l
Operator Interfaces
MicrO/I® HG3F Operator Interface
ey features of the
• 10.4” TFT LCD screen
• RS-232, RS-485 or RS-422 compatible
• Field replaceable backlight
• Alarm logging capability
• 256 colors
• Bar graphs and bitmap capability
• Trending capability
• Real time clock
• Ethernet and compact flash support
• CE marked, c-UL and UL listed
• UL1604 for hazardous locations
• Meets IP65 standards
• Programmable with WindO/I-NV2 software
Dimensions & Panel Cutout
e:
K
Dimensions
Installation Panel Layout
Operator Interfaces
324mm
301mm
B
227mm
240mm
6mm
55.8mm
Mounting Clip
Panel
A
A: 228mm + 0.5mm B: 302mm + 0.5mm Panel thickness: 2 to 5mm
www.idec.com
HG3F
Mounting Clip
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
Operator Interfaces
Standards
Electrical
Environmental
General Specifications
Structural
Noise
Safety Standards UL508, UL1604, CSA C22-2, No. 213, CE
EMC Standards IEC/EN61131-2, IEC/EN 61000-6-4, IEC/EN61000-6-2, CE
Rated voltage 24V DC
Voltage variation range 80 to 120% of the rated voltage (including ripple)
Power consumption 25W
Momentary Power Interruption 10ms maximum, Level: PS-2
Inrush current 15A maximum (cold start)
Dielectric strength AC 1500V 10mA, 1 minute (between power terminals & FG)
Insulation resistance
Operating temperature range 0 to 50°C (no freezing)
Operating humidity range 20 to 85% RH (no condensation)
Storage temperature -20 to 60°C (no freezing)
Storage humidity 20 to 85% RH (no condensation)
Vibration resistance 10 to 55Hz 9.8m/s2 (2 HRS in each axis X, Y and Z) (IEC 60068-2-6)
Shock resistance 147 m/s2 (5 times each axis X, Y and Z) (IEC 60062-2-27)
Altitude
Pollution degree Pollution degree 2 (IEC60664-1)
Degree of protection IP66, NEMA 4, 4X, and 13 (front of panel)
Exterior Dimensions (W x H x D) 324mm x 240mm x 56mm
Panel Cutout Dimensions (W x H) 302mm +0.5 x 228mm +0.5
Weight Approx. 2.8kg
Electrostatic Discharge
Electromagnetic Field
Fast Transient Burst Withstandability
Damped Oscillatory Wave Serial mode Power supply: ± 1kV IEC/EN 61000-4-12
Surge Immunity turning on electricity 500V between L-FG IEC/EN 61000-4-5
Radiated Emission IEC/EN 61000-6-4
MicrO/I® HG3F Specifications
10 M
minimum (500V DC megger)
(Between power terminals and FG)
0 to 2000m (operation) 0 to 3000m (transport) (IEC 61131-2)
ESD-3 (RH-1) Level 3 Contact ±6kV Air ±8kV
10V/m 0.27M to 500MHz 10V/m AM80% 80M to 1000MHz
Common mode: Level 3 Power supply: ±2kV Communication line: ±1kV
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
MicrO/I
®
HG3F Series
K
Operator Interfaces
Display 10.4" TFT 256-Color LCD
Device
Backlight
Graphic Display
Display Specifications
Number of Pixels 640 (W) x 480 (H)
Pitch 0.33 x 0.33 mm
Element life 100,700 hours minimum
Backlight Cold cathode tube (Field Replaceable)
Backlight life 50,000 hours minimum
Graphics Line, polyline, rectangle, circle, arc, pie, ellipse, polygon, bitmaps, paint
Lines Solid, dotted, dash, long dash, dotted, long dotted