When replacing any part on this appliance use only spare parts that you can be
assured conform to the safety and performance specification that we require. Do not
use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
RS485, RS4100 & RS4125
May 2004 UIN 200 942 A02
GENERAL
Table 1 - General Data
Boiler SizeRS485RS4100RS4125
Gas Supply Connectionin. BSPRc 1/2 (1/2)
Number of Boiler Sections445
Flow and Return ConnectionsRc 1 (1" BSP)
MAXIMUM Static Water Headm (ft.)30.5 (100) (3 bar)
MINIMUM Static Water Headm (ft.)1.0 (3.3)
Electrical Supply230 V ~ 50 Hz
External Fuse Rating(Power Consumption)3 A (5 W)
Water Contentlitre (gal.)9.8 (2.1)9.8 (2.1)12.2 (2.7)
*The value is used in the UK government's Standard Assessment Procedure (SAP) for energy rating of
dwellings. The test data from which it has been calculated have been certified by Advantica 0087
Note.
Gas consumption is calculated using a calorific value of
38.7 MJ/m
3
(1038 Btu/ft3) gross or 34.9 MJ/m3 (935 Btu/ft3)
nett. To obtain the gas consumption at a different calorific
value:-
a. For l/s - divide the gross heat input (kW) by the gross
C.V. of the gas (MJ/m3)
3
b. For ft
/h - divide the gross heat input (Btu/h) by the
gross C.V. of the gas (Btu/ft3)
c. The appliance is preset at the factory to the highest
nominal rating.
Key to symbols
GB = United KingdomIE = Ireland
(Countries of destination)
PMS = Maximum operating pressure of water
= A room sealed appliance designed for connection via
C
11
ducts to a horizontal terminal, which admits fresh air
to the burner and discharges the products of
combustion to the outside without a fan in the
combustion products circuit.
I
= An appliance designed for use on 2nd Family gas,
2H
Group H only.
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of this
appliance, care should be taken when handling edges of sheet steel components.
2
Mexico Super RS485 - RS4125 - Installation & Servicing
GENERAL
CONTENTS
Air Supply. ...................................................................... 6
Mexico Super RS485 ..................... 41 392 78
Mexico Super RS4100 ................... 41 392 79
Mexico Super RS4125 ................... 41 392 80
Natural Gas only
11
INTRODUCTION
Mexico Super RS above rangeis of floor standing, natural
draught, balanced flue gas boilers. They are rated to provide
central heating outputs of 24.9 kW (85,000 Btu/h) to 36.6 kW
(125,000 Btu/h).
The boiler has a cast iron heat exchanger and is supplied fully
assembled, complete with a white enamelled mild steel
casing.
A door at the top of the casing front panel hinges down,
revealing the boiler thermostat control (and programmer, if
fitted).
The boilers are suitable, as standard, for connection to openvented systems ONLY - an overheat thermostat kit is available
to allow the boiler to be used on sealed water systems.
The systems may be:
•pumped or gravity circulating indirect DHW only
•pumped central heating only
•pumped central heating combined with either a pumped or
gravity circulating indirect DHW circuit.
For GB, to comply with Building Regulations Part L1 (Part J in Scotland) the boiler should be fitted in accordance with the
manufacturer's instructions. Self-certification that the boiler has been installed to comply with Building Regulations can be
demonstrated by completing and signing the Benchmark log book.
BENCHMARK LOG BOOK DETAILS
BoilerPage
Make and model ....................................................... 3
Appliance serial no. on data badge ........................ 11
For all boilers:complete, sign & hand over to customer
For assistance see Technical Helpline on the back page
Page
NOTE TO THE INSTALLER:
LEAVE THESE
INSTRUCTIONS ADJACENT TO THE GAS METER.
ALSO COMPLETE THE BENCHMARK LOG BOOK
AND GIVE THIS TO THE CUSTOMER.
Mexico Super RS485 - RS4125 - Installation & Servicing
3
GENERAL
This boiler will require 2 or more operatives to move it to its
installation site, remove it from its packaging base and during
movement into its installation location. Manoeuvring the boiler
may include the use of a sack truck and involve lifting, pushing
and pulling. The use of 1" pipe stubs of suitable lengths may
be temporarily screwed into the boiler tappings to act as
handles.
