Boiler SizeFF 350 PFF 360 PFF 380 P
Gas supply connectionRc 1/2 (1/2)
Flow connection22mm28mm copper
copper(FEMALE)
Return connection22mm28mm copper
copper(FEMALE)
Maximum static water head m (ft.)30.5 (100)
Minimum static water head m (ft.) 0.45 (1.5)
Electrical supply230 V ~ 50 Hz Boiler power consumption; 100W
Fuse ratingExternal; 3AInternal; F1A to BS.4265
Water contentlitre (gal.)3.65 (0.8)4.65 (1.0)
Dry Weight
kg (lb)46.6 (102.8)52.6 (116.0)
Maximum installation weight kg (lb)37.4 (82.5)43.1 (95.0)
Boiler sizeHeight mm (in.)700 (27.5)
Width mm (in.)380 (15.0)
Depthmm (in.)300 (11.8)
Flue duct diameter mm (in.)100 (4.0)
Table 2 - Performance Data
Boiler SizeFF 350 PFF 360 PFF 380 P
Boiler inputkW18.321.929.3
Classic FF 350 P ........................... 41 392 06
Classic FF 360 P ........................... 41 392 07
Classic FF 380 P ........................... 41 392 08
Key to symbols
IE= Ireland
GB= United Kingdom
PMS = Maximum operating
C
C
I
pressure of water
& C32 = A room sealed
12
appliance designed for
connection via ducts to a
horizontal or vertical
terminal, which admits fresh air to the
burner and discharges the products of combustion to
the outside through orifices which, in this case, are
concentric. The fan is up stream of the combustion
chamber.
= A room sealed appliance designed for connection via
72
concentric vertical ducts and a draught diverter
located in the roof space to a secondary flue. The
combustion air is taken from the roof space. The fan
is down stream of the combustion chamber.
= An appliance designed for use on 3rd Family gas,
3P
Group P only.
Propane Gas only
Appliance type:
C12 & C
C
32,
(360P,380P only)
72
CONTENTS
Air Supply. ..................................................................... 7
Water and Systems ..................................................... 7
Water Treatment .......................................................... 7
For GB, to comply with Building Regulations Part L1 (Part J in Scotland) the boiler should be fitted in accordance with the
manufacturer's instructions. Self-certification that the boiler has been installed to comply with Building Regulations can be
demonstrated by completing and signing the Benchmark log book.
BENCHMARK LOG BOOK DETAILS
BoilerPage
Make and model .......................................................3
Appliance serial no. on data badge ........................ 11
For vertical flue connection on FF 360 and FF 380 only (to
a maximum primary flue length of 4m and a maximum
secondary flue length of 6m (FF360) and 7m (FF380)).
Roof Flue Kit.
For vertical flue connection (to a maximum of 3m).
90° Flue Elbow Turret Kit
Sealed System Unit. Fits on top of the appliance.
Extension ducts.Up to 3 m (118").
CURRENT GAS SAFETY (INSTALLATION AND USE)
REGULATIONS OR RULES IN FORCE.
The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a CORGI
Registered Installer. It must be carried out in accordance with
the relevant requirements of the:
•Gas Safety (Installation and Use) Regulations
•The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (northern Ireland).
•The Water Fittings Regulations or Water byelaws in
Scotland.
•The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a Competent
Person and installed in accordance with the current edition of
I.S.813 "Domestic Gas Installations", the current Building
Regulations and reference should be made to the current ETCI
rules for electrical installation.
Detailed recommendations are contained in the following British
Standard Codes of Practice:
BS.5482Domestic butane and propane burning
appliances
BS.6891Low pressure installation pipes.
BS.6798Installation of gas fired hot water boilers of rated
input not exceeding 60 kW.
BS.5449Forced circulation hot water systems.
BS.5546Installation of gas hot water supplies for domestic
purposes (2nd and 3rd Family Gases).
BS.5440.1Flues for gas appliances of rated input not
exceeding 60 kW.
BS.5440.2Ventilation for gas appliances of rated input not
exceeding 60 kW.
BS.7593Treatment of water in domestic hot water central
heating systems.
Health & Safety Document No. 635.
The Electricity at Work Regulations, 1989.
Manufacturer’s notes must NOT be taken in any way as
overriding statutory obligations.
IMPORTANT. These appliances are certificated by the British
Standards Institution for safety and performance. It is, therefore,
important that no external control devices, e.g. flue dampers,
economisers etc., are directly connected to these appliances unless covered by these ‘Installation and Servicing’ instructions
or otherwise recommended by Caradon Ideal Limited in writing. If
in doubt please enquire.
Any direct reconnection of a control device not approved by CaradonIdeal Limited could invalidate the BSI Certification and the normal
appliance warranty. It could also infringe the Gas Safety Regulations
and the above regulations.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation panels
which can cause irritation to the skin. No asbestos, mercury or
CFCs are included in any part of this boiler.
LOCATION OF BOILER
The boiler must be installed on a flat and vertical wall, capable
of adequately supporting the weight of the boiler and any
ancillary equipment.
The boiler may be fitted on a combustible wall and insulation
between the wall and the boiler is not necessary - unless
required by the local authority. The boiler must not be fitted
outside.
Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should
be fitted in accordance with the Institute of Gas Engineering
document IG/UP/7:1998.
Bathrooms
This range of appliances is rated IP 1XB.
The boiler may be installed in any room or internal space, although
particular attention is drawn to the requirements of the current
I.E.E. (BS.7671) Wiring Regulations and, in Scotland, the
electrical provisions of the building regulations applicable in
Scotland with respect to the installation of the boiler in a room or
internal space containing a bath or shower. For Ireland reference
should be made to the current ETCI rules for electrical
installations and I.S. 813: 2002.
4
Classic FF -
Propane Installation & Servicing
Page 5
1
BOILER WATER CONNECTIONS
This appliance in NOT suitable for use in a direct
hot water system or for gravity circulation.
FF 380P boiler ONLY
must be fitted with the 22mm x 28mm copper sockets,
provided in the Hardware Pack (or equivalent 22mm x
28mm compression fittings), and the pumped flow and
return pipes run in 28mm pipe.
2
BOILER CLEARANCES
The following minimum clearances
must be maintained for operation and
servicing
Additional space will be required for
installation, depending upon site
conditions.
Side and Rear Flue
a. Provided that the flue hole is cut
accurately, e.g. with a core drill, the
flue can be installed from inside the
building.
Installation from inside ONLY
b. If a core boring tool is to be used
inside the building; the space in
which the boiler is to be installed
must be at least wide enough to
accommodate the tool.
c. If using the Complete Sealed
System Unit then refer to the
instructions packed with the unit for
the necessary clearances.
GENERAL
Front clearance: 533mm (21")
from the front of the boiler
casing.
Minimum front clearance when
built in to cupboard is 75 mm
(3").
