IDEAL Electrical Ideal 61-517 Manual

IDEAL® Test and Measurement
61-517 GFCI
Receptacle/VoltageTester
Operation and Safety Manual
Instrucciones en español adentro / Instructions en français à l’intérieur
Notes
2
Introduction .............................................. 3
Contacting IDEAL INDUSTRIES, INC ................. 3
Safety Information ...................................... 4
Warnings ...............................................................5-6
Cautions ................................................................... 6
Symbols ................................................................... 7
Operation............................................. 8-15
Identification and description of operating
controls and functions ..........................................8-9
Operating Features ................................................. 10
Meter Operation ...............................................11-12
Voltage and Polarity ........................................ 11
Testing a GFCI .................................................12
Polarity Indications Table ....................................... 13
Functions Operation Table ......................................14
Functions Indication Table .....................................14
Electrical Specifications ......................................... 15
Environmental Specifications ........................15
Mechanical .............................................16
EMC / EMI ...............................................16
FCC ................................................16
Safety ................................................16
Maintenance and Service ............................17
Disposal and Warranty ................................18
3
Introduction
The IDEAL 61-517 GFCI Receptacle Tester is a 120V AC plug in outlet tester that indicates proper polarity or mis-wired outlets via Green and Red LEDs and line voltage via a LCD. It also tests for GFCI functioning.
Arc Flash and Shock Hazard, Proper PPE Required. Follow all safety procedures, wear proper PPE in accordance to NFPA 70E. Read and fully understand the instruction manual prior to using this product. Failure to comply can result in serious injury or death.
4
Safety Information
Warning - Identifies conditions and actions that could result in possible death or serious injury if the hazard is realized.
Caution - Identifies conditions and actions that could result in meter damage, equipment under test damage or data loss if the hazard is realized.
Arc Flash and Shock Hazard, Proper PPE Required. Follow all safety procedures, wear proper PPE in accordance to NFPA 70E and follow the guidelines below and the instructions in this manual when operating the meter. Failure to comply can result in serious injury or death.
Choking Hazard, Small Parts. Keep Away from Children.
• Only experienced or technically competent consumers should
• Use the Meter only as specified in this manual or protection
• Before using or connecting the Meter, visually inspect it
• This Meter is intended for use by qualified electricians.
• Do not use without the batteries correctly in place and the
• Do not use Meter if it operates incorrectly as protection may
• When servicing the Meter, use only specified replacement
WARNING
Sharp Objects Hazard, This is not a toy. It is not for use or play by children. Keep Away from Children. Failure to do so can result in serious injury.
use this equipment. When in doubt, call an experienced electrician to make any and all necessary repairs or installations. At all times, perform any necessary work on a de-energized circuit that has had its circuit breaker turned off and has been locked out.
provided by the Meter can be compromised.
to ensure the cases are not cracked and the back case is securely in place. Do not use if the Meter appears damaged.
Follow NFPA 70E Standards for Electrical Safety in the Workplace when using this Meter.
battery door closed and secured.
be compromised. When in doubt, have the Meter serviced.
parts.
5
WARNING
Arc Flash and Shock Hazard, Proper PPE Required. Follow all safety procedures, wear proper PPE in accordance to NFPA 70E and follow the guidelines below and the instructions in this manual when operating the meter. Failure to comply can result in serious injury or death.
• Have the Meter serviced only by qualified service personnel.
• Do not use the Meter around explosive gas, dust, or vapor, or during electrical storms, or in wet environments.
• Do not apply more than the rated voltage, as marked on the Meter, between the terminals or between any terminal and earth ground.
• To avoid false readings that can lead to electrical shock and injury, replace the batteries as soon as the low battery indicator ( ) appears.
• Voltages exceeding 30VAC or 60VDC pose a shock hazard so use caution.
• Do not work alone so that assistance can be rendered in an emergency.
• Use extreme caution when working around bare conductors. Contact with the conductor could result in electric shock.
• Adhere to local and national safety codes. Individual protective equipment must be used to prevent shock and arc blast injury where hazardous live conductors are exposed.
• Never operate the Meter with the back cover removed or the case open.
• Cancer and Reproductive Harm
Meter damage, equipment under test damage or data loss can occur if the following guidelines are not adhered to.
• Clean the case and accessories with a damp cloth and mild detergents only. Do not use abrasives or solvents. Make sure the meter is completely dry before use.
6
CAUTION
Symbols & Descriptions
SYMBOL DESCRIPTION
Arc Flash and Shock Hazard
Shock Hazard
Warning or Caution
Choking Hazard
AC (Alternating Current)
Low Battery Indicator
Earth Ground
IEC Measurement Category II
CAT II
CAT II has protection against transients in fixed and non-fixed powered devices including appliances, lighting, and 120V or 240V equipment inside a building.
Voltage AC
VAC
LCD Liquid Crystal Display
Double Insulation
Do not dispose of this product as unsorted municipal waste. It must be properly disposed of in accordance with local regulations.
