ideal Isar M3080 User guide

GENERAL
Table 1 - General Data
Gas supply 2H-G20-20mbar Gas Supply Connection Rc1/2 (1/2" BSP Female) Injector size Stereomatic 5.6mm dia. Flow Connection Central Heating 22mm copper compression Return Connection Central Heating 22mm copper compression Flue Terminal Diameter mm (in) 100 (4)
2
Maximum Working Pressure (Sealed Systems) bar (lb/in Electrical Supply / Power consumption 230 V ~ 50 Hz. / 148 W Fuse Rating External : 3A Internal : T3.15A L 250V Water content Central Heating litre (gal) 2.0 (0.44) Packaged Weight kg (lb) 47 (103) Maximum Installation Weight kg (lb) 40 (88) Boiler Casing Size Height mm (in) 687 (27)
Width mm (in) 390 (15 3/8) Depth mm (in) 278 (11)
Table 2 - Performance Data
) 2.65 (38.5)
Boiler Size Max Min
Boiler input 'Q' = Nett CV kW 24.4 9.1
Btu/h 83 300 31 000
Gross CV kW 27.1 10.1
Btu/h 92 500 34 400
Boiler output 'P' = Gas consumption l/s (cu.ft/h) 0.70 (89.0) 0.26 (33.2)
70 °C Mean water kW 23.4 8.8 temperature Btu/h 80,000 30,000
40 °C Mean water kW 25.1 9.6
temperature Btu/h 85 700 32 800 Seasonal efficiency (SEDBUK) * Band A [90.2]% NOx classification Class 4
* The value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from
which it has been calculated have been certified by a notified body.
Gas consumption is calculated using a
Note.
calorific value of 38.7 MJ/m3 (1038 Btu/ft3) gross or 34.9 MJ/m3 (935 Btu/ft3) nett
To obtain the gas consumption at a different calorific value:
a. For l/s- divide the gross heat input (kW) by
the gross C.V. of the gas (MJ/m
3
b. For ft
/h - divide the gross heat input (Btu/
3
)
h) by the gross C.V. of the gas (Btu/ft3)
Key to symbols GB = United Kingdom IE = Ireland (Countries of destination)
PMS = Maximum operating pressure of water
C
13 C33 C53
= A room sealed appliance designed for connection via ducts to a horizontal or vertical terminal, which admits fresh air to the burner and discharges the products of combustion to the outside through orifices which, in this case, are concentric. The fan is up stream of the combustion chamber.
= An appliance designed for use on 2nd Family gas, Group H only.
I
2H
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of
this appliance care should be taken when handling edges of sheet steel components.
2
icos system -
Installation and Servicing
GENERAL
icos system m3080
Natural Gas only
G.C. Appliance No. 41 391 52
PI No. 0063BM9802
Destination Country: GB, IE
CONTENTS
Air Supply ....................................................................... 7
Boiler Clearances ......................................................... 6
Boiler Interlocks............................................................ 8
Boiler Exploded Diagram ................................... 10 & 11
Condensate Drain ................................................ 8 & 21
Electrical Connections ............................................... 23
Electrical Supply ........................................................... 8
Extension Ducts - Fitting .............................................17
Fault Finding ........................................................... 45-48
Flow Wiring Diagram ..................................................26
Flue Fitting .................................................................... 15
Flue Installation ............................................................. 7
Gas Safety Regulations ................................................ 5
Gas Supply ..................................................................... 7
Installation .............................................................. 11-29
Mandatory Requirements....................................... 5-10
Pump .......................................................................... 42
Servicing ................................................................ 30-44
Short List of Parts....................................................... 49
Thermostatic Radiator valves ..................................... 8
Water and Systems ................................................ 7-10
Water Connections ..................................................... 20
Water Treatment ......................................................... 10
Wiring Diagrams ................................................... 23-26
For GB, to comply with Building Regulations Part L1 (Part J in Scotland) the boiler should be fitted in accordance with the manufacturer's instructions. Self-certification that the boiler has been installed to comply with Building Regulations can be demonstrated by completing and signing the Benchmark log book.