Pelmet restrictions.
If the ability to fit or remove the
casing during installation and
subsequent servicing is impaired
by pelmets etc. this operation can
be made easier by first removing
the controls pod casing in line
with the following instructions:
a. Release the controls pod
casing fixing screws (a) 3 full
turns only. Remove the pod by
pulling it forward to disengage
from the keyhole slots.
b. Undo the 2 screws (b)
retaining casing to the back
panel.
c. The casing can now be
removed in the direction of the
arrow, first lifting the casing
slightly to disengage the
casing top return from the
back panel. (For this purpose
a minimum clearance of
12mm is required between
the top of the boiler and
pelmet or other similar
obstruction.
Classic FF -
Propane Installation & Servicing
5
Page 6
GENERAL
If the appliance is to be installed in a room containing a bath or
shower then, providing waterjets are not going to be used for
cleaning purposes (such as communal baths/showers), the
appliance can be installed in Zone 3, as detailed in BS.7671.
Where installation will be in an unusual location, special
procedures may be necessary and BS.6798 gives detailed
guidance on this aspect.
Compartment Installations
A compartment used to enclose the boiler should be designed
and constructed specially for this purpose.
An existing cupboard or compartment may be used, provided it
is modified for the purpose.
In both cases details of essential features of cupboards/
compartment design, including airing cupboard installation, are
to conform to the following :
! BS. 6798.
! The position selected for installation MUST allow adequate
space for servicing in front of the boiler and for air circulation
around the boiler, see section on 'Air Supply'.
! For the minimum clearances required for safety and
subsequent service, see the wall mounting diagram, Frame
2. In addition, sufficient space may be required to allow lifting
access to the wall mounting plate.
GAS SUPPLY
A local propane supplier should be consulted, at the installation
planning stage, in order to establish the availability of an adequate
supply of gas.
Installation pipes, cylinders and pressure regulators MUST be
fitted in accordance with BS. 5482.1. In IE refer to I.S. 813:2002.
Pipework from the supply to the boiler MUST be of an adequate
size.
Bulk tank installations must comply with the Home Office code of
practice for the storage of liquefied petroleum gas at fixed
installations.
The complete installation MUST be tested for gas soundness and
purged as described in the above code.
Table 3 - Balanced flue terminal position
Approved Manufacturer’s Clearances
Terminal PositionMinimum Spacing
1a. Directly BELOW an opening, air brick,
opening window, etc.300 mm (12")
1b. Directly ABOVE an opening, air brick,
opening window, etc.300 mm (12")
1c. HORIZONTALLY to an opening,
air brick, opening window, etc.300 mm (12")
2. Below guttering, drain pipes or soil
pipes25 mm ( 1")
3. Below eaves25 mm ( 1")
4. Below balconies or a car port roof25 mm ( 1")
5. From vertical drain pipes or soil pipes25 mm ( 1")
6. From an internal or external corner or
to a boundary alongside the terminal25 mm ( 1")
7. Above adjacent ground, roof or
balcony level300 mm (12")
8. From a surface or a boundary
facing the terminal600 mm (24")
9. From a terminal facing a terminal1200 mm (48")
10. From an opening in a car port
(e.g. door or window) into dwelling1200 mm (48")
11. Vertically from a terminal on the
same wall1500 mm (60")
12. Horizontally from a terminal on the wall300 mm (12")
Terminals guards are available from boiler suppliers. Ask for
TFC Flue Guard, Model K1. In case of difficulty seek advice
from:
5. The flue assembly shall be so placed or shielded as to
prevent ignition or damage to any part of any building.
FLUE INSTALLATION
Pluming may occur at the terminal so terminal positions which
would cause a nuisance should be avoided.
The flue must be installed in accordance with the
recommendations of BS.5440-1:2000. In IE refer to I.S. 813:2002.
The following notes are intended for general guidance.
1. The boiler MUST be installed so that the terminal is exposed to
external air.
2. It is important that the position of the terminal allows the free
passage of air across it at all times.
3. Minimum acceptable spacing from the terminal to obstructions
and ventilation openings are specified in Table 3.
4. Where the lowest part of the terminal is fitted less than 2m
(6'6") above a balcony, above ground or above a flat roof to
which people have access then the terminal MUST be protected
by a purpose designed guard. The minimum spacing in Table 3,
Nos. 2,3, 4, 5 and 6 would be 75mm in order to allow a terminal
guard to be fitted.
6
6. The air inlet/products outlet duct and the terminal of the
boiler MUST NOT be closer than 25mm (1") to combustible
material. Detailed recommendations on the protection of
combustible material are given in BS.5440-1:2000. In IE
refer to I.S. 813:2002.
7. Where it is essential that the terminal wall plate is fitted, i.e.
wall thicknesses over 600mm (23
cut hole, the minimum spacing in Table 3 Nos. 2,3, 4, 5 and 6
would be 60mm (2 1/2") in order to allow the terminal wall
plate to be fitted.
1/2") or with an inaccurately
IMPORTANT. It is absolutely ESSENTIAL to ensure, in practice,
that products of combustion discharging from the terminal cannot
re-enter the building or any other adjacent building through
ventilators, windows, doors, other sources of natural air infiltration,
or forced ventilation/air conditioning.
If this should occur, the appliance MUST be turned OFF, labelled
'unsafe' and corrective action taken.
TERMINAL
The terminal assembly can be adapted to accommodate
various wall thicknesses. Refer to Frame 10.
Classic FF -
Propane Installation & Servicing
Page 7
GENERAL
AIR SUPPLY
Detailed recommendations for air supply are given in BS.5440:2.
In IE refer to I.S. 813:2002. The following notes are for general
guidance:
1. It is NOT necessary to have a purpose provided air vent in the
room or internal space in which the boiler is installed.
2. If the boiler is to be installed in a cupboard or compartment,
permanent air vents are required (for cooling purposes) in the
cupboard/compartment, at both high and low levels. The air vents
must either communicate with room/internal space, or be direct
to outside air. The minimum effective areas of the permanent air
vents, required in the cupboard/compartment, are specified in
Table 4 and are related to maximum rated heat input.
3. Both air vents MUST communicate with the same room or
internal space or MUST be on the same wall to outside air.
4. In siting the air vents care must be taken to avoid the freezing of
pipework.
Refer to Table 4 for details of air vent position and sizing.
The boiler must NOT be used for direct hot water supply. For the
types of system and correct piping procedure refer to 'Introduction'
and Frame 1.
The central heating system should be in accordance with BS. 6798
and, in addition, for Smallbore and Microbore systems, BS. 5449.
The domestic hot water system, if applicable, should be in
accordance with the relevant recommendations of BS. 5546. Copper
tubing to BS. 2871:1 is recommended for water carrying pipework.