Conforms to applicable North American Safety Standards
7
Operation Identification and Description of
Operating Controls and Functions for the 61-517 GFCI Receptacle/ Voltage Tester:
1. On Off Button
2. GFCI Test Active LED
3. GFCI Test Button
4. Polarity Legend
5. AC Voltage LCD
6. Red-Green Polarity Indicator LEDs
7. Hot-Neutral-Ground Prongs
8
6
5
4
1
3
6
2
7
9
Operating Features
High Voltage Warning (HI-V)
The meter indicates a when measuring ~120V AC
Backlight
Backlight is always on when
meter is functioning.
10
Meter Operation
Voltage and Polarity
First, turn the meter on by pressing the ON/OFF Button and then insert into an outlet. If the batteries are good, the 61-517 will beep continuously to indicate live voltage, display the correct voltage, and indicate 3 bright green LEDS on the top and the bottom IF the HOT NEUTRAL and GROUND polarity of the outlet is correct. After removing the 61-517 from an outlet it will continue to display the polarity LED’s and measured voltage value for 5 seconds and shut off after 3 minutes of inactivity. This gives the user time to unplug from hard to reach or limited access outlets such as those behind furniture and still have a clear indication of the outlets condition.
If any other polarity condition is encountered other than correct H-N-G, one or more red lights will illuminate. Refer to the legend to identify the incorrect wiring condition.
See table on page 13 for all conditions the 61-517 can detect.
NOTE: The 61-517 will automatically turn itself on when inserted into a live outlet.
11
Testing a GFCI
Turn the unit on. Insert the unit into a live GFCI receptacle. Confirm that the 3 polarity indicators are all green. Press and hold the GFCI button for 6 seconds or until the GFCI trips. The light next to the GFCI button will turn RED until the GFCI trips. If the GFCI DOES NOT trip then a defective GFCI or a wiring issue is likely the cause.
NOTE: Modern GFCI’s will trip when self testing even without a ground connected. The 61-517 requires a low impedance ground to trip a GFCI. If the GFCI does not trip, pressing the GFCI repeatedly or for more than 6 seconds will not make it function and may cause damage to the 61-517.
12
Polarity Indications Table
Wire
Indication When Plugged Into Outlet (Values Maintained for 5
Condition
Correct Wiring
is indicated by 3 Green
LED’s
Open (No)
Neutral
Open (No) Hot NA 000V display on LCD
Open (No)
Ground
Hot and Ground
Reversed
Hot and Neutral
Reversed
Hot on Ground and Open (No)
Ground
One or more red
LED’s indicates
incorrect polarity
and a miswired
outlet.
Seconds After Unplugging from Outlet)
LED Indication Buzzer LCD display
Green (G)
Red (R)
Off (O)
1. 5s continuous beep
(if Voltage between 108
~ 132 VAC(120+/-
2. 5s intermittent beep if voltage <108VAC or
>132VAC
5s intermittent beep Err displayed on LCD
5s intermittent beep
5s intermittent beep Err displayed on LCD
5s intermittent beep
5s intermittent beep Err displayed on LCD
10%))
1. If Voltage is between 85 ~ 150VAC, LCD Displays
Live voltage
2. If voltage is <85VAC,
recycle displays “”85--LO-
-85””; if >150VAC, LCD
recycle displays “”150--
OL---150””
1. If Voltage is between 85 ~ 150VAC, LCD Displays
Live voltage
2. If voltage is <85VAC,
recycle displays “”85--LO-
-85””; if >150VAC, LCD
recycle displays “”150--
OL---150””
1. If Voltage is between 85 ~ 150VAC, LCD Displays
Live voltage
2. If voltage is <85VAC,
recycle displays “”85--LO-
-85””; if >150VAC, LCD
recycle displays “”150--
OL---150””
13
Functions Operation Table
Button Response
Silent Mode Audible
Default
Function
Turns ON OFF
RED LED OFF
Operation
1) Press the on button for longer than 2 sec. The unit will turn on and be in the silent mode.
2) Press the ON button for less than 1 sec. The unit will turn on and be in the audible mode.
3) Press the ON/OFF button for longer than 2 seconds when unit is on to turn off. Unit will automatically power off after 2 minutes.
4) Press the GFCI Button to test a GFCI.
Functions Indication Table
Function Description
LCD 300 count LCD. Displays VAC and LCD Backlight White backlight. High Voltage
Alarm
Over Range Indication
Low Battery Indication
APO No button presses for 3 minutes will be automat-
14
1) Effective setting: ACV.
2) In ACV/DCV, voltage measurement value: ACV/DCV 30V, LCD displays high voltage alarm is Simultaneously the buzzer emits a continuous tone.
LCD displays “OL” when over range is encountered.
The “ ” symbol appears in the LCD display with insufficient voltage. The low battery icon will flash for 5 seconds and the unit will power off. This ensures accurate readings.
ically cause the unit to shut down and enter the low-power state.
