Boiler output 'P' =70 °C Mean water kW8.814.714.723.4
temperatureBtu/h30 00050 00050 00080 000
Seasonal efficiency (SEDBUK) *Band D [ 78.8 ]%Band D [ 78.6 ]%
Nox classificationclass 4
* The value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings.
The test data from which it has been calculated have been certified by a notified body.
Note.
Gas consumption is calculated using a calorific value of 38.7
MJ/m3 (1038 Btu/ft3) gross or 34.9 MJ/m3 (935 Btu/ft3) nett. To
obtain the gas consumption at a different calorific value:-
a. For l/s - divide the gross heat input (kW) by the gross C.V.
of the gas (MJ/m3)
3
b. For ft
/h - divide the gross heat input (Btu/h) by the gross
C.V. of the gas (Btu/ft3)
Key to symbols
GB = United Kingdom IE = Ireland
PMS = Maximum operating pressure of water
C13C33C53 = A room sealed appliance designed for connection
via ducts to a horizontal terminal which admits
fresh air to the burner and discharges the
products of combustion to the outside through
orifices which, in this case, are concentric. The
fan is up stream of the combustion chamber.
= An appliance designed for use on 2nd Family gas,
I
2H
Group H only.
(Countries of destination)
CAUTION.
this appliance, care should be taken when handling edges of sheet steel components.
To avoid the possibility of injury during the installation, servicing or cleaning of
The boiler flow and return pipes are supplied fitted to the
boiler ready for top connection
Notes.
a. For the heating loads in excess of 60, 000 Btu/hr boilers,
28mm (1") flow and return pipes should be used to and
from the boiler.
b. This appliance is NOT suitable for use with a direct hot
water cylinder.
2
BOILER CLEARANCESall dimensions in mm (in.)
The following minimum clearances must be maintained for
operation and servicing.
Additional space will be required for installation, depending upon
site conditions.
Side and Rear Flue
a Provided that the flue hole is cut accurately, e.g. with a core
drill, the flue can be installed from inside the building where wall
thicknesses do not exceed 600mm (24"). Where the space into
which the boiler is going to be installed is less than the length of
flue required the flue must be fitted from the outside.
Installation from inside ONLY
b. If a core boring tool is to be used inside
the building the space in which the boiler
is to be installed must be at least wide
enough to accommodate the tool.
5 (1/4")
5 (1/4")
165
(6 1/2")
50 (2")
50
(2")
Ecl 1574
400 (15 3/4")
Front clearance
The minimum front clearance when built in to a cupboard is
5mm (1/4") from the cupboard door but 450mm (17 3/4")
overall clearance is still required, with the cupboard door open,
to allow for servicing.
100 (4")
Jacking
screw
Gas
30 mm
(1
1/8
")
390 (15 3/8")
50 (2")
278 (11")
50 (2")
50 (2")
Flue
terminal
582
(23")
Ecl 1575
111mm
Gas
(4
3/8
")
* Bottom clearance
Bottom clearance after installation can be reduced to 5mm.
However, 100mm must be available for servicing.
4
classic m - Installation & Servicing
GENERAL
INTRODUCTION
The classic m boiler is a fully automatically controlled, wall
mounted, low water content, fan flued, non condensing gas
boiler. It has full modulating central heating outputs of 8.8 kW
(30,000 Btu/h) to 14.7 kW (50,000 Btu/h) and 14.7Kw (50 000
Btu/h) to 23.4Kw (80 000 Btu/h)
The boiler casing is of white painted mild steel with user controls
capable of being mounted remotely from the boiler, if the option
is required.
The heat exchanger is cast iron.
Note. These boilers cannot be used on systems which include
gravity circulation.
The boilers are suitable for connection to fully pumped, open
vented or sealed water systems. Adequate arrangements for
completely draining the system by provision of drain cocks
MUST be provided in the installation pipework.
OPERATION
When there is a demand for heat, the heating system is supplied
selected temperature of between 65oC and 82oC.
The boiler features a comprehensive diagnostic system which
gives detailed information on the boiler status when operating
and performance of key components to aid commissioning and
fault finding.
BS. 5440:2 Ventilation (for gas appliances of rated input not
exceeding 70 kW).
BS. 5449Forced circulation hot water systems.
BS. 5546Installation of gas hot water supplies for domestic
purposes (2nd Family Gases).
BS. 6798Installation of gas fired hot water boilers of rated
input not exceeding 60 kW.
BS. 6891Low pressure installation pipes.
Health & Safety Document No. 635
The Electricity at Work Regulations, 1989.
The manufacturer’s notes must NOT be taken, in any way, as
overriding statutory obligations.
IMPORTANT. These appliances are CE certificated for safety
and performance. It is, therefore, important that no external
control devices, e.g. flue dampers, economisers etc., are directly
connected to these appliances unless covered by these
Installation and Servicing Instructions or as otherwise
recommended by Caradon Plumbing Limited in writing. If in
doubt please enquire.
Any direct connection of a control device not approved by
Caradon Plumbing Ltd. could invalidate the certification and
the normal appliance warranty. It could also infringe the Gas
Safety Regulations and the above regulations.
OPTIONAL EXTRA KITS
z D Pack Flue Extension Ducts (1000mm long)
z Flue Finishing Kit
o
Elbow Kit (Maximum 2 per installation)
z 90
o
Elbow Kit (Maximum 2 per installation)
z 45
z Roof flue Kit
z Powered Vertical Flue Kit
z Remote User Controls Kit
z Boiler Stand-off Kit
SAFETY
Current Gas Safety (Installation and Use) Regulations or rules
in force.
It is law that all gas appliances are installed and serviced by a
CORGI registered installer in accordance with the above
regulations. Failure to install appliances correctly could lead to
prosecution. It is in your own interest, and that of safety, to
ensure the law is complied with.
The installation of the boiler MUST also be in accordance with
the latest I.E.E (BS 7671) Wiring Regulations, local building
regulations, bye-laws of the local water authority, the building
regulations and the Building Standards (Scotland) and any
relevant requirements of the local authority.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation
panels, which can cause irritation to the skin. No asbestos,
mercury or CFCs are included in any part of the boiler or its
manufacture.
LOCATION OF BOILER
The boiler must be installed on a flat and vertical wall, capable
of adequately supporting the weight of the boiler and any
ancillary equipment.
The boiler may be fitted on a combustible wall and insulation
between the wall and the boiler is not necessary, unless
required by the local authority.
For electrical safety reasons there must be no access from the
back of the boiler.
The boiler must not be fitted outside.
Detailed recommendations are contained in the following British
Standard Codes of Practice:
BS. 5440:1Flues (for gas appliances of rated input not
exceeding 70 kW).
classic m - Installation & Servicing
Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should be
fitted in accordance with the British Gas publication 'Guide for
Gas Installations in Timber Frame Housing', reference IGE/UP/
7:1998.
5
GENERAL
Compartment Installations
A compartment used to enclose the boiler should be designed
and constructed specially for this purpose.
An existing cupboard or compartment may be used, provided
that it is modified for the purpose.
In both cases details of essential features of cupboard /
compartment design, including airing cupboard installation, are
to conform to the following:
z BS. 6798. (No cupboard ventilation is required - see “Air
Supply” for details).
z The position selected for installation MUST allow adequate
space for servicing in front of the boiler.
z For the minimum clearances required for safety and
subsequent service, see the wall mounting template and
Frame 2. In addition, sufficient space may be required to
allow lifting access to the wall mounting plate.
GAS SUPPLY
The local gas supplier should be consulted, at the installation
planning stage, in order to establish the availability of an
adequate supply of gas. An existing service pipe must NOT be
used without prior consultation with the local gas supplier. The
boiler must installed on a gas supply with a governed meter
only.
A gas meter can only be connected by the local gas supplier or
by a registered CORGI engineer.
An existing meter should be checked, preferably by the gas
supplier, to ensure that the meter is adequate to deal with the
rate of gas supply required. A working gas pressure of
20 mbar should be available at the boiler inlet.
IMPORTANT.
Installation pipes MUST be fitted in accordance with BS. 6891.
