Comparison between FC4A and FC5A CPU Module Functions
CPU Module
ogram Capacity
I/O Points
Advanced Instr uction
32-bit Pr ocessing
Floating Point Data Pr ocessing
rigonometric/Logarithm
ocessing Time
LOD Instruction
MOV Instr uction
Basic Instr uction
END Pr ocessing (Note)0.64 ms0.35 ms
Inter nal Relay
Shift Register
Data Register
Bit Addr essing in Basic Instruction
Counter
imer
Catch Input / Inter rupt Input
Four Inputs (I2 thr ough I5)
High-speed Counter
Counting Fr equency
Counting Range
Multi-stage Comparison
Comparison Action
equency Measurement
Pulse Output
Output Points
Output Pulse Fr equency
Communication
Baud Rate
Modbus Master/Slave Communication
Quantity of AS-Inter face Modules
PID Advanced Auto T uning
Online Edit / T est Program Download
Run-T ime Program Download Size
System Pr ogram Download
ogram Download from Memory Cartridge
31,200 bytes maximum
(5,200 steps)
264 points maximum
72 maximum
1 µs
66 µs
1.65 ms (1000 steps)
1,584 maximum
128 maximum
7,600 maximum
100 maximum
100 maximum
Minimum tur n on pulse width / Minimum turn off pulse width
40 µs / 150 µs
20 kHz maximum
0 to 65535 (16 bits)
Comparison output
2 points maximum
20 kHz maximum
19,200 bps maximum
(Data link: 38,400 bps maximum)
1 maximum
600 bytes maximum
FC4A
FC5A
62,400 bytes maximum
(10,400 steps)
512 points maximum
92 maximum
Possible
Possible
Possible
0.056 µs maximum
0.167 µs maximum
83 µs (1000 steps)
2,048 maximum
256 maximum
48,000 maximum
Possible
256
256
5 µs / 5 µs
100 kHz maximum
0 to 4,294,967,295 (32 bits)
Possible
Comparison output
Inter rupt program
Possible
3 points maximum
100 kHz maximum
57,600 bps maximum
Possible
2 maximum
Possible
Possible
ithout limit
Possible
Possible
Note: END pr ocessing does not include expansion I/O ser vice, clock function pr ocessing, data link pr ocessing, and inter r upt
ocessing
C
OMPARISON
FC5A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
SAFETY PRECAUTIONS
• Read this user’s manual to make sure of correct operation before starting installation, wiring, operation, maintenance, and
inspection of the MicroSmart.
• All MicroSmart modules are manufactured under IDEC’s rigorous quality control system, but users must add a backup or
failsafe provision to the control system using the MicroSmart in applications where heavy damage or personal injury may
be caused in case the MicroSmart should fail.
• In this user’s manual, safety precautions are categorized in order of importance to Warning and Caution:
Warning
•Turn off the power to the MicroSmart before starting installation, removal, wiring, maintenance, and inspection of the
MicroSmart. Failure to turn power off may cause electrical shocks or fire hazard.
• Special expertise is required to install, wire, program, and operate the MicroSmart. People without such expertise must not
use the MicroSmart.
• Emergency stop and interlocking circuits must be configured outside the MicroSmart. If such a circuit is configured inside
the MicroSmart, failure of the MicroSmart may cause disorder of the control system, damage, or accidents.
• Install the MicroSmart according to the instructions described in this user’s manual. Improper installation will result in falling, failure, or malfunction of the MicroSmart.
Caution
• The MicroSmart is designed for installation in a cabinet. Do not install the MicroSmart outside a cabinet.
• Install the MicroSmart in environments described in this user’s manual. If the MicroSmartis used in places where the
MicroSmart is subjected to high-temperature, high-humidity, condensation, corrosive gases, excessive vibrations, and
excessive shocks, then electrical shocks, fire hazard, or malfunction will result.
• The environment for using the MicroSmart is “Pollution degree 2.” Use the MicroSmart in environments of pollution
degree 2 (according to IEC 60664-1).
• Prevent the MicroSmart from falling while moving or transporting the MicroSmart, otherwise damage or malfunction of
the MicroSmart will result.
• Prevent metal fragments and pieces of wire from dropping inside the MicroSmart housing. Put a cover on the MicroSmart
modules during installation and wiring. Ingress of such fragments and chips may cause fire hazard, damage, or malfunction.
• Use a power supply of the rated value. Use of a wrong power supply may cause fire hazard.
• Use an IEC 60127-approved fuse on the power line outside the MicroSmart. This is required when equipment containing
the MicroSmart is destined for Europe.
• Use an IEC 60127-approved fuse on the output circuit. This is required when equipment containing the MicroSmart is destined for Europe.
• Use an EU-approved circuit breaker. This is required when equipment containing the MicroSmart is destined for Europe.
• Make sure of safety before starting and stopping the MicroSmart or when operating the MicroSmar t to force outputs on or
off. Incorrect operation on the MicroSmart may cause machine damage or accidents.
• If relays or transistors in the MicroSmart output modules should fail, outputs may remain on or off. For output signals
which may cause heavy accidents, provide a monitor circuit outside the MicroSmart.