The hot water storage cylinder MUST be of the indirect type and
should preferably be manufactured of copper.
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The appliances are NOT suitable for gravity central heating, nor
are they suitable for the provision of gravity domestic hot water.
The hot water cylinder and ancillary pipework, not forming part of
the useful heating surface, should be lagged to prevent heat loss
and any possible freezing - particularly where pipes run through
roof spaces and ventilated under floor spaces.
The boiler must be vented (not on sealed system).
IMPORTANT
A minimum length of 1m of copper pipe MUST be fitted to both
flow and return connections from the boiler before connection to
any plastic piping. This applies to ALL types of installation.
Draining taps MUST be located in accessible positions, which
permit the draining of the whole system - including the boiler
and hot water storage vessel. They should be at least 1/2" BSP
nominal size and be in accordance with BS. 2879.
The boiler is fitted with a special drain plug which is provided to
drain the BOILER ONLY in the event of the system drain plug
being unable to do so. The hydraulic resistances of the boilers,
at MAXIMUM OUTPUT with an 11
differential, are shown in Table 5.
Maximum boiler operating temperature should be 82 oC (180oF).
2
(in2 )outside cm2 (in2)
o
C (20OF) temperature
Table 5 - Water flow rate and pressure loss
Boiler SizeFF 350 PFF 360 PFF 380 P
BoilerkW 14.717.623.5
Output Btu/h50 00060 00080 000
Water Flowl/min19.022.830.3
Rategal/h250300400
Pressurembar31.541.777.0
Lossin w.g.12.616.730.9
WATER TREATMENT
These boilers incorporate a cast iron heat exchanger.
IMPORTANT. The application of any other treatment to this
product may render the guarantee of Caradon Ideal Limited
INVALID.
Caradon Ideal Limited recommend Water Treatment in
accordance with the
Treatment in Central Heating Systems.
Caradon Ideal Limited recommend the use of Fernox, GE Betz
Sentinel or Salamander water treatment products, which must
be used on accordance with the manufacturers instructions.
For further information contact:
Fernox Manufacturing Co. Ltd, Cookson Electronics, Forsyth Road,
1. It is most important that the correct concentration of the water
treatment products is maintained in accordance with the
manufacturers' instructions.
2. If the boiler is installed in an existing system any unsuitable
additives MUST be removed by thorough cleansing.
BS7593:1992 details the steps necessary to clean a
domestic heating system.
3. In hard water areas, treatment to prevent limescale may be
necessary - however the use of artificially softened water is
NOT permitted.
4. Under no circumstances should the boiler be fired before the
system has been thoroughly flushed.
BOILER CONTROL INTERLOCKS
Caradon Ideal Limited recommend that heating systems utilising
full thermostatic radiator valve control of temperature in individual
rooms should also be fitted with a room thermostat controlling the
temperature in a space served by radiators not fitted with such a
valve as stated in BS. 5449.
Central heating systems controls should be installed to ensure the
boiler is switched off when there is no demand for heating or hot water.
When thermostatic radiator valves are used, the space heating
temperature control over a living / dining area or hallway having a
heating requirement of at least 10% of the boiler heat output should
be achieved using a room thermostat, whilst other rooms are
individually controlled by thermostatic radiator valves. However, if
the system employs thermostatic radiator valves on all radiators,
or two port valves without end switches, then a bypass circuit must
be fitted with an automatic bypass valve to ensure a flow of water
should all valves be in the closed position.
Guidance Notes on Water
Classic FF -
Propane Installation & Servicing
7
Page 8
GENERAL
ELECTRICAL SUPPLY
WARNING.
Wiring external to the appliance MUST be in accordance with the
current I.E.E. (BS 7671) Wiring Regulations and any local
regulations which apply. For Ireland reference should be made
to the current ETCI rules for electrical installations.
The point of connection to the mains should be readily
accessible and adjacent to the boiler, except that for bathroom
installations; the point of connection to the mains MUST be
situated outside of the bathroom.
3
The system should be vented directly off the boiler flow pipe,
as close to the boiler as possible. The cold feed entry should
be inverted and MUST be positioned between the pump and
the vent, and not more than 150mm (6") away from the vent
connection.
There should be a minimum height - 450mm (18") of open
vent above cistern water level. If this is impossible refer below.
The vertical distance between the highest point of the system
and the feed/expansion cistern water level MUST not be less
than 450mm (18").
The pump MUST be fitted on the flow side of the boiler.
A suitable pump is a domestic circulator capable of providing
an 11°C (20°F) temperature differential (e.g. Grundfos UPS
15/50 or equivalent). The vertical distance between the pump
and feed/expansion cistern MUST comply with the pump
manufacturers minimum requirements to avoid cavitation.
Should these conditions not apply, either lower the pump
position or raise the cistern above the minimum requirement
specified by Caradon Ideal Limited.
Note.
A cold water feed must be available back to the boiler, when
all automatic valves are in the closed position (Refer BS.
6798) and when close coupled the feed must not be in a
vertical leg.
The appliance MUST be efficiently earthed.
OPEN VENT SYSTEM REQUIREMENTS - FULLY PUMPED.
Note.
Where a room sealed appliance is installed in a room containing
a bath or shower then the appliance and any electrical switch or
appliance control utilising mains electricity should be so situated
that it cannot be touched by a person using the bath or shower.
Feed / expansion
cistern
Water
level
(cold)
22mm
Open vent
System
return
Connections
to boiler
15mm
Cold
feed
Inverted cold
feed entry
450 (18")
Mimimum
450 (18")
Mimimum
150 (6")
Max
System
flow to
pump
4
LOW HEAD INSTALLATIONS
The Classic range of boilers can be installed in low
head situations by fitting a 'surge arrester' in the
expansion pipe as shown.
The following conditions MUST be observed:
1. The surge arrester must be at least 42mm in
diameter x 150mm long, thus ensuring a
MINIMUM air gap and a MINIMUM depth of water
below the static water level (cold) of 75mm.
2. The static water level (cold) must be at least
200mm above the top of the horizontal flow pipe,
fitted as shown. The vent connection MUST NOT
be made immediately off the top of the boiler, as
venting is made less efficient.
3. The maximum practical length of 15mm cold feed
pipe should be used in order to reduce the
effective volume of system water expanding into
the feed/expansion cistern to a minimum.
The pump manufacturers minimum
Note.
requirements must be complied with.
8
Minimum Requirements
75 (3)
Min.
450
(18)
Min.
Return
All dimensions in mm (in.). NB. Imperial dimensions are approximate.
200
(8)
Min.
Surge
arrester
75 (3) Min.