Pipework from the meter to the boiler MUST be of an adequate
size, i.e. not less than 15mm O.D.
The complete installation MUST be tested for gas soundness
and purged as described in the above code.
Table 3 - Balanced flue terminal position
Terminal Position
1. Directly below or alongside an
opening window, air vent or other300 mm (12")
ventilation opening
2. Below guttering, drain pipes or soil
pipes75 mm ( 3")
3. Below eaves200 mm ( 8")
4. Below balconies or a car port roof200 mm ( 8")
5. From vertical drain pipes or soil pipes75 mm ( 3")
6. From internal or external corners300mm (12")
7. Above adjacent ground, roof or
balcony level300 mm (12")
8. From a surface facing the terminal600 mm (24")
9. From a terminal facing a terminal1200 mm (48")
10. From an opening in a car port
(e.g. door or window) into dwelling1200 mm (48")
11. Vertically from a terminal on the
same wall1500 mm (60")
12. Horizontally from a terminal on the wall300 mm (12")
boiler MUST NOT be closer than 25mm (1") to combustible
material. Detailed recommendations on the protection of
combustible material are given in BS. 5440: 2000.
Minimum Spacing
IMPORTANT. It is absolutely ESSENTIAL to ensure, in
practice, that products of combustion discharging from the
terminal cannot re-enter the building or any other adjacent
building through ventilators, windows, doors, other sources of
natural air infiltration, or forced ventilation / air conditioning.
If this should occur the appliance MUST be turned OFF, labelled
as 'unsafe' until corrective action taken.
TERMINAL
The terminal assembly can be adapted to accommodate various
wall thicknesses. Refer to Frame 11 - Unpacking.
FLUE INSTALLATION
The flue must be installed in accordance with the
recommendations of BS. 5440: Part 1.
The following notes are intended for general guidance.
1. The boiler MUST be installed so that the terminal is exposed
to external air.
2. It is important that the position of the terminal allows the free
passage of air across it at all times.
3. Minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in
Table 3.
4. Where the lowest part of the terminal is fitted less than 2m
(6'6") above a balcony, above ground or above a flat roof to
which people have access, then the terminal MUST be
protected by a purpose designed guard.
Ensure that the guard is fitted centrally.
5. Where the terminal is fitted within 850mm (34") of a plastic or
painted gutter or 450mm (18") of painted eaves then an
aluminium shield at least 750mm (30") long should be fitted
centrally to the underside of the gutter or painted surface.
6. The air inlet/products outlet duct and the terminal of the
AIR SUPPLY
It is NOT necessary to have a purpose-provided air vent in the
room or internal space in which the boiler is installed. Neither is
it necessary to ventilate a cupboard or compartment in which the
boiler is installed, due to the low surface temperatures of the
boiler casing during operation; therefore the requirements of BS
6798, Clause 12, and BS 5440:2 may be disregarded.
WATER CIRCULATION SYSTEM
For the types of system and correct piping procedure see
Frames 1, and 3 to 8.
The central heating system should be in accordance with
BS. 6798 and, in addition, for smallbore and microbore systems,
BS. 5449.
WATER TREATMENT - see Frame 9
The hot water storage cylinder MUST be of the indirect type and
should preferably be manufactured of copper.
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The appliances are NOT suitable for gravity central heating nor
are they suitable for the provision of gravity domestic hot water.
6
classic m - Installation & Servicing
GENERAL
The hot water cylinder and ancillary pipework, not forming part
of the useful heating surface, should be lagged to prevent heat
loss and any possible freezing - particularly where pipes run
through roof spaces and ventilated underfloor spaces.
The boiler must be vented.
The hydraulic resistance of the boilers, at MAXIMUM OUTPUT,
with an 11 oC (20 oF) temperature differential, is shown in
Graph 1.
Graph 1 - Water flow rate and pressure loss
1.0
0.5
THERMOSTATIC RADIATOR VALVES (TRV)
Caradon Plumbing Ltd. recommend that heating systems
utilising full thermostatic radiator valve control of temperature in
individual rooms should also be fitted with a room thermostat
controlling the temperature in a space served by radiators not
fitted with such a valve as stated in BS. 5449.
For further information refer to the 'Good Practice Guide 143',
publication of the Energy Efficiency Office, available from the
Building Research Establishment, Garston, Watford WD2 7JR.
Tel: 01923 664 258
ELECTRICAL SUPPLY
Wiring external to the appliance MUST be in accordance with
the current I.E.E. (BS.7671) Wiring Regulations and any local
regulations which apply.
The point of connection to the mains should be readily
accessible and adjacent to the boiler.
Pressure Drop Across Boiler
(metres water)
8.811.714.717.620.523.4
Boiler Output (kW)
Ecl 1603
classic m - Installation & Servicing
7
GENERAL
3
OPEN VENT SYSTEM REQUIREMENTS
The system should be vented directly off the boiler flow pipe, as close to the
boiler as possible. The cold feed entry should be inverted and MUST be
positioned between the pump and the vent, and not more than 150mm (6")
away from the vent connection.
Note.Combined feed and vent pipes may also be fitted.
There should be a minimum height, 450mm (18"), of open vent above the
cistern water level. If this is not possible refer to
Frame 5. The vertical distance between the highest point of the system and
the feed/expansion cistern water level MUST not be less than 450 mm (18").
The pump must be fitted on the flow side of the boiler.
A suitable pump is a domestic circulator capable of providing a maximum
o
C (20oF) temperature differential across the boiler with the whole of the
11
heating circuit open (e.g. Grundfos UPS 15/50, 15/60 or equivalent). With the
minimum flow circuit allowed by the controls the differential must not exceed
25 oC.
The vertical distance between the pump and feed/expansion cistern MUST
comply with the pump manufacturer's minimum requirements, to avoid
cavitation. Should these conditions not apply either lower the pump position
or raise the cistern above the minimum requirement specified by CaradonPlumbing Ltd. The isolation valves should be fitted as close to the pump as
possible.
Ecl 1604
4
SCHEMATIC PIPEWORK AND SYSTEM BALANCING
The boiler does not normally need a
bypass but at least some radiators on the
heating circuit, of load at least 10% of the
minimum boiler output, must be provided
with twin lockshield valves so that this
minimum heating load is always available
(see footnote re. thermostatic radiator
valves).
Balancing
1. Set the programmer to ON for both
CH and HW. Turn the cylinder
thermostat down. Close the manual
or thermostatic valves on all radiators,
leaving the twin lockshield valves (on
the radiators referred to above) in the
open position. Turn up the room
thermostat and adjust these lockshield
valves to give boiler flow and return
temperatures not more than 20
apart. These valves should now be left
as set.
2. Open all manual or thermostatic
radiator valves and adjust the
lockshield valves on remaining
radiators to give around 11
temperature drop at each radiator.
3. Turn up the cylinder thermostat and
adjust the cylinder balancing valve so
that the cylinder achieves a maximum
flow consistent with adequate flow to
the radiators. Check that with only the
domestic hot water loop in circuit a
differential temperature of 20
across the boiler is not exceeded.
4. Adjust room and cylinder thermostats
and programmer to NORMAL settings.
o
C
o
C
o
C
Ecl 1605
Note.
Systems incorporating zone valves which
could completely shut off the flow through
the system, must be wired such that the
boiler will not fire or continue to fire when
this occurs.
8
classic m - Installation & Servicing
GENERAL
5
LOW HEAD AND LARGE SYSTEMS WITH EXTENSIVE PIPE RUNS - OPEN VENT
This arrangement is useful for large systems where
radiators at the extremities are difficult to vent. This can
lead to pumping over with conventional feed and vent
arrangements.
The following conditions MUST be observed:
1. The top of the automatic air vent must be below the
cold water level.
2. The static water level (cold) must be at least 200mm
above the top of the horizontal flow pipe, fitted as
shown. The vent connection MUST NOT be made
immediately off the top of the boiler as venting is
made less efficient.
3. The maximum practical length of 22mm cold feed pipe
should be used in order to reduce the effective
volume of hot system water expanding into the feed/
expansion cistern to a minimum.
Note.The pump manufacturers' minimum requirements must be complied with.