• Do not connect the ground wire directly to the MicroSmart. Connect a protective ground to the cabinet containing the
MicroSmart using an M4 or larger screw. This is required when equipment containing the MicroSmar t is destined for
Europe.
• Do not disassemble, repair, or modify the MicroSmart modules.
• Dispose of the battery in the MicroSmart modules when the battery is dead in accordance with pertaining regulations.
When storing or disposing of the battery, use a proper container prepared for this purpose. This is required when equipment
containing the MicroSmart is destined for Europe.
• When disposing of the MicroSmart, do so as an industrial waste.
War ning notices are used to emphasize that improper operation may cause
severe personal injury or death.
Caution notices are used where inattention might cause personal injury or
damage to equipment.
FC5A M
ICROSMART USER’S MANUALPREFACE-1
About This Manual
This user’s manual primarily describes entire functions, installation, and programming of the MicroSmart CPU, I/O, and
all other modules. Also included are powerful communications of the MicroSmart and troubleshooting procedures.
CHAPTER 1: GENERAL INFORMATION
General information about the MicroSmart, features, brief description on special functions, and various system setup configurations for communication.
CHAPTER 2: MODULE SPECIFICATIONS
Specifications of CPU, input, output, mixed I/O, analog I/O, and other optional modules.
CHAPTER 3: INSTALLATIONAND WIRING
Methods and precautions for installing and wiring the MicroSmart modules.
CHAPTER 4: OPERATION BASICS
General information about setting up the basic MicroSmart system for programming, starting and stopping MicroSmart
operation, and simple operating procedures from creating a user program using WindLDR on a PC to monitoring the
MicroSmart operation.
CHAPTER 5: SPECIAL FUNCTIONS
Stop/reset inputs, run/stop selection at memory backup error, keep designation for internal relays, shift registers, counters,
and data registers. Also included are high-speed counter, frequency measurement, catch input, interrupt input, timer interrupt, input filter, user program protection, constant scan time, online edit, and many more special functions.
CHAPTER 6: ALLOCATION NUMBERS
Allocation numbers available for the MicroSmart CPU modules to program basic and advanced instructions. Special internal relays and special data registers are also described.
CHAPTER 7: BASIC INSTRUCTIONS
Programming of the basic instructions, available operands, and sample programs.
CHAPTER 8: ADVANCED INSTRUCTIONS
General rules of using advanced instructions, terms, data types, and formats used for advanced instructions.
CHAPTER 9 THROUGH CHAPTER 25:
Detailed descriptions on advanced instructions grouped into 17 chapters.
CHAPTER 26 THROUGH CHAPTER 31:
Analog I/O control and various communication functions such as data link, computer link, modem mode, Modbus, and
AS-Interface.
CHAPTER 32: TROUBLESHOOTING
Procedures to determine the cause of trouble and actions to be taken when any trouble occurs while operating the Micro-
.
Smart
APPENDIX
Additional information about execution times for instructions, I/O delay time, and MicroSmart type list.
INDEX
Alphabetical listing of key words.
IMPORTANT INFORMATION
Under no circumstances shall IDEC Corporation be held liable or responsible for indirect or consequential damages resulting
from the use of or the application of IDEC PLC components, individually or in combination with other equipment.
All persons using these components must be willing to accept responsibility for choosing the correct component to suit their
application and for choosing an application appropriate for the component, individually or in combination with other equipment.
All diagrams and examples in this manual are for illustrative purposes only. In no way does including these diagrams and examples in this manual constitute a guarantee as to their suitability for any specific application. To test and approve all programs,
prior to installation, is the responsibility of the end user.
This chapter describes general information about the powerful capabilities of the upgraded FC5A series MicroSmart micro
programmable logic controllers and system setups to use the MicroSmart in various ways of communication.
About the MicroSmart
IDEC’s FC5A MicroSmart is an upgraded family of micro programmable logic controllers available in two styles of CPU
modules; all-in-one and slim types.
The all-in-one type CPU module has 10, 16, or 24 I/O terminals and is equipped with a built-in universal power supply to
operate on 100 to 240V AC or 24V DC. Using four optional 16-point I/O modules, the 24-I/O type CPU module can
expand the I/O points up to a total of 88 points. Program capacity of the all-in-one type CPU modules is 13,800 bytes
(2,300 steps) on the 10-I/O type CPU module, 27,000 bytes (4,500 steps) on the 16-I/O type, and 54,000 bytes (9,000
steps) on the 24-I/O type.
The slim type CPU module has 16 or 32 I/O terminals and operates on 24V DC. The total I/O points can be expanded to a
maximum of 512. When using two AS-Interface master modules, a maximum of 1,380 I/O points can be connected. The
program capacity of slim type CPU modules is 62,400 bytes (10,400 steps).
Slim type CPU modules feature Logic Engine for superior ladder processing capabilities to achieve fast execution of
instructions — 0.056 µs for a basic instruction (LOD) and 0.167 µs for an advanced instruction (MOV).
User programs for the MicroSmart can be edited using WindLDR on a Windows PC. Since WindLDR can load existing user
programs made for IDEC’s previous PLCs such as all FA series, MICRO-1, MICRO3, MICRO
well as the FC4A MicroSmart, your software assets can be used in the new control system.
