Ideal VDT1300 User Manual

Product Manual
Qty
Description
1
Occ/Vac Sensor VDT1300
1
Sensor Cradle
2
Mounting Screw
1
Locking Screw
1
Instruction card
VDT1300 Ceiling Mount Dual Technology Occupancy/Vacancy Sensor
PRODUCT DESCRIPTION
The Audacy VDT1300 Occupancy/Vacancy Sensor is a line powered device specially designed to detect the presence or absence of occupants and wirelessly transmit this information to the Audacy Gateway. The information provided by the sensor is used to determine whether lights should remain on or turned off to reduce energy consumption. The product makes use of both passive infrared and ultrasonic sensing to achieve detection of minor motion.
KEY FEATURES
FCC and IC approved Flexible ceiling mounting options Small form factor with internal antenna RoHS compliant Factory configurable for custom applications
Audacy®, Smart Connector® and Smart Switch® are registered trademarks of IDEAL INDUSTRIES.
All other trademarks are the property of their respective owners.
PRODUCT CONTENTS
The following items are included inside the package:
NDxxxx-x 01/2016 Users Manual – VDT1300 Dual Technology Occupancy/Vacancy Sensor Page 1 www.idealindustries.com
Product Manual
Item
Description
Radio
915 MHz Internal Antenna
Regulatory Approvals
FCC Part 15 and Industry Canada FCC ID: 2AAMXVDT1300 IC: 11250A-VDT1300
Transmit Range
200 ft. indoors to an Audacy Gateway or Smart Connector in a typical commercial office building
Power
120VAC/277VAC
Operating Temperature
10°C to 32°C
Storage Temperature
-20°C to 50°C
Installation Environment
Indoor use only Mounting
2 bracket mounting holes (See mechanical drawing for dimensions)
Color
White
Dimensions
4.56” x 2.29” x 1.5” (115.82 x 58.17 x 38.1 mm)
Weight
2.9 oz
Warranty
1 year
VDT1300 Ceiling Mount Dual Technology Occupancy/Vacancy Sensor
SET-UP AND OPERATION
1. Ceiling-mount the VDT1300 cradle in the desired location with the optional mounting
screws(2). Cradle can be mounted directly to drywall or ceiling tiles.
2. Connect to AC mains power to sensor. BLACK:line, WHITE:neutral
3. Mount sensor to cradle.
4. Adjust to desired sensitivity and range on ultrasonic sensors via the potentiometer
screws available through the holes in the housing cover.
5. An optional screw can be used to lock the Smart Switch in the cradle.
SPECIFICATIONS
NDxxxx-x 01/2016 Users Manual – VDT1300 Dual Technology Occupancy/Vacancy Sensor Page 2 www.idealindustries.com
Product Manual
VDT1300 Ceiling Mount Dual Technology Occupancy/Vacancy Sensor
MECHANICAL (REAR VIEW)
MECHANICAL (TOP VIEW)
NDxxxx-x 01/2016 Users Manual – VDT1300 Dual Technology Occupancy/Vacancy Sensor Page 3 www.idealindustries.com