IDEAL Logic HIU 50 Indirect, Logic HIU 75 Indirect, Logic HIU 50 Direct MT, Logic HIU 50 Direct HT Product Manual

PRODUCT GUIDE
WE HAVE IT COVERED.
LOGIC HEAT INTERFACE UNITS (HIUs)
02
Operating from its Hull manufacturing plant and offices since 1906, Ideal Commercial Boilers is one of the few true British manufacturers left in the heating industry.
Your phone or tablet can let you appreciate our Condensing Boiler range in a new dimension.
The Ideal Commercial Eye app uses the latest technology to project 3D renders from the page of this brochure on to your device.
To see this for yourself, simply download the Ideal Commercial Eye app for free from your device’s app store. Open the app and then place your device over the image that has this icon next to it:
DOWNLOAD
THE APP
BRING BOILERS TO LIFE
03
4 HIU Introduction
Logic HIU range
6-9 Logic HIU 50 Indirect
10-13 Logic HIU 75 Indirect
14-17 Logic HIU 50 Direct MT
18-20 Logic HIU 50 Direct HT
Metering & Accessories
21 CF Echo II
21 CF UltramaxX V
21 Accessories
Condensing Boiler range
23 Evomax
24-25 Evomax Cascade
26 Imax Xtra
27 Imax Xtra EL
28 Evomod
29 Evojet
30-31 Commercial range overview
32-33 Stelrad radiators
34-35 Ideal Training & Support
04
TYPICAL SYSTEM.
DOWNLOAD
THE APP
LOGIC HIU
INTRODUCTION
The Ideal Heat Interface Units are heat energy transfer units. Designed for use in conjunction with centralised boilers, district heating or central energy systems. The function is to efficiently transfer heat from the plant room to the individual dwelling’s central heating (CH) and domestic hot water (DHW) systems.
TYPICAL SYSTEM
05
Ideal HIUs incorporate an internal electronic control unit which ensures not only maximum efficiency, improved reaction time and control but also incorporates other additional features. Modulating valves control the supply of hot water to both the space heating and domestic hot water within the apartment.
The thermally insulated casings minimise heat loss from the unit.
Maximum energy saving from the HIUs can only be achieved if the system is designed correctly and HIUs are selected and sized correctly.
To ensure maximum efficiency, reliability and performance the system must be designed and commissioned in accordance with CIBSE.
IDEAL LOGIC HIU
BENEFITS
THE BENEFITS OF IDEAL LOGIC HIUs ARE:
• Compact design requiring a minimum amount of space
• Minimal routine maintenance since they do not require regular servicing or maintenance
• All the Logic HIUs incorporate a spacer piece which can be easily removed and a heat meter fitted inside the unit. This allows the energy used by each individual apartment to be recorded and charged accordingly
THE LOGIC HIU RANGE HAS TWO METER OPTI O N S AVAI L AB L E :
• CF ECHO II
• CF ULTRAMAXX V
Depending upon the meter chosen the energy used can be monitored and recorded automatically which enables automatic billing to the tenants.
For information on how to design Ideal Logic HIUs into you next project please refer to the Design Guide which covers:
• Unit selection
• Heating system layout
• Integration of low carbon heat sources
• Prediction of hot water simultaneous demands
SAP has been adopted by the Government as part of the UK’s national standard for calculating the energy performance of buildings.
Every new building has to have an SAP rating. It provides a simple means of reliably estimating the energy efficiency.
SAP ratings are expressed on a scale of 1 to 100, the higher the number the more energy efficient the building.
SAP RATING
06
* After shut-off valves are installed the connections become a female 3/4’’.
CONNECTION A B C
Thread G¾” G½ G1”*
D E F Depth inc. Cover kg
65mm 550mm 630mm 265mm 19
F
A ABB
D
D
E
D
C
C
• Twin plate design hydraulically separates both domestic and space heating from the central primary supply
• Internal electronic control unit with LCD display
• The standard unit can be set to hold a stable heating flow temperature, to suit the installation (radiators, UFH for example), but crucially, can also be set to vary the heating flow temperature automatically depending on the temperature of the heating return water
• Automatically compensates for changes due to external influences, such as outside temperature etc. thereby ensuring that the unit and the system operate at maximum efficiency
• Pump bypass protection, in case of complete radiator TRV shutdown
• Compact and lightweight
• Fully insulated EPP front cover
• Convertible to underfloor heating
• Configurable hot water priority
• Pressure independent control valve
• Ability to pre-heating of the DHW exchanger
FEATURES & BENEFITS
The Logic heat interface unit is the latest ‘intelligent’ range of HIU from Ideal. The Logic HIU is the complete solution for instantaneous hot water production and space heating control.
This is an indirect wall mounted HIU, providing 50 kW instantaneous priority DHW and 15 kW modulated CH. This can be converted to under floor heating including inbuilt safety thermostat capability.
