70mA (Typ.)
24V AC: 75mA (Typ.)
10/100M full/half duplex data transmission rate
LCD Display / Backlight Specications
LCD Display Durability
Backlight Durability
3 Display durability is calculated under ordinary operating and storage conditions: room temperature,
normal humidity below 65% RH, and not subjected to direct sunlight.
4 Backlight durability is the number of hours taken for the light to become 50% of the original brightness.
3
4
50,000 hours
20,000 hours
2
PART NUMBERS
Sn=8
AX
Sn
AQAx
Monday
TR TSTR TSTR TS
Q
TuesdayWednesday...
Q
0
380
Mode
En
(IfERst=1)
En
R
AQ
LapT
CurT
Lap
AQ
En
Lap
R
St=10s
St=10s
AX
En
R
AQ
Sn
AQ
En
R
Ax
AQ
En
S1
Ax
Base Module
Rated Power Voltage Input SignalOutput SignalDisplayClockI/O PointsWeight (approx.)Part No.
24V DC
12/ 24V DC
24V AC/ DC
100 to 240V AC/D C
1 With NPN/PNP sensor input. For details, see Input Internal Circuits in the Specifications table.
DC
I1, I2, I7 and I8 are used for digital/
analog inputs
1
AC/DC
AC/DCRelay
Expansion I/O Module
TypeRated Power VoltageInput SignalOutput SignalI/O PointsWeight (approx.) Part No.
24V DCDCTransistor4/4 points95gFL1F-M08B1S2
Input/Output
12/24VDCDCRelay4/4 points130gFL1F-M08B2R2
2
24V AC/DC
100 to 240V AC/DCAC/DCRelay4/4 point s130gFL1F-M08C2R2
Analog Input
Analog Output
2 With NPN/PNP sensor input. For details, see Input Internal Circuits in the Specifications table.
I/O points within the maximum number of expandable I/O points can be used.
When using modules of the same power voltage, supply power to the base module and expansion I/O modules using one power supply.
When power is supplied to the modules from different power supplies, the fast transient burst is 1 kV (IEC61000-4-4).
Rated Power Voltage Weight (approx.)Part NumberRemarks
24V AC/DC
12V DC
220gFL1F -RD1
TransistorYesYes8/4 points195gFL1F-H12SCD
AC/DC
Relay
Relay
2
Yes
—200gFL1F-B12RCE
Yes
—200gFL1F-B12RCA
Yes
—200gFL1F-B12RCC
Yes8/4 points
Yes8/4 points
Yes8/4 points
Relay4/4 point s130gFL1F-M08D2R2
240gFL1F-H12RCE
240gFL1F-H12RCA
240gFL1F-H12RCC
Supplied with mounting clip and gasket
Options
DescriptionPart NumberPackage Quantity Remarks
Application Software: WindLGC
Mounting Clip for Base Module
Mounting Clip and Waterproof Gasket for Text Display
IDEC SmartRelay User’s Manual (English)
3 Supplied with a base module and an expansion module.
4 Supplied with a text display, it includes a gasket, four mounting clips, and a power supply connector.
NEW FUNCTION BLOCKS
AQ
Sn=8Sn=8Sn=8Sn=8Sn=8
Sn=8
Ta
300
350
250
200
100
100
300
200
380
250
100
0
3
2
1
Ax
Analog filter
Astronomical
clock
Max/Min
1 2 3 4 5 6 7 8 9 10 ...
Ax
TaTa
AC
300
Ax
S1
AQ
0
FL9Y-LP1CDW1DVD-ROM (incl. online help manual)
FL1F-PSP1PN055Supplied with a module
FL1F -KW11Supplied with text display
(betwe en power/input te rminals
and output ter minals)
Output Voltage
Maximum Load Current
Output
Surge Current
Short-circuit Protection
Minimum Switching Load
Initial Contact Resistance
Mechanical Life
Electrical Life
1 When selecting frequency trigger function and up/down counter function.
2 10m when connected to analog input (twisted pair cable)
Initialization Time: After power-up, the FL1F takes a maximum of 9 seconds (when using a micro SD card) for initialization. When initialization is complete, the FL1F is automatically set to RUN mode.