BENCHMARK LOG BOOK DETAILS
Boiler Page
Make and model .......................................................3
Appliance serial no. on data badge ....................... 11
SEDBUK No. % ......................................................... 2
Controls
Time and temperature control to heating ............. 24
Time and temperature control to hot water .......... 24
Heating zone valves .............................................. n/a
TRV's .........................................................................8
Auto bypass ..............................................................8
Boiler interlock ..........................................................8
For all boilers
Flushing to BS.7593 .............................................. 10
Inhibitor .................................................................. 10
Central heating mode
Heat input ................................................ to be calculated
Burner operating pressure...... measure and record
Central heating flow temp. ...... measure and record
Central heating return temp. ... measure and record
For combination boilers only
Scale reducer ......................................................... n/a
Hot water mode
Heat input ............................................................... n/a
Max. operating burner pressure .............................. n/a
Max. operating water pressure .............................n/a
Cold water inlet temp ............................................n/a
Hot water outlet temp. ........................................... n/a
Water flow rate at max. setting ..............................n/a
For condensing boilers only
Condensate drain .................................................. 21
For all boilers:
For assistance see Technical Helpline on the back page
complete, sign & hand over to customer
Page
NOTE TO THE INSTALLER:
LEAVE THESE
INSTRUCTIONS ADJACENT TO THE GAS METER.
ALSO COMPLETE THE BENCHMARK LOG BOOK
AND GIVE THIS TO THE CUSTOMER.
icos system -
Installation and Servicing
3
GENERAL
INTRODUCTION
The icos system m3080 is a cast aluminium wall mounted, full sequence, automatic spark ignition, low water content, fanned flue, high efficiency, condensing system gas boiler.
Due to the high efficiency of the boiler a plume of water
Note.
vapour will form at the terminal during operation.
The output is fully modulating with a range of:
8.8 to 23.4 kW (30,000 to 80,000 Btu/h)
The boiler is supplied fully assembled with circulating pump, pressure gauge, safety valve and expansion vessel.
Variable temperature control is fitted on the user control. The boiler casing is of white painted coated mild steel with
the user controls capable of being mounted remotely from the boiler if the option is required.
The heat exchanger is of cast aluminium. The boiler is suitable for connection to fully pumped, sealed
water systems ONLY. Adequate arrangements for completely draining the system
by provision of drain cocks MUST be provided in the installation pipework.
Pipework from the boiler is routed downwards as standard, but may be routed upwards behind the boiler using the stand-off frame (supplied in a separate kit).
OPERATION
When there is a demand for heat, the heating system is supplied at the selected temperature of between 30
Refer also to Frame 1 - 'Boiler Water Circuit Diagram' The boiler features a comprehensive diagnostic system which
gives detailed information on the boiler status when operating, and performance of key components to aid commissioning and fault finding.
o
C and 82oC.
1
BOILER WATER CIRCUIT DIAGRAM
Fan
Sump
Condensate 'S' trap
Expansion vessel
Burner
Automatic air vent
Heat exchanger
Gas valve
Pump
Water pressure gauge
Flow
Gas
Return
Condensate drain
4
Safety relief valve
Discharge pipe
icos system -
Ecl 2532
Installation and Servicing
GENERAL
OPTIONAL EXTRA KITS
! Flue Extension Ducts (1000mm long, up to 6m ) . ! Flue Finishing Kit
o
! 90
Elbow Kit (Maximum 4 elbows / installation).
! 45o Elbow Kit (Maximum 4 elbows / installation). ! Powered Vertical Flue Kit (to a maximum primary flue
length of 8m + a maximum secondary flue length of 6m)
! Roof Flue Kit (to a maximum of 8m). ! Twin flueing Kit (to a maximum of 46m combined total of
flue and air ducts)
! Remote User Controls Kit. ! Boiler Stand-off Kit. ! Siphon Kit. ! Valve Cover Kit.
SAFETY
Current Gas Safety (Installation & Use) Regulations or rules in force.
The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a CORGI Registered Installer. It must be carried out in accordance with the relevant requirements of the:
Gas Safety (Installation and Use) Regulations
The appropriate Building Regulations either The Building Regulations, The Building Regulations (Scotland), Building Regulations (northern Ireland).
The Water Fittings Regulations or Water byelaws in Scotland.
The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a Competent Person and installed in accordance with the current edition of I.S.813 "Domestic Gas Installations", the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
Detailed recommendations are contained in the following British Standard Codes of Practice:
BS. 5440:1 Flues (for gas appliances of rated input not
exceeding 70 kW).
BS. 5440:2 Ventilation (for gas appliances of rated input not
exceeding 70 kW).
