IDEAL INDUSTRIES S28, C32, C24, C28, S24 User Manual

users guide
back
mini
Your Ideal users guide
C24/C28/C32 S24/S28
When replacing any part of this appliance, use only spare parts that you can be assured conform to safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers
Mini
MiniC24
back
Mini C24 G.C. appliance No. 47 ---348 ---18 Mini C28 G.C. appliance No. 47 ---348 ---19 Mini C32 G.C. appliance No. 47 ---348 ---25A Mini S24 G.C. appliance No. 41 ---392 ---98 Mini S28 G.C. appliance No. 41 ---392 ---99
Destination countries: GB, IE
INTRODUCTION
BOILER CONTROLS
Mini C28 Mini C32
Mini are wall mounted, room sealed, non condensing boilers
featuring full sequence automatic spark ignition and fan assisted combustion.
Mini C24, Mini C28 and Mini C32 are low water content
combination gas boilers.
Mini S24 and Mini S28 are low water content system gas boilers.
SAFETY
Current Gas Safety (Installation & Use) Regulations or rules in force
In your own interest, and that of safety, it is the law that this boiler must be installed by CORGI registered installer or in IE a competent person, in accordance with the above regulations.
It is essential that the instructions in this booklet are strictly followed, for safe and economical operation of the boiler.
A Appliance On lamp
B Domestic hot water temperature control
C Main switch and radiator temperature control
D Boiler reset button
E Lock---out signal lamp
F Programmer (optional)
G System pressure and temperature gauge
B C D E F GA
TO LIGHT THE BOILER
ELECTRICITY SUPPLY
The appliance must be efficiently earthed.
Supply 230 V 50 Hz. The fusing should be 3 A.
Connection must be made in a way that allows complete isolation of the electrical supply, such as a double pole switch, having a 3 mm (1/8”) contact separation in both poles, or a plug and socket serving only the boiler and system controls. The means of isolation must be accessible to the user after installation.
IMPORTANT NOTES
F This appliance must not be operated without the casing
correctly fitted and forming an adequate seal.
F If the boiler is installed in a compartment then the
compartment MUST NOT be used for storage purposes.
F Under no circumstances should any of the sealed
components on this appliance be used incorrectly or tampered with.
F If it is known or suspected that a fault exist on the boiler
then it MUST NOT BE USED until the fault has been corrected by a CORGI registered installer or in IE a competent person.
MINIMUM CLEARANCES
Clearances of 200 mm (7 7/8“) above and below, 25 mm (1“) at left, 50 mm (2“) at right and 450 mm (17 3/4“) at the front of the boiler case must be allowed for servicing. After installation the following clearances are allowable during use, providing the encasing parts are removeable for servicing: The bottom clearance can be reduced to 20mm (3/4”). The front clearance can be reduced to 50mm (2”).
All CORGI registered installers carry a CORGI ID card, and have a registration number. Both should be
recorded in your Benchmark Log Book. You can check your installer by calling CORGI direct on 01563 72300
Caradon Ideal Limited is a member of the Benchmark initiative and fully supports the aims of the programme. Benchmark has been introduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency.
THE LOG BOOK SHOULD BE COMPLETED AFTER EACH SERVICE AND KEPT WITH THESE INSTRUCTIONS
1 Check that the valves located in the lower part of the boiler
are open.
2 Switch the the electricity supply on.
The appliance On lamp A will flash every 4 seconds (stand--- by condition).
For combination models Mini C24, Mini C28 and Mini C32
3 If the boiler is to be used for CH and DHW position the
main switch as in the following illustration. The appliance On lamp A will flash every 2 seconds (operating boiler).
CA
For system models Mini S24 and Mini S28
4 To operate the boiler position the main switch as in the
following illustration. The appliance On lamp A will flash every 2 seconds (operating boiler).
CA
Mini S24 Mini S28
CONTROL OF CH TEMPERATURE
back
The output temperature of CH water is adjustable from a minimum of about 38°C to a maximum of about 85°C by turning the knob C.
Approx CH flow temperatures for the boiler thermostat settings:
In these cases, however, it is advisable to install a small water treatment device or softener. With such a device you should avoid periodic descaling.
Consequently, the DHW heat exchanger will keep its performance consistent for a longer period of time with resulting gas savings.
TO SHUT DOWN THE BOILER
Minimum (38 ° C)
C
Maximum (85 ° C)
CONTROL OF DHW TEMPERATURE (Mini C24, Mini C28 and Mini C32)
The temperature of the DHW leaving the boiler can be varied from a minimum of about 35°C to a maximum of about 55°C (within the power limits of the appliance) by turning the temperature control knob B.
Minimum (35 ° C)
B
Maximum (55 ° C)
For short periods
To turn the boiler off set the function selector C to the O position. The appliance On lamp A will flash every 4 seconds.
For long periods
When you do not expect to use the boiler for a long period:
1 Switch the the electricity supply off.
2 Shut off the gas supply cock and the valves for the water
circuits fitted under the boiler.