Flow
Highest
point of
flow or
return
Classic FF -
Feed / expansion
cistern
22 (3/4)
Open vent
150
(6)
Max
Max. practical
length
Propane Installation & Servicing
Cold
water
level
To pump
Page 9
SEALED SYSTEM REQUIREMENTS
5
ecl6060
GENERAL
Hose unions
Temporary hose
(disconnect
after filling)
Non-return
valve
Automatic
air vent
Hosepipe
(disconnect
after filling)
Additional
stop valve
Double check valve
assembly
(note direction of flow)
Hose connector
Note.
The method of filling, refilling, topping up or flushing sealed
primary hot water circuits from the mains via a temporary hose
connection is only allowed if acceptable to the local water
authority.
1. General
a. The installation must comply with the requirements of
BS.6798 and BS.5449.
b. The installation should be designed to work with flow
temperatures of up to 82
o
C.
c. All components of the system, including the heat
exchanger of the indirect cylinder, must be suitable for a
working pressure of 3 bar (45 lb/in
2
) and temperature of
110oC. Care should be taken in making all connections
so that the risk of leakage is minimised.
2. Safety Valve
A spring loaded safety valve complying with the relevant
requirements of BS.6759 must be fitted in the flow pipe, as
close to the boiler as possible and with no intervening valve
or restriction. The valve should have the following features:
a. A non-adjustable pre-set lift pressure not exceeding 3
bar (45 lb./in
2
)
b. A manual testing device.
c. Provision for connection of a discharge pipe.
The valve
or discharge pipe should be positioned so that the
discharge of water or steam cannot create a hazard to
the occupants of the premises or cause damage to
electrical components and wiring.
3. Pressure Gauge
A pressure gauge covering at least the range 0-4 bar
(0-60lb./in
2
) must be fitted to the system. The gauge should
be easily seen from the filling point and should preferably
be connected at the same point as the expansion vessel.
4. Expansion Vessel
a. A diaphragm type expansion vessel must be connected
at a point close to the inlet side of the pump, the
connecting pipe being not less than 15mm (
1/2"
nominal) size and not incorporating valves of any sort.
b. The vessel capacity must be adequate to accept the
expansion of the system water when heated to 110
o
F)
(230
c. The charge pressure must not be less than the static
water head above the vessel The pressure attained in
the system when heated to 110
o
C (230oF) should be at
least 0.35 bar (5lb/in2) less than the lift pressure of the
safety valve.
For guidance on vessel sizing refer to the table in Frame 6.
For further details refer to BS.5449. For IE refer to the
current edition of I.S. 813.
5. Cylinder
The cylinder must be either of the indirect coil type or a
direct cylinder fitted with an immersion calorifier which is
suitable for operating on a gauge pressure of 0.35 bar
2
) in excess of the safety valve setting.
(5lb./in
Single feed
indirect cylinders are not suitable for sealed systems.
6. Make-up Water
Provision must be made for replacing water loss from the
system, either:
a. From a manually fitted make-up vessel with a readily
visible water level. The vessel should be mounted at
least 150mm (6") above the highest point of the system
and be connected through a non-return valve to the
system, fitted at least 300mm (12") below the make-up
vessel on the return side of the domestic hot water
cylinder or radiators.
b. Where access to a make-up vessel would be difficult by
pre-pressurisation of the system. Refer to 'Filling.'
o
C
Classic FF -
Propane Installation & Servicing
9
Page 10
GENERAL
6
SEALED SYSTEM REQUIREMENTS - cont.
7. Mains Connection
There must be no direct connection to the mains water supply
or to the water storage tank supplying domestic water, even
through a non-return valve, without the approval of the local
water authority.
8. Filling
The system may be filled by one of the following methods:
a. Through a cistern, used for no other purposes, via a ball
valve permanently connected directly to a service pipe
and / or a cold water distributing pipe.
The static head available from the cistern should be
adequate to provide the desired initial system design
pressure. The cold feed pipe from the cistern should
include a non-return valve and a stop valve with an
automatic air vent connected between them, the stop
valve being located between the system and the
automatic air vent. The stop valve may remain open
during normal operation of the system if automatic water
make-up is required.
b. Through a self-contained unit comprising a cistern,
pressure booster pump (if required) and, if necessary,
an automatic pressure reducing valve and flow restrictor.
The cistern should be supplied through a temporary
connection from a service pipe or cold water distributing
pipe.
This unit may remain permanently connected to the
heating system to provide limited automatic water
make-up. Where the temporary connection is supplied
from a service pipe or distributing pipe which also
Sizing procedure for expansion vessels: The volume of the expansion vessel (litres) fitted to a sealed system shall not be
less than that given by the table on the following page, multiplied by a factor of 0.8 (for flow temperatures of less than 88 oC).
supplies other draw-off points at a lower level then a
double check valve shall be installed upstream of the
draw-off point.
c. Through a temporary hose connection from a draw-off tap
supplied from a service pipe under mains pressure. Where
the mains pressure is excessive a pressure-reducing valve
shall be used to facilitate filling.
The following fittings shall form a permanent part of the
system and shall be fitted in the order stated:
A stop valve complying with the requirements of
BS. 1010, Part 2 (the hose from the draw-off tap shall be
connected to this fitting).
A test cock.
A double check valve of an approved type.
• Thoroughly flush out the whole of the system with cold
water, without the pump in position.
• With the pump fitted, fill and vent the system until the
pressure gauge registers 1.5 bar (21.5lb/in
Examine for leaks.
• Check the operation of the safety valve by manually
raising the water pressure until the valve lifts. This
should occur within ± 0.3 bar (± 4.3lb/in2.) of the pre-set
lift pressure.
• Release water from the system until the initial system
design pressure is reached.
• Light the boiler and heat the system to the maximum
working temperature. Examine for leaks.
• Turn off the boiler and drain the system while still hot.
• Refill and vent the system.
2
).
Safety valve setting3.0 bar2.5 bar2.0 bar
Vessel charge and initial0.51.01.50.51.01.50.51.0
system pressurebarbarbarbarbarbarbarbar
Total water content of systemExpansion vessel volume
The boiler is supplied fully assembled in Pack A, together with
a standard flue assembly for lengths up to 600mm (23
rear or side flue outlet, in Pack B.
!Flue extension tube, 1 off
!Boiler sealing ring, 1 off
Wall mounting plate
Hardware Pack Contents
! 50mm x No. 14 wood screw, 4 off
! 50mm x No. 10 wood screw, 8 off
! Wall plug , 12 off
! M8 washer, 1 off
Pack B Contents
!Duct cutting support, 1 off
(cardboard )
!Terminal wall plate, 1 off.
!Terminal grille assy, 1 off.
!Polyurethane foam seal 400 lg., 1 off.
!No. 8 x 8 lg. Pozi pan hd. screws, 3 off.