BS. 5449 Forced circulation hot water systems. BS. 5546 Installation of gas hot water supplies for
domestic purposes (2nd Family Gases)
BS. 6798 Installation of gas fired hot water boilers of rated
input not exceeding 70 kW.
BS. 6891 Low pressure installation pipes.
Health & Safety Document No. 635. The Electricity at Work Regulations, 1989.
The manufacturer’s notes must NOT be taken, in any way, as overriding statutory obligations.
IMPORTANT. These appliances are CE certificated for safety and performance. It is, therefore, important that no external control devices, e.g. flue dampers, economisers etc., are directly connected to these appliances unless covered by these Installation and Servicing Instructions or as otherwise recommended by Caradon Ideal Limited in writing. If in doubt please enquire.
Any direct connection of a control device not approved by Caradon Ideal Limited could invalidate the certification and the normal appliance warranty. It could also infringe the Gas Safety Regulations and the above regulations.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation panels, which can cause irritation to the skin. No asbestos, mercury or CFCs are included in any part of the boiler or its manufacture.
LOCATION OF BOILER
The boiler must be installed on a flat and vertical wall, capable of adequately supporting the weight of the boiler and any ancillary equipment.
The boiler may be fitted on a combustible wall and insulation between the wall and the boiler is not necessary, unless required by the local authority.
For electrical safety reasons there must be no access available from the back of the boiler.
The boiler must not be fitted outside.
Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should be fitted in accordance with the Institute of Gas Engineering document IGE/UP/7:1998.
Bathroom Installations
This appliance is rated IP20. The boiler may be installed in any room or internal space,
although particular attention is drawn to the requirements of the current IEE (BS.7671) Wiring Regulations and, in Scotland, the electrical provisions of the building regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. For Ireland reference should be made to the current ETCI rules for electrical installations and I.S.813:2002.
If the appliance is to be installed in a room containing a bath or shower then, providing water jets are not going to be used for cleaning purposes (as in communal baths/showers), the appliance can be installed in Zone 3, as detailed in BS.7671.
Compartment Installations
A compartment used to enclose the boiler should be designed and constructed specially for this purpose.
An existing cupboard or compartment may be used, provided that it is modified for the purpose.
In both cases, details of essential features of cupboard / compartment design, including airing cupboard installation, are to conform to the following:
! BS. 6798 (No cupboard ventilation is required - see 'Air
Supply' for details).
! The position selected for installation MUST allow adequate
space for servicing in front of the boiler.
! For the minimum clearances required for safety and
subsequent service, see the wall mounting template and Frame 2. In addition, sufficient space may be required to allow lifting access to the wall mounting plate.
icos system -
Installation and Servicing
5
GENERAL
2
BOILER DIMENSIONS, SERVICES & CLEARANCES
The boiler connections are made on the boiler piping frame. Refer to Frames 20 & 21.
The following minimum clearances must be maintained for operation and servicing.
Additional space will be required for installation, depending upon site conditions.
Side and Rear Flue a. Provided that the flue hole is cut accurately, e.g. with a
core drill, the flue can be installed from inside the building
all dimensions in mm (in)
where wall thicknesses do not exceed 600mm (24"). Where the space into which the boiler is going to be installed is less than the length of flue required the flue must be fitted from the outside.
Installation from inside ONLY b. If a core boring tool is to be used inside the building the
space in which the boiler is to be installed must be at least wide enough to accommodate the tool.
5 (1/4")
400 (15 3/4")
5 (1/4")
165 (6 1/2")
100 (4")
390 (15 3/8")
278 (11")
Flue terminal
687 (27")
*
Ecl 2479
See inset A
A
CLEARANCES
Centre line of boiler
43
Flow
Condensate drain
112
Gas control
49
123
Return
Inset A Water Connections and Gas Connection
Front clearance
The minimum front clearance when built in to a cupboard is
1/4") from the cupboard door but 450mm (17 3/4")
5mm ( overall clearance is still required, with the cupboard door open, to allow for servicing.
* Bottom clearance
After installation can be reduced to 5mm in an adequately ventilated enclosed cupboard. However, 100mm must be available for servicing.
