When replacing any part on this appliance use only spare parts that you can be
assured conform to the safety and performance specification that we require. Do not
use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
RS485, RS4100 & RS4125
May 2004 UIN 200 942 A02
Page 2
GENERAL
Table 1 - General Data
Boiler SizeRS485RS4100RS4125
Gas Supply Connectionin. BSPRc 1/2 (1/2)
Number of Boiler Sections445
Flow and Return ConnectionsRc 1 (1" BSP)
MAXIMUM Static Water Headm (ft.)30.5 (100) (3 bar)
MINIMUM Static Water Headm (ft.)1.0 (3.3)
Electrical Supply230 V ~ 50 Hz
External Fuse Rating(Power Consumption)3 A (5 W)
Water Contentlitre (gal.)9.8 (2.1)9.8 (2.1)12.2 (2.7)
*The value is used in the UK government's Standard Assessment Procedure (SAP) for energy rating of
dwellings. The test data from which it has been calculated have been certified by Advantica 0087
Note.
Gas consumption is calculated using a calorific value of
38.7 MJ/m
3
(1038 Btu/ft3) gross or 34.9 MJ/m3 (935 Btu/ft3)
nett. To obtain the gas consumption at a different calorific
value:-
a. For l/s - divide the gross heat input (kW) by the gross
C.V. of the gas (MJ/m3)
3
b. For ft
/h - divide the gross heat input (Btu/h) by the
gross C.V. of the gas (Btu/ft3)
c. The appliance is preset at the factory to the highest
nominal rating.
Key to symbols
GB = United KingdomIE = Ireland
(Countries of destination)
PMS = Maximum operating pressure of water
= A room sealed appliance designed for connection via
C
11
ducts to a horizontal terminal, which admits fresh air
to the burner and discharges the products of
combustion to the outside without a fan in the
combustion products circuit.
I
= An appliance designed for use on 2nd Family gas,
2H
Group H only.
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of this
appliance, care should be taken when handling edges of sheet steel components.
2
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 3
GENERAL
CONTENTS
Air Supply. ...................................................................... 6
Mexico Super RS485 ..................... 41 392 78
Mexico Super RS4100 ................... 41 392 79
Mexico Super RS4125 ................... 41 392 80
Natural Gas only
11
INTRODUCTION
Mexico Super RS above rangeis of floor standing, natural
draught, balanced flue gas boilers. They are rated to provide
central heating outputs of 24.9 kW (85,000 Btu/h) to 36.6 kW
(125,000 Btu/h).
The boiler has a cast iron heat exchanger and is supplied fully
assembled, complete with a white enamelled mild steel
casing.
A door at the top of the casing front panel hinges down,
revealing the boiler thermostat control (and programmer, if
fitted).
The boilers are suitable, as standard, for connection to openvented systems ONLY - an overheat thermostat kit is available
to allow the boiler to be used on sealed water systems.
The systems may be:
•pumped or gravity circulating indirect DHW only
•pumped central heating only
•pumped central heating combined with either a pumped or
gravity circulating indirect DHW circuit.
For GB, to comply with Building Regulations Part L1 (Part J in Scotland) the boiler should be fitted in accordance with the
manufacturer's instructions. Self-certification that the boiler has been installed to comply with Building Regulations can be
demonstrated by completing and signing the Benchmark log book.
BENCHMARK LOG BOOK DETAILS
BoilerPage
Make and model ....................................................... 3
Appliance serial no. on data badge ........................ 11
For all boilers:complete, sign & hand over to customer
For assistance see Technical Helpline on the back page
Page
NOTE TO THE INSTALLER:
LEAVE THESE
INSTRUCTIONS ADJACENT TO THE GAS METER.
ALSO COMPLETE THE BENCHMARK LOG BOOK
AND GIVE THIS TO THE CUSTOMER.
Mexico Super RS485 - RS4125 - Installation & Servicing
3
Page 4
GENERAL
This boiler will require 2 or more operatives to move it to its
installation site, remove it from its packaging base and during
movement into its installation location. Manoeuvring the boiler
may include the use of a sack truck and involve lifting, pushing
and pulling. The use of 1" pipe stubs of suitable lengths may
be temporarily screwed into the boiler tappings to act as
handles.
Caution should be exercised during these operations.
Operatives should be knowledgeable in handling techniques
when performing these tasks and the following precautions
should be considered:
•Split the boiler down to reduce the weight, e.g. remove
casing and hardware pack. Refer to Frame 9.
•Be physically capable.
•Use PPE as appropriate, e.g. gloves, safety footwear.
During all manoeuvres and handling actions, every attempt
should be made to ensure the following unless unavoidable
and/or the weight is light.
•Keep back straight.
•Avoid twisting at the waist.
•Avoid upper body/top heavy bending.
•Always grip with the palm of the hand.
•Use designated hand holds.
•Keep load as close to the body as possible.
•Always use assistance if required.
OPTIONAL EXTRA KITS
Programmer KitFits neatly within the casing. Separate
fitting instructions are included with this kit.
Overheatis available to allow the boiler to be used
Thermostat Kiton sealed water systems.
CURRENT GAS SAFETY (INSTALLATION AND USE)
REGULATIONS OR RULES IN FORCE.
The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a CORGI
Registered Installer or in IE a competent person. It must be
carried out in accordance with the relevant requirements of the:
•Gas Safety (Installation and Use) Regulations
•The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (northern Ireland).
•The Water Fittings Regulations or Water byelaws in
Scotland.
•The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a Competent
Person and installed in accordance with the current edition of
I.S.813 "Domestic Gas Installations", the current Building
Regulations and reference should be made to the current ETCI
rules for electrical installation.
Detailed recommendations are contained in the following British
Standard Codes of Practice:
BS. 6891Low pressure installation pipes.
BS. 6798Installation of gas fired hot water boilers of rated
input not exceeding 60 kW.
BS. 5449:1Forced circulation hot water systems (small bore
and microbore domestic central heating systems).
BS. 5546Installation of gas hot water supplies for
domestic purposes (2nd Family Gases).
BS. 5440: 1 Flues for gas appliances of rated input not
exceeding 60 kW.
BS. 5440: 2 Ventilation for gas appliances of rated input not
exceeding 60 kW.
BS 7593Treatment of water in Domestic Hot Water
Central Heating Systems.
Health and Safety Document No. 635.
The Electricity at Work Regulations, 1989.
Manufacturer’s notes must NOT be taken in any way as
overriding statutory obligations.
IMPORTANT. These appliances are certificated by the British
Standards Institution for safety and performance. It is
important, therefore, that no external control devices, e.g. flue
dampers, economisers etc., are directly connected to these
appliances unless covered by these Installation and Servicing
Instructions or otherwise recommended by Caradon IdealLimited in writing. If in doubt please enquire.
Any direct connection of a control device not approved by
Caradon Ideal Limited could invalidate the BSI Certification
and the normal appliance warranty. It could also infringe the
Gas Safety Regulations and the above regulations or other
statutory requirements.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation
panels, which can cause irritation to the skin. No asbestos,
mercury or CFCs are included in any part of the boiler.
LOCATION OF BOILER
The boiler must be installed on a flat and level floor, capable of
adequately supporting the weight of the boiler and any ancillary
equipment.
The boiler may be fitted on a combustible floor.
Insulation is not necessary, unless required by the local
authority.
The boiler must not be fitted outside.
Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should
be fitted in accordance with theInstitute of Gas Engineering
document IGE/UP/7:1998.
Bathrooms
The boiler may be installed in any room or internal space,
although particular attention is drawn to the requirements of
the current I.E.E. (BS 7671) Wiring Regulations and, in
Scotland, the electrical provisions of the building regulations
applicable in Scotland with respect to the installation of the
boiler in a room or internal space containing a bath or shower.
For Ireland reference should be made to the current ETCI rules
for electrical installations and I.S. 813: 2002.
Where a room-sealed appliance is installed in a room
containing a bath or shower then the appliance and any
electrical switch or appliance control utilising mains electricity
should be so situated that it cannot be touched by a person
using the bath or shower.
Where installation will be in an unusual location, special
procedures may be necessary and BS.6798 gives detailed
guidance on this aspect.
Compartment Installations
A compartment used to enclose the boiler MUST be designed
and constructed specially for this purpose.
An existing cupboard or compartment may be used, providing it
is modified for the purpose.
4
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 5
1
BOILER WATER CONNECTIONS
GENERAL
1. This appliance is NOT suitable for use in a
direct hot water system.
2. If the boiler is to be used on a sealed system,
an Overheat Thermostat Kit is available and
must be installed in accordance with the
instructions supplied with the kit.