Function Range Resolution Accuracy
61-517 ±(a%+b)
AC Voltage (V) 150V 1V ±(3.0%+2)
GFI (mA) 6mA~9mA 102V,>6.0mA ±(2.0%+5)
Environmental Specifications
Operating Temperature:
Operating Altitude:
Storage Temperature:
Intended for indoor use.
32ºF to 104ºF (0ºC to 40ºC)
(<80%RH)
6500 ft (2000 m)
14ºF to 122ºF (-10ºC to 50ºC)
(<80%RH)
15
Mechanical Specifications
Dimensions: (L x W x H)
Weight: 0.25 LBS (0.1 KG) Display: LCD Display Count: 300 Power Source: 2 x 1.5V AAA Battery Life: 100 Hours Typical
3.25 in. x 2.6 in. x 1.25 in.
(85 mm x 65 mm x 33 mm)
EMC/EMI
CISPR 22 3rd Edition. Class B Limits. EN 55032 CISPR 32 CISPR 11 FCC 15. 107 with reference to Section 15.109 (g). ICES-003 EN 61326-2-2 Sec 6.4.2.101
USA (FCC)
47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
Safety
Complies with the following: IEC 61010-1, Edition 3 (2010-06) +AMD1 (2016-12) ANSI/UL/IEC EN 61010-1, Edition 3 (2016-04-29) CSA-C22.2 No. 61010-1-12 Edition 3 (2019-07-19) IEC 61010-031 Hand-held Probe Assemblies (2015-
05)+AMD1(2018-05) IEC 61010-2-033 (2019-06) UL1436 Overvoltage CAT II 150V. Any voltages exceeding the defined maximum voltage measurement categories described above are outside the normal use of the equip­ment and protection cannot be guaranteed. Pollution Degree Class 2
16
Maintenance and Service
Equipment Maintenance and Service
Meter Inspection
Do not use if meter appears damaged. Visually inspect the meter to ensure case is not cracked.
Prong Inspection
Inspect the insertion prongs and ground pin for any signs of corrosion and for straightness. If the blades are bent, do no use the unit. Return to IDEAL for service.
Battery Inspection/Replacement
Inspect the battery compartment monthly for any signs of degradation. Low battery voltages will cause inaccuracies in readings. Remove the batteries for storage or if the meter will not be used for longer than one month. Battery leakage will compromise the safety of the meter and cause irreparable damage to internal components.
Maintenance and Storage
Switch off and disconnect the meter completely before carrying out any maintenance. Clean the case with a damp cloth and mild detergent. Do not use abrasives or solvents. Keep away from liquids and ensure the meter is completely dry before use.
Service and Replacement Parts
This unit has no user-serviceable parts.
17
Disposal of Waste, Electrical & Electronic Equipment
In order to preserve, protect and improve the quality of the environment, protect human health and utilize natural resources prudently and rationally, the user should return unserviceable product to relevant facilities in accordance with statutory regulations. The crossed-out wheeled bin indicates the product needs to be disposed separately and not as municipal waste.
Do not dispose of this product as unsorted municipal waste. It must be properly disposed of in accordance with local regulations.
Disposal of Used Batteries/Accumulators
The user is legally obliged to return used batteries and accumulators. Disposing used batteries in household waste is prohibited! Batteries/accumulators containing hazardous substances are marked with the crossed-out wheeled bin. The symbol indicates that the product is forbidden to be disposed via domestic refuse. The chemical symbols for the respective hazardous substances are Cd = Cadmium, Hg = Mercury, Pb = Lead.
You can return used batteries/accumulators free of charge to any collecting point of your local authority, our stores, or where batteries/accumulators are sold. Consequently, you must comply with your legal obligations and contribute to environmental protection.
TWO YEAR LIMITED WARRANTY
This tester is warranted to the original purchaser against defects in material and workmanship for a period of two (2) years from date of purchase. With proof of purchase from an authorized IDEAL distributor, a defective tester will be repaired or replaced with the same product or a functionally equivalent product, at the option of IDEAL INDUSTRIES, INC. during the warranty period, subject to verification of the defect or malfunction. Warranty does not cover consumables such as fuses, batteries, and excludes defects caused by leakage from batteries, abuse, mishandling, dropping, ordinary wear and tear, misuse, neglect, unauthorized repair, improper use, alterations, accidents or any causes beyond IDEAL’s reasonable control. Consequential or incidental damages are not recoverable under this warranty. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This LIMITED WARRANTY gives you specific legal rights, which vary from state to state. This warranty constitutes the sole and exclusive remedy of the purchaser and the exclusive liability of IDEAL, and is in lieu of any and all other warranties, and expressly disclaims all other warranties, implied, or statutory as to merchantability, fitness for purpose sold, description, quality productiveness, or any other matter. No agent, distributor or other supplier has the authority to modify or amend this warranty or make other representations or warranties other than those contained in this warranty without express written authorization from IDEAL. For warranty service, call IDEAL customer service at 1-800-435-0705.
Made in China.
18
+ 39 hidden pages