Caution should be exercised during these operations.
Operatives should be knowledgeable in handling techniques
when performing these tasks and the following precautions
should be considered:
•Split the boiler down to reduce the weight, e.g. remove
casing and hardware pack. Refer to Frame 9.
•Be physically capable.
•Use PPE as appropriate, e.g. gloves, safety footwear.
During all manoeuvres and handling actions, every attempt
should be made to ensure the following unless unavoidable
and/or the weight is light.
•Keep back straight.
•Avoid twisting at the waist.
•Avoid upper body/top heavy bending.
•Always grip with the palm of the hand.
•Use designated hand holds.
•Keep load as close to the body as possible.
•Always use assistance if required.
OPTIONAL EXTRA KITS
Programmer KitFits neatly within the casing. Separate
fitting instructions are included with this kit.
Overheatis available to allow the boiler to be used
Thermostat Kiton sealed water systems.
CURRENT GAS SAFETY (INSTALLATION AND USE)
REGULATIONS OR RULES IN FORCE.
The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a CORGI
Registered Installer or in IE a competent person. It must be
carried out in accordance with the relevant requirements of the:
•Gas Safety (Installation and Use) Regulations
•The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (northern Ireland).
•The Water Fittings Regulations or Water byelaws in
Scotland.
•The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a Competent
Person and installed in accordance with the current edition of
I.S.813 "Domestic Gas Installations", the current Building
Regulations and reference should be made to the current ETCI
rules for electrical installation.
Detailed recommendations are contained in the following British
Standard Codes of Practice:
BS. 6891Low pressure installation pipes.
BS. 6798Installation of gas fired hot water boilers of rated
input not exceeding 60 kW.
BS. 5449:1Forced circulation hot water systems (small bore
and microbore domestic central heating systems).
BS. 5546Installation of gas hot water supplies for
domestic purposes (2nd Family Gases).
BS. 5440: 1 Flues for gas appliances of rated input not
exceeding 60 kW.
BS. 5440: 2 Ventilation for gas appliances of rated input not
exceeding 60 kW.
BS 7593Treatment of water in Domestic Hot Water
Central Heating Systems.
Health and Safety Document No. 635.
The Electricity at Work Regulations, 1989.
Manufacturer’s notes must NOT be taken in any way as
overriding statutory obligations.
IMPORTANT. These appliances are certificated by the British
Standards Institution for safety and performance. It is
important, therefore, that no external control devices, e.g. flue
dampers, economisers etc., are directly connected to these
appliances unless covered by these Installation and Servicing
Instructions or otherwise recommended by Caradon IdealLimited in writing. If in doubt please enquire.
Any direct connection of a control device not approved by
Caradon Ideal Limited could invalidate the BSI Certification
and the normal appliance warranty. It could also infringe the
Gas Safety Regulations and the above regulations or other
statutory requirements.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation
panels, which can cause irritation to the skin. No asbestos,
mercury or CFCs are included in any part of the boiler.
LOCATION OF BOILER
The boiler must be installed on a flat and level floor, capable of
adequately supporting the weight of the boiler and any ancillary
equipment.
The boiler may be fitted on a combustible floor.
Insulation is not necessary, unless required by the local
authority.
The boiler must not be fitted outside.
Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should
be fitted in accordance with theInstitute of Gas Engineering
document IGE/UP/7:1998.
Bathrooms
The boiler may be installed in any room or internal space,
although particular attention is drawn to the requirements of
the current I.E.E. (BS 7671) Wiring Regulations and, in
Scotland, the electrical provisions of the building regulations
applicable in Scotland with respect to the installation of the
boiler in a room or internal space containing a bath or shower.
For Ireland reference should be made to the current ETCI rules
for electrical installations and I.S. 813: 2002.
Where a room-sealed appliance is installed in a room
containing a bath or shower then the appliance and any
electrical switch or appliance control utilising mains electricity
should be so situated that it cannot be touched by a person
using the bath or shower.
Where installation will be in an unusual location, special
procedures may be necessary and BS.6798 gives detailed
guidance on this aspect.