! 22mm x 28mm copper reducing socket
(FF 380 P ONLY), 2 off
! M5 wing nut, 3 off
! Sealing plate, 1 off
! M8 x 12 lg. screw, 1 off
12
Classic FF -
Propane Installation & Servicing
Page 13
9
PACKAGING AND CASING REMOVAL
1. Unpack the boiler
2. Remove the casing as follows and place to one
side to avoid damage.
a. Undo the 2 casing retaining screws (a)
retaining the casing to the back panel.
b. Swing the bottom of the boiler casing up until
the controls pod casing has cleared the
controls then unhook the top from the back
panel.
3. Remove the boiler from its packaging base. The
boiler may now be stood upright on its controls
support protection frame to ease handling and
installation.
4. Unpack the boiler terminal box and, if applicable,
the extension flue box(es)
INSTALLATION
(a) Casing retaining
screws, 2 off
INSTALLATION
10
DETERMINING THE FLUE LENGTH
It is MOST important that the boiler is installed in a
vertical position.
REAR FLUE
INSTALLATION
SIDE FLUE
INSTALLATION
Flue length
for rear
Packing base
Controls pod casing
FLUE KITS
Pack B: supplied as standard.
Pack D: optional extension kit for side flue or rear flue
outlet. Refer to 'Flue Extension Ducts'
1. A maximum of 3 extension ducts (plus the
standard flue duct) may be used together.
2. Flue extensions of greater than 1m (39") should
be supported with the bracket provided. If the
stand off brackets have been used, it is necessary,
in order to keep the flue aligned, to use the spacer
bracket with the support bracket.
Flue length for side
Jacking screw for
boiler alignment
Note.
Vertex and roof flue kits are available as optional
extras for vertical flue installation, supplied with
separate fitting instructions.
Classic FF -
Propane Installation & Servicing
Flue length
Up to 600B Pack 1 off150308
600 to 1550B Pack 1 off + D Pack, 1 off150308+153883
1550 to 2500B Pack 1 off + D Pack, 2 off150308+
2500 to 3000B Pack 1 off + D Pack, 3 off150308+
mm
AccessoriesProduct No.
153883, 2 off
153883, 3 off
13
Page 14
11
FLUE ASSEMBLY - Exploded View
1. An optional flue
duct extension kit
is required for
wall thicknesses
greater than
600mm (23 1/2")
Refer to Frame
10.
2. When cutting the
ducts, always use
the cardboard
support rings
provided.
12
WALL MOUNTING TEMPLATE
INSTALLATION
LEGEND
1. Terminal.
2. Weather seal.
3. Flue assembly.
4. Boiler sealing ring.
5. Flue extension tube.
Note.
The template shows the positions for the fixing holes
and the flue hole centres for standard installation. Care
must be taken to ensure the correct holes are drilled.
1. Separate the templates.
2. Tape the templates into the selected position.
3. Ensure squareness by hanging a plumb line as
shown.
4. Mark onto the wall (if required) the following:
a. The wall mounting plate screw positions (choose
one from each group). Note.
flue hole as well as the circumference.
b. The position of the flue duct hole.
c. Downward pipe routing bracket screw positions
5. Remove the templates from the wall.
13
PREPARING THE WALL
IMPORTANT. Ensure that, during the cutting operation, masonry
falling outside of the building does not cause damage or
personal injury.
1. Cut the flue hole preferably with a 125mm (5") core boring
tool ensuring that the hole is square to the wall. If the hole
has been quite accurately cut with a drill, then making good
the wall faces is not essential as seals are provided at both
ends of the flue. However, both wall faces immediately
around the cut hole should be flat; make good if necessary.
For less accurate holes make good to approximately
125mm (5") diameter at the two wall faces.
2. Drill 4 holes for the wall mounting plate with an 8mm (5/16")
masonry drill. If the stand-off brackets are used ensure the
correct holes are chosen.
3. Insert the plastic plugs provided.
Mark the centre of the
REAR FLUE OUTLET
Check all of the hole
Note.
positions BEFORE drilling
Note. I
f the
terminal is to be
sited within 2540mm of a corner
or vertical pipe
(refer to Table 3)
then the hole
MUST be
accurately cut and
the rubber
weather seal
trimmed around
the groove
provided.
The terminal wall
plate need not be
fitted.
14
Classic FF -
Propane Installation & Servicing
Page 15
INSTALLATION
14
CUTTING THE FLUE - wall thicknesses of 114 to 600mm
Note.
If the stand-off brackets are used it is essential that
30mm is added to the measured wall thickness when
marking the flue, (to allow for the thickness of the brackets).
1. Measure and note the wall thickness 'X'.
2. Mark the wall thickness onto the flue .
3. To ensure the tube is cut square, mark the flue all the way
round.
4. Cut to length 'X', using the cardboard ring for support.
5. Remove cardboard ring and remove any burrs.
15
FITTING BOILER SEALING RING TO THE FLUE
1. Fit the boiler sealing ring inside the outer flue duct.
Ensure boiler sealing ring is fully engaged.
Ensure the notch aligns with the groove on the outer flue
duct. This ensures correct alignment of the flue terminal.
16
FITTING THE FLUE ASSEMBLY
1. Insert the flue extension tube into the flue assembly.
2. Insert the flue assembly through the hole sufficiently far
enough to allow the rubber seal to unfold completely
and form an adequate seal on the outside wall.
2. Drill 3 holes 3.2mm (1/8") dia. through the outer flue duct
and boiler sealing ring. Do NOT drill the inner flue
duct.
3. Insert the self tapping screws, provided, in order to fix the
boiler sealing ring in position.
4. Stick the self adhesive
foam strip, provided in the
hardware pack, onto the
flue immediately behind the
boiler sealing ring.
3. Ensure the notch is at the top. This will aid the location
of the studs into the boiler back panel.
17
WALL MOUNTING PLATE
1. Fix the mounting plate to the wall with the No.14 x 50mm
wood screws.
2. If the down ward routing of pipes is required, then the
downward routing pipe brackets and M8 spacer
(supplied in the Downward Piping Kit) should be fitted to
the wall mounting plate now.
3. Fit the bottom 2 screws to secure the bracket(s) to the
wall, through the wall mounting plate.
4. Check with a spirit level that the plate is vertical.
Classic FF -
Propane Installation & Servicing
REAR FLUE OUTLET
15
Page 16
18
MOUNTING THE BOILER
Note.
Have ready to hand the M8 screw, washer
and rectangular plate supplied in the hardware
pack. For downward routing of pipes the M5
spacer (supplied in the Downward Piping Kit)
should now be fitted to the back of the boiler.
1. Lift the boiler onto the wall mounting plate
hooks as shown.
Do not use the burner / controls for lifting
2. Fit the M8 screw washer and rectangular
plate to retain the boiler.
Note.
Before fully tightening the M8 screw check the
boiler alignment, using a spirit level, and adjust
as necessary with the jacking screw.
19
CONNECTING THE FLUE TO THE BOILER
INSTALLATION
1. Pull the flue through the wall mounting plate
and locate the 3 studs in the holes in the back
panel.