DimensionAB
RS485 &299mm (11
RS4100
RS4125373 mm (14
3/4")533 (21")
5/8")600 (23 5/8")
2
FLOOR MOUNTING AND BOILER CLEARANCES
Flammable materials must not be placed in close proximity
to the appliance. Materials giving off flammable vapours
must not be stored in the same room as the appliance.
Floor mounting
1. The floor must be flat, level and of suitable load bearing
capacity.
2. The back of the boiler may be fitted up to the wall.
Boiler clearances
The minimum overall dimensions of the space in which the
boiler is to operate and to facilitate servicing are as follows:-
Boiler SizeWidthDepthHeight
85 &
RS4
RS4100
RS4125mm (in.) 550 (21
mm (in.)460 (18)533 (21)870 (34 1/4)
1/2) 600 (23 5/8) 870 (34 1/4)
Additional space will be required for installation, depending
upon site conditions.
IMPORTANT.
In order to facilitate gas connection, a clearance of at least 100
mm (4") must be available at either the left hand side or the right
hand side DURING installation. Refer to Frame 10.
In addition a MINIMUM clearance of 533 mm (21") MUST be
available at the front of the boiler, for servicing.
Terminal sizes
Boiler SizeDepthHeightWidth
RS485167392372
RS4100 & 4125182431372
Mexico Super RS485 - RS4125 - Installation & Servicing
DimensionA
RS485 & 410010 mm (
RS412555 mm (2
3/8")
1/4")
5
Page 6
GENERAL
In both cases details of essential features of cupboards/
compartment design, including airing cupboard installation, are
to conform to the following:
!!
BS. 6798.
!
!!
!!
! The position selected for installation MUST allow
!!
adequate space for servicing in front of the boiler
and for air circulation around the boiler.
Side clearance is only necessary for installation. The amount
of side clearance will depend upon the type of connection used.
! This position MUST also permit the provision of a
satisfactory flue termination.
! For the minimum clearances required for safety, and
subsequent service, see Frame 2.
GAS SUPPLY
The local gas supplier should be consulted, at the installation
planning stage, in order to establish the availability of an
adequate supply of gas. An existing service pipe must NOT be
used without prior consultation with the local gas supplier.
The boiler is to be installed only on a gas supply with a
governed meter.
A gas meter can only be connected by the local gas supplier or
by a local regional contractor.
Check that the appliance is suitable for the proposed gas
supply. An existing meter should be checked, preferably by the
gas supplier, to ensure that the meter is adequate to deal with
the rate of gas supply required. A minimum gas pressure of
20 mbar MUST be available at the boiler inlet, with the boiler
operating.
Installation pipes MUST be fitted in accordance with BS. 6891. In
IE refer to I.S. 813:2002. Pipework from the meter to the boiler
MUST be of an adequate size.
The complete installation MUST be tested for gas soundness
and purged as described in the above code.
FLUE INSTALLATION
Some pluming may occur at the termination, so terminal
positions where this could cause a nuisance should be
avoided.
The flue must be installed in accordance with the
recommendations of BS.5440-1: 2000. In IE refer to I.S.
813:2002.
The following notes are intended for general guidance:-
1. The boiler MUST be installed so that the terminal is exposed
to external air.
2. It is important that the position of the terminal allows the free
passage of air across it at all times.
3. Minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in Table 3.
4. Where the lowest part of the terminal is fitted less than 2m
(6' 6") above a balcony, above ground or above a flat roof to
which people have access then the terminal MUST be
protected by a purpose designed guard.
Terminals guards are available from boiler suppliers. In
case of difficulty seek advice from:
5. Where the terminal is fitted within 1000mm (39 1/2") of a
plastic or painted gutter or 500mm (19 1/2") of painted eaves
then an aluminium shield at least 1000mm (39 1/2") long
should be fitted to the underside of the gutter or painted
surface.
6. The air inlet/products outlet duct and the terminal of the
boiler MUST NOT be closer than 25mm (1") to combustible
material. Detailed recommendations on the protection of
combustible material are given in BS.5440-1: 2000.
In IE
refer to I.S. 813:2002.
IMPORTANT.
It is absolutely ESSENTIAL to ensure, in practice, that products
of combustion discharging from the terminal cannot re-enter the
building or any other adjacent building through ventilators,
windows, doors, other sources of natural air infiltration or forced
ventilation/air conditioning. If this should occur, the appliance
MUST be turned OFF, labelled 'unsafe' and corrective action
taken.
Table 3 - Balanced flue terminal position
Terminal Position
1a. Directly BELOW an opening,1500 mm 2000mm
air brick, opening window etc.(60")(79")
1b. Directly ABOVE an opening,300 mm600mm
air brick, opening window etc.(12")(24")
1c. HORIZONTALLY to an opening,600 mm600mm
air brick, opening window etc.(24")(24")
2. Below guttering, drain pipes or
soil pipes300 mm(12")
3. Below eaves300 mm(12")
4. Below balconies or a car port roof600 mm(24")
5. From vertical drain pipes or300mm ( 12")
soil pipes
6. From an internal or external corner or
to a boundary alongside the terminal600 mm(24")
7. Above adjacent ground, roof or
balcony level300 mm(12")
8. From a surface or a boundary
facing the terminal600 mm(24")
9. From a terminal facing a terminal600 mm(24")
10. From an opening in a car port
(e.g. door or window) into dwelling1200 mm(48")
11. Vertically from a terminal on the
same wall1500 mm(60")
12. Horizontally from a terminal300 mm(12")
on the wall
Minimum Spacing
RS4854100-4125
TERMINAL
The terminal assembly can be adapted to accommodate
various wall thicknesses. Refer to Frame 8.
AIR SUPPLY
Detailed recommendations for air supply are given in
BS.5440:2. In IE refer to I.S. 813:2002.
The following notes are for general guidance:
1. It is NOT necessary to have a purpose provided air vent in
the room or internal space in which the boiler is installed.
6
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 7
GENERAL
Mex 1920
RS 4100
RS 485
RS 4125
RS 4100 & RS 4125
Table 4 - High and low vent areas
BoilerAir from room/internalAir direct from
space cm
High level Low levelHigh levelLow level
RS485275 (43)275 (43)137 (21)137 (21)
RS4100438 (68)438 (68)219 (34)219 (34)
RS4125438 (68)438 (68)219 (34)219 (34)
2. If the boiler is to be installed in a cupboard or compartment,
permanent air vents are required (for cooling purposes) in
the cupboard/compartment, at both high and low levels. The
air vents must either communicate with room/internal space,
or be direct to outside air. The minimum effective areas of the
permanent air vents, required in the cupboard/compartment,
are specified in Table 4 and are related to maximum rated
heat input.
3. Both air vents MUST communicate with the same room or
internal space or MUST be on the same wall to outside air.
4. In siting the air vents care must be taken to avoid the freezing
of pipework.
2
(in.2)outside cm2 (in.2)
WATER CIRCULATION SYSTEM
The boiler must NOT be used for direct hot water supply. The
boiler is suitable for connection to pumped open vent central
heating systems, pumped central heating combined with
pumped or gravity indirect domestic hot water supply systems.
The boiler is NOT suitable for gravity heating systems. The
hydraulic resistance of the boilers at maximum output with 11ºC
(20ºF) temperature differentials are shown in the graph below.
The central heating system should be in accordance with
BS. 6798 and, in addition, for smallbore and microbore
systems, BS. 5449:1.
The domestic hot water system, if applicable, should be in
accordance with the relevant recommendations of BS. 5546.
Copper tubing to BS. 2871:1 is recommended for water carrying
pipework.
The hot water storage cylinder MUST be of the indirect type and
should preferably be manufactured of copper.
Water Flow Rate and Pressure Loss
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The hot water cylinder and ancillary pipework not forming part of
the useful heating surface should be lagged to prevent heat loss
and any possible freezing - particularly where pipes run through
roof spaces and ventilated underfloor spaces.
IMPORTANT
A minimum length of 2 metres of copper pipe MUST be fitted to
both flow and return connections from the boiler before
connection to any plastic piping.
The boiler must be vented. If venting cannot be done via a flow
connection a separate vent MUST be fitted by the installer.
Draining taps MUST be located in accessible positions, which
permit the draining of the whole system - including the boiler
and hot water storage vessel. They should be at least 1/2" BSP
nominal size and be in accordance with BS. 2879.
If required, a drain tap (not supplied) may be fitted to an unused
bottom (1" BSP) tapping on the front of the boiler.
BOILER CONTROL INTERLOCKS
Caradon Ideal Limited recommend that heating systems utilising
full thermostatic radiator valve control of temperature in individual
rooms should also be fitted with a room thermostat controlling the
temperature in a space served by radiators not fitted with such a
valve as stated in BS. 5449.
Central heating systems controls should be installed to ensure the
boiler is switched off when there is no demand for heating or hot water.