Compartment Installations
A compartment used to enclose the boiler MUST be designed
and constructed specially for this purpose.
An existing cupboard or compartment may be used, providing it
is modified for the purpose.
4
Mexico Super RS485 - RS4125 - Installation & Servicing
1
BOILER WATER CONNECTIONS
GENERAL
1. This appliance is NOT suitable for use in a
direct hot water system.
2. If the boiler is to be used on a sealed system,
an Overheat Thermostat Kit is available and
must be installed in accordance with the
instructions supplied with the kit.
DimensionAB
RS485 &299mm (11
RS4100
RS4125373 mm (14
3/4")533 (21")
5/8")600 (23 5/8")
2
FLOOR MOUNTING AND BOILER CLEARANCES
Flammable materials must not be placed in close proximity
to the appliance. Materials giving off flammable vapours
must not be stored in the same room as the appliance.
Floor mounting
1. The floor must be flat, level and of suitable load bearing
capacity.
2. The back of the boiler may be fitted up to the wall.
Boiler clearances
The minimum overall dimensions of the space in which the
boiler is to operate and to facilitate servicing are as follows:-
Boiler SizeWidthDepthHeight
85 &
RS4
RS4100
RS4125mm (in.) 550 (21
mm (in.)460 (18)533 (21)870 (34 1/4)
1/2) 600 (23 5/8) 870 (34 1/4)
Additional space will be required for installation, depending
upon site conditions.
IMPORTANT.
In order to facilitate gas connection, a clearance of at least 100
mm (4") must be available at either the left hand side or the right
hand side DURING installation. Refer to Frame 10.
In addition a MINIMUM clearance of 533 mm (21") MUST be
available at the front of the boiler, for servicing.
Terminal sizes
Boiler SizeDepthHeightWidth
RS485167392372
RS4100 & 4125182431372
Mexico Super RS485 - RS4125 - Installation & Servicing
DimensionA
RS485 & 410010 mm (
RS412555 mm (2
3/8")
1/4")
5
GENERAL
In both cases details of essential features of cupboards/
compartment design, including airing cupboard installation, are
to conform to the following:
!!
BS. 6798.
!
!!
!!
! The position selected for installation MUST allow
!!
adequate space for servicing in front of the boiler
and for air circulation around the boiler.
Side clearance is only necessary for installation. The amount
of side clearance will depend upon the type of connection used.
! This position MUST also permit the provision of a
satisfactory flue termination.
! For the minimum clearances required for safety, and
subsequent service, see Frame 2.
GAS SUPPLY
The local gas supplier should be consulted, at the installation
planning stage, in order to establish the availability of an
adequate supply of gas. An existing service pipe must NOT be
used without prior consultation with the local gas supplier.
The boiler is to be installed only on a gas supply with a
governed meter.
A gas meter can only be connected by the local gas supplier or
by a local regional contractor.
Check that the appliance is suitable for the proposed gas
supply. An existing meter should be checked, preferably by the
gas supplier, to ensure that the meter is adequate to deal with
the rate of gas supply required. A minimum gas pressure of
20 mbar MUST be available at the boiler inlet, with the boiler
operating.
Installation pipes MUST be fitted in accordance with BS. 6891. In
IE refer to I.S. 813:2002. Pipework from the meter to the boiler
MUST be of an adequate size.
The complete installation MUST be tested for gas soundness
and purged as described in the above code.
FLUE INSTALLATION
Some pluming may occur at the termination, so terminal
positions where this could cause a nuisance should be
avoided.
The flue must be installed in accordance with the
recommendations of BS.5440-1: 2000. In IE refer to I.S.
813:2002.
The following notes are intended for general guidance:-
1. The boiler MUST be installed so that the terminal is exposed
to external air.
2. It is important that the position of the terminal allows the free
passage of air across it at all times.
3. Minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in Table 3.
4. Where the lowest part of the terminal is fitted less than 2m
(6' 6") above a balcony, above ground or above a flat roof to
which people have access then the terminal MUST be
protected by a purpose designed guard.
