6th-Generation IDEC SmartRelay
BASE MODULE GENERAL SPECIFICATIONS
Item Specications Standard
Operating
Temperature
Storage/Transportation Temp.
Relative Humidity
Atmospheric Pressure
Operating Condition
Degree of Protection
Vibration Resistance
Shock Resistance
Drop Test (packaged)
Emissions
Electrostatic Discharge Immunity
Radiation Field Immunity
Fast Transient Burst
Surge Immunity
(FL1F-H12RCC, FL1F-B12RCC only)
Communication Cable
Terminal Style
1: For protection against surge noise on DC power supply types (FL1F-H12RCE/B12RCE, FL1F-H12SCD, FL1F-H12RCA/B12RCA), use surge absorbers,
noise cut transformers or noise filters. Use of a surge protection device (DEHN + SÖHNE GmbH + Co, BVT AD 24 Part No. 918 402) is recommended.
2: Tightening torque 0.5 to 0.6N·m
Horizontal Mounting
Vertical Mounting
1
0 to 55°C (no freezing)
0 to 55°C (no freezing)
–40 to +70°C (no freezing) —
10 to 95% (no condensation) IEC60068-2-30
795 to 1080hPa —
No corrosive gas —
IP20 —
5 to 8.4Hz, amplitude 3.5mm
8.4 to 150Hz, acceleration 9.8m/s²
147m/s² IEC60068-2-27
0.3m IEC60068-2-32
Limit class B Group 1
8kV air discharge
6kV contact discharge
Field Strength:
1V/m a nd 10V/m
2kV (power line)
2kV (I/O signal line)
1kV (power line) normal
2kV (power line) common
2.5mm ² (one wire)
1.5mm² (two wires)
Finger-safe type
2
Cold: IEC60068-2-1
Hot: IEC60068-2-2
IEC60068-2-6
EN 550 11/A
EN55022/B
EN50081-1
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
—
—
PRODUCT DESCRIPTION
With an ever-changing market and
tough competition, you need an edge to
stay on top. This sixth-generation IDEC
SmartRelay meets your demands from all
small-scale applications by offering more
powerful hardware, a new display and full
communication options via Ethernet.
BASE MODULE HIGHLIGHTS
Embedded RJ45 Ethernet Port
• Remote program download, upload and
monitor
• Integrated web server for remote
monitoring and control
Micro SD Card
• Equipped with micro SD slot for program
storage, transfer and data logging
• No need for a special memory cartridge
Data Logging
• Up to 20,000 lines in a file with a maximum
of 50 files can be stored in the Micro SD
Memory card
Integrated Web Server
• Easily monitor and control web pages with
no HTML knowledge
• Instant monitoring and control using
standard web browser like Chrome, IE and
Firefox
• View and control I/O status, timer,
counters, analog set point and more
There's an App for that!
• Download iOS and Android App for free
• Using the SmartRelay App, users can view
and control any I/O status, timer, counters,
and analog set point anywhere and at any
time
1:N Communication
• FL1F SmartRelays now have the capability
to communicate with each other over an
Ethernet network
• Up to 16 FL1F SmartRelays can be
configured on the network
R
USC
1
TEXT DISPLAY PANEL HIGHLIGHTS:
New and improved LCD display
• Improved display with 6 lines and 20 characters per line, more than twice as many characters as before
• Selectable white, amber or red backlighting for optical emphasis on alarms and events
Two RJ45 Ethernet ports
• Use a standard Ethernet cable to the connect FL1F base module to the Text Display Panel. A special cable is not required.
• Provide different ways to connect
TEXT DISPLAY SPECIFICATIONS
Text Display General Specications
Item Specications Standard
Horizontal
Operating
Temperature
Storage/Transportation Temp.
Relative Humidity
Atmospheric Pressure
Operating Condition
Degree of Protection
Vibration Resistance
Shock Resistance
Drop Test (packaged)
Emissions
Electrostatic Discharge
Immunity
Radiation Field Immunity
Fast Transient Burst
Surge Immunity
(FL1F-H12RCC, FL1F-B12RCC only)
Communication Cable
Terminal Style
1 For protection against surge noise on DC power supply types (FL1F-H12RCE/B12RCE, FL1F-H12SCD, FL1F-
H12RCA/B12RCA), use surge absorbers, noise cut transformers, or noise filters. Use of a surge protection device
(DEHN + SÖHNE GmbH + Co, BVT AD 24 Part No. 918 402) is recommended.
2 Tightening torque 0.5 to 0.6N·m
Mounting
Vertical
Mounting
1
0 to 55°C (no freezing)
0 to 55°C (no freezing)
Cold: IEC60068-2-1
Hot: IEC60068-2-2
–40 to +70°C (no freezing) —
10 to 95% (no condensation) IEC60068-2-30
795 to 1080hPa —
No corrosive gas —
IP20 —
5 to 8.4Hz, amplitude
3.5mm
8.4 to 150Hz, acceleration
2
9.8m/s
2
147m/s
IEC60068-2-6
IEC60068-2-27
0.3m IEC60068-2-32
EN 55011/A
Limit class B Group 1
EN55022/B
EN50081-1
8kV air discharge
6kV contact discharge
Field Strength:
1V/m and 10 V/m
2kV (power line)
2kV (I/O signal line)
1kV (power line) normal
2kV (power line) common
2.5mm2 (one wire)
1.5mm2 (two wires)
Finger-safe type
2
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
—
—
Text Display General Specications Cont.
Dimensions (W × H × D)
Weight (approx.)
Installation
Keyboard
Display
128.2 × 86 × 38.7 mm
220g
Panel cut-out using mounting clips
Membrane keypad
FSTN graphic display
(W × H: 160 × 96 dots)
LED backlight (White, Amber, Red)
Font type
Displayable string
English, Spanish, Russian, Chinese, Italian, Turkish,
German, Dutch, French, Japanese
1 screen 6 lines × 20 columns
Power Supply Specications
Power Voltage
Allowable Voltage Range
Allowable Voltage Frequency
Power Consumption
Data Transmission Rate
24V AC/DC
12V DC
20.4 to 26.4V AC
10.2 to 28.8V DC
47 to 63Hz
12V DC: 145mA (Typ.)
24V DC: 70mA (Typ.)
24V AC: 75mA (Typ.)
10/100M full/half duplex data transmission rate
LCD Display / Backlight Specications
LCD Display Durability
Backlight Durability
3 Display durability is calculated under ordinary operating and storage conditions: room temperature,
normal humidity below 65% RH, and not subjected to direct sunlight.
4 Backlight durability is the number of hours taken for the light to become 50% of the original brightness.
3
4
50,000 hours
20,000 hours
2