Ecl 1606
Ecl 1606
All dimensions in mm (in.).
NB. Imperial dimensions are approximate
6
SEALED SYSTEM REQUIREMENTS
Note. The method of filling, refilling, topping up or flushing
sealed primary hot water circuit from the mains via a
temporary hose connection is only allowed if acceptable
to the local water authority.
1. General
a. The installation must
comply with the
requirements of BS.
6798 and BS. 5449.
b. The installation
should be designed
to work with flow
temperatures of up
to 82° C.
c. All components of the
system, including the
heat exchanger of the
indirect cylinder, must
be suitable for a working pressure of 3 bar (45lb/in
) and temperature of 110°C. Care should be taken
in making all connections so that the risk of leakage
is minimised.
2. Safety Valve
A spring loaded safety valve complying with the relevant
requirements of BS. 6759 must be fitted in the flow pipe
as close to the boiler as possible and with no intervening
valve or restriction. The valve should have the following
features:
a. A non-adjustable preset lift pressure not exceeding
3bar (45lb/in
b. A manual testing device.
2
).
2
c. Provision for connection of a discharge pipe.
3. Pressure Gauge
A pressure gauge covering at least the range 0-4 bar
(0-60 lb/in
be easily seen from the filling point and should preferably be
connected at the same point as the expansion vessel.
The valve or discharge pipe should be positioned so that
the discharge of water or steam cannot create a hazard
to the occupants of the premises or cause damage to
electrical components and wiring.
2
) must be fitted to the system. The gauge should
classic m - Installation & Servicing
9
7
SEALED SYSTEM REQUIREMENTS - continued
4. Expansion Vessel
a. A diaphragm type expansion vessel must be
connected to a point close to the inlet side of the
pump, the connecting pipe being not less than 15
1/2" nominal) size and not incorporating valves
mm (
of any sort.
b. The vessel capacity must be adequate to accept the
expansion of the system water when heated to 110°
C (230° F).
c. The charge pressure must not be less than the static
water head above the vessel. The pressure attained
in the system when heated to 110° C (230° F) should
be at least 0.35 bar (5 Ib/in
2
) less than the lift
pressure of the safety valve.
For guidance on vessel sizing refer to the table in
Frame 8.
For further details refer to BS. 5449, BS. 7074:1 and
the British Gas Corporation publication 'Material and
Installation Specifications for Domestic Central
Heating and Hot Water'.
5. Cylinder
The cylinder must be either of the indirect coil type or a
direct cylinder fitted with an immersion calorifier which is
suitable for operating on a gauge pressure of 0.35 bar
2
(5 Ib/in
) in excess of the safety valve setting. Single feed
indirect cylinders are not suitable for sealed systems.
6. Make-up Water
Provision must be made for replacing water loss from the
system, either:
a. From a manually filled make-up vessel with a readily
visible water level. The vessel should be mounted at
least 150 mm (6") above the highest point of the
system, and be connected through a non-return
valve to the system, fitted at least 300 mm (12")
below the make-up vessel on the return side of the
domestic hot water cylinder or radiators.
or
b. Where access to a make-up vessel would be difficult
by pre-pressurisation of the system. Refer to 'Filling',
below.
7. Mains Connection
There must be no direct connection to the mains water
supply or to the water storage tank supplying domestic
water, even through a non-return valve, without the
approval of the local water authority.
8. Filling
The system may be filled by one of the following
methods:
a. Through a cistern, used for no other purposes, via a
ball valve permanently connected directly to a
service pipe and/or a cold water distributing pipe.
The static head available from the cistern should be
adequate to provide the desired initial system design
pressure. The cold feed pipe from the cistern should
GENERAL
include a non-return valve and a stop valve with an
automatic air vent connected between them, the stop
valve being located between the system and the
automatic air vent. The stop valve may remain open
during normal operation of the system if automatic
water make-up is required.
b. Through a self-contained unit comprising a cistern,
pressure booster pump (if required) and, if necessary,
an automatic pressure reducing valve and flow
restrictor. The cistern should be supplied through a
temporary connection from a service pipe or cold
water distributing pipe.
This unit may remain permanently connected to the
heating system to provide limited automatic water
make-up. Where the temporary connection is
supplied from a service pipe or distributing pipe which
also supplies other draw-off points at a lower level
then a double check valve shall be installed upstream
of the draw-off point.
c. Through a temporary hose connection from a draw-off
tap supplied from a service pipe under mains
pressure. Where the mains pressure is excessive a
pressure reducing valve shall be used to facilitate
filling.
The following fittings shall form a permanent part of
the system and shall be fitted in the order stated:
A stop valve complying with the requirements of
BS. 1010, Part 2 (the hose from the draw-off tap shall
be connected to this fitting).
A test cock.
A double check valve of an approved type.
• Thoroughly flush out the whole of the system with
cold water, without the pump in position.
• With the pump fitted, fill and vent the system until the
pressure gauge registers 1.5 bar (21.5lb/in
2
).
Examine for leaks.
• Check the operation of the safety valve by manually
raising the water pressure until the valve lifts. This
should occur within ± 0.3 bar (± 4.3lb/in
2.
) of the pre-
set lift pressure.
• Release water from the system until the initial
system design pressure is reached.
• Light the boiler and heat the system to the maximum
working temperature. Examine for leaks.
• Turn off the boiler and drain the system while still
hot.
• Refill and vent the system.
• Adjust the initial pressure to the required value.
Sizing procedure for expansion vessels: The volume of the expansion vessel (litres) fitted to a sealed system shall not be
less than that given by the table on the following page, multiplied by a factor of 0.8 (for flow temperatures of less than 83 °C).
10
classic m - Installation & Servicing
GENERAL
8
SEALED SYSTEM REQUIREMENTS - continued
Safety valve setting3.0 bar2.5 bar2.0 bar
Vessel charge and initial0.51.01.50.51.01.50.51.0
system pressurebarbarbarbarbarbarbarbar
Total water content of systemExpansion vessel volume litres
25litres2.12.73.92.33.35.92.85.0
504.25.47.84.76.711.85.610.0
756.38.211.77.010.017.78.415.0
1008.310.915.69.413.423.711.320.0
12510.413.619.511.716.729.614.125.0
15012.516.323.414.120.135.516.930.0
17514.619.127.316.423.441.419.735.0
20016.721.831.218.826.847.422.640.0
22518.724.535.121.130.153.325.445.0
25020.827.239.023.533.559.228.250.0
27522.930.042.925.836.865.131.055.0
30025.032.746.828.240.271.133.960.0
Multiplying factors for
other system volumes0.08330.1090.1560.0940.1340.2370.1130.20
9
WATER TREATMENT
The classic m boiler has a cast iron heat exchanger
IMPORTANT.
The application of any other treatment to this product may render the guarantee of Caradon Plumbing
invalid.
If water treatment is used Caradon Plumbing Ltd. recommend only the use of FERNOX or SENTINEL water treatment
products, which must be used in accordance with the manufacturers' instructions. For further information contact:
Fernox Manufacturing Co. Ltd.
Tandem House
Marlowe Way
Croydon
Surrey CRO 4XS
Tel: 0870 5601 5000
Notes.
1. It is most important that the correct concentration of the
water treatment product is maintained in accordance with
the manufacturers' instructions.
2. If the boiler is installed in an existing system any unsuitable
additives MUST be removed by thorough cleansing.
BS. 7593:1992 details the steps necessary to clean a
domestic central heating system.
3. In hard water areas, treatment to prevent lime scale
may be necessary - however, the use of artificially
softened water is NOT permitted.
4. Under no circumstances should the boiler be fired
before the system has been thoroughly flushed.
Sentinel Division
Betz Dearborn Ltd.
Widnes
Cheshire
WA8 8UD
Tel:0151 424 5351
classic m - Installation & Servicing
11
10
BOILER ASSEMBLY - Exploded view
INSTALLATION
INSTALLATION
8
53
5
44
9
10
7
23
2
24
6
13
25
1
LEGEND
1.Front casing panel.
2.Case sealing panel.
4.Bottom cover panel.
5.Flue sensing nipple.
6.Flue baffle (5080 only).
7.Flue hood.