2. Secure the flue to the boiler, using the three M5
wing nuts provided.
3. Pull the flue extension tube and engage onto
fan, locate and secure with the M4 screw
attached to the fan.
Note.
The sealing ring studs will locate in the back panel
one way only. This will ensure that the terminal
grille is correctly aligned.
20
TERMINAL WALL PLATE
This plate allows neat concealment and full compression of
the rubber seal. Its use is not essential if the flue hole and
flue ducts have been accurately cut and the outside wall
face is flat.
1. Position the terminal wall plate over the terminal.
2. Mark and drill 4 fixing holes with an 7mm (
drill.
3. Insert the 4 plastic plugs provided.
4. Secure the plate with 4 of the No.10 x 2" screws
provided.
If the terminal is less than 2m (6' 6") above ground
Note.
level, an approved terminal guard should be fitted. Refer to
the Contents List on Page 3.
9/32") masonry
REAR FLUE OUTLET
16
Classic FF -
Propane Installation & Servicing
Page 17
INSTALLATION
21
FLUE ASSEMBLY - Exploded view
For wall thickness 114mm to 600mm
1. An optional flue duct
extension kit is required for
lengths (distance from the
outside wall to the relevant
side of the boiler casing)
greater than 600mm (23 1/2")
Refer to Frame 10.
2. When cutting the ducts
always use the cardboard
support provided.
22
WALL MOUNTING TEMPLATE
Note.
The template shows the positions for the fixing holes and the flue
hole centres for standard installation.
If the flow and return pipes are to be routed down behind the boiler, the
downward routing pipe brackets (supplied in the Downward Piping Kit)
must be used. These brackets are secured to the wall mounting plate and
it is essential to use only those holes as shown on the wall mounting
template.
Care MUST be taken to ensure the correct holes are drilled.
1. Separate the templates.
2. Tape both templates into the selected position locating template B
through an extended centre line as shown.
LEGEND
1. Terminal.
2. Weather seal.
Extended centre
3. Flue assembly.
4. Boiler sealing plate.
5. Flue extension tube.
line
Terminal
mounting
plate screw
and flue
duct hole
positions
3. Ensure squareness by hanging a plumb line as shown.
4. Mark onto the wall (if required) the following:
a. The four wall mounting plate screw positions (choose one
from each group). If the downward routing pipe brackets
are used ensure the correct holes are chosen.
b. The 4 screw positions for the side outlet plate.
c. The position of the flue duct hole (ensure that the correct
centre is marked depending on whether the downward
routing pipe brackets are used or not).
23
PREPARING THE WALL
IMPORTANT. Ensure that, during the cutting operation, masonry falling
outside of the building does not cause damage or personal injury.
1. Cut the flue hole preferably with a 125mm (5") core boring tool
ensuring that the hole is square to the wall. If the hole has been
accurately cut with a drill, then making good the wall faces is not
essential - as seals are provided at both ends of the flue. However,
both wall faces immediately around the cut hole should be flat;
make good if necessary. For less accurate holes make good to
approximately 125mm (5") diameter at the 2 wall faces.
2. Drill 4 holes with an 8mm (5/16") masonry drill and insert the plastic
plugs provided, for the wall mounting plate.
Note.
5. Remove both templates from the wall.
SIDE FLUE OUTLET
Mark the centre of the hole as well as the circumference.
d. The side of the casing nearest the flue outlet.
3. Drill 4 holes with an 7mm (9/32") masonry drill and insert the plastic
plugs provided, for the side mounting plate .
Note.
If the terminal is to be sited within 25-40mm of a corner or
vertical pipe (refer to Table 3) then the hole MUST be accurately cut
and the rubber weather seal trimmed around the groove provided. The terminal wall plate need not be fitted.
Classic FF -
Propane Installation & Servicing
17
Page 18
INSTALLATION
24
CUTTING THE FLUE
For flue lengths 114 to 600mm ONLY
1. Measure the flue length required (i.e. the distance from
the side of the boiler to the outside face of the wall) Refer to Frame 10.
2. Mark the flue length required onto the flue, measuring
from the groove near the terminal.
3. To ensure the tube is cut square, mark the flue all the
way round.
4. Insert the cardboard support , and cut to length.
5. Remove cardboard support and remove any burrs.
25
FITTING THE FOAM SEAL
1. To determine the position for the foam seal measure
the wall thickness and mark it onto the flue, measuring
from the groove near the terminal.
2. Wrap the self adhesive foam strip round the flue,
ensuring that the foam is on the terminal side of the
line. This seals the gap between the flue and the wall.
For flue lengths greater than 600mm refer to
Frames 33 & 34 - Flue extension ducts.
26
FITTING BOILER SEALING RING
TO THE FLUE
SIDE FLUE OUTLET
SIDE FLUE OUTLET
1. Fit the boiler sealing ring inside the outer flue duct.
Ensure boiler sealing ring is fully engaged.
Ensure the notch aligns with the groove on the outer
flue duct. This ensures correct alignment of the flue
terminal.
2. Drill 3 holes 3.2mm (
duct and boiler sealing ring.
duct
.
3. Insert the self tapping screws, provided, in order to fix
the boiler sealing ring in position.
1/8") dia. through the outer flue
Do not drill the inner flue
27
FITTING THE FLUE ASSEMBLY
1. Insert the flue assembly through the hole sufficiently
far enough to allow the rubber seal to unfold
completely and form an adequate seal on the outside
wall. This will also ensure the correct alignment of the
flue terminal.
2. Ensure the notch is at the top. This will aid the location
of the studs into the boiler back panel.
18
Classic FF -
Propane Installation & Servicing
Page 19
28
FITTING THE SIDE OUTLET PLATES
Note.
If the boiler is fitted closer than 25mm to the side
wall the side outlet plate must be fitted now.
1. Split the side outlet plate into 2 down the split line.
2. Fit the 2 halves of the side outlet plate to the wall,
ensuring they are behind the boiler sealing ring.
INSTALLATION
29
WALL MOUNTING PLATE
1. Fix the mounting plate to the wall with the No.14 x 50mm wood
screws.
2. If the downward routing of pipes is required, then the downward
routing pipe brackets and M8 spacer (supplied in the
Downward Piping Kit) should be fitted to the wall mounting
plate now.
3. Fit the bottom 2 screws to secure the bracket(s) to the wall,
through the wall mounting plate.
4. Check with a spirit level that the plate is vertical.
30
MOUNTING THE BOILER
Notes1.
1. The boiler is supplied for rear outlet
installation. Remove the blanking plate from
the direction required and use this to blank off
the rear outlet.
2. Lift the boiler onto the wall mounting plate
hooks as shown.
Do not use the burner/controls for lifting.
3. Fit the M8 screw, washer and rectangular
plate to retain the boiler.