When thermostatic radiator valves are used, the space heating
temperature control over a living / dining area or hallway having a
heating requirement of at least 10% of the boiler heat output should
be achieved using a room thermostat, whilst other rooms are
individually controlled by thermostatic radiator valves. However, if
the system employs thermostatic radiator valves on all radiators,
or two port valves without end switches, then a bypass circuit must
be fitted with an automatic bypass valve to ensure a flow of water
should all valves be in the closed position.
ELECTRICAL SUPPLY
WARNING. The appliance MUST be efficiently earthed.
Wiring external to the appliance MUST be in accordance with the
current I.E.E. (BS 7671) Wiring Regulations and any local
regulations which apply. For Ireland reference should be made
to the current ETCI rules for electrical installations.
The boiler is supplied for 230 V ~ 50 Hz single phase. The fuse
rating is 3A.
Connection must be made in a way that allows complete
isolation of the electrical supply - such as a double pole switch,
having a 3mm (1/8") contact separation in both poles, or a plug
and socket serving only the boiler and system controls.
The means of isolation must be accessible to the user after
installation.
For bathroom installations the point of connection to the mains
must be situated outside the bathroom.
Dotted lines indicate
flow rates equivalent
to a temperature rise
of 11 oC (20 oF)
Mexico Super RS485 - RS4125 - Installation & Servicing
7
Page 8
GENERAL
Mex 1923
3
MINIMUM REQUIREMENTSFully pumped systems
1. Open vent and cold feed connections must be made to the
boiler flow and return tappings according to the options
shown in Frame 11.
2. The boiler is assumed to be the highest point of the
circulating system.
3. The circulating pump is positioned on the FLOW and the
vertical distance, between the pump and feed/ expansion
tank, must comply with the pump manufacturer's minimum
requirements, to avoid cavitation. Should these conditions
not apply, either lower the pump position or raise the feed/
expansion tank above the minimum requirements of
Caradon Ideal Limited.
4. The water velocity through the boiler flow / return pipes is
assumed to be below 1 m/s (3 ft./s), whilst the pump flow
rate is set to provide a temperature difference of 11
(200F) across the boiler flow / return, at design input.
5. This information is intended as a GUlDE ONLY and cannot
take into account instantaneous changes in head caused
by the operation of motorised valves, pumps etc.
Due allowance MUST be made if surging is liable to occur.
If in any doubt, contact Caradon Ideal Limited
o
C
4
GRAVITY HOT WATER & PUMPED CENTRAL HEATING
1. Separate flow and return connections are used for each
service. All possible configurations are given in Frame 11
and ONLY those shown should be used.
2. The schematic pipework graph is based on the
assumption that NO MORE than 8 elbows are used in the
gravity loop, including entry to the boiler.
3. For each extra elbow in excess of 8 (R) MUST be reduced
by 300 mm (12") or (H) increased by 100 mm (4")
4. Whatever value is selected for (R), the value of (H) MUST
be at least that indicated by the graph.
(R) = the horizontal distance between the
centre line of the cylinder and the boiler
tappings used - measured along the pipe run.
(H) = the vertical distance between the top of the boiler
and the base of the cylinder.
Notes.
a. Flow and return pipes should rise vertically on
leaving the boiler.
8
Mexico Super RS485 - RS4125 - Installation & Servicing
b. Horizontal pipes should be ABOVE ceiling level
and as short as possible.
c. A MINIMUM inclination of 25 mm per 3 m run (1"
per 10') is required to avoid air locks.
If the above conditions cannot be met, pumped
primaries should be used.
Page 9
5
SEALED SYSTEM REQUIREMENTS
ecl6060
GENERAL
Hoseunions
Temporary hose
(disconnect
afterfilling)
Non-return
valve
Automatic
airvent
Hosepipe
(disconnect
afterfilling)
Additional
stop valve
Double check valve
assembly
(note direction of flow)
Hoseconnector
Note.
The method of filling, refilling, topping up or flushing sealed
primary hot water circuits from the mains via a temporary hose
connection is only allowed if acceptable to the local water
authority.
1. General
a. The installation must comply with the requirements of
BS.6798 and BS.5449.
b. The installation should be designed to work with flow
temperatures of up to 82
o
C.
c. All components of the system, including the heat
exchanger of the indirect cylinder, must be suitable for a
working pressure of 3 bar (45 lb/in
2
) and temperature of
110oC. Care should be taken in making all connections
so that the risk of leakage is minimised.
2. Safety Valve
A spring loaded safety valve complying with the relevant
requirements of BS.6759 must be fitted in the flow pipe, as
close to the boiler as possible and with no intervening valve
or restriction. The valve should have the following features:
a. A non-adjustable pre-set lift pressure not exceeding 3
bar (45 lb./in
2
)
b. A manual testing device.
c. Provision for connection of a discharge pipe. The valve
or discharge pipe should be positioned so that the
discharge of water or steam cannot create a hazard to
the occupants of the premises or cause damage to
electrical components and wiring.
3. Pressure Gauge
A pressure gauge covering at least the range 0-4 bar (0-60
lb./in2) must be fitted to the system. The gauge should be
easily seen from the filling point and should preferably be
connected at the same point as the expansion vessel.
4. Expansion Vessel
a. A diaphragm type expansion vessel must be connected
at a point close to the inlet side of the pump, the
connecting pipe being not less than 15mm (
1/2"
nominal) size and not incorporating valves of any sort.
b. The vessel capacity must be adequate to accept the
expansion of the system water when heated to 110
(230oF)
c. The charge pressure must not be less than the static
water head above the vessel The pressure attained in
the system when heated to 110oC (230oF) should be at
least 0.35 bar (5lb/in2) less than the lift pressure of the
safety valve.
For guidance on vessel sizing refer to Table 5,Frame 6.
For further details refer to BS.5449. For IE refer to the
current edition of I.S. 813.
5. Cylinder
The cylinder must be either of the indirect coil type or a
direct cylinder fitted with an immersion calorifier which is
suitable for operating on a gauge pressure of 0.35 bar
2
) in excess of the safety valve setting. Single feed
(5lb./in
indirect cylinders are not suitable for sealed systems.
6. Make-up Water
Provision must be made for replacing water loss from the
system, either:
a. From a manually fitted make-up vessel with a readily
visible water level. The vessel should be mounted at
least 150mm (6") above the highest point of the system
and be connected through a non-return valve to the
system, fitted at least 300mm (12") below the make-up
vessel on the return side of the domestic hot water
cylinder or radiators.
b. Where access to a make-up vessel would be difficult by
pre-pressurisation of the system. Refer to 'Filling.'
o
C
Mexico Super RS485 - RS4125 - Installation & Servicing
9
Page 10
GENERAL
6
SEALED SYSTEM REQUIREMENTS - continued
7. Mains Connection
There must be no direct connection to the mains water
supply or to the water storage tank supplying domestic
water, even through a non-return valve, without the approval
of the local water authority.
8. Filling
The system may be filled by one of the following methods:
a. Through a cistern, used for no other purposes, via a
ball valve permanently connected directly to a service
pipe and / or a cold water distributing pipe.
The static head available from the cistern should be
adequate to provide the desired initial system design
pressure. The cold feed pipe from the cistern should
include a non-return valve and a stop valve with an
automatic air vent connected between them, the stop
valve being located between the system and the
automatic air vent. The stop valve may remain open
during normal operation of the system if automatic
water make-up is required.
b. Through a self-contained unit comprising a cistern,
pressure booster pump (if required) and, if
necessary, an automatic pressure reducing valve and
flow restrictor. The cistern should be supplied through
a temporary connection from a service pipe or cold
water distributing pipe.
This unit may remain permanently connected to the
heating system to provide limited automatic water
make-up. Where the temporary connection is
supplied from a service pipe or distributing pipe
which also supplies other draw-off points at a lower
level then a double check valve shall be installed
upstream of the draw-off point.
c. Through a temporary hose connection from a draw-off tap
supplied from a service pipe under mains pressure. Where
the mains pressure is excessive a pressure-reducing valve
shall be used to facilitate filling.
The following fittings shall form a permanent part of the
system and shall be fitted in the order stated:
A stop valve complying with the requirements of
BS. 1010, Part 2 (the hose from the draw-off tap shall be
connected to this fitting).
A test cock.
A double check valve of an approved type.
• Thoroughly flush out the whole of the system with cold
water, without the pump in position.
• With the pump fitted, fill and vent the system until the
pressure gauge registers 1.5 bar (21.5lb/in
Examine for leaks.
• Check the operation of the safety valve by manually
raising the water pressure until the valve lifts. This
should occur within ± 0.3 bar (± 4.3lb/in2.) of the pre-set
lift pressure.
• Release water from the system until the initial system
design pressure is reached.
• Light the boiler and heat the system to the maximum
working temperature. Examine for leaks.