3
C, and OpenNet Controller as
Features
Powerful Communication Functions
The MicroSmart features five powerful communication functions.
Maintenance
Communication
(Computer Link)
User Communication
Modem Communication
Data Link
Modbus Communication
When a MicroSmart CPU module is connected to a computer, operating status and I/O status can be monitored on the computer, data in the CPU can be monitored or updated, and
user programs can be downloaded and uploaded. All CPU modules can set up a 1:N computer link system to connect a maximum of 32 CPU modules to a computer.
All MicroSmart CPU modules can be linked to external RS232C devices such as computers,
printers, and barcode readers through por t 1 and por t 2, using the user communication function. RS485 user communication is also available through port 2.
All MicroSmart CPU modules can communicate through modems using the built-in modem
protocol.
All MicroSmart CPU modules can set up a data link system. One CPU module at the master
station can communicate with 31 slave stations through an RS485 line to exchange data and
perform distributed control ef fectively.
All MicroSmart CPU modules can be used as a Modbus master or slave, and can be connected to other Modbus devices.
FC5A MICROSMART USER’S MANUAL1-1
1: GENERAL INFORMATION
Communication Adapter (All-in-one type CPU modules)
Communication Module (Slim type CPU modules)
In addition to the standard RS232C port 1, all-in-one type CPU modules feature a port 2 connector to install an optional
RS232C or RS485 communication adapter. Any slim type CPU module can be used with an optional RS232C or RS485
communication module to add communication port 2. With an optional HMI base module mounted with a slim type CPU
module, an optional RS232C or RS485 communication adapter can also be installed on the HMI base module.
RS232C Communication Adapter
RS232C Communication Module
RS485 Communication Adapter
RS485 Communication Module
HMI Module (all CPU modules)
Used for computer link 1:1 communication, user communication, and modem
communication.
Available in mini DIN connector and terminal block styles. Used for computer link
1:1 or 1:N communication, user communication, data link communication, and
Modbus communication.
An optional HMI module can be installed on any all-in-one type CPU module, and also on the HMI base module mounted
next to any slim type CPU module. The HMI module makes it possible to manipulate the RAM data in the CPU module
without using the Online menu options in WindLDR.
HMI module functions include:
• Displaying timer/counter current values and changing timer/counter preset values
• Displaying and changing data register values
• Setting and resetting bit operand statuses, such as inputs, outputs, internal relays, and shift register bits
• Displaying and clearing error data
• Starting and stopping the PLC
• Displaying and changing calendar/clock data (only when using the clock cartridge)
• Confirming changed timer/counter preset values
Clock Cartridge (all CPU modules)
An optional clock cartridge can be installed on the CPU module to store real time calendar/clock data for use with
advanced instructions to perform time-scheduled control.
Memory Cartridge (all CPU modules)
A user program can be stored on an optional memory cartridge using WindLDR. The memory cartridge can be installed on
another CPU module to replace user programs without the need for connecting to a computer. The original user program in
the CPU module is restored after removing the memory cartridge. The user program on the memory cartridge can also be
downloaded to the CPU module. The download option is selected using WindLDR.
Analog I/O Modules (all CPU modules except all-in-one 10- and 16-I/O types)
The analog input channel can accept either voltage (0 to 10V DC) and current (4 to 20 mA) signals or thermocouple (types
K, J, and T) and resistance thermometer (Pt 100, Pt1000, Ni100, and Ni1000) signals. The output channel generates voltage (0 to 10V DC or –10 to +10V DC) and current (4 to 20 mA) signals.
AS-Interface Master Module (all CPU modules except all-in-one 10- and 16-I/O types)
One or two AS-Interface master modules can be mounted to communicate with a maximum of 124 slaves, or 496 inputs
and 372 outputs, such as actuators and sensors, through the AS-Interface bus.
Web Server Unit (all CPU modules)
The web server unit is used to connect the MicroSmart to Ethernet. Remote monitoring is made possible, sending Email
messages to personal computers or mobile phones.
1-2FC5A MICROSMART USER’S MANUAL
1: GENERAL INFORMATION
Special Functions
The MicroSmart features various special functions packed in the small housing as described below. For details about these
functions, see the following chapters.
Stop and Reset Inputs
Any input terminal on the CPU module can be designated as a stop or reset input to control the MicroSmart operation.
RUN/STOP Selection at Startup when “Keep” Data is Broken
When data to be kept such as “keep” designated counter values are broken while the CPU is powered down, the user can
select whether the CPU starts to run or not to prevent undesirable operation at the next startup.
“Keep” or “Clear” Designation of CPU Data
Internal relays, shift register bits, counter current values, and data register values can be designated to be kept or cleared
when the CPU is powered down. All or a specified range of these operands can be designated as keep or clear types.
High-speed Counter
The MicroSmart has four built-in high-speed counters to count high-speed pulses which cannot be counted by the normal
user program processing. All-in-one type CPU modules can count up to 65,535 pulses at 50 kHz. Slim type CPU modules
can count up to 4,294,967,295 pulses at 100 kHz. Both CPU modules can use either single-phase or two-phase high-speed
counters. The high-speed counters can be used for simple positioning control and simple motor control.