Note.
Before fully tightening the M8
screw check, the boiler alignment
using a spirit level and adjust as
necessary with the jacking screw.
Have ready to hand the M8 screw, washer and rectangular plate supplied in the hardware pack.
2.
For downward routing of pipes the M5 spacer (supplied in the Downward Piping Kit) should now be
fitted to the back of the boiler.
SIDE FLUE OUTLET
SIDE FLUE OUTLET
Classic FF -
Propane Installation & Servicing
19
Page 20
INSTALLATION
31
CONNECTING THE FLUE TO THE BOILER
1. Pull the flue through the side outlet plate and locate
the 3 studs in the hole in the side of the boiler.
2. Secure the flue to the boiler using the three M5 nuts
provided.
3. Insert the flue extension tube into the flue.
4. Fit the 90° flue elbow, supplied with the boiler, onto
the fan in the direction required, after first removing
the underside screw, which is not required. Secure in
position with the screw attached to the fan.
5. Pull the flue extension tube and engage onto the fan
elbow and secure with the screw attached to the
elbow.
The sealing ring studs will locate in the back panel
Note.
one way only. This will ensure that the terminal grille is
correctly aligned.
32
TERMINAL WALL PLATE
This plate allows neat concealment and full compression of
the rubber seal. Its use is not essential if the flue hole and
flue ducts have been accurately cut and the outside wall
face is flat.
1. Position the terminal wall plate over the terminal.
2. Drill 4 fixing holes with a 7mm (
3. Insert the 4 plastic plugs provided.
4. Secure the plate with 4 of the No.10 x 2" screws
provided.
If the terminal is less than 2m (6' 6") above ground
Note.
level, an approved terminal guard should be fitted. Refer to
the Contents List on Page 3.
33
FLUE EXTENSION DUCTS - For flue lengths greater than 600mm
9/32") masonry drill.
PACK D Flue extension duct kit contents
REAR & SIDE FLUE OUTLET
20
Classic FF -
Propane Installation & Servicing
Page 21
INSTALLATION
34
FLUE EXTENSION DUCTS - continued
General arrangement
Side flue shown.
Note.
1. A
maximum
duct) may be used together.
2. Flue extensions of greater length than 1m (39") should be
supported with the bracket provided. If the stand-off
brackets have been used it is necessary, in order to keep
the flue aligned, to use the spacer bracket with the
support bracket.
Flue lengthAccessoriesProduct No.
Up to 600B Pack 1 offsee Frame 10
600 to 1550B Pack 1 off + D Pack, 1 offsee Frame 10
1550 to 2500B Pack 1 off + D Pack, 2 offsee Frame 10
2500 to 3000B Pack 1 off + D Pack, 3 offsee Frame 10
35
FITTING THE KIT
of 3 extension ducts (plus the standard flue
Extension
tube
Boiler
Flue length
Extension duct
Flue connector
Standard flue
Terminal grille
INSTALLATION
1. Remove the cardboard support aid from the
flue and place safely to one side.
2. Fit the inner flue extension duct onto the
inner flue duct.
3. Fit the outer flue extension duct onto the
outer air duct.
4. Drill one - 3.2mm (
the outer air duct.
duct.
5. Insert the self tapping screw provided to fix
the air duct in position.
6. Repeat steps 1-5 if a second flue extension
is required.
1/8") dia. holes through
Do not drill the inner flue
Classic FF -
Propane Installation & Servicing
21
Page 22
INSTALLATION
36
GAS CONNECTION
Refer to 'Gas Supply ', page 6.
Refer to Frame 2 for gas inlet service dimensions.
A minimum pressure of 37 mbar MUST be available at the boiler
inlet with the boiler operating. The main gas cock is on the left hand
side of the gas control valve, as shown. To facilitate connection the
gas cock may be removed from the gas control valve.
38
ELECTRICAL CONNECTIONS
37
WATER CONNECTIONS
1. Remove the plastic plugs from the flow and
return pipes.
2. Make all water connections and check for
water soundness.
WARNING.
The appliance must be efficiently earthed.
A mains supply of 230 V ~ 50 Hz is required.
All external controls and wiring must be suitable for mains voltage. Wiring
INSTALLATION
should be in 3-core PVC insulating cable, not less than 0.75mm
0.2mm) to BS. 6500 Table 16 Wiring Regulations and local regulations.
For IE reference should be made to the current ETCI rules for electrical
installations.
Connection must be made in a way that allows complete isolation of the
electrical supply - such as a double pole switch, having a 3mm (1/8") contact
separation in both poles or a plug and socket, serving only the boiler and
system controls. The means of isolation must be accessible to the user
after installation.
LEGEND
bblue
bk black
br brown
gy grey
or orange
pk pink
rred
vviolet
w white
y/g yellow/green
Flow wiring diagram
Programmer unit
L
8 Pin connector to
system controls
ALL EARTHS must be connected
(Not all earths are shown for clarity)
Optional Programmer Kit
br
B
L
Limit
thermostat
yor
r
Off On Off On
HW CH
w
Connect
to
Air
pressure
switch
r
com
N
b
B
L
v
r
y
NC
NO
Switch
O/heat thermostat
L
br
br
bk
L
NTC
NC
C
P.C.B. 25
NO
bk
bk
Thermostat sensor
bk
N
E
FAN
GV 1
GV 2
or
pk
w
Combined spark &
sensing electrode
Boiler
y/g
gy
bk
br
Main gas
2
(24 x
b
Fan
Pilot gas
b
N
Cla 2642
If an optional programmer is to be fitted
Note.
refer to the instructions provided with the kit
and Frame 39.
1. Remove the control box securing screws.
Swing the box down into the servicing
position. Refer to Frame 46.
2. Route the mains cable into the box from the
RHS of the boiler.
3. Connect the live, neutral and earth wires into
the terminal strip as shown.
4. Secure the mains lead with the cable clamp.
5. On completion of all wiring connections,
relocate the control box and secure.
39
EXTERNAL CONTROLS
External wiring must be in accordance with the current I.E.E.
(BS 7671) Wiring Regulations. For Ireland reference should be
made to the current ETCI rules for electrical installations.
The wiring diagrams illustrated in Frames 41-43 cover the
systems most likely to be fitted to this appliance.
For wiring external controls to the Classic FF boiler, reference
should be made to the system wiring diagrams supplied by the
relevant manufacturer, in conjunction with the wiring diagrams
shown in Frames 41-43.
Difficulty in wiring should not arise, providing the following
directions are observed:
1. Controls that switch the system on or off, e.g. a time switch,
must be wired, in series, in the live mains lead to the boiler.
2. Controls that override an on/off control, e.g. frost thermostat,
must be wired into the mains lead, in parallel, with the
control(s) to be overridden. Refer to Frame 43.
