Idec PS5R-B12, PS5R-B24, PS5R-F24, PS5R-A24, PS5R-A12 Data Sheet

...
Power Supplies
PS5R Standard Series
Key features:
• Universal input :
7.5W-50W: 85-264V AC/105-370V DC 100W: 85-132V AC/170-264V AC 240-370V DC (selectable) 75W, 120W, 240W: 85-264V AC/110-350V DC
• Overcurrent/overvoltage protection
• Power Factor Correction (75W, 120W, 240W models)
EN61000-3-3 EN61000-3-2
• Voltage adjustment +10%
• Spring-up crew terminal, IP20 (finger-safe)
• DIN rail or panel surface mount
• Approvals:
CE marked UL 508 Listed c-UL TÜV approved EMC Directives: EN50081-2 EN50082-2 EN61000-6-2 LVD EN60950:2000
PS5R Standard Series
Switching Power Supplies
Part Numbers
UL 508 Listed File #E177168
OI Touchscreens PLCs Automation Software Power Supplies Sensors Communication Barriers
Cert No. BL980213332392
Style Watts
7.5
15
30
50 24V DC 2.1A PS5R-D24
Rated Voltage
5V DC 1.5A PS5R-A05
12V DC 0.6A PS5R-A12
24V DC 0.3A PS5R-A24
5V DC 2.5A PS5R-B05
12V DC 1.2A PS5R-B12
24V DC 0.6A PS5R-B24
12V DC 2.5A PS5R-C12
24V DC 1.3A PS5R-C24
Rated Current
Part Number
Style Watts
75 24V DC 3.1A PS5R-Q24
100 24V DC 4.2A PS5R-E24
120 24V DC 5A PS5R-F24
240 24V DC 10A PS5R-G24
Rated Voltage
Rated Current
Part Number
800-262-IDEC (4332) USA & Canada
147
PS5R Standard Series
Power Supplies
Specifications
PS5R-A05 PS5R-B05*
Model
OI TouchscreensPLCsAutomation SoftwarePower SuppliesSensorsCommunicationBarriers
Output Capacity 7.5W 15W 30W 50W 75W 100W 120W 240W
Input Voltage (single­phase, 2-wire)
Input Current (typical)
Internal Fuse Rating 2A 2A 3.15A 3.15A 3.15A 4A 4A 6.3A
Input
Inrush Current 50A maximum (at cold start at 200V AC)
Leakage Current (at no load)
Typical Efficiency
Overvoltage Protection Outputs turns off at 105% (typical)
Voltage and Current Ratings
Voltage Adjustments ±10% (V.ADJ screw on top) Output Holding Time 20ms minimum (at full rated input and output) Rise Time 200ms maximum (at full rated input and output) 150ms max. Line Regulation 0.4% maximum
Output
Load Regulation 1.5% maximum
Fluctuation due to Ambient Temperature Change
Ripple Voltage 2% peak to peak maximum (including noise) Overload Protection 120% typical (Zener-limiting) 120% typical, auto reset
Operation Indicator LED (green)
Parallel Operation Allowed
Dielectric Strength
Insulation Resistance Between input and output terminals/input terminals and housing: 100MΩ minimum (500V DC megger) Operating Temperature –10˚ to +60˚C (14˚ to 140˚F) (see derating curves) Storage Temperature –30˚ to +85˚C (-22˚ to 185˚F) Operating Humidity 20 to 90% relative humidity (no condensation) Vibration Resistance 45m/s Shock Resistance 300m/s
Approvals
Weight 150g 170g 360g 390g 800g 600g 1200g 2000g Termination Spring-up, fingersafe terminals with captive M3.5 screws IP protection IP20 (finger safe) Dimensions H x W x D (mm) 75 x 45 x 70 75 x 45 x95 75 x 90 x 95 75 x 90 x 95 120 x 85 x 140 75 x 145 x 95 120 x 115 x140 120 x 200x 140
Dimensions H x W x D (inches)
1. For dimensions, see page 151.
2. For usage instructions, see page 150.
PS5R-A12 PS5R-B12 PS5R-C12
PS5R-A24 PS5R-B24 PS5R-C24 PS5R-D24 PS5R-Q24 PS5R-E24 PS5R-F24 PS5R-G24
100 to 120V AC,
100 to 240V AC nominal (85 to 264V AC), 50/60Hz (47 to 63Hz) 110 to 340V DC nominal (105 to 370V DC)
0.17A at 100V AC
5V, 1.5A 12V, 0.6A 24V, 0.3A
PS5R-A PS5R-B PS5R-C PS5R-D PS5R-Q PS5R-E PS5R-F PS5R-G
2.95 x 1.77 x
2.76
0.3A at 100V AC
69% at 5V 75% at 12V 79% at 24V
5V, 2.5A 12V, 1.2A 24V, 0.6A
2
, 10 to 55Hz, 2 hours on each of 3 axes 10 to 50Hz, 0.75mm p-p, 2 hrs on each of 3 axes
Conforms to EMC Directives EN50081-2 & EN50082-2. LVD Directive EN60529 — Certified to EN60950.
2.95 x 1.77 x
3.74
3. *12.5W for 5VDC model.
0.68A at 100V AC
0.75mA maximum (60Hz, measured in conformance with UL, CSA, VDE)
75% at 12V 75% at 24V
12V, 2.5A 24V, 1.3A
No Yes No Yes
Between input terminals and housing: 2,000V AC, 1 minute
UL508 listed. c-UL, TUV approved. CE marked. EN61000-3-2
2.95 x 3.54 x
3.74
1.15A at 100V AC
79% at 24V 83% at 24V 85% at 24V 83% at 24V
24V, 2.1A 24V, 3.1A 24V, 4.2A 24V, 5A 24V, 10A
Between input and output terminals: 3,000V AC, 1 minute
Between output terminal and housing: 500V AC, 1 minute
2
(30G), 3 shocks in each of 6 directions
2.95 x 3.54 x
3.74
1.1A at 100V AC
70A maximum (at cold start at 230V AC)
0.05% maximum
4.72 x 3.35 x
5.52
50/60Hz 200 to 240V AC, 50/60Hz (jumper selectable) 240 to 370V DC
2.5A at 100V AC
1.5A at 200V AC
50A maximum (at cold start at 200V AC)
2.95 x 5.71 x 3.74
100 to 240V AC, 50/60Hz, 110 to 340V DC
1.8A at 100V AC
70A maximum (at cold start at 230V AC)
4.72 x 4.53 x
5.52
4A at 100V AC
4.72 x 7.87 x
5.51
148
www.IDEC.com
Loading...