Frequency Measurement
The pulse frequency of input signals to four input terminals can be counted using the high-speed counter function at a
maximum of 50 kHz (all-in-one type CPU modules) or 100 kHz (slim type CPU modules).
Catch Input
Four inputs can be used as catch inputs. The catch input makes sure to receive short input pulses from sensors without
regard to the scan time — rising and falling pulse widths of 40 µs and 150 µs (all-in-one type CPU modules) or 5 µs and 5
µs (slim type CPU modules).
Interrupt Input
Four inputs can be used as interrupt inputs. When a quick response to an external input is required, such as positioning
control, the interrupt input can call a subroutine to execute an interrupt program.
Timer Interrupt
In addition to the interrupt input, all CPU modules have a timer interrupt function. When a repetitive operation is required,
the timer interrupt can be used to call a subroutine repeatedly at predetermined intervals of 10 through 140 ms.
Input Filter
The input filter can be adjusted for eight inputs to reject input noises. Selectable input filter values to pass input signals are
0 ms, and 3 through 15 ms in 1-ms increments. The input filter rejects inputs shorter than the selected input filter value
minus 2 ms. This function is useful for eliminating input noises and chatter in limit switches.
User Program Read/Write Protection
The user program in the CPU module can be protected against reading and/or writing by including a password in the user
program. This function is effective for security of user programs.
Constant Scan Time
The scan time may vary whether basic and advanced instructions are executed or not depending on input conditions to
these instructions. When performing repetitive control, the scan time can be made constant by entering a required scan
time value into a special data register reserved for constant scan time.
Online Edit, Run-Time Program Download, and Test Program Download
Normally, the CPU module has to be stopped before downloading a user program. All CPU modules have online edit, runtime program download, and test program download capabilities to download a user program containing small changes
while the CPU is running in either 1:1 or 1:N computer link system. This function is particularly useful to make small
modifications to the user program and confirm the changes while the CPU is running.
FC5A MICROSMART USER’S MANUAL1-3
1: GENERAL INFORMATION
Analog Potentiometer
All CPU modules have an analog potentiometer, except the all-in-one 24-I/O type CPU module has two analog potentiometers. The values (0 through 255) set with analog potentiometers 1 and 2 are stored to special data registers. The analog
potentiometer can be used to change the preset value for a timer or counter.
Analog Voltage Input
Every slim type CPU module has an analog voltage input connector. When an analog voltage of 0 through 10V DC is
applied to the analog voltage input connector, the signal is converted to a digital value of 0 through 255 and stored to a special data register. The data is updated in every scan.
Pulse Output
Slim type CPU modules have pulse output instructions to generate high-speed pulse outputs from transistor output terminals used for simple position control applications, illumination control, trapezoidal control, and zero-return control.
PID Control
All CPU modules (except the all-in-one 10- and 16-I/O types) have the PID instruction, which implements a PID (proportional, integral, and derivative) algorithm with built-in auto tuning or advanced auto tuning to determine PID parameters.
This instruction is primarily designed for use with an analog I/O module to read analog input data, and turns on and off a
designated output to perform PID control in applications such as temperature control. In addition, the PID instruction can
also generate an analog output using an analog I/O module.
Expansion Data Register
Slim type CPU modules have expansion data registers D2000 through D7999. Numerical data can be set to expansion data
registers using WindLDR. When downloading the user program, the preset values of the expansion data registers are also
downloaded to the EEPROM in the CPU module. Since the data in the EEPROM is non-volatile, the preset values of the
expansion data registers are maintained semi-permanently and loaded to the RAM each time the CPU is powered up.
32-bit and Floating Point Data Types
Some advanced instructions can select 32-bit data types from D (double word), L (long), and F (float) in addition to W
(word) and I (integer).
1-4FC5A MICROSMART USER’S MANUAL
1: GENERAL INFORMATION
System Setup
This section illustrates system setup configurations for using powerful communication functions of the MicroSmart.
User Communication and Modem Communication System
The all-in-one type MicroSmart CPU modules have port 1 for RS232C communication and port 2 connector. An optional
RS232C or RS485 communication adapter can be installed on the port 2 connector. With an RS232C communication
adapter installed on port 2, the MicroSmart CPU module can communicate with two RS232C devices at the same time.
The figure below illustrates a system setup of user communication and modem communication. In this example, the operating status of a remote machine is monitored on a computer through modems connected to port 2 and the data is transferred through port 1 to a pager transmitter using the user communication.
The same system can be set up using any slim type CPU module and an optional RS232C communication module.
For details about the user communication, see page 17-1.
For details about the modem mode, see page 29-1.
All-in-One Type CPU Module
Port 1
Port 2 Connector
Pager Transmitter
Data
Transmission
Pager
RS232C
Communication
Adapter on
Modem
Data
Communication
Modem
Computer
FC5A MICROSMART USER’S MANUAL1-5
1: GENERAL INFORMATION
Computer Link System
When the MicroSmart is connected to a computer, operating status and I/O status can be monitored on the computer, data
in the CPU module can be monitored or updated, and user programs can be downloaded and uploaded. When an optional
RS485 communication adapter is installed on the port 2 connector of the all-in-one type CPU modules or when an optional
RS485 communication module is mounted with any slim type CPU modules, a maximum of 32 CPU modules can be connected to one computer in the 1:N computer link system.