8.Flue connection.
9.Flue hood clip.
42
26
15
16
10. Flue hood seal.
11. Burner assy.
12. C/Cham Insulation.
13. Heat engine.
14. Injector & housing.
15. Venturi assy.
16. Fan assy.
17. Gas pipe assy.
21
14
20
19
17
35
19. Gas valve assy.
20. Fan bracket assy.
21. Orifice plate.
23. Control thermistor.
24. Overheat thermostat.
25. Igniton electrode.
26. Flame sensing electrode.
35. User control.
12
11
Ecl 1628
4
51
36
36. PCB - primary controls.
42. Sightglass.
44. Wall mtg. plate.
51. Mains connector.
53. Turret gasket .
12
classic m - Installation & Servicing
INSTALLATION
11
UNPACKING
The boiler is supplied fully assembled in one Pack A,
together with a standard flue assembly for lengths up to
460mm, rear or side flue outlet, in Pack B.
Optional extras if ordered are supplied in separate boxes.
Unpack and check the contents.
Pack A Contents
Also contained in Pack A:
z Hardware Pack (listed below).
z These Installation & Servicing Instructions.
z The User's Instructions.
z The User's control.
z Benchmark log book.
Hardware Pack
z 50mm x No.10 wood screws -
3 off.
z Wall plugs (TP2B ) - 3 off.
z Turret clamp.
z M5 x 10 pozi Hex screw.
z Mains connector.
INSTALLATION
Pack B Contents
zFlue turret.
zFlue terminal.
zFlue support cutting aid.
12
PACKAGING REMOVAL
1. Ensure the boiler is stood correctly as marked on the
carton.
2. Remove the strapping.
3. Fold back the top flaps to gain access to the wall
mounting plate, instructions, user controls and
hardware pack.
Ecl 1608
Flue turret assembly
Ecl 1460
Flue terminal
4. Remove instructions and read thoroughly before
unpacking, user’s controls and hardware pack and
retain in safe place.
5. Lift off the cardboard carton.
6. Dispose of packaging.
classic m - Installation & Servicing
Ecl 1576
13
INSTALLATION
13
FRONT PANEL AND BOTTOM PANEL REMOVAL
1. Remove the 2 retaining screws.
2. Lift front panel and remove.
3. Remove the 2 bottom panel screws.
4. Allow the RHS of the bottom panel to lower slightly.
5. Withdraw the LHS of the bottom panel from the retaining
clips.
6. Place bottom and front panel to one side to avoid
damage.
Ecl 157
3
INSTALLATION
14
DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED
IMPORTANT.
The boiler MUST be installed in a vertical position
Dimension X - Wall thickness.
Dimension L - Wall thickness plus
boiler spacing.
Dimension S - Stand-off frame depth = 33mm
FLUE KITS
Pack B - supplied as standard
Pack D - optional extension kit for side flue
or rear flue outlet.
Refer to 'Flue Extension Ducts'
1
160 + S = 193mm
160mm
Total Flue length dimensionFlue
Rear flueSide flueExtra packs
dim. X+160flue dim. L+195required
Up to 480 mmUp to 480 mmnone
Up to 1430 mmUp to 1430 mmPack D - 1 off
Up to 2380 mmUp to 2380 mmPack D - 2 off
Up to 3000 mmUp to 3000 mmPack D - 3 off
Note.
If the boiler is to be installed with downward routing of
pipes then the optional stand-off kit can be used. Care
must taken when cutting the ducts and marking the wall
to suit this condition.
Ecl 1578
14
classic m - Installation & Servicing
INSTALLATION
Ecl 1579
5
4
3
2
6
1
15
FLUE ASSEMBLY - Exploded View
1. An optional flue duct extension kit is required for wall
thicknesses greater than :
Side300mm (11
Rear345mm (13
LEGEND
1. Duct assembly.
2. Flue Turret.
3. Turret gasket.
4. M5 x 10 pozi screw.
5. Turret clamp.
Rear flue arrangement shown
3/4").
1/2").
16
WALL MOUNTING TEMPLATE
1. Separate the templates.
2. Tape template A into the selected position.
3. Ensure squareness by hanging a plumbline as shown. If
fitting a side flue extend the flue centre line onto the side
wall, tape template B into selected position.
4. Mark onto the wall the following:
a. The wall mounting plate screw positions (choose one
from each group) and lower fixing screw position.
b. The position of the flue duct hole.
Note.
Mark the centre of the hole as well as the
circumference
4. Remove the template from the wall.
classic m - Installation & Servicing
Ecl1675
FLUE OUTLET
15
17
PREPARING THE WALL
IMPORTANT. Ensure that, during the cutting
operation, masonry falling outside of the building
does not cause damage or personal injury.
1. Cut the flue hole (preferably with a 5" core boring
tool), ensuring that the hole is square to the wall.
Both wall faces immediately around the cut hole
should be flat.
2. Drill 3 holes with a 7mm (
insert the plastic plugs provided, for the wall
mounting plate and the jacking screw plate.
Note.
If using the stand-off kit then drill 4 holes
(choosing one from each group but not the
jacking screw).
3. Locate two No.10 x 2" screws in the wall
mounting plate (one at each side, in any of the 3
holes provided at each side) and screw home.
Note.
If using the stand-0ff kit then locate the stand-off
channel and screw home.
1/4") masonry drill and
INSTALLATION
18
CUTTING THE FLUE - REARWall thicknesses of 114 to 345mm
Note. If using the extension ducts go to Frame 20.
If the stand-off frame is used it is essential to add
33mm to dimension X.
1. Measure and note wall thickness X. Refer Frame 14.
2. Add 75mm (3 ") to dimension X and, measuring from
the groove, cut the outer tube only.
3. To ensure the tube is cut square, mark the flue all the
way round.
4. Cut the inner tube to a length 20mm (3/4") longer to aid
engagement. Use the cardboard support.
19
CUTTING THE FLUE - SIDEWall thicknesses of 114 to 300mm
Note. If using the extension ducts go to Frame 20.
1. Measure and note wall thickness X. Refer Frame 14.
2. Add 115mm (4 1/2 ") to dimension X and, measuring
from the groove, cut the outer tube only.
3. To ensure the tube is cut square, mark the flue all the
way round.
4. Cut the inner tube to a length 20mm (3/4") longer to aid
engagement. Use the cardboard support.
Ecl 1461
Ecl 1461
FLUE OUTLET
16
classic m - Installation & Servicing
INSTALLATION
20
FLUE EXTENSION DUCTS - For flue lengths greater than 480mm
Pack D Flue extension duct kit contents.
Extension duct & clamp
1.0m (39") long
Flue support cutting aid
(shown folded up)
Wall plugs - 4 off
Ecl 1244
21
FLUE EXTENSION DUCTS - continued
Use a maximum of 3m extended flue ONLY
Flue duct support
General arrangement
1. A maximum of 3 extension ducts (one suitably
cut) plus the standard flue duct may be used
together.
2. Flue extensions of greater length than 1m (39")
should be supported with the bracket provided,
suitably adjusted. Refer to Frame 24.
Note. Side flue shown
No. 10 x2" wood screw - 4 off
Flue length
Extension flue
Standard flue
Boiler
Ecl 1591
Terminal grille
22
FITTING THE KIT
1. Remove the cardboard support aid from the flue and
place safely to one side.
2. Fit the inner flue extension duct onto the inner flue duct.
3. Fit the outer flue extension duct onto the outer air duct.
4. Using the clamp provided clamp the flue lengths together.
5. Repeat steps 1-4 if a second flue extension is required.
6. Measure and mark the flue length required onto the flue,
measuring from the groove near the terminal.
7. To ensure a square cut, mark the flue all the way round.
8. Cut to length using the cardboard support aid.
9. Remove the cardboard off-cut and deburr the metal
edges.
classic m - Installation & Servicing
2
3
GROOVE
9
Ecl 1532
FLUE OUTLET
17
23
MOUNTING THE BOILER
1. Lift the boiler onto the wall mounting plate, as
shown.
2. Check the boiler alignment using a spirit level
and adjust as necessary with the jacking screw.