BOILER DIMENSIONS
SIDE FLUE ONLY
Horizontal length of flue Top clearance from centre line of boiler required (MIN.)
to outside wall Dim. A
0.5 m 160 mm (6
1.0 m 170 mm (6 11/16)
1.5 m 185 mm (7 1/4")
2.0 m 200 mm (
2.5 m 210 mm (8 1/4")
3.0 m 225 mm (8 7/8")
3.5 m 265 mm (9 1/4")
3.5 m 250 mm (10
4.5 m 260 mm (10 1/4")
5.0 m 275 mm (10 13/16")
5.5 m 290 mm (11 3/8")
6.0 m 300 mm (11
REAR FLUE ONLY
MIN. Top clearance required = 145 mm (5 3/
4")
5/16")
7 7/8")
5/8")
13/16")
6
icos system -
Installation and Servicing
GENERAL
GAS SUPPLY
The local gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas. An existing service pipe must NOT be used without prior consultation with the local gas supplier.
The boiler MUST be installed on a gas supply with a governed meter only.
A gas meter can only be connected by the local gas supplier or by a CORGI registered engineer. In IE by a Competent Person.
An existing meter should be checked, preferably by the gas supplier, to ensure that the meter is adequate to deal with the rate of gas supply required.
N.B.The principle of the 1:1 gas valve ensures that the icos
system is able to deliver its full output at inlet pressures
well below those required by BS. 6891.
IMPORTANT.
Installation pipes MUST be fitted in accordance with BS.6891. In IE refer to I.S.813:2002. Pipework from the meter to the boiler MUST be of an adequate size, i.e. no longer than 20m and not less than 15mm O.D.
The complete installation MUST be tested for gas soundness and purged as described in the above code.
FLUE INSTALLATION
Pluming will occur at the terminal, so where possible, terminal positions where this could cause a nuisance should be avoided.
The flue must be installed in accordance with the recommendations of BS.5440-1:2000. In IE refer to I.S.813:2002.
The following notes are intended for general guidance:
1. The boiler MUST be installed so that the terminal is exposed to external air.
2. It is important that the position of the terminal allows the free passage of air across it at all times.
Table 3 - Balanced Flue Terminal Position
Terminal Position
1. Directly below or alongside an
opening window, air brick or other ventilation opening 300 mm (12")
2. Below guttering, drain pipes or soil
pipes 75 mm ( 3")
3. Below eaves 200 mm ( 8")
4. Below balconies or a car port roof 200 mm ( 8")
5. From vertical drain pipes or soil pipes 150 mm ( 6")
6. From an internal or external corner or
to a boundary alongside the terminal 300 mm ( 12")
7. Above adjacent ground, roof or
balcony level 300 mm (12")
8. From a surface or a boundary
facing the terminal 600 mm (24")
9. From a terminal facing a terminal 1200 mm (48")
10.From an opening in a car port
(e.g. door or window) into dwelling 1200 mm (48")
11. Vertically from a terminal on the
same wall 1500 mm (60")
12.Horizontally from a terminal on the wall 300 mm (12")
Minimum Spacing
3. Minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in Table 3.
4. Where the lowest part of the terminal is fitted less than 2m
(6'6") above a balcony, above ground or above a flat roof to which people have access then the terminal MUST be protected by a purpose designed guard.
Terminal guards are available from boiler suppliers. (ask for TFC flue guard model no. K6 - round, plastic coated). In case of difficulty contact:
Grasslin (UK) Ltd., Tower House, Vale Rise, Tonbridge, Kent TN9 1TB Tel: +44 (0) 1732 359 888. Fax: +44 (0) 1732 354 445 www.tfc-group.co.uk
Ensure that the guard is fitted centrally.
5. The flue assembly shall be so placed or shielded as to
prevent ignition or damage to any art of any building.
6. The air inlet/products outlet duct and the terminal of the
boiler MUST NOT be closer than 25mm (1") to combustible material. Detailed recommendations on the protection of combustible material are given in BS.5440-1:2000. In IE refer to I.S.813:2002.
IMPORTANT. It is absolutely essential to ensure, in practice, that products of combustion discharging from the terminal cannot re-enter the building or any other adjacent building through ventilators, windows, doors, other sources of natural air infiltration, or forced ventilation / air conditioning.
If this should occur the appliance MUST be turned OFF, labelled as 'unsafe' until corrective action can be taken.
TERMINAL
The terminal assembly can be adapted to accommodate various wall thicknesses. Refer to Frame 12.
AIR SUPPLY
It is NOT necessary to have a purpose-provided air vent in the room or internal space in which the boiler is installed. Neither is it necessary to ventilate a cupboard or compartment in which the boiler is installed, due to the low surface temperatures of the boiler casing during operation; therefore the requirements of BS.6798, Clause 12, and BS 5440:2 may be disregarded. In IE the requirements of I.S.813:2002 may be disregarded.