For details about the computer link communication, see pages 4-1 and 28-1.
Computer Link 1:1 Communication
Computer Link Cable 4C
3m (9.84 ft.) long
Computer Link Cable 4C
3m (9.84 ft.) long
Computer Link 1:N Communication
FC2A-KC4C
RS232C Communication Module
FC2A-KC4C
Port 1
All-in-One Type CPU Module
RS232C Communication
Adapter on Port 2 Connector
Slim Type CPU Module
Port 1
Port 2
All-in-One Type CPU Module
RS485 Communication
Adapter on Port 2 Connector
RS232C/RS485 Converter
FC2A-MD1
RS232C Cable
HD9Z-C52
1.5m (4.92 ft.) long
Twisted-pair Shielded Cable
RS485 Communication Module
Port 2
1-6FC5A MICROSMART USER’S MANUAL
1st Unit
2nd Unit
Slim Type CPU Module
32nd Unit
1: GENERAL INFORMATION
Data Link System
With an optional RS485 communication adapter installed on the port 2 connector, one CPU module at the master station
can communicate with 31 slave stations through the RS485 line to exchange data and perform distributed control effectively. The RS485 terminals are connected with each other using a 2-core twisted pair cable.
The same data link system can also be set up using any slim type CPU modules mounted with RS485 communication
modules.
For details about the data link communication, see page 27-1.
Master StationSlave Station 1Slave Station 31
Modbus Communication System
With an optional RS485 communication adapter installed on the port 2 connector, any FC5A MicroSmart CPU module
can be used as a Modbus master or slave station. Using the Modbus communication, the MicroSmart CPU module can
exchange data with other Modbus devices.
For details about the Modbus communication, see page 30-1.
Master StationSlave Station 1Slave Station 31
FC5A MICROSMART USER’S MANUAL1-7
1: GENERAL INFORMATION
Operator Interface Communication System
The MicroSmart can communicate with IDEC’s HG series operator interfaces through RS232C port 1 and port 2.
Optional cables are available for connection between the MicroSmart and HG series operator interfaces. When installing
an optional RS232C communication adapter on the all-in-one type CPU module or an optional RS232C communication
module on the slim type CPU module, two operator interfaces can be connected to one MicroSmart CPU module.
For details about communication settings, see the user’s manual for the operator interface.
To RS232C Por t 1 or 2
HG series Operator Interface
O/I Communication Cable
Applicable Cables to Operator Interfaces
Operator InterfaceO/I Communication CableFor Use on MicroSmart
FC4A-KC1CPor t 1 and por t 2 (RS232C)
HG1B, HG2A Series
HG2F, HG3F, HG4F Series
Note: HG series communication cables HG9Z-XC183 and HG9Z-3C125 can be used on port 2 only.
The MicroSmart can be connected to the AS-Interface network using the AS-Interface master module (FC4A-AS62M).
AS-Interface is a type of field bus that is primarily intended to be used to control sensors and actuators. AS-Interface is a
network system that is compatible with the IEC62026 standard and is not proprietary to any one manufacturer. A master
device can communicate with slave devices such as sensors, actuators, and remote I/Os, using digital and analog signals
transmitted over the AS-Interface bus.
The AS-Interface system is comprised of the following three major components:
• One master, such as the MicroSmart AS-Interface master module
• One or more slave devices, such as sensors, actuators, switches, and indicators
• Dedicated 30V DC AS-Interface power supply (26.5 to 31.6V DC)
These components are connected using a two-core cable for both data transmission and AS-Interface power supply. ASInterface employs a simple yet efficient wiring system and features automatic slave address assignment function, while
installation and maintenance are also very easy.
For details about AS-Interface communication, see a separate user’s manual for the MicroSmart AS-Interface master mod-
ule (manual No. FC9Y-B644).
Maximum Communication Distance
Without repeater:100 m
With 2 repeaters:300 m
MicroSmart AS-Interface Master Module
PS2R AS-Interface Power Supply
SX5A AS-Interface
Communication Terminal
IP67 Outside-panel Type
Sensor
AS-Interface
Gateway
SX5A AS-Interface
Communication Terminal
IP20 Inside-panel Type
Sensor
(AS-Interface Direct
Connection Type)
Manifold Solenoid Valve
Open Network (DeviceNet, CC-Link)
Light Tower
(AS-Interface
Direct
Connection Type)
AS-Interface Safety at Work
AS-Interface
Safety Monitor
Light Curtain
Emergency
Stop Switch
SwitchNet Control Units
(AS-Interface Direct Connection Type)
TM
SwitchNet is an IDEC trademark for pushbuttons, pilot lights, and other control units
capable of direct connection to the AS-Interface. SwitchNet devices are completely
compatible with AS-Interface Ver. 2.1.
The AS-Interface Safety Monitor is required
to connect safety devices, such as the light
curtain and emer gency stop switch, to the
AS-Interface line.