LOGIC HIU
50 INDIRECT
07
Maximum working pressure: 16 bar - primar y
3 bar - secondary
Maximum temperature 85°C
Max. Percentage of glycol 30%
Max. Recommended primary circuit flow rate
1.2 m³/h
PRIMARY PERFORMANCE
Heat Interface Unit 50
Primary ball valve set
Domestic connection flow & return valve kit
Filling loop connection kit valves
Flushing By-pass
CF Echo II
CF Ultramaxx V
UIN PRODUC T NAME METERING OPTIONS
211094 Logic HIU Indirect 50
HIU only, meter not included
211347 Logic HIU Indirect 50
Factory fitted, CF Echo 11 MbBus 1
211351 Logic HIU Indirect 50
Factory fitted, CF Ultramaxx V MBus PS
Power supply 230 V (ac)±10% 50 Hz
Max. Power consumption 105 W
Protection class IP 40
Actuator Stepper 24 V
Probes NTC 10 kΩ
ELECTRICAL
Frame RAL 9010 sprayed steel
Protective shell cover EPP (Expanded polypropylene)
Components Brass BS EN 12165 CW617N
Pipes Stainless steel
Exchanger Brazed stainless steel
CONSTRUCTION
INCLUDED AS STANDARD
ACCESSORIES
The temperature setting operates on the principle of set point regulation and can be fixed within application limits.
Heating Set Point 25 to 75°C
Nom. heating exchanger net output:
15 kW
Secondary circuit: Maximum pressure rating 3 bar
Maximum operating pressure
2.5 bar
Pump UPS 15/60
Pump bypass setting 0.45 bar
Pressure switch Opening 0.4 bar
Closing 0.8 bar
Safety relief valve setting 3 bar
Safety thermostat 55˚C ±3
Expansion vessel 7.5 litre
Under floor heating capability Optional
Heating control circuit VOLT FREE
HEATING
The DHW function takes priority over the heating function controlled by the DHW priority flow switch.
Set Point DHW temperature 42 to 60°C
Max. Domestic hot water pressure
10 bar
DHW circuit max. flow rate 18 l/m (0.3 l/s)
Min. flow rate to activate domestic flow sensor
2.7 l/m ±0.3
Max. Differential pressure on domestic water modulating valve
Δp 1.65 bar
Min. Differential pressure on domestic water modulating valve
Δp 0.35 bar
Nom. DHW heat exchanger net output
50 kW - Logic HIU 50 Indirect
DOMESTIC HOT WATER - DHW
INCLUDING OPTIONAL PRE HEAT FUNCTION
08
HYDRAULIC CHARACTERISTICS DOMESTIC HOT WATER - PRIMARY SIDE
HYDRAULIC CHARACTERISTICS HEATING - PRIMARY SIDE
DOMESTIC HOT WATER
0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5
Flowrate - l/s
50
10
1
0.5
20
30
2
3
5
Pressure loss - kPa
Kv = 2.03 m³/h
Flow Path Heating - primary side
ONON DHWDHW CHCH FAFAULULTT
RRESETESET
11
22
HR
HF
CHS
HEATI N G
CHS
HRHF
DHW - heat exchanger
0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5
0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5
Flowrate - l/s
50
10
1
0.5
20
30
2
3
5
Pressure loss - kPa
Kv = 2.25 m³/h
Hydraulic Characteristics Heating - secondary side
Flow Path Heating - secondary side
ONON DHWDHWCHCHFAFAULULTT
RRESETESET
11
22
CHS
0
10
20
30
40
50
60
0 0.1 0.2 0.3 0.4 0.5 0.6
Flowrate -l/s
Pressure loss -kPa
3
2
1
Kv = 2.63 m³/h
UPS 15 - 60 pump settings
ONON DHWDHW CHCH FAFAULULTT
RRESETESET
11
22
CHS
HRHF
DHW - heat exchanger
Flowrate - l/s
50
10
1
0.5
20
30
2
3
5
Pressure loss - kPa
Kv = 2.03 m³/h
Flow Path Heating - primary side
ONON DHWDHW CHCH FAFAULULTT
RRESETESET
11
22
HR
HF
CHS
CHS
PRIMARY FLOW CHARACTERISTICS
09
HYDRAULIC CHARACTERISTICS HEATING - SECONDARY SIDE
0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5
Hydraulic Characteristics Heating - secondary side
Flow Path Heating - secondary side
0
10
20
30
40
50
60
0 0.1 0.2 0.3 0.4 0.5 0.6
Flowrate -l/s
Pressure loss -kPa
3
2
1
Kv = 2.63 m³/h
UPS 15 - 60 pump settings
ONON DHWDHW CHCH FAFAULULTT
RRESETESET
11
22
CHS
HRHF
Flowrate - l/s
50
10
1
0.5
20
30
2
3
5
Pressure loss - kPa
Kv = 2.03 m³/h
Flow Path Heating - primary side
ONON DHWDHW CHCH FAFAULULTT
RRESETESET
11
22
HR
HF
CHS
CHS
HRHF
Primary Flow Rate I/h
Primary flow temperatures
1,500
1,400
1,200
1,000
800
600
400
200
0
0 100 200 300 400 500 600 700 800 900 1,000 1,100
Domestic Hot Water Flow Rate @ 48˚C - l/h
55˚C
60˚C
65˚C
70˚C
75˚C
80˚C
85˚C
Primary flow temperatures
55˚C
60˚C
65˚C
70˚C
75˚C
80˚C
85˚C
Primary flow temperatures
55˚C
60˚C
65˚C
70˚C
Primary
flow temperatures
temperatures
DOMESTIC HOT WATER OUTPUT
10
ON DHW CH FAULT
RESET
F
A ABB
D
D
E
D
C
C
* After shut-off valves are installed the connections become a female 3/4’’.