• Turn off the boiler and drain the system while still hot.
• Refill and vent the system.
2
).
Sizing procedure for expansion vessels: The volume of the expansion vessel (litres) fitted to a sealed system shall not be
less than that given by Table 5, multiplied by a factor of 0.8 (for flow temperatures of less than 88 oC).
Table 5
Safety valve setting3.0 bar2.5 bar2.0 bar
Vessel charge and initial0.51.01.50.51.01.50.51.0
system pressurebarbarbarbarbarbarbarbar
Total water content of systemExpansion vessel volume
(litres)(litres)
252.12.73.92.33.35.92.85.0
504.25.47.84.76.711.85.610.0
756.38.211.77.010.017.78.415.0
1008.310.915.69.413.423.711.320.0
12510.413.619.511.716.729.614.125.0
15012.516.323.414.120.135.516.930.0
17514.619.127.316.423.441.419.735.0
20016.721.831.218.826.847.422.640.0
22518.724.535.121.130.153.325.445.0
25020.827.239.023.533.559.228.250.0
27522.930.042.925.836.865.131.055.0
30025.032.746.828.240.271.133.960.0
Multiplying factors for
other system volumes0.08330.1090.1560.0940.1340.2370.1130.20
10
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 11
INSTALLATION
Mex 1921
12
94
49
44
5
1
7
Tie rod
8
46
Data badge
28
18
30
24
6
69
68
2
4
3
47
Terminal
grille
7
BOILER ASSEMBLY - Exploded View
Mexico Super RS with casing removed - RS485 shown.
INSTALLATION
Detail of distributor
tube alignment
Index mark on
section boss
Mex 2215
Distributor tube
LEGEND
1. Heat exchanger assy.
2. Front section.
3. Middle section.
4. Section alignment rings & 'O' rings.
5.. Back section.
6. Thermostat pocket.
7. Distributor tube.
8. Combustion chamber.
Mexico Super RS485 - RS4125 - Installation & Servicing
12. Collector hood.
18. Front plate.
24. Gas control valve.
28. Gas cock.
30. PCB.
44. Air/flue duct assy.
46. Baseplate.
47. Heat shield.
49. Baffles.
68. Phial clip.
69. Split pin.
94. Cleanout cover.
11
Page 12
8
UNPACKING
INSTALLATION
PACK 'A' CONTENTS
The boiler is supplied fully assembled in Pack A,
together with either one of 3 packs: B, B1 or C.
Packs B, B1 or C contain the flue terminal appropriate
to the wall thickness.
Unpack and check the contents.
complete
boiler
assembly
INSTALLATION
! Complete boiler assembly
! The Hardware Pack (listed separately below)
! These Installation and Servicing/User
Instructions
FLUE PACKS
Packs B, B1 and C contents
! Flue terminal assembly
! Sachet of sealing mastic - 2 off
HARDWARE PACK
! 1" BSP plugs - 5 off
! 1" x 1/2" BSP reducing bush - 1 off
! Cable strap - 2 off
! Distributor tube
! 28mm Comp nut - 1 off
! 28mm olive - 1 off
! Thermostat pocket -1 off
! Thermostat clip - 1 off
! Thermostat retaining pin - 1 off
Table 6. This table shows the pack required for the given wall thicknesses
Wall thicknessFlue
Dimension (duct length) X shown abovepack
Boiler fitted flush with wallBoiler fitted in line with 600mm kitchen unitsrequired
RS485114 to 191 mm(4
RS4100229 to 305 mm(9" to 12")163 to 242 mm(6 1/2" to 9 1/2")B
318 to 394 mm(12 1/2" to 15 1/2")253 to 332 mm(10" to 13")B1
1/2" to 7 1/2")up to 125 mm(up to 5")C
RS4125114 to 191mm (4
229 to 305 mm (9" to 12")B
318 to 394 mm (12 1/2" to 15 1/2")B1
12
1/2" to 7 1/2")C
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 13
9
MEX 2195
7
6
11
8
8
MEX 2179
Baffles
BOILER CASING REMOVAL
To install the boiler the casing MUST be removed.
INSTALLATION
Control
panel
1. Undo the 2 screws and lift off the lower front panel.
2. Remove 2 screws and lift off the grille assembly.
3. Disconnect the in-line connector on the PCB lead.
4. Remove the Burner On neon cable from the back of
the control panel.
5. Remove the 2 screws securing the control panel and
disengage the panel by lowering and pulling it
forward.
5
1
2
MEX 1941
6. Remove the 2 screws securing the top panel to the
side.
7. Draw the top panel forward and lift it off the boiler.
8. Remove the 2 screws securing the LH side panel to
the flue collector and baseplate.
9. Pull the panel forward, lifting it clear of the locating
peg and remove.
Grille
Assy.
INSTALLATION
10
CHECKING THE FLUEWAY BAFFLES
1. Remove the flue cleanout cover.
2. RS485 & RS4100 only.
Ensure that the baffles are fully inserted in the flueways.
RS 485
RS 4100
10. Repeat steps 8 and 9 to remove the RH panel.
11. The boiler is held to the packaging base by 4 x M6
hex head screws. Remove the front screws, slacken
the rear screws and remove the boiler from the
packaging base.
Side view of boiler sections
showing the baffle arrangements
Mex 6042
Mexico Super RS485 - RS4125 - Installation & Servicing
13
& se
Page 14
11
PREPARING THE BOILER
Table 7 - Fully Pumped Systems
Connections - as viewed at frontThermostat Position
Back SectionFront Section
FlowReturnTop
LHLHLH
LHRHLH
RHRHRH
RHLHRH
INSTALLATION
Table 8 - Gravity Domestic Hot Water
and Pumped Central Heating
Connections - as viewed at frontThermostat Position
Back SectionFront Section
CHDHW
Flow ReturnFlowReturnTop
LHLHRHRHLH
LHRHRHLHLH
RHRHLHLHRH
RHLHLHRHRH
INSTALLATION
Note.
Before placing the boiler in the selected position any gas
and water connections at the rear of the boiler should be
prepared, due to the possible lack of access.
1. Screw the distributor tube (supplied with a 1" BSP x
28mm copper adaptor) into the selected heating return
tapping, using an appropriate jointing material.
IMPORTANT.
It is IMPERATIVE that the index mark on the distributor
tube bush is in alignment with the mark on the section
boss, as shown in Frame 7.
DO NOT disturb it when connecting subsequent
pipework.
Fully pumped systems using more than 1 pump,
serving separate zones, must have a common return
connection to the distributor tube.
2. Select the desired pumped flow tapping.
3. Screw the supplied boiler thermostat pocket into the
appropriate front section tapping, using an approved
jointing material. Refer to Tables 7 and 8.
4. Connect pipe fittings to the rear tappings and plug any
unused tappings.
Note. If using iron elbows fit a short straight connector into
the boiler tapping first, to clear the casing.
12
PREPARING THE WALL
1. Cut the appropriate hole in
the wall for insertion of the
terminal assembly.
Notes.
a. Make good the hole on
the INSIDE of the
building to the given
dimensions BEFORE
fitting the boiler, to
facilitate sealing
between the terminal
and the wall when the
boiler is in position.
b. The terminal MUST NOT
come into contact with a
combustible material
such as that used in nonstandard construction of
timber frame and
plasterboard etc.
2. Place the boiler in the selected position.
3. Make good the brickwork around the air duct.
BoilerDimension A
RS485533 mm (21")
RS4100533 mm (21")
RS4125600 mm (23
5/8")
14
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 15
13
FITTING THE FLUE ASSEMBLY
INSTALLATION
A. Air duct join
B. Flue duct join
Legend
1.Boiler air duct.
2.Boiler flue duct.
3.Terminal air duct.
4.Terminal flue duct.
1. Remove the 2 screws and separate the terminal grille,
terminal air duct and terminal flue duct.
2. From OUTSIDE of the building, pass the terminal air duct
through the wall opening and slide it into the extension
air duct, locating it as shown.
3. Push the duct fully in until the fixing brackets contact the
wall face.
4. Ensure that the duct is level and make good between the
wall and the duct from OUTSIDE of the building.
5. From OUTSIDE the building, seal the duct join (A) with
the mastic provided.
14
GAS CONNECTION
1. A MINIMUM working gas pressure of 20 mbar (8 in.w.g.)
MUST be available at the boiler inlet, with the boiler
operating.
2. Extend a gas supply pipe NOT LESS THAN 15mm (
OD to the boiler and connect to the gas cock situated at
the front LH side of the boiler.
3. Test the gas installation for soundness and purge in
accordance with BS.6891: 1988. Refer to Frame 28.
5.Terminal grille assembly.
6.Terminal grille.
7.Securing screws - 2 off.