FC5A MICROSMART USER’S MANUAL1-9
1: GENERAL INFORMATION
Web Server Unit FC4A-SX5ES1E
A New Powerful Tool for the MicroSmart to communicate through Ethernet
• Email messages can be sent to PCs and mobile phones to alert a user by programming the MicroSmart to receive inputs
of abnormal machine conditions.
• Ethernet communication between the
• User communication enables 1:1 communication between
• Allows for access to data within the MicroSmart using a standard web browser.
• Connect to the MicroSmart and as well as any operator interface with an ethernet interface and a TCP/IP client function.
For details about the web server unit, see the separate brochure and user’s manual.
Sending Email messages
Web Server Unit
PLC1
Ethernet
MicroSmart and PC enables remote maintenance.
MicroSmart CPU modules via Ethernet.
• The MicroSmar t is programmed to detect
abnormal conditions of machines. When
an error occurs, an email message is
PC
Internet
sent to the address of PCs and mobile
phones registered within the web ser ver
unit.
PLC2
Email Server
Remote monitoring and control
PC1PC2
Ethernet
PLC1
PLC2PLC3
Data exchange between two MicroSmart CPU modules
PLC1PLC2
Mobile Phone
• Operating conditions of machines can be
easily monitored and changed from
remote places.
•WindLDR functions can be used on a
MicroSmart installed in remote places,
for monitoring of machines, configuration,
and to upload user programs. The MicroSmart does not need special user programs to communicate with a PC. Also,
not only WindLDR but standard SCADA
software applicable to Ethernet enables
graphical displays of monitoring and maintenance status.
• Data can be exchanged between MicroSmart cpu modules connected with web
server units using the user communication function.
Ethernet
PLC3
1-10FC5A MICROSMART USER’S MANUAL
PLC4
1: GENERAL INFORMATION
Basic System
The all-in-one 10-I/O type CPU module has 6 input terminals and 4 output terminals. The 16-I/O type CPU module has 9
input terminals and 7 output terminals. The 24-I/O type CPU module has 14 input terminals and 10 output terminals. Only
the 24-I/O type CPU module has an expansion connector to connect I/O modules. When four 16-point input or output
modules are connected to the 24-I/O type CPU module, the I/O points can be expanded to a maximum of 88 points.
Any slim type CPU module can add a maximum of seven expansion I/O modules. When using an expansion interface
module, eight more expansion I/O modules can be added. For details, see page 2-58.
4 I/O modules maximumAll-in-One 24-I/O Type CPU Module
FC5A MICROSMART USER’S MANUAL1-11
1: GENERAL INFORMATION
1-12FC5A MICROSMART USER’S MANUAL
2: MODULE SPECIFICATIONS
Introduction
This chapter describes MicroSmart modules, parts names, and specifications of each module.
Available modules include all-in-one type and slim type CPU modules, digital input modules, digital output modules,
mixed I/O modules, analog I/O modules, HMI module, HMI base module, communication adapters, communication modules, memory cartridge, and clock cartridge.
CPU Modules (All-in-One Type)
All-in-one type CPU modules are available in 10-, 16-, and 24-I/O types. The 10-I/O type has 6 input and 4 output terminals, the 16-I/O type 9 input and 7 output terminals, and the 24-I/O type 14 input and 10 output terminals. Every all-in-one
type CPU module has communication port 1 for RS232C communication and port 2 connector to install an optional
RS232C or RS485 communication adapter for 1:N computer link, modem communication, or data link communication.
Every all-in-one type CPU module has a cartridge connector to install an optional memory cartridge or clock cartridge.
CPU Module Type Numbers (All-in-One Type)
Power Voltage10-I/O Type16-I/O Type24-I/O Type
100 -240V AC (50/60 Hz)FC5A-C10R2FC5A-C16R2FC5A-C24R2
24V DCFC5A-C10R2CFC5A-C16R2CFC5A-C24R2C
Parts Description (All-in-One Type)
(2) Sensor Power Terminals
(12) Port 1
(13) Analog Potentiometer
(14) Port 2 Connector
Bottom View
(15) Cartridge Connector
(1) Power Supply Terminals
(16) Terminal Cover
(17) Hinged Lid
(18) HMI Connector Cover
(4) Output Terminals
(3) Input Terminals
(5) Expansion Connector
(6) Input LED (IN)
From Left:
(7) Power LED (PWR)
(8) Run LED (RUN)
(9) Error LED (ERR)
(10) Status LED (STAT)
(11) Output LED (OUT)
(20) Expansion
Connector
Seal
These figures illustrate the 24-I/O
type CPU module.
Functions of each part are described
on the following page.
(16) Terminal Cover
(19) Dummy Cartridge
FC5A MICROSMART USER’S MANUAL2-1
2: MODULE SPECIFICATIONS
(1) Power Supply Terminals
Connect power supply to these terminals. Power voltage 100-240V AC or 24V DC. See page 3-17.
(2) Sensor Power Terminals (AC power type only)
For supplying power to sensors (24V DC, 250mA). These terminals can be used for supplying power to input circuits. Use the sensor power supply only for supplying power to input devices connected to the MicroSmart.