WATER CIRCULATION SYSTEM
IMPORTANT.
A minimum length of 1metre of copper pipe MUST be fitted to both flow and return connections from the boiler before connection to any plastic piping.
The central heating system should be in accordance with BS.6798 and, in addition, for smallbore and microbore systems, BS.5449.
The hot water storage cylinder MUST be of the indirect type and should preferably be made of copper.
Single feed, indirect cylinders MUST NOT be used. The appliances are NOT suitable for gravity central heating nor are they suitable for the provision of gravity domestic hot water.
The hot water cylinder and ancillary pipework, not forming part of the useful heating surface, should be lagged to prevent heat loss and any possible freezing - particularly where pipes run through roof spaces and ventilated underfloor spaces.
WATER TREATMENT - see Frame 6
icos system -
Installation and Servicing
7
GENERAL
The hydraulic resistance of the boilers, at with an 11oC (20oF) temperature differential, is shown in Graph 1.
Graph 1 - Water flow rate and pressure loss
1.0
0.5
Pressure Drop Across Boiler
(metres water)
8.8 11.7 14.7 17.6 20.5 Boiler Output (kW)
MAXIMUM OUTPUT
,
Ecl 1603
23.4
BOILER CONTROL INTERLOCKS
Caradon Ideal Limited recommend that heating systems
utilising full thermostatic radiator valve control of temperature in individual rooms should also be fitted with a room thermostat controlling the temperature in a space served by radiators not fitted with such a valve as stated in BS. 5449.
When thermostatic radiator valves are used, the space heating temperature control over a living area having a heating requirement of at least 0.9kW (3000Btu/h) of the boiler heat output should be achieved using a room thermostat whilst other rooms are individually controlled by thermostatic radiator valves. A higher proportion of TRVs may be used, provided that
a bypass between the boiler flow and return is fitted, to ensure adequate flow when all TRVs are closed.
For further information refer to the 'Good Practice Guide 143', a publication of the Energy Efficiency Office, available from the Building Research Establishment, Garston, Watford WD2 7JR. Tel: +44 (0) 1923 664258.
ELECTRICAL SUPPLY
WARNING.
Wiring external to the appliance MUST be in accordance with the current I.E.E. (BS.7671) Wiring Regulations and any local regualtions which apply. For Ireland reference should be made to the current ETCI rules for electrical installations.
The point of connection to the mains should be readily accessible and adjacent to the boiler.
The appliance MUST be efficiently earthed.
CONDENSATE DRAIN - Refer to Frames 27 & 45
A condensate drain is provided on the boiler. This drain must be connected to a drainage point on site. All pipework and fittings in the condensate drainage system MUST be made of plastic -
no other materials may be used.
IMPORTANT.
Any external runs must be insulated The drain outlet on the boiler is standard 21.5mm (3/4")
overflow pipe.
3
SYSTEM REQUIREMENTS
Notes
The method of filling, refilling, topping up or flushing
a.
sealed primary hot water circuits from the mains via a temporary hose connection is only allowed if acceptable to the local water authority.
b.
Antifreeze fluid, corrosion and scale inhibitor fluids suitable for use with boilers having aluminium heat exchangers may be used in the central heating system.
Advice should be sought from a local water treatment company.
Safety valve setting bar 3.0 Vessel charge pressure bar 0.5 to 0.75 System pre-charge pressure bar None 1.0
System volume Expansion vessel
(litres) volume (litres)
25 1.6 1.8 50 3.1 3.7
75 4.7 5.5 100 6.3 7.4 125 7.8 9.2 150 9.4 11.0 175 10.9 12.9 190 11.9 14.0 200 12.5 14.7 250 15.6 18.4 300 18.8 22.1
For other system volumes multiply by the factor across 0.063 0.074
8
icos system -
Installation and Servicing
GENERAL
4
SYSTEM REQUIREMENTS - continued
General
1. The installation must comply with all relevant national and
local regulations.
2. The installation should be designed to work with flow
temperatures of up to 82
3. All components of the system must be suitable for a working
pressure of 3 bar and temperature of 110 should be taken in making all connections so that the risk of leakage is minimised.
The following components are incorporated within the appliance:
a. Circulating pump. b. Safety valve, with a non-adjustable preset lift pressure
of 3 bar.
c. Pressure gauge, covering a range of 0 to 6 bar. d. An 8-litre expansion vessel, with an initial charge pressure
of 0.75 bar.