3. Align the hole in the jacking plate with the predrilled hole in the wall and fix in position with
the No.10 x 2" screw provided.
INSTALLATION
INSTALLATION
24
CONNECTING THE FLUE TO THE BOILER
1. Insert the flue assembly through the prepared hole in the
wall.
2. Locate the flue turret on the top of the boiler, ensuring
that the turret gasket is in place.
3. Locate the flue into the turret.
4. Secure the flue turret on top of the boiler by inserting the
open ends of the turret
clamp under the 2 studs and
fixing it in the middle with
the single M5 x 10mm pozihex screw provided.
5. Flues over 1 metre long.
Fix the flue support bracket
to the wall, using the wall
plug and wood screw. For
standard installations use
the short wood screw.
If the stand-off option is
used, secure the support
bracket using the spacer
bracket and long wood
screw.
4
gasket
1
2
18
Ecl1592
classic m - Installation & Servicing
INSTALLATION
25
BOILER WATER CONNECTIONS
The boiler flow and return pipes are supplied fitted to the boiler
and ready for top connection.
Note. For heating loads in excess of 60 000 Btu/hr use 28mm
connectors.
TOP CONNECTION
Connect the system pipework to the boiler flow and return pipes.
Return
Flow
INSTALLATION
Ecl 1573
26
GAS CONNECTION
IMPORTANT. The gas service cock contains a non-metallic
seal so must not be overheated when making capillary
connections.
Refer to Frame 2 for details of the position of the gas
connection.
A working gas pressure of 20 mbar (8" w.g.) should be
27
ELECTRICAL CONNECTIONS
available at the boiler inlet with the boiler firing. Refer to Frame
33 or 'Servicing' for details of the pressure test point position.
Extend a gas supply pipe NOT LESS THAN 15mm O.D. to
the boiler and connect to the gas service cock via the union.
Ensure that the gas supply pipe does not foul the boiler
casing.
WARNING. This appliance MUST be earthed.
A mains supply of 230 V ~ 50 Hz is required.
The fuse rating should be 3 A.
Wiring external to the boiler MUST be in accordance with the
current I.E.E. (BS.7671) Wiring Regulations and any local
regulations.
classic m - Installation & Servicing
All external controls and wiring MUST be suitable for mains
voltage.
Wiring should be 3 core PVC insulated cable NOT LESS
than 0.75 mm
Connection must be made in a way that allows complete
isolation of the electrical supply - such as a double pole
switch having a 3mm (
poles, or a plug and socket serving only the boiler and
system controls. The means of isolation must be accessible
to the user after installation.
2
(24 x 0.2mm) and to BS. 6500, Table 16.
1/8") contact separation in both
19
INSTALLATION
28
INTERNAL WIRING
A pictorial wiring diagram is shown in Frame 29 .
1. Route the mains cable into the bottom Rear centre of the boiler.
2. Wire the live and neutral and earth wires into the plug.
Note. Ensure that the lengths of the current carrying conductors
are shorter than the earth conductor so that if the cable slips in its
anchorage the current carrying conductors become taut before the
earth conductor.
3. Secure the mains lead with the cable clamp.
4. Reconnect the mains lead plug. Ensure it is fully located.
Note. Wire any switched live supply into L2.
INSTALLATION
L3
N
Ecl 1542
Incoming mains
wiring detail
Removelinkwhenconnectingexternalprogrammer.
29
EXTERNAL ELECTRICAL CONTROLS
Wiring external to the boiler MUST be in accordance with the
current I.E.E. (BS.7671) Wiring Regulations and any local
regulations.
The fuse should be 3A.
Room Thermostat
If the thermostat has a neutral connection use it. (It provides
for more energy efficient operation by reducing switching
temperature differentials.)
If parts of the pipework run outside the house or if the boiler
will be left off for more than a day or so then a frost thermostat
should be wired into the system. This is usually done at the
programmer, in which case the programmer selector switches
are set to OFF and all other controls MUST be left in the
running position.
The frost thermostat should be sited in a cold place but where
it can sense heat from the system.
Note. If the boiler is installed in a garage it may be necessary
to fit a pipe thermostat, preferably on the return pipework.
Designation of the terminals will vary but the programmer and
thermostat manufacturers' leaflets will give full details.
Diagram A shows an application to boilers fitted with a room
thermostat only
L2
L1
MainsPlug
(suppliedinhardwarepack)
A
L3
Optional Frost ’stat
B
Mains in
C
Socket
(fixedtoboiler)
N
Mains in
L3L2 L1
L2
N
Optional Frost ’stat
L1
System controls
L3L2 L1N
Ecl1257
Room ’stat
if required
Room ’stat
if required
N
System
controls
N
System
controls
Ecl 1543
Ecl 1544
Diagrams B and C show applications to boilers fitted with
alternative time controls.
Earths are not shown for clarity but must never be omitted.
20
Mains in
Room ’stat
Ecl 1545
N
if required
Optional Frost ’stat
classic m - Installation & Servicing
30
PICTORIAL WIRING
Fan
INSTALLATION
pk
b
bk
r
y
or
or
Overheat
thermostat
r
r
Permanent
black link
Control
thermistor
MAINS
SUPPLY
230V 50Hz
bk
br
Fused at
3.15ATL
Control PCB
Gas valve
Chassis
earth y/g
y/g
b
bk
b
or
or
y
bk
b
bk
b
Service
connection
INSTALLATION
b
r
LEGEND
b- blue
bk - black
br - brown
r- red
w - white
or - orange
classic m - Installation & Servicing
r
r
User control
and display
pkr
pk
vv
Ecl 1848
pk
y/g
br
ON /
OFF
Switch
y- yellow
pk - pink
y/g - yellow/green
21
31
FUNCTIONAL FLOW WIRING DIAGRAM
INSTALLATION
INSTALLATION
Mains Switch
DC
Fan
electrode
Ecl 1849
3
2
1
Flame detection electrode
r
Control thermistor
b
r
br
r
bk
y
pk
b
r
y/g
r
r
PCB
vv
bk
or
or
br
External switch.e.g.
room'stat, programmer
b
Overheat
thermostat
DC Gas valve
y/g
bk
b
L
N
LEGEND
b- blue
bk - black
br - brown
32
COMMISSIONING AND TESTING
A. Electrical Installation
1. Checks to ensure electrical safety should be carried out by a
competent person.
2. ALWAYS carry out the preliminary electrical system checks, i.e.
earth continuity, polarity, resistance to earth and short circuit,
using a suitable test meter.
r- red
y- yellow
w - white
WARNING. Whilst effecting the required gas soundness test and purging air from the gas
installation, open all windows and doors, extinguish naked lights and DO NOT SMOKE.
22
y/g - yellow/green
gy - grey
v- violet
pk - pink
or - orange
B. Gas Installation
1. The whole of the gas installation, including the meter, should
be inspected and tested for soundness and purged in
accordance with the recommendations of BS. 6891.
2. Purge air from the gas installation by the approved methods
only.
classic m - Installation & Servicing
INSTALLATION
33
INITIAL LIGHTING
LEGEND
A On/Off switch.
B Thermostat knob.
C 'Mains On' neon.
D 'Burner On' neon.
E Reset button.
F Inlet pressure test point.
G Gas service cock.
1. Check that the system has been filled and that the boiler is
not air locked.
H Casing pressure test point.
J Overheat thermostat.
K Flow thermistor.
Note. Boiler is shown with the front panel and sealing panel removed.
J
K
2. Check that all drain cocks are closed and any valves in the
flow and return are open.
3. Check the electrical supply is off.
4. Refit the boiler sealing panel
5. Check the gas service is ON and the On/Off switch is OFF.
6. Carefully align the user control and gently push into place
and secure with the single screw located underneath.
7. Remove the screw in the inlet pressure test point and
connect a gas pressure gauge via a flexible tube .
8. Switch the electricity supply ON and check all external
controls are calling for heat.
9. Set the boiler thermostat knob to maximum position and
switch the boiler ON - OFF switch to ON the RED mains ON
neon should now be illuminated. The boiler control should
now go through its ignition sequence until the burner is
established.