(3) Input Terminals
For connecting input signals from input devices such as sensors, pushbuttons, and limit switches. The input terminals accept both sink and source DC input signals.
(4) Output Terminals
For connecting output signals to output devices such as electromechanical relays and solenoid valves. The internal output relay is rated at 240V AC/2A or 30V DC/2A.
(5) Expansion Connector (24-I/O type CPU module only)
For connecting digital and analog I/O modules to the 24-I/O type CPU module.
(6) Input LED (IN)
Turns on when a corresponding input is on.
(7) Power LED (PWR)
10-I/O Type
LED Indicators
IN
012345
Turns on when power is supplied to the CPU module.
(8) Run LED (RUN)
Turns on when the CPU module is executing the user program.
(9) Error LED (ERR)
Turns on when an error has occurred in the CPU module.
16-I/O Type
PRES0123
WRUNR
T
A
T
R
0123456710
OUT
IN
(10) Status LED (STAT )
The status LED can be turned on or off using the user program
to indicate a specified status.
(11) Output LED (OUT)
Turns on when a corresponding output is on.
24-I/O Type
PRES0123456
WRUNR
01234567101112131415
T
A
T
R
OUT
(12) Port 1 (RS232C)
For connecting a computer to download a user program and
monitor the PLC operation on a computer using WindLDR.
PRES012345671011
WRUNR
T
A
T
R
(13) Analog Potentiometer
Sets a value of 0 through 255 to a special data register. The 10- and 16-I/O types have one potentiometer. The
24-I/O type has two potentiometers. The analog potentiometer can be used to set a preset value for an analog
timer.
(14) Port 2 Connector
For connecting an optional RS232C or RS485 communication adapter.
IN
OUT
(15) Cartridge Connector
For connecting an optional memory cartridge or clock car tridge.
(16) Terminal Cover
For protecting the input and output terminals. When wiring the terminals, open the covers.
(17) Hinged Lid
Open the lid to gain access to the port 1, por t 2 connector, and analog potentiometer.
(18) HMI Connector Cover
Remove the HMI connector cover when using an optional HMI module.
(19) Dummy Cartridge
Remove the dummy cartridge when using an optional memory car tridge or clock car tridge.
(20) Expansion Connector Seal (24-I/O type CPU module only)
Remove the expansion connector seal when connecting an expansion module.
2-2FC5A MICROSMART USER’S MANUAL
2: MODULE SPECIFICATIONS
General Specifications (All-in-One Type CPU Module)
Normal Operating Conditions
CPU Module
Operating Temperature0 to 55°C (operating ambient temperature)
Storage Temperature–25 to +70°C (no freezing)
Relative Humidity10 to 95% (non-condensing, operating and storage humidity)
Pollution Degree2 (IEC 60664-1)
Degree of ProtectionIP20 (IEC 60529)
Corrosion ImmunityAtmosphere free from corrosive gases
Operation: 0 to 2,000m (0 to 6,565 feet)
Transport: 0 to 3,000m (0 to 9,840 feet)
When mounted on a DIN rail or panel surface:
5 to 9 Hz amplitude 3.5 mm, 9 to 150 Hz acceleration 9.8 m/s
2 hours per axis on each of three mutually perpendicular axes (IEC 61131-2)
2
147 m/s
axes (IEC 61131-2)
AC Power Type230g250g305g
DC Power Type240g260g310g
(15G), 11 ms duration, 3 shocks per axis on three mutually perpendicular
2
(1G)
Power Supply (AC Power Type)
CPU ModuleFC5A-C10R2FC5A-C16R2FC5A-C24R2
Rated Power Voltage100 to 240V AC
Allowable Voltage Range85 to 264V AC
Rated Power Frequency50/60 Hz (47 to 63 Hz)
Maximum Input Current250 mA (85V AC)300 mA (85V AC)450 mA (85V AC)
30VA (264V AC),
Maximum Power Consumption
Allowable Momentary Power
Interruption
Dielectric Strength
Insulation Resistance
Noise Resistance
Inrush Current35A maximum35A maximum40A maximum
Grounding WireUL1007 AWG16
Power Supply WireUL1015 AWG22, UL1007 AWG18
Effect of Improper Power
Supply Connection
20VA (100V AC)
(Note 1)
10 ms (at the rated power voltage)
Between power and terminals: 1,500V AC, 1 minute
Between I/O and terminals: 1,500V AC, 1 minute
Between power and terminals: 10 MΩ minimum (500V DC megger)
Between I/O and terminals: 10 MΩ minimum (500V DC megger)
AC power terminals:1.5 kV, 50 ns to 1 µs
I/O terminals (coupling clamp):1.5 kV, 50 ns to 1 µs
Reverse polarity:Normal operation (AC)
Improper voltage or frequency:Permanent damage may be caused
Improper lead connection:Permanent damage may be caused
31VA (264V AC),
22VA (100V AC)
(Note 1)
40VA (264V AC),
33VA (100V AC)
(Note 2)
Note 1: Power consumption by the CPU module, including 250mA sensor power
Note 2: Power consumption by the CPU module, including 250mA sensor power, and four I/O modules
Note: The maximum number of relay outputs that can be turned on simultaneously is 33 points (AC power type CPU module)
including relay outputs on the CPU module.