Terminals guards are available from boiler suppliers. In
case of difficulty seek advice from:
5. Where the terminal is fitted within 1000mm (39 1/2") of a
plastic or painted gutter or 500mm (19 1/2") of painted eaves
then an aluminium shield at least 1000mm (39 1/2") long
should be fitted to the underside of the gutter or painted
surface.
6. The air inlet/products outlet duct and the terminal of the
boiler MUST NOT be closer than 25mm (1") to combustible
material. Detailed recommendations on the protection of
combustible material are given in BS.5440-1: 2000.
In IE
refer to I.S. 813:2002.
IMPORTANT.
It is absolutely ESSENTIAL to ensure, in practice, that products
of combustion discharging from the terminal cannot re-enter the
building or any other adjacent building through ventilators,
windows, doors, other sources of natural air infiltration or forced
ventilation/air conditioning. If this should occur, the appliance
MUST be turned OFF, labelled 'unsafe' and corrective action
taken.
Table 3 - Balanced flue terminal position
Terminal Position
1a. Directly BELOW an opening,1500 mm 2000mm
air brick, opening window etc.(60")(79")
1b. Directly ABOVE an opening,300 mm600mm
air brick, opening window etc.(12")(24")
1c. HORIZONTALLY to an opening,600 mm600mm
air brick, opening window etc.(24")(24")
2. Below guttering, drain pipes or
soil pipes300 mm(12")
3. Below eaves300 mm(12")
4. Below balconies or a car port roof600 mm(24")
5. From vertical drain pipes or300mm ( 12")
soil pipes
6. From an internal or external corner or
to a boundary alongside the terminal600 mm(24")
7. Above adjacent ground, roof or
balcony level300 mm(12")
8. From a surface or a boundary
facing the terminal600 mm(24")
9. From a terminal facing a terminal600 mm(24")
10. From an opening in a car port
(e.g. door or window) into dwelling1200 mm(48")
11. Vertically from a terminal on the
same wall1500 mm(60")
12. Horizontally from a terminal300 mm(12")
on the wall
Minimum Spacing
RS4854100-4125
TERMINAL
The terminal assembly can be adapted to accommodate
various wall thicknesses. Refer to Frame 8.
AIR SUPPLY
Detailed recommendations for air supply are given in
BS.5440:2. In IE refer to I.S. 813:2002.
The following notes are for general guidance:
1. It is NOT necessary to have a purpose provided air vent in
the room or internal space in which the boiler is installed.
6
Mexico Super RS485 - RS4125 - Installation & Servicing
GENERAL
Mex 1920
RS 4100
RS 485
RS 4125
RS 4100 & RS 4125
Table 4 - High and low vent areas
BoilerAir from room/internalAir direct from
space cm
High level Low levelHigh levelLow level
RS485275 (43)275 (43)137 (21)137 (21)
RS4100438 (68)438 (68)219 (34)219 (34)
RS4125438 (68)438 (68)219 (34)219 (34)
2. If the boiler is to be installed in a cupboard or compartment,
permanent air vents are required (for cooling purposes) in
the cupboard/compartment, at both high and low levels. The
air vents must either communicate with room/internal space,
or be direct to outside air. The minimum effective areas of the
permanent air vents, required in the cupboard/compartment,
are specified in Table 4 and are related to maximum rated
heat input.
3. Both air vents MUST communicate with the same room or
internal space or MUST be on the same wall to outside air.
4. In siting the air vents care must be taken to avoid the freezing
of pipework.
2
(in.2)outside cm2 (in.2)
WATER CIRCULATION SYSTEM
The boiler must NOT be used for direct hot water supply. The
boiler is suitable for connection to pumped open vent central
heating systems, pumped central heating combined with
pumped or gravity indirect domestic hot water supply systems.
The boiler is NOT suitable for gravity heating systems. The
hydraulic resistance of the boilers at maximum output with 11ºC
(20ºF) temperature differentials are shown in the graph below.
The central heating system should be in accordance with
BS. 6798 and, in addition, for smallbore and microbore
systems, BS. 5449:1.
The domestic hot water system, if applicable, should be in
accordance with the relevant recommendations of BS. 5546.
Copper tubing to BS. 2871:1 is recommended for water carrying
pipework.
The hot water storage cylinder MUST be of the indirect type and
should preferably be manufactured of copper.