8.Splitter plate.
1/2")
Flue terminal
shown in position
6. From OUTSIDE the building, pass the terminal flue duct
through the wall opening and slide
it into the boiler flue duct
pushing the flue duct fully
in, up to the locating
stops. Locate it as shown
.
7. From OUTSIDE of the
building, seal the duct join
(B) with the mastic
provided.
8. Fasten the terminal grille
to the duct assembly.
BoilerDimension A
RS485 &
RS4100473(18 5/8")
RS4125546(21 1/2")
INSTALLATION
Mexico Super RS485 - RS4125 - Installation & Servicing
15
Page 16
15
WATER CONNECTIONS
INSTALLATION
1. Connect the system flow and return pipework to the
boiler as appropriate. Refer to Frames 3 and 4 for
guidance on system design.
Note.
When the required output exceeds 14.4 kW (49 000 Btu/
h) then 28mm (1") pumped flow and return pipes should
be used, both to and from the boiler.
Gravity connections MUST be at least 28mm (1").
2. Ensure that all valves are open. Fill and vent the
system and check for water soundness.
Notes.
a. Isolating valves must be fitted as close to the pump
as possible.
b. The boiler is not suitable for use with a direct hot
water cylinder.
INSTALLATION
16
WATER TREATMENT
These boilers incorporate a cast iron heat exchanger.
IMPORTANT. The application of any other treatment to this product may render the guarantee of Caradon Ideal Limited INVALID.
Caradon Ideal Limited recommend Water Treatment in accordance with the Benchmark Guidance Notes on Water Treatment in
Central Heating Systems.
Caradon Ideal Limited recommend the use of Fernox, GE Betz Sentinel or Salamander water treatment products, which must be
used on accordance with the manufacturers instructions.
G E Betz Ltd, Sentinel Division, Foundry Lane, Widnes, Cheshire, WA8 8UD. Tel. +44 (0) 151 424 5351
or
Salamander Engineering Ltd, Unit 24, Reddicap Trading Estate, Sutton Coldfield, West Midlands B75 7BU. Tel. +44 (0) 121 378 0952
Notes.
1. It is most important that the correct concentration of the water treatment products is maintained in accordance with the
manufacturers' instructions.
2. If the boiler is installed in an existing system any unsuitable additives MUST be removed by thorough cleansing.
BS7593:1992 details the steps necessary to clean a domestic heating system.
3. In hard water areas, treatment to prevent limescale may be necessary - however the use of artificially softened water is NOT
permitted.
4. Under no circumstances should the boiler be fired before the system has been thoroughly flushed.
17
ELECTRICAL CONNECTIONS
WARNING.
The appliance MUST be efficiently earthed.
A mains supply of 230 V ~ 50 Hz is required.
The fuse rating should be 3A.
All external controls and wiring MUST be suitable for mains
voltage.
Wiring should be in 3-core PVC insulated cable NOT LESS
than 0.75 mm
Wiring external to the boiler MUST be in accordance with
current l.E.E. (BS7671) Wiring Regulations and local
regulations. For Ireland reference should be made to the
current ETCI rules for electrical installations.
2
(24 x 0.2 mm) to BS.6500, Table 16.
Connection must be made in a way that allows complete
isolation of the electrical supply - such as a double pole
switch, having a 3mm (1/8") contact separation in both
poles, or a plug and socket serving only the boiler and
system controls.
The means of isolation must be accessible to the user after
installation.
This connection should be readily accessible and be made
adjacent to the boiler (except in the case of bathroom
installations for domestic boilers where the point of
connection to the mains MUST be outside of the bathroom).
16
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 17
G
MEX2553
r
r
br
b
bk
bk
MAINSSUPPLY
y/g
b
br
br
y/g
y/g
b
bk
Ignition/Detectionelectrode
BurnerOnneon
w
w
Controlthermostat
Gasvalve
LHL
G
N
L
18
INTERNAL WIRING
Flow and pictorial wiring diagrams are shown in
Frames 19 and 20.
1. Remove the securing screw and lift off the
control box cover.
2. Route the electrical leads into the box and
wire into the terminal strip, as shown.
Notes.
INSTALLATION
a. Secure each lead with one of the cable
clamps.
b. The mains lead connection MUST be made
so that, should the lead slip from its
anchorage, the current conductors become
taut before the earthing conductor.
19
EXTERNAL CONTROLS
External wiring must be in accordance with the current I.E.E.
(BS 7671) Wiring Regulations. For Ireland reference should be
made to the current ETCI rules for electrical installations.
The wiring diagrams illustrated in Frames 21-23 cover the
systems most likely to be fitted to this appliance.
For wiring external controls to the Mexico Super 4 RS boiler
reference should be made to the system wiring diagrams
supplied by the relevant manufacturer, in conjunction with the
flow wiring diagram below and also Frame 18.
Difficulty in wiring should not arise, providing the following
directions are observed:
INSTALLATION
1. Controls that switch the system ON and OFF, e.g. a time
switch, MUST be wired, in series, in the live mains lead to
the boiler.
2. Controls that override an on/off control, e.g. a frost
thermostat, MUST be wired into the mains lead, in parallel,
with the control(s) to be overridden. Refer to Frame 25.
3. If a proprietary system is used, follow the instructions
supplied by the manufacturer.
Advice on required modifications to the wiring may be obtained
from the component manufacturers.
Note. If there are no external controls the circulating pump
MUST be wired into the control box.
Mexico Super RS485 - RS4125 - Installation & Servicing
Flow Wiring Diagram
From systems controls
Boiler
thermostat
Gas valve
PCB
MEX 1926
17
Page 18
20
PICTORIAL WIRING
INSTALLATION
r
MAINS SUPPLY
br
b
INSTALLATION
r
b
br y/g
bk
bk
Control thermostat
w
w
Neon
Control box
earth screw
Ignition/Detection electrode
b
bk
bk
br
w
w
b
br
bk
LEGEND
wwhite
rred
bkblack
brbrown
bblue
y/gyellow/green
21
MID POSITION VALVE
Pumped only
Notes.
1. Some earth wires are omitted for clarity.
Ensure proper earth continuity when
wiring.
2. Numbering of terminals on thermostats is
specific to the manufacturer indicated.
3. This is a fully controlled system - set the
boiler thermostat to maximum.
4. 'Switchmaster Midi' is similar in operation
but the wiring differs slightly; see
manufacturer's literature.
b
b
bk
w
y/g
w
br
Mex 2554
Room
Thermostat
Terminal
Mid Position
valve details
Cylinder
Thermostat
Terminal
MEX 6037
LEGEND
b blue
bk black
br brown
rred
or orange
wwhite
gygrey
y/g yellow/green
18
Terminal strip
suitably
Pump
MAINS
Boiler supply connector
enclosed
Typical programmer CH may
be selected independently
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 19
22
TWO SPRING CLOSED VALVES
Pumped only
Notes.
1. Some earth wires are omitted for clarity.
Ensure proper earth continuity when
wiring.
2. Numbering of terminals on thermostats is
specific to the manufacturer.
3. This is a fully controlled system - set the
boiler thermostat to maximum.
4. 'Switchmaster Autozone' has grey and
orange auxiliary switch leads but the
GREY (NOT the orange) wire must be
connected to the incoming live supply.
LEGEND
b blue
bk black
br brown
rred
w white
or orange
y/g yellow/green
gy grey
INSTALLATION
Pump
MAINS
Boiler supply connector
Terminal strip
suitably
enclosed
mex 6038
INSTALLATION
Typical programmer CH may
be selected independently
23
HONEYWELL 'C' PLAN
Gravity HW & Pumped CH
Notes.
1. Some earth wires are omitted for clarity.
Ensure proper earth continuity when
wiring
2. Numbering of terminals on thermostats
is specific to the manufacturer.
LEGEND
w white
rred
bk black
br brown
or orange
b blue
gy grey
y/g yellow/green
Pump
N
E
L
MAINS
Boiler supply connector
Terminal strip
suitably
enclosed
MEX 6039
Typical programmer CH may
be selected independently
Mexico Super RS485 - RS4125 - Installation & Servicing
19
Page 20
INSTALLATION
MEX 2196
5
25
FROST PROTECTION
Central heating systems fitted wholly inside the house do not
normally require frost protection as the house acts as a 'storage
heater' and can normally be left at least 24 hrs. without frost
damage. However, if parts of the pipework run outside the house or
if the boiler will be left off for more than a day or so then a frost 'stat
should be wired into the system.
This is usually done at the programmer, in which case the
programme selector switches are set to OFF and all other controls
MUST be left in the running position.
The frost 'stat should be sited in a cold place but where it can
sense heat from the system.
Wiring should be as shown, with minimal disturbance to other
wiring of the programmer.