FC5A MICROSMART USER’S MANUAL2-3
2: MODULE SPECIFICATIONS
Power Supply (DC Power Type)
CPU ModuleFC5A-C10R2CFC5A-C16R2CFC5A-C24R2C
Allowable Voltage RangeDC power type: 20.4 to 28.8V DC
Maximum Input Current160 mA (24V DC)190 mA (24V DC)360 mA (24V DC)
Maximum Power Consumption
Allowable Momentary Power
Interruption
Dielectric Strength
Insulation Resistance
Noise Resistance
Inrush Current35A maximum35A maximum40A maximum
Grounding WireUL1007 AWG16
Power Supply WireUL1015 AWG22, UL1007 AWG18
Effect of Improper Power
Supply Connection
3.9W (24V DC)
(Note 1)
10 ms (at the rated power voltage)
Between power and terminals: 1,500V AC, 1 minute
Between I/O and terminals: 1,500V AC, 1 minute
Between power and terminals: 10 MΩ minimum (500V DC megger)
Between I/O and terminals: 10 MΩ minimum (500V DC megger)
DC power terminals:1.0 kV, 50 ns to 1 µs
I/O terminals (coupling clamp):1.5 kV, 50 ns to 1 µs
Reverse polarity:No operation, no damage
Improper voltage or frequency:Permanent damage may be caused
Improper lead connection:Permanent damage may be caused
4.6W (24V DC)
(Note 1)
8.7W (24V DC)
(Note 2)
Note 1: Power consumption by the CPU module
Note 2: Power consumption by the CPU module and four I/O modules
Note: The maximum number of relay outputs that can be turned on simultaneously is 44 points (DC power type CPU module)
including relay outputs on the CPU module.
Function Specifications (All-in-One Type CPU Module)
CPU Module Specifications
CPU Module
Program Capacity
Expandable I/O Modules——4 modules
I/O Points
User Program StorageEEPROM (10,000 rewriting life)
RAM Backup
Control SystemStored program system
Instruction Words
Processing
Time
Internal Relay2048
Shift Register128
Input6914
Output4710
Backup DurationApprox. 30 days (typical) at 25°C after backup battery fully charged
Backup DataInternal relay, shift register, counter, data register
BatteryLithium secondary battery
Charging TimeApprox. 15 hours for charging from 0% to 90% of full charge
Battery Life5 years in cycles of 9-hour charging and 15-hour discharging
ReplaceabilityImpossible to replace batter y
Basic instruction1.16 ms (1000 steps) See page A-1.
END processing
FC5A-C10R2
FC5A-C10R2C
13,800 bytes
(2,300 steps)
35 basic
76 advanced
0.64 ms (not including expansion I/O service, clock function processing, data link
processing, and interrupt processing) See page A-4.
Input FilterWithout filter, 3 to 15 ms (selectable in increments of 1 ms)
Catch Input
Interrupt Input
Self-diagnostic Function
Start/Stop Method
High-speed Counter
Analog Potentiometer
Sensor Power Supply
(AC power type only)
Communication Port
Cartridge Connector1 point for connecting a memory cartridge (32KB or 64KB) or a clock cartridge
FC5A-C10R2
FC5A-C10R2C
Four inputs (I2 through I5) can be designated as catch inputs or interrupt inputs
Minimum turn on pulse width: 40 µs maximum
Minimum turn off pulse width: 150 µs maximum
Power failure, watchdog timer, data link connection, user program EEPROM sum
check, timer/counter preset value sum check, user program RAM sum check, keep
data, user program syntax, user program writing, CPU module, clock IC, I/O bus initialize, user program execution
Turning power on and off
Start/stop command in WindLDR
Turning start control special internal relay M8000 on and of f
Turning designated stop or reset input off and on
Total 4 points
Single/two-phase selectable: 50 kHz (1 point)
Single-phase: 5 kHz (3 points)
Counting range:0 to 65535 (16 bits)
Operation mode:Rotary encoder mode and adding counter mode
1 point1 point2 points
Data range:0 to 255
Output voltage/current:24V DC (+10% to –15%), 250 mA
Overload detection:Not available
Isolation:Isolated from the internal circuit
Quantity of Stored ProgramsOne user program can be stored on one memor y car tridge.
Program Execution Priority
The maximum program capacity depends on the CPU module.
When using the 32 KB memory cartridge on the 24-I/O type CPU module, the maximum program capacity is limited to 30,000 bytes.
When a memory cartridge is installed, the user program on the memory cartridge is
executed.
User programs can be downloaded from the memor y car tridge to the CPU module.
Clock Cartridge (Option)
Accuracy±30 sec/month (typical) at 25°C
Backup DurationApprox. 30 days (typical) at 25°C after backup battery fully charged
BatteryLithium secondary battery
Charging TimeApprox. 10 hours for charging from 0% to 90% of full charge
Battery LifeApprox. 100 recharge cycles after discharging down to 10% of full charge
ReplaceabilityImpossible to replace battery
2-6FC5A MICROSMART USER’S MANUAL
Loading...
+ 613 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.