CONNECTION A B C
Thread G¾” G½ G1”*
D E F Depth inc. Cover kg
65mm 550mm 630mm 265mm 19
• Twin plate design hydraulically separates both domestic and space heating from the central primary supply
• Internal electronic control unit with LCD display
• The standard unit can be set to hold a stable heating flow temperature, to suit the installation (radiators, UFH for example), but crucially, can also be set to vary the heating flow temperature automatically depending on the temperature of the heating return water
• Automatically compensate for changes due to external influences, such as outside temperature etc. thereby ensuring that the unit and the system operate at maximum efficiency
• Convertible to underfloor heating
• Configurable hot water priority
• Pressure independent control valve
• Pump bypass protection, in case of complete radiator TRV shutdown
• Ability to pre-heating of the DHW exchanger
FEATURES & BENEFITS
The Logic heat interface unit is the latest ‘intelligent’ range of Logic HIUs from Ideal. The Logic HIU is the complete solution for instantaneous hot water production and space heating control.
This is an indirect wall mounted HIU, providing 75 kW instantaneous priority DHW and 15 kW modulated CH. This can be converted to under floor heating including inbuilt safety thermostat capability.
LOGIC HIU
75 INDIRECT
11
Maximum working pressure: 16 bar - primar y
3 bar - secondary
Maximum temperature 85°C
Max. Percentage of glycol 30%
Max. Recommended primary circuit flow rate
1.2 m³/h
PRIMARY PERFORMANCE
Heat Interface Unit 75
Primary ball valve set
Domestic connection flow & return valve kit
Filling loop connection kit valves
Flushing By-pass
CF Echo II
CF Ultramaxx V
UIN PRODUC T NAME METERING OPTIONS
211093 Logic HIU Indirect 75
HIU only, meter not included
211346 Logic HIU Indirect 75
Factory fitted, CF Echo 11 MbBus 1
211350 Logic HIU Indirect 75
Factory fitted, CF Ultramaxx V MBus PS
Power supply 230 V (ac)±10% 50 Hz
Max. Power consumption 105 W
Protection class IP 40
Actuator Stepper 24 V
Probes NTC 10 kΩ
ELECTRICAL
Frame RAL 9010 sprayed steel
Protective shell cover EPP (Expanded polypropylene)
Components Brass BS EN 12165 CW617N
Pipes Stainless steel
Exchanger Brazed stainless steel
CONSTRUCTION
INCLUDED AS STANDARD
ACCESSORIES
The temperature setting operates on the principle of set point regulation and can be fixed within application limits.
Heating Set Point 25 to 75°C
Nom. heating exchanger net output:
15 kW
Secondary circuit: Maximum pressure rating 3 bar
Maximum operating pressure
2.5 bar
Pump UPS 15/60
Pump bypass setting 0.45 bar
Pressure switch Opening 0.4 bar
Closing 0.8 bar
Safety relief valve setting 3 bar
Safety thermostat 55˚C ±3
Expansion vessel 7.5 litre
Under floor heating capability Optional
Heating control circuit VOLT FREE
HEATING
The DHW function takes priority over the heating function controlled by the DHW priority flow switch.
Set Point DHW temperature 42 to 60°C
Max. Domestic hot water pressure
10 bar
DHW circuit max. flow rate 26.6l/m (0.44l/s)
Min. flow rate to activate domestic flow sensor
2.7 l/m ±0.3
Max. Differential pressure on domestic water modulating valve
Δp 1.65 bar
Min. Differential pressure on domestic water modulating valve
Δp 0.35 bar
Nom. DHW heat exchanger net output
75 kW - Logic HIU 75 Indirect
DOMESTIC HOT WATER - DHW
INCLUDING OPTIONAL PRE HEAT FUNCTION