Water Flow Rate and Pressure Loss
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The hot water cylinder and ancillary pipework not forming part of
the useful heating surface should be lagged to prevent heat loss
and any possible freezing - particularly where pipes run through
roof spaces and ventilated underfloor spaces.
IMPORTANT
A minimum length of 2 metres of copper pipe MUST be fitted to
both flow and return connections from the boiler before
connection to any plastic piping.
The boiler must be vented. If venting cannot be done via a flow
connection a separate vent MUST be fitted by the installer.
Draining taps MUST be located in accessible positions, which
permit the draining of the whole system - including the boiler
and hot water storage vessel. They should be at least 1/2" BSP
nominal size and be in accordance with BS. 2879.
If required, a drain tap (not supplied) may be fitted to an unused
bottom (1" BSP) tapping on the front of the boiler.
BOILER CONTROL INTERLOCKS
Caradon Ideal Limited recommend that heating systems utilising
full thermostatic radiator valve control of temperature in individual
rooms should also be fitted with a room thermostat controlling the
temperature in a space served by radiators not fitted with such a
valve as stated in BS. 5449.
Central heating systems controls should be installed to ensure the
boiler is switched off when there is no demand for heating or hot water.
When thermostatic radiator valves are used, the space heating
temperature control over a living / dining area or hallway having a
heating requirement of at least 10% of the boiler heat output should
be achieved using a room thermostat, whilst other rooms are
individually controlled by thermostatic radiator valves. However, if
the system employs thermostatic radiator valves on all radiators,
or two port valves without end switches, then a bypass circuit must
be fitted with an automatic bypass valve to ensure a flow of water
should all valves be in the closed position.
ELECTRICAL SUPPLY
WARNING. The appliance MUST be efficiently earthed.
Wiring external to the appliance MUST be in accordance with the
current I.E.E. (BS 7671) Wiring Regulations and any local
regulations which apply. For Ireland reference should be made
to the current ETCI rules for electrical installations.
The boiler is supplied for 230 V ~ 50 Hz single phase. The fuse
rating is 3A.
Connection must be made in a way that allows complete
isolation of the electrical supply - such as a double pole switch,
having a 3mm (1/8") contact separation in both poles, or a plug
and socket serving only the boiler and system controls.
The means of isolation must be accessible to the user after
installation.
For bathroom installations the point of connection to the mains
must be situated outside the bathroom.
Dotted lines indicate
flow rates equivalent
to a temperature rise
of 11 oC (20 oF)
Mexico Super RS485 - RS4125 - Installation & Servicing
7
GENERAL
Mex 1923
3
MINIMUM REQUIREMENTSFully pumped systems
1. Open vent and cold feed connections must be made to the
boiler flow and return tappings according to the options
shown in Frame 11.
2. The boiler is assumed to be the highest point of the
circulating system.
3. The circulating pump is positioned on the FLOW and the
vertical distance, between the pump and feed/ expansion
tank, must comply with the pump manufacturer's minimum
requirements, to avoid cavitation. Should these conditions
not apply, either lower the pump position or raise the feed/
expansion tank above the minimum requirements of
Caradon Ideal Limited.
4. The water velocity through the boiler flow / return pipes is
assumed to be below 1 m/s (3 ft./s), whilst the pump flow
rate is set to provide a temperature difference of 11
(200F) across the boiler flow / return, at design input.
5. This information is intended as a GUlDE ONLY and cannot
take into account instantaneous changes in head caused
by the operation of motorised valves, pumps etc.
Due allowance MUST be made if surging is liable to occur.
If in any doubt, contact Caradon Ideal Limited
o
C
4
GRAVITY HOT WATER & PUMPED CENTRAL HEATING
1. Separate flow and return connections are used for each
service. All possible configurations are given in Frame 11
and ONLY those shown should be used.
2. The schematic pipework graph is based on the
assumption that NO MORE than 8 elbows are used in the
gravity loop, including entry to the boiler.
3. For each extra elbow in excess of 8 (R) MUST be reduced
by 300 mm (12") or (H) increased by 100 mm (4")
4. Whatever value is selected for (R), the value of (H) MUST
be at least that indicated by the graph.