3 If necessary, empty the water circuits.
FROST PROTECTION
Mini C24, Mini C28 and Mini C32 appliances are provided
with a built in anti--- freeze system that operates the boiler when the temperature is below 4 ° C Therefore, when the boiler is not lit and used in cold weather, with consequent risk of freezing do not isolate the boiler
from the electricity supply or close the gas inlet cock.
ESCAPE OF GAS
Should a gas leak or fault be suspected contact your local gas supplier without delay.
Do not search for gas leaks with a naked flame.
CLEANING
Adjustment of the DHW temperature is completely separate from that of the CH circuit.
The adjustment system integrated within the boiler automatically controls the flow of gas to the burner in order to keep the temperature of DHW delivered constant, between the limits of maximum and minimum output.
Where the demand is at a low level or with the temperature set to the minimum, it is normal to see a cycle of lighting and extinguishing of the burner when running.
Adjustment
It is advisable to adjust the DHW temperature to a level commensurate with the demand, minimising the need to mix with cold water. In this way, the automatic control facilities will be fully exploited.
Moreover, where the amount of limescale present in the water may be particularly great, not exceeding the position as shown in the following illustration (about 50 ° C) minimises annoying incidences of scale deposits and clogging.
B
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains use a damp cloth and mild detergent.
Do not use abrasive cleaning materials.
MAINTENANCE
The appliance should be serviced at least once a year by a CORGI registered installer.
FAULTS
No heating or hot water
Check that gas and electricity are available at the boiler and that all switches are on.
Check that the system water water pressure gauge G reads at least 0,5 bar.
Check the lock--- out signal lamp E. If it is illuminated press the boiler reset button D to restart the ignition sequence.
Hot water but no heating
Check that the programmer and room thermostat (if fitted) are both calling for heat.
Heating but no hot water
Check that cold water flows out of the taps at a minimum rate of 3.5 litres per minute (or 1 pint in 10 seconds or less). If not, look for stop valves not fully open.
If these simple checks fail to solve the problem, or the problem recurs, consult your service engineer.
Points for Boiler User
back
Note. In line with our current warranty policy we would ask that you check through the following guide to identify any problems external to the boiler prior to requesting a service engineers visit. Should the problem be found to be other than with the appliance we reserve the right to levy a charge for the visit, or for any pre-arranged visit where access is not gained by the engineer.
Troubleshooting – Typical Non Product Faults
Problem Solution
Is there power to the boiler i.e. is the left hand side green LED (A) alight and flashing every 4 seconds. If not this is not a boiler fault – contact the installer
Check pressure gauge on boiler shows a minimum of 1 bar
Boiler is not working for central heating or hot water
Boiler goes through ignition sequence but will not fire for either central heating or hot water and then goes to ignition lockout
If not re-pressurise via the filling loop to 1 bar (if unsure contact your installer), turn off the tap on the filling loop and press the reset button (D) to reset the boiler. If unable to do so or if the pressure continues to drop after filling then contact your installer
Is the lockout signal lamp (E) alight – Press boiler reset button (D) – If boiler still does not fire contact the installer
Check gas supply (try another gas appliance cooker/fire etc) If no gas supply then this is not a boiler fault – Contact the gas supplier
Fan & pump run continuously but there is no attempt at ignition
Mini C Only
Operating for hot water but will not operate for central heating
The nature of all combination boilers is to heat up water directly from the incoming mains water supply directly through the boiler to supply domestic hot water at the stated flow rates, (as shown in the boiler installation instructions), to achieve a 35°C temperature rise. As the ambient temperature of the cold main varies during the summer and winter months it is likely in the colder winter months that the flow rate will need to be reduced at the outlet taps to achieve the same temperatures achieved in the warmer summer months. This is not a fault with the
appliance but is relevant to the varying temperature of the incoming cold mains water supply.
Mini S Only
Operating for hot water but will not operate for central heating
Operating for central heating but will not operate for hot water
Check that the air pressure switch test caps, on top of the boiler, are fitted correctly.
Check that integral programmer is set to an ‘on’ period and the function
switch is set to ‘auto’ – If it still does not operate contact your installer
If fitted with an external programmer check that the central heating channel
is set at an ‘on’ period – If it still does not operate contact your installer.
Check the room thermostat is set at the required temperature – Test the
room thermostat by turning fully up – If this does not respond contact your installer
Check the radiator temperature control (C) is set at the winter setting for
central heating.
If fitted with an external programmer check that the central heating channel
is set at an ‘on’ period – If it still does not operate contact your installer.
Check the room thermostat is set at the required temperature – Test the
room thermostat by turning fully up – If this does not respond contact your installer
If fitted with an external programmer check that the domestic hot water
channel is set at an ‘on’ period – If it still does not operate contact your installer.
Check the cylinder thermostat is set at the required temperature – Test the
cylinder thermostat by turning fully up – If this does not respond contact your installer
Ideal Consumer Helpline
Tel: 01482 498660
www.idealboilers.com
Caradon Ideal Limited pursues a policy of continuing improvement in the design and performance of its products. The right is therefore reserved to vary specification without notice.
Ideal Boilers, P.O. Box 103, National Ave, Kingston Upon Hull, HU5 4JN. Tel. 01482 492251 Fax. 01482 448858. Registration No. London 322 137.
Loading...