4. 'Make-up' Water. Provision must be made for replacing water
loss from the system, either : a. From a manually filled 'make-up' vessel with a readily
visible water level. The vessel should be mounted at least 150mm above the highest point of the system and be connected through a non-return valve to the system, fitted at least 150mm below the 'make-up' vessel on the return side of the radiators.
or
b. Where access to a 'make-up' vessel would be difficult,
by pre-pressurisation of the system. The maximum cold water capacity of the system
should not exceed 143 litres, if not pressurized. However, if the system is to be pressurized, the efficiency of the expansion vessel will be reduced and a larger vessel (or smaller system volume) may be necessary. If the capacity of the vessel is not considered sufficient for this, or for any other reason, an additional vessel MUST be installed on the return to the boiler.
Guidance on vessel sizing is given in Frame 3.
0
C.
0
C. Extra care
5. Filling. The system may be filled by the following
method: Through a temporary hose connection from a 'draw-off'
tap, supplied from a service pipe under mains pressure. Where the mains pressure is excessive, a pressure reducing valve must be used to facilitate filling.
When installing the filling device, it must be connected as below to fully comply with the water regulations.
This may involve the fitting of an additional WRAS approved isolator valve to the mains supply.
i. Thoroughly flush out the whole system with
cold water.
ii. Fill and vent the system until the pressure gauge
registers 1.5 bar, and examine for leaks.
iii. Check the operation of the safety valve by
raising the water pressure until the valve lifts. This should occur within 0.3 bar of the preset lift pressure.
iv. Release water from the system until the
minimum system design pressure is reached;
1.0 bar if the system is to be pre-pressurised.
Mains
water supply
icos system -
CH Return
Ecl 6053
Installation and Servicing
Hose unions
Temporary hose
(disconnect after filling)
Additional stop valve
Double check valve
assembly
(
note direction of flow)
9
GENERAL
5
SYSTEM BALANCING
The boiler does not normally need a bypass but at least some radiators on the heating circuit, of load at least 10% of the minimum boiler output, must be provided with twin lockshield valves so that this minimum heating load is always available. See note regarding thermostatic radiator valves on page 8.
Note.
Systems incorporating zone valves which could completely cut off the flow through the system, must also include a bypass.
BALANCING
1. Set the programmer to ON, for both CH and DHW. Turn
the cylinder thermostat down. Close the manual or thermostatic valves on all radiators,
leaving the twin lockshield valves (on the radiators referred to above) in the OPEN position.
6
WATER TREATMENT
These boilers incorporate an ALUMINIUM heat exchanger.
Turn up the room thermostat and adjust these lockshield valves to give boiler flow and return temperatures not more than 20
These valves should now be left as set.
2. Open all manual or thermostatic radiator valves and adjust
the lockshield valves on the remaining radiators, to give around 15
3. Turn up the cylinder thermostat and adjust the cylinder
balancing valve so that the cylinder achieves a maximum flow consistent with adequate flow to the radiators. Check that with only the domestic hot water loop in circuit a differential temperature of 20 oC across the boiler is not exceeded.
4. Adjust the room and cylinder thermostat and programmer
to NORMAL settings.
o
C apart.
o
C temperature drop at each radiator.
IMPORTANT. The application of any other treatment to this product may render the guarantee of Caradon Ideal Limited INVALID.
Caradon Ideal Limited recommend Water Treatment in accordance with the
Central Heating Systems.
Caradon Ideal Limited recommend the use of Fernox Copal or MB1, GE Betz Sentinel X100 or Salamander Corrosion Guard inhibitors and associated water treatment products, which must be used in accordance with the manufacturers instructions.
For further information contact:
Fernox Manufacturing Co. Ltd, Cookson Electronics, Forsyth Road, Sheerwater, Woking, Surrey. GU21 5RZ. Tel. +44 (0) 1799 521133 or G E Betz Ltd, Sentinel Division, Foundry Lane, Widnes, Cheshire, WA8 8UD. Tel. +44 (0) 151 424 5351 or Salamander Engineering Ltd, Unit 24, Reddicap Trading Estate, Sutton Coldfield, West Midlands B75 7BU. Tel. +44 (0) 121 378 0952
Notes.
Benchmark
Guidance Notes on Water Treatment in
1. It is most important that the correct concentration of the water treatment products is maintained in accordance with the
manufacturers' instructions.