(R) = the horizontal distance between the
centre line of the cylinder and the boiler
tappings used - measured along the pipe run.
(H) = the vertical distance between the top of the boiler
and the base of the cylinder.
Notes.
a. Flow and return pipes should rise vertically on
leaving the boiler.
8
Mexico Super RS485 - RS4125 - Installation & Servicing
b. Horizontal pipes should be ABOVE ceiling level
and as short as possible.
c. A MINIMUM inclination of 25 mm per 3 m run (1"
per 10') is required to avoid air locks.
If the above conditions cannot be met, pumped
primaries should be used.
5
SEALED SYSTEM REQUIREMENTS
ecl6060
GENERAL
Hoseunions
Temporary hose
(disconnect
afterfilling)
Non-return
valve
Automatic
airvent
Hosepipe
(disconnect
afterfilling)
Additional
stop valve
Double check valve
assembly
(note direction of flow)
Hoseconnector
Note.
The method of filling, refilling, topping up or flushing sealed
primary hot water circuits from the mains via a temporary hose
connection is only allowed if acceptable to the local water
authority.
1. General
a. The installation must comply with the requirements of
BS.6798 and BS.5449.
b. The installation should be designed to work with flow
temperatures of up to 82
o
C.
c. All components of the system, including the heat
exchanger of the indirect cylinder, must be suitable for a
working pressure of 3 bar (45 lb/in
2
) and temperature of
110oC. Care should be taken in making all connections
so that the risk of leakage is minimised.
2. Safety Valve
A spring loaded safety valve complying with the relevant
requirements of BS.6759 must be fitted in the flow pipe, as
close to the boiler as possible and with no intervening valve
or restriction. The valve should have the following features:
a. A non-adjustable pre-set lift pressure not exceeding 3
bar (45 lb./in
2
)
b. A manual testing device.
c. Provision for connection of a discharge pipe. The valve
or discharge pipe should be positioned so that the
discharge of water or steam cannot create a hazard to
the occupants of the premises or cause damage to
electrical components and wiring.
3. Pressure Gauge
A pressure gauge covering at least the range 0-4 bar (0-60
lb./in2) must be fitted to the system. The gauge should be
easily seen from the filling point and should preferably be
connected at the same point as the expansion vessel.
4. Expansion Vessel
a. A diaphragm type expansion vessel must be connected
at a point close to the inlet side of the pump, the
connecting pipe being not less than 15mm (
1/2"
nominal) size and not incorporating valves of any sort.
b. The vessel capacity must be adequate to accept the
expansion of the system water when heated to 110
(230oF)
c. The charge pressure must not be less than the static
water head above the vessel The pressure attained in
the system when heated to 110oC (230oF) should be at
least 0.35 bar (5lb/in2) less than the lift pressure of the
safety valve.
For guidance on vessel sizing refer to Table 5,Frame 6.
For further details refer to BS.5449. For IE refer to the
current edition of I.S. 813.
5. Cylinder
The cylinder must be either of the indirect coil type or a
direct cylinder fitted with an immersion calorifier which is
suitable for operating on a gauge pressure of 0.35 bar
2
) in excess of the safety valve setting. Single feed
(5lb./in
indirect cylinders are not suitable for sealed systems.
6. Make-up Water
Provision must be made for replacing water loss from the
system, either:
a. From a manually fitted make-up vessel with a readily
visible water level. The vessel should be mounted at
least 150mm (6") above the highest point of the system
and be connected through a non-return valve to the
system, fitted at least 300mm (12") below the make-up
vessel on the return side of the domestic hot water
cylinder or radiators.
b. Where access to a make-up vessel would be difficult by
pre-pressurisation of the system. Refer to 'Filling.'
o
C
Mexico Super RS485 - RS4125 - Installation & Servicing
9
GENERAL
6
SEALED SYSTEM REQUIREMENTS - continued
7. Mains Connection
There must be no direct connection to the mains water
supply or to the water storage tank supplying domestic
water, even through a non-return valve, without the approval
of the local water authority.
8. Filling
The system may be filled by one of the following methods:
a. Through a cistern, used for no other purposes, via a
ball valve permanently connected directly to a service
pipe and / or a cold water distributing pipe.