INSTALLATION
Designation of the terminals will vary, but the programmer and
thermostat manufacturer's leaflets will give full details.
Diagram A shows a double pole frost thermostat, which should
suffice for all systems which do not use the OFF terminals of the
programmer.
26
FITTING THE CASING
1. Offer up the RH side panel, locating it with the peg in the
baseplate, and push the panel back.
2. Secure the panel to the baseplate and collector hood.
3. Repeat steps 1 and 2 to refit the LH side panel.
4. Place the top panel and push back.
5. Secure the top panel to the side panels.
IMPORTANT. Wiring within the boiler casing must be neatly secured
with the cable straps provided and MUST NOT be allowed to touch the
burner front plate, or the cleanout cover and the collector hood.
6. Reconnect the in-line connector to the PCB lead and the Burner
On neon cable to the control panel.
Thermostat phial
Diagram B shows a 'change-over' frost thermostat, which will
cover most systems which do use CH OFF. If, however, on
such a system the HW pipework is in an isolated part of the
house, a second frost thermostat may be used to protect it.
If in doubt, ask your installer for advice.
Phial retaining
clip
7. Replace the control box cover and refit the control panel using
Split pin
Thermostat pocket
27
COMMISSIONING AND TESTING
The Benchmark Log Book or equivalent self certification should be completed and signed to demonstrate compliance
with Building Regulations.
MEX 729
A.ELECTRICAL INSTALLATION
1. Checks to ensure electrical safety should be carried out
by a competent person.
2. ALWAYS carry out preliminary electrical system checks,
i.e. earth continuity, polarity, resistance to earth and
short circuit using a suitable test meter.
WARNING. Whilst effecting the required gas soundness test and purging air from the gas installation,
open all windows and doors, extinguish naked lights and DO NOT SMOKE.
20
the screws previously removed.
8. Insert the thermostat phial and phial retaining clip into the
thermostat pocket. Take care not to kink the thermostat capillary
as it is unwound and secure it with the split pin as shown.
9. Refit the grille assembly
B.GAS INSTALLATION
1. The whole of the gas installation, including the meter,
MUST be inspected and tested for soundness, and
purged in accordance with the recommendations of
BS. 6891. In IE refer to I.S.813:2002.
2. Purging air from the gas installation may be expedited by
loosening the union on the gas service cock on the boiler
and purging until gas is detected.
3. Retighten the union and check for gas soundness.
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 21
28
INITIAL LIGHTING
INSTALLATION
INSTALLATION
LEGEND
A. Gas control valve.
B. Burner pressure test point.
C. Main burner pressure adjuster.
D. Inlet pressure test point.
TO LIGHT THE BOILER
1. Check that all the drain cocks are closed and any valves in
the flow and return are open.
2. Check that the gas service cock (E) is OPEN and the boiler
mains on/off switch is OFF.
3. Slacken the screw in the burner pressure test point (B)
and connect a gas pressure gauge via a flexible tube.
4. Switch the electricity supply ON and check that all external
controls are calling for heat.
5. Set the boiler thermostat knob (G) to position 6. The pilot
solenoid valve should open and the intermittent spark
commence, continuing until the pilot is established. The
main burner will then cross-light smoothly. If this sequence
does not occur, refer to the Fault Finding section.
E. Gas service cock.
F.Sightglass.
G. Boiler thermostat knob.
H. Main burner 'On' neon.
J. Overheat thermostat reset button (optional).
6. Test for gas soundness around ALL boiler gas
components using leak detection fluid.
7. Operate the boiler for 10 minutes to stabilise the burner
temperature.
8. The boiler is preset at the factory to its nominal rating.
Refer to Table 2 (page 2). If adjustment is necessary
remove the sealing cap and turn the adjusting screw
clockwise to increase/anticlockwise to decrease the
pressure until the required burner pressure is achieved.
Refit the sealing cap.
9. Set the boiler mains on/off switch to OFF.
10. Remove the pressure gauge and tube. Retighten the
sealing screw in the pressure test point.
11. Turn ON and check for gas soundness at the pressure
test point.
12. Refit the lower front panel and secure with the 2 fixing
screws.
Mexico Super RS485 - RS4125 - Installation & Servicing
21
Page 22
28
GENERAL CHECKS
Make the following checks for correct operation:
INSTALLATION
1. Turn the boiler thermostat OFF and ON to check that the
main burner is extinguished and relit in response.
2. Check that the programmer, if fitted, and all other system
controls function correctly.
Operate each control separately and check that the main
burner or circulating pump (as the case may be)
responds.
3. Water circulation System
a. With the system HOT, examine all water connections
INSTALLATION
for soundness.
b. With the system still hot, turn off the gas, water and
electricity supplies to the boiler and drain down, in
order to complete the flushing process.
c. Refill and vent the system, clear all air locks and again
check for water soundness.
d. Balance the system.
4. Finally, set the controls to the user's requirements, refit the
lower front panel and close the controls door.
WARNING. The boiler must not be operated with the casing removed
Notes.
!!
! If an optional programmer kit is fitted refer to the
!!
separate Programmer Kit Installation Instructions and
Programmer Kit User's Instructions.
!!
! The temperatures quoted below are approximate and
!!
vary between installations.
ThermostatFlow Temperature
Knob Setting
260140
366150
471160
577170
682180
o
C
o
F
29
HANDING OVER
After completing the installation and commissioning of the system the
installer should hand over to the householder by the following actions:
1. Hand the User's Instructions to the householder and explain
his or her responsibilities under the current Gas Safety
(Installation and Use) Regulations or rules in force.
2. Draw attention to the lighting instruction label affixed to the
inside of the controls door.
3. Explain and demonstrate the lighting and shutting down
procedures.
4. The operation of the boiler and the use and adjustment of
ALL system controls should be fully explained to the
householder, to ensure the greatest possible fuel economy
consistent with household requirements of both heating and
hot water consumption.
Advise the User of the precautions necessary to prevent
damage to the system and to the building in the event of the
system remaining inoperative during frosty conditions.
6. Explain and demonstrate the function of time and
temperature controls, radiator valves etc., for the economic
use of the system.
7. If an optional Programmer Kit is fitted then draw attention to
the Programmer Kit User's Instructions and hand them to
the householder.
8. After installation, commissioning and customer hand-
over please complete the
and leave this with the customer. For IE, it is necessary
to complete a "Declaration of Conformity" to indicate
compliance to I.S. 813:2002.
9. Stress the importance of regular servicing by a CORGI
registered installer and that a comprehensive service
should be carried out AT LEAST ONCE A YEAR. In IE
servicing work must be carried out by a Competent Person.
appliance log book
5. Explain the function and the use of the boiler thermostat and
external controls.
22
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 23
SERVICING
MEX 1927
6
2
Control
panel
Grille
Assy.
30
SCHEDULE
To ensure the continued safe and efficient operation of the
appliance it is recommended that it is checked at regular
intervals and serviced as necessary. The frequency of
servicing will depend upon the installation condition and
usage but should be carried out at least annually .
It is the law that any service work must be carried out by a
CORGI registered installer. In IE servicing work must be
carried out by a Competent Person.
a. Light the boiler and carry out a pre-service check, noting
any operational faults.
b. Clean the main burner.
c. Clean the heat exchanger.
d. Clean the main injectors.
WARNING. The boiler must not be operated with the casing removed
31
BOILER CASING REMOVAL
e. Check that the flue terminal is unobstructed and that the
flue system, including the flue cleanout cover, is sealed
correctly.
f. If the appliance has been installed in a compartment,
check that the ventilation areas are clear.
The servicing procedures are covered more fully in Frames
31-35 and MUST be carried out in sequence.
WARNING. Always turn OFF the gas supply at the gas
service cock and switch OFF and DISCONNECT the electrical
supply to the appliance BEFORE SERVICING.
IMPORTANT. After completing the servicing or exchange of
components always test for gas soundness and carry out
functional checks as appropriate.
1. Remove the 2 screws and lift off the lower front panel.
2. Remove the 2 screws and lift off the grille assembly.
3. Disconnect the in-line connector on the PCB lead.
4. Remove the Burner On neon cable from the back of the
control panel.
Thermostat phial
Phial retaining
clip
Split pin
Thermostat pocket
MEX 729
SERVICING
3
5. Remove the thermostat phial from the
pocket as shown.
6. Remove the 2 screws securing the
control panel and pull down to release the
tabs from under the top panel.
7. If the boiler is not fitted under a work top,
access for flue cleaning will be improved
by removing the top panel.
MEX 2212
Mexico Super RS485 - RS4125 - Installation & Servicing
4
23
Page 24
SERVICING
MEX 2179
Baffles
32
BURNER AND CONTROLS ASSEMBLY REMOVAL
1. Remove the 2 screws, lift off
the front panel and remove
the grille assembly. Refer to
Frame 31.