Resistive load
5A at 12/ 24V AC/DC
5A at 100/120V AC
5A at 230/240V AC
0.2A at 120V DC
0.1A at 240V DC
Inductive load
2A at 12/24V AC/DC
3A at 100/120V AC
3A at 23 0/240V AC
0.2A at 120V DC
0.1A at 240V DC
External fuse
required:
16A maximum
10mA, 12V DC
(reference value)
100mΩ ma ximum
(at 1A, 24V DC)
10 million operations
(no load, 10Hz)
100,000 operations
(rated resistive load)
1800 operations/hour
20.4 to 26.4V AC
20.4 to 28.8V DC
20 to 100mA (24V AC)
8 to 50mA (24V DC)
5 ms (typ.) (24V AC/DC)
2.4W (24V AC)
1.2W (24V DC)
20.4 to 26.4V AC
20.4 to 28.8V DC
2500V AC, 1 minute
500V DC, 1 minute
Resistive load
5A at 12/ 24V AC/DC
5A at 100/120V AC
5A at 230/240V AC
0.2A at 120V DC
0.1A at 240V DC
Inductive load
2A at 12/24V AC/DC
3A at 100/120V AC
3A at 23 0/240V AC
0.2A at 120V DC
0.1A at 240V DC
External fuse required:
16A maximum
10mA, 12V DC
(reference value)
100mΩ ma ximum
(at 1A, 24V DC)
10 million operations
(no load, 10Hz)
100,000 operations
(rated resistive load)
1800 operations/hour
85 to 26 5V AC
100 to 25 3V DC
10 to 30mA (100V AC)
10 to 20mA (240V AC)
5 to 15mA (100 V DC)
5 to 10mA (240V DC)
10ms (typ) (100V AC/DC)
20ms (typ.) (240V AC/DC)
3.5W (100V AC) 1.8W (100V DC)
4.8W (240V AC) 2.4W (240V DC)
85 to 26 5V AC
100 to 25 3V DC
< 0.05mA (AC)
< 0.06mA (DC)
≥ 0.08mA (AC)
≥ 0.13mA (DC)
100V AC: 40 ms (t yp.)
240V AC: 30 ms (t yp.)
100V DC: 25 ms (typ.)
240V DC: 20 ms (t yp.)
100V AC: 45 ms (t yp.)
240V AC: 70 ms (t yp.)
100V DC: 60 ms (t yp.)
240V DC: 75 ms (t yp.)
2500V AC, 1 minute
500V DC, 1 minute
Resistive load
5A at 12/ 24V AC/DC
5A at 100/120V AC
5A at 230/240V AC
0.2A at 120V DC
0.1A at 240V DC
Inductive load
2A at 12/24V AC/DC
3A at 100/120V AC
3A at 23 0/240V AC
0.2A at 120V DC
0.1A at 240V DC
External fuse required:
16A maximum
10mA, 12V DC (reference value)——
100 mΩ maximum
(at 1A, 24V DC)
10 million operations
(no load, 10Hz)
100,000 operations
(rated resistive load)
1800 operations/hour
10.8 to 28.8V DC20.4 to 28.8V DC
15 to 30mA15 to 82mA
10ms (typ.) (12/24V DC)10ms (typ.)
0.4W (12V DC)
0.8W (24V DC)
——
——
——
——
——
0 to 10V
(max. rated input: 28.8 V)
0 to 20m A
(max. rated input: 40m A)
76kΩ (0 to 10V)
250Ω (0 to 20mA)
10m (twisted-pair
shielded cable)
——
——
—Yes
——
——
——
2.0W
Voltage: 0-10V DC
Current: 0-20, 4-20 mA
Voltage output: ±2.5%
Current output: ±3%
Voltage: 5kΩ min
Current: 250Ω max
10m (twisted-pair
shielded cable)
—
—
—
5
DIMENSIONS (All d imens ions in mm)
78.5+0.5mm
Base Module (with Display)
Base Module (with Display)
71.5
Base Module (without Display)
71.5
Base Module (without Display)
Expansion I/O Module
Mounting Hole Layout (Using Mounting Slides)
+0.2
+0.2
+0.2
53.5 -0.0
35.5 -0.0
90
98 +/- 0.3
➀
55
60
➁➁➁➁➁➁➁
+0.2
n x 35.5 -0.0
+0.2
35.5 -0.0
35.5 -0.0
+0.2
35.5 -0.0
+0.2
35.5 -0.0
Tex t D isplay
90
53
58
128.2
86
31.9
34.7
38.7
77.6
Expansion I/O Module
35.5
Note: Drawings are not to scale
(Panel Cutout)
Mounting clip
119.0+0.5mm
90
53
58
Gasket
Panel (thickness: 1.5 to 4mm)
Mounting screws
(tightening torque:
0.15 to 0.2N·m)
Mounting clip