10. If the boiler does not light after 3 attempts the fault codes
'L' 'F' will be displayed. Press the reset button; the boiler
will then repeat its ignition sequence. When the burner is
established the GREEN burner ON neon will be
permanently illuminated
11. Ensure that with the boiler operating the dynamic gas
pressure is 20 mb.
IMPORTANT.
The gas input to the burner is regulated by the gas
valve according to the air flow produced by the fan. It is
NOT user-adjustable. Any interference to sealed
settings on the gas valve will adversely affect operation
and render our warranty void.
6
Ecl 1619
14
14
Ecl 1280
E
LED Display
D
C
F
A
B
H
G
12. Switch OFF the ON-OFF switch.
13. Remove the pressure gauge and tube. Replace the
sealing screw in pressure test point. Ensure a gas tight
seal is made.
14. Refit the boiler front panel and bottom panel .
THE DISPLAY
The user controls has one neon and one display to inform the
user about the status. The display will show the status of the
boiler. The neon will show the status of the flame. If no flame
is detected the neon is blinking. When the flame is detected
the neon will be lit permanently.
Below is a list with display function in normal operation.
'o' Standby, no demand for heat present.
'c' Boiler is active for central heating.
'H' Boiler is blocking for a specific error, display will be
blinking alternating with a number and letter to show
what kind error is detected.
'L' Boiler is in lockout for a specific error, the display will
be blinking alternating with a number and letter to
show what kind of error is detected.
INSTALLATION
classic m - Installation & Servicing
23
34
GENERAL CHECKS
INSTALLATION
Make the following checks for correct operation
1. Central Heating
The correct operation of ANY programmer and all other
system controls should be proved. Operate each control
separately and check that the main burner or circulating
pump, as the case may be, responds.
2. Gas rate
Operate the boiler for 10 minutes. Check the boiler gas
rate, ensuring the boiler is at full output whilst
measurements are recorded (see Table 2).
3. Water circulation system
INSTALLATION
Note. Flushing solutions should be used during the flushing
procedure - refer to Frame 9.
a. With the system HOT examine all water connections for
soundness.
Knob SettingFlow Temperature
°C°F
Min65150
Max82180
b. With the system still HOT, turn off the gas, water
and electricity supplies to the boiler and drain down
to complete the flushing process.
c. Refill and vent the system, add inhibitor (see Frame
9), clear all air locks and again check for water
soundness.
d. Balance the system (see Frame 4).
4. Finally set the controls to the User’s requirements.
• The temperatures quoted alongside are approximate, and
vary between installations.
35
HANDING OVER
After completing the installation and commissioning of the system the
installer should hand over to the householder by the following actions:
1. Hand the User's Instructions to the householder and
explain his or her responsibilities under Relevant National
Regulations.
2. Explain and demonstrate the lighting and shutting down
procedures.
3. The operation of the boiler and the use and adjustment of
ALL system controls should be fully explained to the
householder to ensure the greatest possible fuel economy
consistent with household requirements of both heating and
hot water consumption.
Advise the User of the precautions necessary to prevent
damage to the system and to the building in the event of
the system remaining inoperative during frosty conditions.
4. Explain the function and the use of the boiler controls and
external controls.
5. Explain the function of the boiler fault mode. Explain that if
a fault is indicated the boiler should be turned off and a
local heating installer consulted.
7. If any programmer is fitted then draw attention to the
Programmer User's Instructions and hand them to the
householder.
8. After installation, commissioning, and customer
hand-over please complete the
appliance log book and leave this with the customer.
9. IMPORTANT
A comprehensive service should be carried out
ANNUALLY.
Stress the importance of regular servicing by a CORGI
registered installer.
As the installer you may wish to undertake the service
contract yourself or, alternatively, offer to the customer
the benefits of the Ideal Care Scheme, details of which
are outlined in the Householder Pack supplied with this
boiler.
6. Explain and demonstrate the function of time and
temperature controls, radiator valves, etc., for the economic
use of the system.
24
classic m - Installation & Servicing
36
Ecl 1596
3
1
Flue gas
sampling point
SERVICING SCHEDULE
SERVICING
To ensure the continued safe and efficient operation of the
appliance it is recommended that it is checked at regular intervals
and serviced as necessary. The frequency of servicing will depend
upon the installation condition and usage but should be carried
out at least annually. It is the law that any service work must be
carried out by a registered CORGI installer.
1. Light the boiler and carry out a pre-service check, noting
any operational faults.
2. Check the gas consumption.
3. Connect a suitable gas analyser to the sampling point on
top of the boiler or into the flue terminal, if access if
possible. Refer to Frame38
For correct boiler operation the CO/CO
gas should not be greater than 0.004 ratio. If this is the
case, and the gas input is at least 90% of the nominal,
once compliance with the note above is ensured, then no
further action need be taken. If not, proceed to step 4 .
4. Clean the main burner.
5. Clean the heat exchanger.
6. Check the main injector for blockage or damage.
content of the flue
2
7. Check that the flue terminal is unobstructed and that the flue
system is sealed correctly.
The servicing procedures are covered more fully in Frames
37 to 42 and MUST be carried out in sequence.
Note. In order to carry out either servicing or replacement of
components the boiler front panel, bottom panel and sealing
panel must be removed. Refer to Frames 37 and 38.
WARNING.
service cock, and switch off and disconnect the
electricity supply to the appliance before servicing.
IMPORTANT.
8. After completing the servicing or exchange of components
always test for gas soundness and carry out functional checks
as in 2 and 3 above.
9. When work is complete the sealing panel MUST be correctly
refitted, ensuring that a good seal is made.
10. Complete the service section in the Benchmark log book.
DO NOT OPERATE THE BOILER IF THE SEALING
PANEL IS NOT FITTED.
Always turn off the gas supply at the gas
37
BOILER FRONT PANEL REMOVAL
1. Remove the 2 securing screws from the underside of
the appliance.
2. Pull the panel forward at the bottom and lift to
disengage it from the top lugs.
Ecl 1595
38
BOILER SEALING/ BOTTOM PANEL
REMOVAL
1. To remove the sealing panel remove the 4 retaining
screws.
2. Remove the panel.
3. To remove the bottom panel remove the 2 screws.
4. Pull the RHS of the panel down and slide it to the right
to withdraw.
SERVICING
classic m - Installation & Servicing
1
25
39
FAN AND VENTURI ASSEMBLY REMOVAL
1. Disconnect the electrical leads from the fan.
2. Undo the gas pipe union connection to the injector
housing.
3. Undo the single retaining screw on the fan mounting
bracket.
4. Lift off fan and venturi assembly.
5. Inspect the injector for blockage or damage.
SERVICING
2
3
5
Ecl1629
40
BURNER REMOVAL AND CLEANING
1. Undo and remove the 6 screws securing the burner. (the 3
screws at the rear are extended to ease access.)
2. Remove the burner from the combustion chamber.
IMPORTANT
The burner head is a ceramic plaque construction.
Care should be taken to ensure that the burner is not
placed down upon its face as this may cause damage to
the ceramic.
SERVICING
3. Brush off any deposits that may be on the ceramic with a
SOFT brush.
4. Inspect the sealing gasket around the burner for any
signs of damage. Replace if necessary.
Ecl1630
26
4
2
1
classic m - Installation & Servicing
41
CLEANING THE HEAT EXCHANGER
1. Remove ignition and sensing
electrodes (Frames 47 &48).
2. Remove the 2 spring clips
securing the collector hood to
the heat exchanger.
3. Slide the flue spigot upwards
into the flue turret to allow the
collector hood to slide forwards
and remove the collector hood.
4. Slide the flue spigot downwards
and remove from the flue turret.
5. Remove the 6 flue baffles
(m5080 only).
6. Using a suitable tool as
supplied in the standard B.G.
flue brush kit clean between the
heat exchanger fins from the
bottom of the heat exchanger.
SERVICING
3
2
1
42
RE-ASSEMBLY
Reassemble the boiler in the following order.
1. Refit the baffles (m5080 only) ensuring baffles are fully
located in the heat exchanger.