The static head available from the cistern should be
adequate to provide the desired initial system design
pressure. The cold feed pipe from the cistern should
include a non-return valve and a stop valve with an
automatic air vent connected between them, the stop
valve being located between the system and the
automatic air vent. The stop valve may remain open
during normal operation of the system if automatic
water make-up is required.
b. Through a self-contained unit comprising a cistern,
pressure booster pump (if required) and, if
necessary, an automatic pressure reducing valve and
flow restrictor. The cistern should be supplied through
a temporary connection from a service pipe or cold
water distributing pipe.
This unit may remain permanently connected to the
heating system to provide limited automatic water
make-up. Where the temporary connection is
supplied from a service pipe or distributing pipe
which also supplies other draw-off points at a lower
level then a double check valve shall be installed
upstream of the draw-off point.
c. Through a temporary hose connection from a draw-off tap
supplied from a service pipe under mains pressure. Where
the mains pressure is excessive a pressure-reducing valve
shall be used to facilitate filling.
The following fittings shall form a permanent part of the
system and shall be fitted in the order stated:
A stop valve complying with the requirements of
BS. 1010, Part 2 (the hose from the draw-off tap shall be
connected to this fitting).
A test cock.
A double check valve of an approved type.
• Thoroughly flush out the whole of the system with cold
water, without the pump in position.
• With the pump fitted, fill and vent the system until the
pressure gauge registers 1.5 bar (21.5lb/in
Examine for leaks.
• Check the operation of the safety valve by manually
raising the water pressure until the valve lifts. This
should occur within ± 0.3 bar (± 4.3lb/in2.) of the pre-set
lift pressure.
• Release water from the system until the initial system
design pressure is reached.
• Light the boiler and heat the system to the maximum
working temperature. Examine for leaks.
• Turn off the boiler and drain the system while still hot.
• Refill and vent the system.
2
).
Sizing procedure for expansion vessels: The volume of the expansion vessel (litres) fitted to a sealed system shall not be
less than that given by Table 5, multiplied by a factor of 0.8 (for flow temperatures of less than 88 oC).
Table 5
Safety valve setting3.0 bar2.5 bar2.0 bar
Vessel charge and initial0.51.01.50.51.01.50.51.0
system pressurebarbarbarbarbarbarbarbar
Total water content of systemExpansion vessel volume
(litres)(litres)
252.12.73.92.33.35.92.85.0
504.25.47.84.76.711.85.610.0
756.38.211.77.010.017.78.415.0
1008.310.915.69.413.423.711.320.0
12510.413.619.511.716.729.614.125.0
15012.516.323.414.120.135.516.930.0
17514.619.127.316.423.441.419.735.0
20016.721.831.218.826.847.422.640.0
22518.724.535.121.130.153.325.445.0
25020.827.239.023.533.559.228.250.0
27522.930.042.925.836.865.131.055.0
30025.032.746.828.240.271.133.960.0
Multiplying factors for
other system volumes0.08330.1090.1560.0940.1340.2370.1130.20
10
Mexico Super RS485 - RS4125 - Installation & Servicing
INSTALLATION
Mex 1921
12
94
49
44
5
1
7
Tie rod
8
46
Data badge
28
18
30
24
6
69
68
2
4
3
47
Terminal
grille
7
BOILER ASSEMBLY - Exploded View
Mexico Super RS with casing removed - RS485 shown.
INSTALLATION
Detail of distributor
tube alignment
Index mark on
section boss
Mex 2215
Distributor tube
LEGEND
1. Heat exchanger assy.
2. Front section.
3. Middle section.
4. Section alignment rings & 'O' rings.
5.. Back section.
6. Thermostat pocket.
7. Distributor tube.
8. Combustion chamber.
Mexico Super RS485 - RS4125 - Installation & Servicing
12. Collector hood.
18. Front plate.
24. Gas control valve.
28. Gas cock.
30. PCB.
44. Air/flue duct assy.
46. Baseplate.
47. Heat shield.
49. Baffles.
68. Phial clip.
69. Split pin.
94. Cleanout cover.
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.