IDEC FC4A-C24R Application Information

Application Note:
Etnernet Pass Through Configuration
System Setup
Before setting up your HG3/4Fs and PLCs, you need to decide which IP addresses
you will assign
configuration shown here:
to the HG3/4Fs. This document shows how to set up the system
HG3F
Network setting
IP address: 192.168.104.35 Subnet Mask: 255.255.255.0 Default Gateway: 192.168.104.254
Ethernet
PC
Network setting
WindO/I NV2 WindLDR
For more information please call 800-262-IDEC or email support@idec.com. 1
IP address: 192.168.104.100 Subnet Mask: 255.255.255.0 Default Gateway: 192.168.104.254
How to set up WindO/I NV2
(1) Confirm that you are using the latest version of WindO/I NV2. Open the
About WindO/I NV2 dialog box by selecting About from the Help menu. If the Version Number is 3.01 or later, you can use the Ethernet pass through function.
2 For more information please call 800-262-IDEC or email support@idec.com.
(2) Open the Project Settings dialog box and make sure all settings are properly
configured. Select the Communication Interface tab and left-click on Ethernet (as shown).
You will see the network settings of the HG interface. Verify that the network setting for the HG is correct.
For more information please call 800-262-IDEC or email support@idec.com. 3
Select the Host I/F Driver tab in the same dialog box and verify that the Enable Pass Through option (shown) is checked.
4 For more information please call 800-262-IDEC or email support@idec.com.
Download the project to the HG3F.
For more information please call 800-262-IDEC or email support@idec.com. 5
How to setup WindLDR
(1) Open the Communication Settings dialog box by selecting Communication
Settings… from the Configure menu. Select Ethernet on the left (as shown) and then select the button for Raw TCP/IP connection (For HG3F/4F Ethernet Pass-through).
Check the box to Enable TCP/IP packets settings. Set 1 for The maximum data size and 100 for Time delay between packets. Click OK to close the dialog box.
Now you can monitor, upload and download the program to your HG3F/4F touchscreen.
6 For more information please call 800-262-IDEC or email support@idec.com.
(2) When you initialize monitoring, uploading or downloading a program,
WindLDR will ask for the IP address. Select the IP address that you have assigned to the HG and click the OK button.
For more information please call 800-262-IDEC or email support@idec.com. 7