2. Disconnect the electrical
leads from the gas valve.
3. Disconnect the ignition lead
from the PCB.
4. Undo the gas cock union.
Remove the 4 wing nuts and
withdraw the burner and
controls assembly, complete,
from the boiler.
5. Place on a convenient
working surface.
33
CLEANING THE BURNER ASSEMBLY
MEX 2213
Combustion
chamber
MEX 2183
Gas service
union nut
Wing nuts
1. Brush off any deposits that may have fallen onto the
burner head (ensuring that the flame ports are
unobstructed) and remove any debris that may have
collected.
Note. Brushes with metallic bristles MUST NOT be used.
2. Remove the main burner injector .Check, clean or
replace, as required.
3. Refit the injector, using an approved jointing compound.
4. Inspect the pilot burner, thermocouple and ignition
electrode; ensure they are clear and in good condition.
SERVICING
34
CLEANING THE FLUEWAYS
1. Remove the 2 wing nuts and lift off the cleanout cover.
2. Lift out the flue baffles, if fitted.
3. Remove all loose deposits from the heat exchanger,
especially from between the fins, using a suitable
brush. Remove all debris from the combustion chamber
base
4. Check that the flue outlet duct is unobstructed.
Check that:
a. The pilot burner is clean and unobstructed.
b. The ignition electrode is clean and undamaged.
c. The ignition lead is in good condition and securely
connected.
d. The spark gap is correct. Refer to Frame 44.
5. Clean or renew components as necessary.
5. Refit flue baffles. Refer to Frame 10.
35
Reassemble the boiler in the following order :
1. Refit the flue cleanout cover, renewing any damaged or
deteriorating sealing gasket.
2. Refit the casing top panel.
3. Reconnect the electrical wiring and refit the control panel,
ensuring that the thermostat phial and phial retaining clip
are correctly located in the thermostat pocket and secured
by the split pin. Refer to Frame 31.
24
REASSEMBLY
4. Check the sightglass in the front plate - clean or renew as
necessary.
5. Renew any damaged or deteriorating front plate gasket.
6. Refit the burner and controls assembly.
7. Reconnect the gas service cock.
8. Refit the grille assembly.
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 25
SERVICING
36
GAS PRESSURE ADJUSTMENT
1. Pilot Pressure
Pilot adjustment is factory set to maximum and
no adjustment is possible.
2. Main Burner Pressure
After servicing, reference should be made to Table 2,
which quotes details of the rated output with the
related burner pressure and heat input. Any required
adjustments should be made using the pressure
adjustment screw. Refer to Frame 27, 'Initial Lighting.
Refit the lower front panel
REPLACEMENT OF PARTS
37
GENERAL
When replacing any component:
1. Isolate the electricity supply.
2. Turn off the gas supply at the boiler.
3. Undo the 2 screws and remove the lower front panel grille assembly.
For replacement of programmer units refer to the separate Programmer Kit Instructions.
38
SIGHTGLASS REPLACEMENT
1. Refer to Frame 37.
2. Unfasten the 2 M5 hexagon nuts and washers.
Remove the assembly from the front plate.
3. Fit the new sightglass and reassemble, as
shown.
4. Retighten the 2 M5 hexagon nuts to ensure an
airtight seal. Do NOT overtighten.
39
PILOT BURNER REPLACEMENT
1. Refer to Frame 37.
2. Undo the 2 screws, lift off the front
panel and remove the grille
assembly. Refer to Frame 31.
3. Disconnect the electrical leads
from the gas valve.
4. Disconnect the ignition lead from
the PCB.
5. Undo the gas cock union. Remove
the 4 wing nuts and withdraw the
burner and controls assembly,
complete, from the boiler.
6. Prise the retaining clip out of the
groove in the electrode, using a
small screwdriver, and withdraw
the electrode.
SERVICING
7. Undo the pilot supply pipe
connection and ease clear of
the pilot burner. DO NOT LOSE
the pilot injector, which is a
push-fit in the pilot burner
housing.
8. Remove the 2 securing screws
and washers, and withdraw the
pilot burner.
9. Fit the new pilot burner and
reassemble in reverse order,
ensuring that:
a. The injector is in position
when refitting the pilot
supply.
b. A gas-tight joint is made.
c. The spark gap is correct.
Refer to Frame 44.
Mexico Super RS485 - RS4125 - Installation & Servicing
25
Page 26
40
CONTROL THERMOSTAT
REPLACEMENT
8
9
6
4
Control
thermostat
Cover
SERVICING
Thermostat
bracket
10
7
Mex 2198
1. Refer to Frame 37.
2. Remove 2 screws and lift off
the front door. Refer to Frame
31.
3. Pull off the thermostat knob.
4. Remove the 2 screws and
pull down the control panel
tabs clear of the top panel.
5. Remove the thermostat phial
from the pocket. Refer to
Frame 31.
6. Remove the bottom screw
3
and remove the cover.
7. Remove the top screw and
ease the control box off the
control panel.
8. Remove the 2 screws to
release the thermostat
bracket.
9. Disconnect the electrical
leads.
10. Unscrew the thermostat nut
to withdraw the thermostat.
11. Fit the new thermostat and
reassemble in reverse order.
41
IGNITION LEAD REPLACEMENT
1. Refer to Frame 37.
SERVICING
2. Remove the 2 screws, lift off the
front panel and remove the grille
assembly . Refer to Frame 31.
3. Disconnect the electrical leads
from the gas valve.
4. Disconnect the ignition lead
from the PCB.
5. Undo the gas cock union.
Remove the 4 wing nuts and
withdraw the burner and
controls assembly, complete,
from the boiler.
6. Remove the purse clip.
7. Undo the 2 securing nuts and
washers. Remove the sealing
plate and gasket.
8. Disconnect the ignition lead
from the base of the electrode
and the PCB, and withdraw the
lead.
9. Fit the new lead and
reassemble in reverse order.
MEX 1931
26
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 27
42
"
mex2209
CONTROL PANEL REPLACEMENT
SERVICING
1. Refer to Frame 37.
2. Remove the 2 screws and lift off the
lower front panel. Refer to Frame 31.
3. Pull off the thermostat knob.
4. Disconnect the inline electrical
connector between the control box
and PCB box.
5. Unscrew the 2 screws and pull
down the control panel so that the 2
tabs clear the top panel.
6. Remove the thermostat phial from
the pocket. Refer to Frame 31.
7. Remove the bottom screw and
remove the cover from the control
box.
8. Remove the top screw and ease the
control box off the control panel.
9. Disconnect the mains electrical
supply from the terminal strip and
release from its clamp.
10. Assemble new control box and
panel and fit to the casing in reverse
order.
11. Insert control thermostat phial into
pocket and secure with the split pin.
12. Refit the inline electrical connector between the control box
and the PCB box.
13. Remove control box cover and remake electrical supply
connections to the terminal strip.
7
5
Control
thermostat
9
Clamp
Thermostat
bracket
8
3
Mex 2184
43
OVERHEAT THERMOSTAT REPLACEMENT (if fitted)
1. Refer to Frame 37.
2. Remove the 2 screws and lift off the lower front
panel. Refer to Frame 31.
3. Slacken the screw at the thermostat pocket and
withdraw the phial from the pocket.
4. Remove the thermostat retaining nut and
withdraw the thermostat from the control panel.
5. Transfer the electrical leads from the old
thermostat to the replacement (polarity is not
important).
6. Fit the new thermostat, ensuring that the
alignment peg on the thermostat sits in the small
hole adjacent to the main fixing hole, and
reassemble in reverse order.
7. Replace the lower front panel and secure with
the 2 fixing screws.
8. Check the operation of the boiler.
SERVICING
Mexico Super RS485 - RS4125 - Installation & Servicing
27
Page 28
44
%
"
IGNITION ELECTRODE REPLACEMENT
1. Refer to Frame 37.
2. Remove the 2 screws, lift off the lower front panel
then remove the grille assembly. Refer to Frame
31.
3. Disconnect the electrical leads from the gas valve.
4. Undo the gas cock union. Remove the 4 wing nuts
and withdraw the burner and controls assembly,
complete, from the boiler.
SERVICING
5. Disconnect the ignition lead from the PCB.
6. Prise the retaining clip out of the groove in
the electrode, using a small screwdriver,
and withdraw the electrode.
45
MAIN BURNER REPLACEMENT
1. Refer to Frame 37.
SERVICING
2. Remove the 2 screws,
lift off the lower front
panel then remove the
grille assembly. Refer
to Frame 31.
3. Disconnect the
electrical leads from
the gas valve.
4. Undo the gas cock
union. Remove the 4
wing nuts and
withdraw the burner
and controls assembly,
complete, from the
boiler.