2. If the boiler is installed in an existing system any unsuitable additives MUST be removed by thorough cleansing.
BS7593:1992 details the steps necessary to clean a domestic heating system.
3. In hard water areas, treatment to prevent limescale may be necessary - however the use of artificially softened water is NOT
permitted.
4. Under no circumstances should the boiler be fired before the system has been thoroughly flushed.
7
BOILER ASSEMBLY - Exploded View Legend
1. Front casing panel.
2. Sealing panel.
3. Sump cover.
4. Bottom casing panel.
5. Flue sensing nipple.
6. Return pipe.
8. Flue manifold.
9. Flue manifold fixing.
10. Interpanel.
11. Burner.
12. Combustion chamber ins.
10
13. Heat exchanger
14. Injector & housing.
15. Venturi assembly.
16. Fan assembly.
17. Automatic air vent.
18. Gas service cock.
19. Gas control valve.
20. Fan bracket.
21. Orifice plate.
22. Flue thermistor.
23. Control thermistor.
24. Overheat thermostat.
25. Ignition electrode.
26. Flame detection electrode.
32. Condensate 'S' trap.
35. User control.
36. Primary controls (PCB).
39. Mains switch.
44. Piping frame.
51. Mains connector.
53. Turret gasket.
57. CH return stub.
icos system -
58. CH flow stub.
61. Pressure relief valve.
62. Expansion vessel.
63. Expansion vessel pipe assy.
64. Pressure gauge.
69. Pump.
70. Pump manifold.
75. Control box clamp
Installation and Servicing
8
BOILER ASSEMBLY - Exploded View
16
20
11
17
12
26
25
21
15
INSTALLATION
14
22
8
53
9
10
44
5
INSTALLATION
64
18
62
24
23
58
3
75
32
69
19
13
6
57
4
63
Data badge
2
36
icos system -
39
35
Installation and Servicing
61
70
Ecl 2533
1
51
11
9
UNPACKING
The boiler is supplied fully assembled in one Pack A, together with a standard flue assembly for lengths up to 650mm, rear or side flue outlet, in Pack B.
Unpack and check the contents.
INSTALLATION
INSTALLATION
Pack A Contents
! Hardware Pack & fittings. ! These Installation & Servicing Instructions. ! The User's Instructions. ! The User Control (Display unit). ! Benchmark log book. ! 1 Year guarantee form.
Hardware Pack & Fittings
! 50mm x No.14 wood screws - 4 off. ! Wall plugs (TP2B ) - 4 off.
! Water treatment warning label. ! Turret clamp. ! M5 x 10 pozi Hex screw.
Pack B Contents
Flue turret. Flue terminal. Flue support cutting aid.
! 'S' Trap hose. ! Safety drain pipe nut and olive. ! Flow isolating valve c/w pressure gauge. ! 22mm fibre washers - 3 off. ! Mains connector.
Flue turret
Flue terminal
Ecl 2354
12
icos system -
Installation and Servicing
INSTALLATION
10
PACKAGING REMOVAL
1. Ensure the boiler is stood correctly, as marked on
the carton.
2. Remove the strapping.
3. Fold back the top flaps to gain access to:
! Wall mounting plate. ! Instructions. ! Hardware pack & fittings. ! User control. ! Pre-piping frame
4. Remove the instructions and read thoroughly
before unpacking the product.
INSTALLATION
5. When ready for installation lift off the cardboard
carton.
11
BOTTOM PANEL AND FRONT PANEL REMOVAL
1. Remove the 2 retaining screws from the under
side of the boiler.
2. Pull the panel forward a the bottom and lift to
disengage it from the top lugs.
3. Unscrew and remove the screws from the
underside of the boiler.
4. Pull the RHS of the panel down, slide it to the
right and withdraw.
Ecl 2356
Front panel
icos system -
Installation and Servicing
Ecl 2425
1
Retaining clip
Bottom panel
3
13
INSTALLATION
12
DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED
IMPORTANT.The boiler MUST be installed in a vertical position
Dimension X - Wall thickness. Dimension L - Wall thickness plus boiler spacing . Dimension S - Stand-off frame depth = 33mm.
FLUE KITS Pack B - supplied as standard Pack D - optional extension kit for side flue or rear flue outlet.