Ecl1631
SERVICING
7. Refit the fan / venturi assembly.
2. Refit the flue spigot to the flue turret.
3. Refit the collector hood to the heat exchanger. Ensure the
sealing gasket around the flue outlet on the collector hood
is in place. Renew any damaged or deteriorating gaskets.
4. Slide the flue spigot downwards and secure the 2 spring
clips. Ensure the clips are located correctly over the inter
panel.
5. Refit the electrodes (check dimensions, see Frame 47 &
48).
6. Refit the burner, renewing any damaged or deteriorating
sealing gaskets.
classic m - Installation & Servicing
8. Reconnect the fan electrical lead.
9. Refit the boiler front and bottom panel.
IMPORTANT.
Ensure the boiler sealing panel is correctly fitted and that
a good seal is made.
10. Refit the boiler casing.
11. Turn on the gas supply at the gas service cock.
12. Reconnect the electrical supply.
27
43
REPLACEMENT OF COMPONENTS
GENERAL
When replacing ANY component:
1. Isolate the electricity supply.
2. Turn off the gas supply.
3. Remove the boiler front panel and sealing panel
(Frames 37 & 38).
4. After replacing any components check the operation
of the boiler including gas soundness, gas rates and
combustion test.
SERVICING
IMPORTANT
When work is complete, the sealing panel must be
correctly fitted, ensuring that a good seal is made.
Note.
In order to assist fault finding, the control panel has an
LCD display. The key to boiler fault conditions is
shown in Frame 59.
THE BOILER MUST NOT BE OPERATED WITHOUT THE SEALING PANEL FITTED
44
CONTROL THERMISTOR REPLACEMENT
1. Refer to Frame 36.
2. Pull the electrical leads off the control
thermistor.
3. Pull the control thermistor and spring
clip off the flow pipe.
4. Replace thermistor and reconnect
SERVICING
leads, ensuring that the spring clip is
securely holding the thermistor to the
flow pipe.
5. Re-assemble the boiler in reverse order.
6. Check the operation of the boiler.
Note.
Removal of the collector hood and flue
spigot will facilitate better access.
WARNING.
Beware these components may be hot if
the boiler has recently been run.
28
Ecl 1636
classic m - Installation & Servicing
45
FAN REPLACEMENT
1. Refer to Frame 36.
2. Disconnect the electrical leads from the fan.
3. Undo the gas pipe union connection to the
injector housing.
4. Undo the single retaining screw on the fan
mounting bracket.
5. Remove the fan
6. Unscrew the 3 retaining screws and remove
the venturi assembly, noting the orientation of
the venturi in relation to the fan body.
7. Transfer the venturi assembly to the new fan,
replacing the gasket if evidence of damage or
deterioration is visible.
8. Fit the new fan / venturi assembly .
9. Re-assemble the boiler in reverse order taking
care not to over tighten the single retaining
screw on the fan mounting bracket.
10. Check the operation of the boiler. Refer to
Frame 36.
SERVICING
6
4
46
BURNER REPLACEMENT
1. Refer to Frame 36.
2. Remove fan assy. Refer paragraphs
2 & 3, Frame 45.
3. Undo and remove the 6 screws
securing the burner (the 3 screws at
the rear are extended to ease
access.)
4. Remove the burner.
5. Fit the new burner.
6. Re-assemble the boiler in reverse
order.
7. Check operation of the boiler. Refer
to Frame 36.
Ecl1632
SERVICING
Ecl1633
classic m - Installation & Servicing
3
3
29
SERVICING
Straight edge
25mm
+ 2
- 2
Ecl 1699
47
IGNITION ELECTRODE REPLACEMENT
1. Refer to Frame 36.
2. Lower the control box, as shown in Frame 52.
3. Unplug the spark electrode lead from the control box.
4. Undo the single retaining screw holding the spark electrode
to the combustion chamber.
5. Remove the electrode, taking care not to dislodge the
grommet from the casing.
6. Fit the new ignition electrode, using the new gasket
supplied and check dimensions on shown.
Spark gap 3mm
+2
-0
3
11mm
+ 0
- 4
Ecl 15555
Straight edge
5
48
SENSING ELECTRODE REPLACEMENT
1. Refer to Frame 36.
SERVICING
2. Lower the control box, as shown in Frame 52.
3. Unplug the sensing electrode lead from the control
box.
5
Ecl 1634
Ecl 1697
7. Reassemble in reverse order.
8. Check operation of the boiler. Refer to Frame 36.
Ecl1558
3
4. Unbolt the sensing electrode earth lead from the earth point beneath
the boiler.
5. Remove the electrode, complete with grommet.
6. Fit the new sensing electrode, using the new gasket supplied.
7. Reassemble in reverse order.
8. Check operation of the boiler. Refer to Frame 36.
Ecl 1634
30
classic m - Installation & Servicing
49
BURNER INJECTOR REPLACEMENT
SERVICING
1. Refer to Frame 36.
2. Remove the fan / venturi assembly,
as shown in Frame 45.
3. Unscrew the 2 injector housing
retaining screws.
4. Withdraw the injector housing.
5. Fit the new injector housing.
6. Reassemble in reverse order,
ensuring that the new gas seal
supplied is located correctly in the
injector housing.
7. Check operation of the boiler. Refer
to Frame 36.
5
3
Ecl 1637
50
GAS CONTROL VALVE REPLACEMENT
1. Refer to Frame 36.
2. Remove the 2 retaining screws from the underside of the
appliance. Unhook and remove the front panel.
3. Remove the bottom panel 2 screws.
4. Allow the RHS of the bottom panel to lower slightly.
5. Remove the gas valve electrical connections and the silicon
sensing pipe.
6. Withdraw the LHS of the bottom panel from the retaining clips.
7. Undo the union nut between the gas valve and the gas inlet
cock.
8. Undo the union nut on the outlet side of the gas
valve.
9. Undo the gas valve bracket retaining nut and slide
the gas valve forward, and remove.
10. Fit new valve, reassemble in reverse order, ensuring
that any seals showing damage or deterioration are
replaced.
11. Check operation of the boiler. Refer to Frame 36.
3
SERVICING
7
classic m - Installation & Servicing
2
Ecl 1638
31
51
CONTROL BOX REPLACEMENT
Refer to Frame 36.
1. Remove the 2 retaining screws.
2. Lift front panel and remove.
3. Remove the 2 bottom panel screws.
4. Allow the RHS of the bottom panel to lower slightly.
5. Withdraw the LHS of the bottom panel from the
retaining clips.
6. Unscrew the 2 control box retaining screws.
7. Unplug all the electrical wiring from the control box.
8. With the control box lowered, pull the assembly
forward to remove from the housing.
9. Transfer the mounting brackets to the new control
box.
10. Reassemble in reverse order, ensuring that the
control box is located correctly in the housing before
reconnecting the electrical wiring.
11. Check operation of the boiler. Refer to Frame 36.
SERVICING
Ecl 1639
3
1
6
Ecl 1566
Mounting brackets
Control box
52
MAINS SWITCH REPLACEMENT
1. Refer to Frame 36.
SERVICING
2. Remove the boiler bottom panel (refer to Frame 37).
3. Unscrew the 2 control box screws and allow the control box
to lower.
4. Push out the mains switch from the rear, as shown.
Ecl 1565
3
5. Refit the new switch ensuring the electrical leads are
reconnected correctly. Ensure that the key on the switch
is correctly aligned with the slot in the plastic moulding.
6. Reassemble in reverse order.
7. Check operation of the boiler. Refer to Frame 36.
32
Ecl 1562
classic m - Installation & Servicing
53
SIGHT GLASS REPLACEMENT
1. Refer to Frame 36.
2. Unscrew the 2 sight glass retaining screws.
3. Remove the sightglass, gasket and
bracket.
4. Fit new sight glass, using the new bracket
and gasket supplied.
5. Reassemble in reverse order.
6. Check operation of the boiler. Refer to
Frame 36.
SERVICING
Sightglass
Gasket
54
OVERHEAT THERMOSTAT REPLACEMENT
1. Refer to Frame 36.
2. Pull off the electrical leads from the
thermostat body.
3. Pull the thermostat and clip from the
pipe.