5. Disconnect the ignition
lead from the PCB.
6. Remove the 2 screws
securing the pilot
burner and pull the
assembly clear of the
main burner.
7. Push in the new electrode until the
retaining clip locates in the groove and
reassemble in reverse order.
7. Remove the 2 nuts and washers securing the burner to
the front plate and manifold. Withdraw the burner.
8. Fit the new burner and reassemble in reverse order,
taking care not to damage the main burner injector
which is screwed into the burner manifold.
28
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 29
46
Burner
manifold
MEX 2185
7
5
Ignition
lead
8
4
MAIN BURNER INJECTOR REPLACEMENT
1. Refer to Frame 37.
2. Remove the 2 screws, lift off the lower front panel
then remove the grille assembly. Refer to Frame
31.
3. Disconnect the electrical leads from the gas
valve.
4. Undo the gas cock union. Remove the 4 wing
nuts and withdraw the burner and controls
assembly, complete, from the boiler.
5. Disconnect the ignition lead from the PCB.
6. Undo the pilot supply connection.
7. Undo the manifold securing nuts and remove the
manifold from the front plate.
8. Unscrew the burner injector from the manifold.
9. Fit the new injector, using an approved jointing
compound, and reassemble in reverse order.
SERVICING
47
GAS VALVE REPLACEMENT
1. Refer to Frame 37.
2. Remove the 2 screws, lift off the lower front panel then
remove the grille assembly. Refer to Frame 31.
3. Disconnect the electrical leads from the gas valve.
4. Disconnect the ignition lead from the PCB.
5. Undo the gas cock union. Remove the 4 wing nuts and
withdraw the burner and controls assembly, complete, from
the boiler.
6. Undo the pilot supply connection.
'O' ring seal
Gas control
valve
7. Unscrew the gas inlet pipe from the valve.
7
8. Remove the 4 securing screws and withdraw the valve
from the burner manifold.
9. Fit the new gas valve, ensuring that:
a. The valve is fitted the correct way round - an arrow
engraved on the valve indicates the direction of flow.
b. The sealing 'O' ring supplied with the valve is
correctly fitted at the outlet flange.
c. An approved jointing compound is used when
reconnecting the gas inlet pipe.
Pilot supply connection
6
8
Securing
screws
SERVICING
7
Gas inlet
pipe
4
MEX 2217
Mexico Super RS485 - RS4125 - Installation & Servicing
Burner manifold
29
Page 30
SERVICING
48
PRINTED CIRCUIT BOARD (PCB) REPLACEMENT
6
5
4
MEX 2325
3
1. Refer to Frame 37.
2. Remove the 2 screws and lift off the
lower front panel. Refer to Frame 31.
3. Undo the PCB cover fixing screw and
remove the cover.
4. Remove the HT lead from the PCB
5. Remove the 6 push-in connectors
from the PCB.
6. Compress the barbs on the PCB
stand-offs to release the PCB from
the box
7. Fit the new PCB and reassemble in
reverse order.
8. Refit the boiler casing.
9. Check the operation of the boiler.
SERVICING
30
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 31
FAULT FINDING
Before attempting any electrical fault finding ALWAYS carry
out preliminary electrical system checks, i.e. earth continuity,
polarity and resistance to earth using a suitable meter.
NO
NO
NO
Has the fuse on the PCB blown?
Replace the PCB.
Check mains supply and fuses. Check controls are
calling for heat. Check boiler wiring connections are OK.
Can the overheat thermostat
be reset with the system cold?
NO
Check mains neon on PCB.
Is it illuminated?
YES
Is there a live supply to
both terminals of overheat
'stat?(If non- overheat 'stat
go to next step).
YES
Check the control 'stat is
set to max and mains
switch is on.
Is there a regular spark
from tube SG1 on the
PCB?
YES
Detailed instructions on the cleaning and adjustment or
replacement of faulty components are contained in the
'Servicing' section of this publication.
NO
YES
YES
Replace fuse but before restoring power check for short circuit
between L/N and L/Earth on all components plugged into the
Replace the overheat 'stat.
Reset the overheat 'stat. Set control
'stat to maximum. Allow the boiler to
reach temperature - if the overheat 'stat
trips again, measure flow temperature.
If above 90°C replace control 'stat.
If below 90°C replace overheat 'stat.
PCB.
Is there a spark at the
ignition electrode?
YES
Does the pilot burner light?
YES
Does the spark stop
after the pilot is lit?
YES
Does the main burner
cross-light from the pilot?
NO
NO
NO
NO
Check gap at ignition electrode. Check electrode and leads are not damaged.
Check the lead is not shorting to earth. Rectify as necessary.
Is there a gas supply to the boiler &
has the gas supply been purged of
air?
YES
Ensure pilot and main gas valve leads are not
crossed over. Is there a supply voltage at the pilot
gas valve?
YES
Is the pilot injector
blocked or the pilot
supply pipe damaged?
Check polarity of mains supply. Check
continuity of ignition lead.
Does spark now stop when pilot is lit?
YES
Is there a supply voltage at the main gas valve?
YES
NO
YES
NO
NO
Rectify or replace as necessary
NO
NO
Connect or rectify and
purge the system of air.
Check connections at the gas
valve and rectify as necessary.
If no connection fault found
replace PCB.
Replace gas valve
Check connections
to PCB.
If no fault change
PCB.
YES
Boiler
operating
Is the main injector blocked?
YES
Clear blockage and refit.
Does main burner light?
YES
satisfactorily
Mexico Super RS485 - RS4125 - Installation & Servicing
The following are parts commonly required as replacement
components, due to damage or expendability. Their failure or
absence is likely to affect safety or performance of this
appliance.
The list is extracted from the British Gas List of Parts, which
contains all available spare parts.
The full list is held by British Gas, Caradon Ideal Limited
distributors and merchants.
When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
22E01 505Pilot burner with injector (Key No. 23)1075 291
23381 656Pilot injector1003 825
24Gas valve assy.1153 726
26386 575Ignition electrode with HT lead1151 079
27E26 398HT lead 1100 lg.1130 918
30H20-882PCB25E1173 799
66E05 070Thermostat1151 903
67308 557Thermostat knob1111 904
32
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 33
48
Mex 1932
SHORT PARTS
LIST OF PARTS
Mexico Super RS485 - RS4125 - Installation & Servicing
33
Page 34
49
BOILER CASING ASSEMBLY
Legend.
46. Baseplate.
62. Casing complete.
63. Controls panel complete.
73. Side panel.
75. Lower front panel.
76. Top panel.
77. Grille assy.
78. Casing fixing pack (not shown)
LIST OF PARTS
76
63
73
75
73
50
BOILER CONTROL PANEL - Exploded View
Legend.
63. Control panel complete.
64. Control panel.
65. Control box.
66. Control thermostat.
67. Control thermostat knob.
71. Control front panel (door)
72. Magnetic strip.
PCB
lead
Mex 1953
46
65
66
Cable clamps
77
Thermostat
bracket
Thermostat
nut
64
34
Cover
Mex 2214
67
72
71
Mexico Super RS485 - RS4125 - Installation & Servicing
Page 35
LIST OF PARTS
51
BURNER AND CONTROLS ASSEMBLY - Exploded View
Legend
16. Front plate assy.
17. Sightglass assy.
18. Burner manifold assy.
19. Pilot burner pipe
20. Main burner
21. Main burner injector
22. Pilot burner assy.
24. Gas valve
25. 'O' ring.
26. Ignition electrode
27. HT lead
28. Gas cock.
50. Sealing plate gasket.
51. Sealing plate.
20
22
26
Mex 1952
28
24
17
25
19
27
18
52
PCB BOX - Exploded View
Legend
29. PCB chassis assy.
30. PCB sub-assy.
33. PCB support.
37. PCB cover.
33
16
21
50
51
29
37
30
Mexico Super RS485 - RS4125 - Installation & Servicing
MEX 2324
35
Page 36
The code of practice for the installation,
commissioning & servicing of central heating systems
THIS SYMBOL IS YOUR
ASSURANCE OF QUALITY
These appliances are designed for use with Natural Gas
only. They have been tested and conform with the
provisions of BS. 6332 and BS. 5258.
Technical Training
The Ideal Boilers Technical Training Centre offers a series
of first class training courses for domestic, commercial and
industrial heating installers, engineers and system
specifiers.
For details of courses please ring: ............ 01482 498 432
CERTIFIED PRODUCT
Manufactured under a BS EN ISO 9001: 2000
Quality System accepted by BSI
Caradon Ideal Limited pursues a policy of continuing
improvement in the design and performance of its products. The
right is therefore reserved to vary specification without notice.
P.O. Box 103, National Ave, Kingston upon Hull,
I
deal Installer/Technical Helpline: 01482 498663
www.idealboilers.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.