Refer to 'Flue Extension Ducts'
Total Flue length dimension Flue
Rear flue Side flue Extra packs
dim. X+160 dim. L+195 required
Up to 650 mm Up to 650 mm none
Up to 1600 mm Up to 1600 mm Pack D - 1 off
Up to 2550 mm Up to 2550 mm Pack D - 2 off
Up to 3500 mm Up to 3500 mm Pack D - 3 off
Up to 4450 mm Up to 4450 mm Pack D - 4 off
Up to 5400 mm Up to 5400 mm Pack D - 5 off
Up to 6000 mm Up to 6000 mm Pack D - 6 off
FLUE OUTLET
14
Notes.
1.
The flue duct MUST be inclined at 1.5 degrees to the horizontal to allow condensate to drain back into the boiler and out through the condensate drain.
2.
If the boiler is to be installed with upward piping routed behind the boiler then the optional stand­off kit should be used. Care must be taken when cutting the ducts and marking the wall to suit this condition.
icos system -
Installation and Servicing
13
ded ce
e
e
ote.
8
g
5
0
5
0
5
0
5
0
5
0
5
FLUE ASSEMBLY - Exploded View
An optional flue duct extension kit is required for wall thicknesses greater than :
Side 455mm (18"). Rear 490mm (19
1/4").
INSTALLATION
2
45
LEGEND
1. Duct assembly.
2. Flue Turret.
3. Turret gasket.
4. M5 x 10 pozi screw.
5. Turret clamp.
Rear flue arrangement shown
14
WALL MOUNTING TEMPLATE
Note.
The template shows the positions of the fixing holes and the flue hole centres for standard installation and for using the stand-off kit. Care MUST be taken to ensure the correct holes are drilled.
1. Separate the templates.
2. Tape template A into the selected position.
3. Ensure squareness by hanging a plumbline as shown. If
fitting a side flue extend the flue centre line onto the side wall. Tape template B into the selected position.
4. Mark onto the wall the following: a The piping frame screw positions (choose one from each
group).
b. The position of the flue duct hole (see diagram below and
template).
Mark the centre of the hole as well as the
Note.
circumference
5. Remove the template from the wall.
See wall mountin
template
1
3
2009
Exten
Ecl 2360
ntre lin
V
icos system -
1
.
1.
1.
istance in metres from side of the boiler to the side wall
N
If wall thickness is greater than 305mm then dimension H must be
reduced by the same amount and the offset may be adjusted accordingly.
44
57
70 83
2.
2. .
96
.
Installation and Servicing
109
122
135
4.
4. .
148
Ecl 2359
.
ee Not
FLUE OUTLET
15
INSTALLATION
15
PREPARING THE WALL
IMPORTANT.
Ensure that, during the cutting operation, masonry falling outside of the building does not cause damage or personal injury.
1. Cut the flue hole (preferably with a 5" core boring
tool), ensuring that the hole is square to the wall. Both wall faces immediately around the cut hole should be flat.
2. Drill 4 holes with a 7mm (
insert the plastic plugs provided, for the piping frame.
3. Locate 4 No.10 x 2" screws in the piping frame
(one at each side, in any of the 3 holes provided at each side) and screw home.
16
CUTTING THE FLUE - REAR Wall thicknesses of 114 to 490mm
1/4") masonry drill and
Section through wall
Rear flue only 5" diameter hole
X
Note. Check all of the hole positions before drilling.
Side flue only 5" diameter hole
2011
Notes.
a. If using the extension ducts go to Frame 18.
b. If the stand-off frame is used it is essential add 33mm
to X, the measured wall thickness, when marking the flue (this will allow for the fitted frame).
1. Measure and note wall thickness X. Refer to Frame
12.
2. Add 90mm (3
from the ring, cut the outer tube only.
3. To ensure the tube is cut square, mark the flue all the
way round.
4. Cut the inner tube to a length 20mm (
aid engagement, using the cardboard support.
17
CUTTING THE FLUE - SIDE Wall thicknesses of 114 to 455mm
Note.
If using the extension ducts go to Frame 18.
1/2") to dimension X and, measuring
3/4") longer to
1. Measure and note side flue length L. Refer to
Frame 12.
2. Add 125mm (5") to dimension L and, measuring
from the ring, cut the outer tube only.
3. To ensure the tube is cut square, mark the flue all
the way round.
4. Cut the inner tube to a length 20mm (
to aid engagement, using the cardboard support.
3/4") longer
FLUE OUTLET
16
icos system -
Installation and Servicing
Loading...
+ 36 hidden pages