PS3L Series Power Supplies
Specifications
Input Voltage
(Single-phase two-wire)
Frequency (AC input only)
Input Current
(Typical)
Inrush Current
Input
(Cold start)
Leakage Current
Power Factor (Typical)
Efficiency (Typical)
Rated Voltage/Current
Adjustable Voltage Range
Output Holding Time
Start Time
Rise Time
Output
Input Fluctuation
Load Fluctuation
Temperature Change
Specifications
(–10 to +50°C)
Regulation
Ripple
Voltage
Overcurrent Protection
Overvoltage Protection
Functions
Operation Indicator
Supplementary
L
Dielectric Strength
Insulation Resistance
Operating Temperature (Note 5)
Storage Temperature
Operating Humidity
Vibration Resistance
Shock Resistance
Dimensions H X W X D (mm)
Weight (Approx.)
Power Supplies
Terminal Screw
1. Including noise. Measured at the terminal block according to EIAJ.
2. Protection against short-circuit and overcurrent of 30 seconds maximum. Overload for 30 seconds or longer
may damage the internal elements.
3. Zener limiter method
4. Turn the input off and after one minute, turn the input on again.
5. Refer to the derating characteristics. No freezing. The maximum temperature is the temperature at 100% output
current (natural air-cooling) in the derating characteristics.
Type
100V
200V
100V
200V
–10 to 0°C
0 to +50°C
PS3L-A
(10W)
100 to 240V AC
(Voltage range: 85 to 264V AC/105 to 370V DC)
47 to 63 Hz
0.25A 0.37A 0.68A 0.68A 1.4A 2.0A 3.8A
0.16A 0.23A 0.45A 0.34A 0.65A 0.95A 2.0A
20A max. 20A max. 20A max. 30A max. 30A max. 30A max. 30A max.
40A max. 40A max. 40A max. 60A max. 60A max. 60A max. 60A max.
0.75 mA max. (60Hz; UL, CSA, VDE)
— 0.99 (100V AC input, rated output), 0.95 (200V AC, rated output)
5V DC: 70%
12V DC: 74%
24V DC: 78%
5V/2A
12V/0.9A
24V/0.5A
±10% (V.ADJ control on front)
20 msec minimum (at the rated input and output)
200 msec maximum (at the rated input and output) 500 msec maximum (at the rated input and output)
100 msec maximum (at the rated input and output) 200 msec maximum (at the rated input and output)
5V: 20 mV maximum, 12V: 48 mV maximum, 24V: 96 mV maximum
5V: 40 mV maximum, 12V: 100 mV maximum, 24V: 150 mV maximum
5V 50 mV maximum
12V: 120 mV maximum
24V: 240 mV maximum
5V: 160 mV maximum, 12V/24V: 180 mV maximum (Note 1)
5V: 120 mV maximum, 12V/24V: 150 mV maximum (Note 1)
105% (Typical), Automatic reset (Note 2)
120% min.
(Note 3)
Provided (Green LED)
Between input and output terminals:3,000V AC, 1 minute
Between input terminal and housing:2,000V AC, 1 minute
Between output terminal and housing:500V AC, 1 minute
Between input and output terminals:100MΩ minimum (500V DC megger)
Between input terminal and housing:100MΩ minimum (500V DC megger)
–10 to +70°C –10 to +60°C –10 to +65°C
–30 to +75°C
20 to 90% RH (no condensation, no freezing)
10 to 55 Hz, 20 m/s2 constant, sweep cycle 1 minute, 2 hours each in 3 axes
200 m/s2, 11 ms, 1 shock each in 3 axes
97 × 35 × 86 97 × 35 × 86 96 × 35 × 114.5 97 × 37 × 147.5 97 × 54 × 200 97 × 62 × 200 158 × 63 × 230
240g 250g 340g 350g 630g 730g 1550g
M4 slotted-Phillips head screw (screw terminal type)
PS3L-B
(15W)
5V DC: 73%
12V DC: 75%
24V DC: 78%
5V/3A
12V/1.4A
24V/0.7A
Output off at 120%, reset when input voltage is restored. (Note 4)
PS3L-C
(30W)
100 to 240V AC
(Voltage range: 85 to 264V AC/105 to 350V DC)
5V DC: 75%
12V DC: 77%
24V DC: 79%
5V/6A
12V/2.5A
24V/1.3A
5V: 60 mV maximum
12V: 150 mV maximum
24V: 290 mV maximum
—
12V DC: 76%
24V DC: 79%
—
12V/4.3A
24V/2.2A
PS3L-D
(50W)
PS3L-E
(100W)
—
12V DC: 78%
24V DC: 81%
—
12V/8.5A
24V/4.5A
PS3L-F
(150W)
—
12V DC: 80%
24V DC: 83%
—
12V/13A
24V/6.5A
PS3L-G24
(300W)
—
—
24V DC: 81%
—
—
24V/12.5A
200 mV maximum (Note 1)
L-14 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
Power Supplies PS3L Series
Characteristics
Operating Temperature vs. Output Current Characteristics (Derating Curves)
PS3L-A/B/C/D
100
90
80
70
60
50
40
Output Current (%)
30
20
10
-10
30 40 50 60 70
50 60 70 80
Operating Temperature (°C)
PS3L-E/F PS3L-G24
➀➁
Conditions: At rated input/output (operating temperature is the temperature around the power supply)
➀ Enclosed (Mounting Directions A and B)
➁ Open frame (Mounting Directions A and B)
Natural air-cooling
Forced air-cooling
(0.5 m/sec)
100
90
80
70
60
50
40
Output Current (%)
30
20
10
-10
➁
➂
➀➃
30 40 50 60 70
50 605565 70 80
Operating Temperature (°C)
Natural air-cooling
Forced air-cooling
(0.5 m/sec)
Conditions: At rated input/output (operating temperature is the temperature around the power supply)
➀ Enclosed (Mounting Direction A)
➁ Enclosed (Mounting Direction B)
➂ Open frame (Mounting Direction A)
➃ Open frame (Mounting Direction B)
A
B
100
90
(88)
80
70
60
50
40
Output Current (%)
30
20
10
-10
Conditions: At rated input/output (operating temperature is the temperature around the power supply)
➀ Enclosed (Mounting Direction A)
➁ Enclosed (Mounting Direction B)
➂ Open frame (Mounting Direction A)
➃ Open frame (Mounting Direction B)
Mounting Direction
Overcurrent Protection Characteristics
PS3L-A/B PS3L-C/D/E/F/G
➀
➁
20 30 40 50 60
403545 504555 605565 7065757080
Operating Temperature (°C)
➂➃
Natural air-cooling
Forced air-cooling
(0.5 m/sec)
A
Mounting Direction
L
Power Supplies
B
100
50
Output Voltage (%)
0
Output Current (%)
100 150
100
50
Output Voltage (%)
0
Output Current (%)
100 120
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC L-15