4. Fit the new thermostat, ensuring that
the clip is securely holding the
thermostat to the flow pipe.
5. Re-assemble in reverse order.
6. Check operation of the boiler. Refer to
Frame 36.
Note.
Removal of the collector hood and
flue spigot will facilitate better access.
WARNING.
Beware these components may be
hot if the boiler has recently been run.
2
Bracket
Ecl1642
SERVICING
classic m - Installation & Servicing
Ecl 1643
33
SERVICING
55
COMBUSTION CHAMBER INSULATION REPLACEMENT
The insulation boards used in the combustion chamber of this
product are made of high temperature glass fibres with a
binder of organic and inorganic materials.
Caradon Plumbing Limited recommend that, for your own
comfort and safety and to comply with good working practise,
the procedure described below is followed:
1. Refer to Frame 36.
2. Remove the fan / venturi assembly, as shown in Frame 39.
3. Remove the burner as shown in Frame 40.
4. Undo the retaining screw from the ignition electrode and
withdraw it from the combustion chamber
5. Undo the retaining screw from the detection electrode and
withdraw it from the combustion chamber.
Prior to removal of the board the following protective
equipment should be worn:
• Face mask supplied with the spare part
• Gloves supplied with the spare part
6. Damp down the combustion chamber area containing the
insulation boards.
7. Remove the split pin and washer from the LHS of the
combustion chamber.
8. Remove the insulation boards. The replacement
boards are supplied in a plastic bag. This bag should
be retained and the discarded boards should now be
placed into it.
9. Sweep any dampened particles and place in the
plastic bag.
10. Fit new insulation boards.
Note. The boards are designed to be interlocking and
should be fitted as shown.
11. Fit the new split pin and washer in the LHS of the
combustion chamber.
12. Remove the gloves and face mask and place them in
the plastic bag.
13. Wash your hands and any areas of skin which may
have come into contact with any of the particles from
the insulation board.
Note. Seal the plastic bag and dispose of it and its
contents into a commercial tip.
14. Reassemble in reverse order.
15. Check operation of the boiler. Refer to Frame 36.
SERVICING
4
5
Ecl 1644
LH Side
Rear
Front
Fit in the following order; Front, RHS, Rear LHS.
34
RH Side
classic m - Installation & Servicing
SERVICING
57
HEAT ENGINE REPLACEMENT
Refer to Frame ‘Exploded view’
1. Refer to Frame 36.
2. Remove the control box (refer to Frame 51) and place to
one side.
3. Remove the fan assembly (refer to Frame 45 ) and place
to one side.
4. Remove the burner (refer to Frame 46) and place to one
side.
5. Remove the ignition and sensing electrodes (refer to
Frames 47 & 48).
6. Remove the collector assembly (refer to Frame 58).
7. Remove the flue baffles (classic m5080 only).
8. Remove the control thermistor and over heat thermostat
from the flow pipe.
9. Drain the boiler using the heat exchanger drain point.
10. Remove the 2 M5 x 10 screws from the bottom of the
inter panel.
11. Slide the heat engine and inter panel assembly
downwards to disengage and remove from the casing.
12. Reassemble in reverse order, replacing gaskets or
seals if any sign of damage or deterioration is evident.
Note.
The heat engine is supplied with new combustion
chamber insulation boards. These should be fitted (refer
to Frame 55) before the burner, fan assemblies and
before the ignition/sensing electrodes are replaced.
13. Check the operation of the boiler. Refer to Frame 36.
11
10
SERVICING
classic m - Installation & Servicing
9
Ecl 1645
35
SERVICING
57
BOILER SEALING PANEL SEAL REPLACEMENT
Refer Frame 36.
1. Remove the 2 retaining screws from the underside of the appliance.
Unhook and remove the front panel.
2. Undo the 4 screws to remove the panel.
3. Remove the old seal from the casing and thoroughly clean the casing
surfaces.
4. Fit the new adhesive seals, note that they are supplied to the correct
length for the relevant sides.
5. Reassemble in reverse order.
Note.
Ensure that the boiler sealing panel is correctly seated, compressing the
seal to make an airtight joint.
6. Check operation of boiler. Refer Frame 36.
2
Ecl 1648
1
58
SERVICING
Refer to Frame 36.
1. Remove the 2 spring clips securing
2. Slide the flue spigot upwards into
3. Remove the collector hood.
4. Reassemble in reverse order
5. Slide the flue spigot down from the
6. Fit the spring retaining clips.
7. Check operation of the boiler.
8. Refer to Frame 36.
COLLECTOR HOOD REMOVAL
the collector hood to the heat
exchanger.
the flue turret to allow the collector
hood to slide forwards.
ensuring the location tabs in the
collector hood gasket fit into the
inter panel locations.
flue turret and locate on the
collector hood.
Ecl 1649
Seals
Ecl 1650
36
classic m - Installation & Servicing
FAULT FINDING
59
FAULT FINDING CHART MAIN MENU
In order to assist fault finding, the boiler has an LCD display. The key to the display codes is as follows:
Due the wave form of this rectified
voltage, the reading will vary
depending on the type of meter
used to measure the valve, (some
may measure the possible peak
voltage of 339 V). In general terms
a reading greater than 150 V
indicates that the correct voltage is
supplied to the gas valve.
NO
Check the ignition electrode and associated harness
for: continuity, visual condition, position
Replace ignition electrode and associated
harness as necessary
Is 17mbar gas pressure
available at the boiler inlet ?
YES
Is 200 v DC supply
available at the gas valve ?
YES
Are these functioning correctly ?
NO
NO
NO
Check gas supply
and rectify fault
Check gas valve
YES
Replace gas valve
wiring for
continuity
Replace PCB
61
L.....E......orH.....E. (BOARD ERROR)
Code indicates internal fault
within the PCB
62
L.......A.........................(OVER HEAT)
Can the overheat condition be reset by pressing
the boiler reset button when the system is cold ?
YES
Is the boiler and CH system filled with
water and all isolation valves open ?
YES
Does the pump setting give a differential
across the boiler in excess of 25 oC
NO
NO
NO
YES
Replace PCB
Replace overheat thermostat
Fill and vent the system and open all
isolation valves
Increase the pump setting.
Is differential now below 25
NO
0
C ?
YES
If the overheat trips again measure the flow temp:
The following are parts commonly required due to damage or
expendability. Their failure or absence is likely to affect safety or
performance of this appliance.
The list is extracted from the British Gas List of Parts, which
contains all available spare parts.
The full lists is held by British Gas Services, British Gas
distributors and merchants.
When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and performance
specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
Key No.GC Part No.DescriptionQty.Product No.
1E67-471Front casing panel1170 897
4E69-260Bottom cover panelm30501171 117
E69-261Bottom cover panelm50801171 118
6E69-262Baffle kitm50801171 133
11E67-489Burner1170 905
When ordering spares please quote:
1. Boiler Model
2. Appliance G.C. Number
3. Description
4. Quantity
5. Product Number
12E67-490Combustion chamber insulation1170 906
14E69-270Injector and housing1170 908
16E69-271Fan assembly1170 909
19E67-497Gas control valve - Honeywell VK115V1170 913
23E67-501Control thermistor1170917
24E67-502Overheat thermostat1170918
25E67-503Ignition electrode and gasket1170 919
26E67-504Flame sensing electrode and gasket1170 920
The Caradon Plumbing Limited Technical Training Centre
offers a series of first class training courses for domestic,
commercial and industrial heating installers, engineers and
system specifiers.
For details of courses please ring:
01482 498432
The code of practice for the installation,
commissioning & servicing of central heating systems
Caradon Plumbing Ltd.
Kingston upon Hull, HU5 4JN. Telephone: 01482 492 251 Fax:
01482 448 858. Registration No. London 322 137.
Caradon Plumbing Ltd.
improvement in the design and performance of its products. The
right is therefore reserved to vary specification without notice.
P.O. Box 103, National Ave.,
pursues a policy of continuing
CERTIFIED PRODUCT
Manufactured under a BS EN ISO 9001:
1994 Quality System accepted by BSI
June 2001156124 A01
Ideal Care Helpline
www.idealboilers.com
Tel: 01482 498 663
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.