22
3. Controls that switch the circulation pump only on and off,
e.g. a room thermostat, must be wired, in series, with the
pump in the live pump lead.
4. If a proprietary system is used, follow the instructions
supplied by the manufacturer.
5. System designs featuring controls or wiring
arrangements which allow the boiler to fire when there is
no pump circulation taking place should not be fitted.
Advice on required modifications to the wiring may be
obtained from the component manufacturers.
Notes.
1.
Connection between a frost thermostat and the time
control should be made without disturbing other wiring.
2.
A frost thermostat should be sited in a cool place in the
house, but where it can sense heat from the system.
Classic FF -
Propane Installation & Servicing
Page 23
40
PICTORIAL WIRING
LEGEND
b-blue
bk - black
br - brown
gy - grey
or - orange
pk - pink
r-red
v-violet
w-white
y-yellow
y/g - yellow/green
INSTALLATION
INSTALLATION
41
MID POSITION VALVE
Pumped only
Notes.
1.
Some earth wires are omitted for clarity.
Ensure proper earth continuity when
wiring.
2.
Numbering of terminals on thermostats
is specific to the manufacturer.
3.
This is fully controlled system - set the
boiler thermostat to maximum.
4.
Switchmaster 'Midi' is similar in
operation, but the wiring differs slightly;
see manufacturer's literature.
LEGEND
b-blue
bk - black
br - brown
gy - grey
or - orange
pk - pink
r-red
v-violet
w-white
y-yellow
y/g - yellow/green
Classic FF -
Propane Installation & Servicing
23
Page 24
42
TWO SPRING CLOSED VALVE
Notes.
1.
Some earth wires are omitted for clarity. Ensure
proper earth continuity when wiring.
2.
Numbering of terminals on thermostats is
specific to the manufacturer.
3.
This is fully controlled system - set the boiler
thermostat to maximum.
4.
Switchmaster valve has grey & orange
INSTALLATION
auxiliary switch leads but the GREY wire must
be connected to the incoming live supply.
LEGEND
b-blue
bk - black
br - brown
gy - grey
or - orange
pk - pink
r-red
v-violet
w-white
y-yellow
y/g - yellow/green
INSTALLATION
Pumped only
43
FROST PROTECTION
Central heating systems fitted wholly inside the house do not
normally require frost protection as the house acts as a 'storage
heater' and can normally be left at least 24 hrs. without frost
damage. However, if parts of the pipework run outside the house
or if the boiler will be left off for more than a day or so, then a
frost 'thermostat should be wired into the system.
This is usually done at the programmer, in which case the
programme selector switches are set to OFF and all other
controls MUST be left in the running position.
The frost 'thermostat should be sited in a cold place but where
it can sense heat from the system.
Wiring should be as shown, with minimal disturbance to other
wiring of the programmer.
Designation of the terminals will vary but the programmer and
thermostat manufacturer's leaflets will give full details.
If a boiler is installed in a garage it may be necessary to fit a pipe
thermostat.
Diagram A shows a double pole frost 'thermostat, which should
suffice for all systems which do not use the OFF terminals of the
programmer.
Diagram B shows a 'change-over' frost 'stat, which will cover
most systems which do use CH OFF. If, however, on such a
system the HW pipework is in an isolated part of the house, a
second frost 'stat may be used to protect it. If in doubt, ask your
installer for advice.
24
Classic FF -
Propane Installation & Servicing
Page 25
INSTALLATION
44
COMMISSIONING AND TESTING
The Benchmark Log Book or equivalent self certification should be completed and signed to demonstrate compliance with
Building Regulations.
A. ELECTRICAL INSTALLATION
1. Checks to ensure electrical safety should be carried
out by a competent person.
2. ALWAYS carry out preliminary electrical system checks,
i.e. earth continuity, polarity, resistance to earth and
short circuit using a suitable test meter.
WARNING.
45
INITIAL LIGHTING
Whilst effecting the required gas soundness test and purging air from the gas installation open all
windows and doors, extinguish naked lights and DO NOT SMOKE.
ADJ
CL1869
B. GAS INSTALLATION
1. The whole of the gas installation, including the meter,
MUST be inspected and tested for soundness, and purged
in accordance with the recommendations of BS. 6891.
In IE refer to I.S.813:2002.
2. Purging air from the gas installation may be expedited by
loosening the union on the gas service cock on the boiler
and purging until gas is detected.
3. Retighten the union and check for gas soundness.
LEGEND
A Sightglass.
B Gas service cock.
C Inlet pressure test point.
D Thermostat knob
E Main burner pressure adjuster.
F Burner pressure test point.
H Boiler mains on/off switch.
J Overheat thermostat reset
button.
INSTALLATION
B
CEF
TO LIGHT THE BOILER
1. Check that all the drain cocks are closed, and any valves
in the flow and return are open.
2. Check that the gas service cock (B) is OPEN and the
boiler mains On/Off switch is OFF.
3. Fitting the Boiler Casing
The boiler casing must be refitted with the controls
support casing attached for alignment purposes. Lift
the boiler casing up to the boiler assembly, with the
casing top angled forward. Hook the top edge of the
boiler casing into the channel on the top of the boiler
assembly. Swing the bottom of the casing down and
secure with the 2 captive screws.
The casing must seat correctly and compress the
sealing strip to make an airtight joint.
Visually check the side seals but, if side clearances are
limited, then check that the top and bottom edges of the
casing are correctly located.
Note. If the Sealed System Unit is fitted remove the unit
casing in order to inspect the top casing seal.
To gain access to the gas valve:
a. Remove the controls support casing. Release the
controls support front fixing screws 3 turns only.
Remove the pod by pulling it forward to disengage
from the keyhole slots.
b. Remove the control box securing screws and swing
it down into the servicing position. See diagram B,
Frame 46.
4. Slacken the screw in the burner pressure test point (F) and
connect a gas pressure gauge via a flexible tube.
5. Swing the control box back into its working position.
6. Press the overheat thermostat reset button (J).
7. Switch the electricity supply ON and check that all external
controls are calling for heat.
8. Set the boiler thermostat knob (D) to position 6 and the
boiler Mains On/Off switch to ON. The fan will start. After
the fan has run for a few seconds the pilot solenoid valve
should open and the intermittent spark commence,
continuing until the pilot is established. The main burner
will then cross-light smoothly. If this sequence does not
occur, refer to the Fault Finding section.
9. Test for gas soundness around ALL boiler gas
components using leak detection fluid.
10.Operate the for 10 minutes to stabilise the burner
temperature.
The boiler is preset at the factory to its nominal rating.
Check the burner pressure against the values quoted in
Table 2 (page 2). The inlet pressure measured at the gas
control valve must be 37mb.
11. Set the main On/Off switch to OFF.
12.Switch the electricity supply OFF.
13.Swing the control box down into the servicing position.
14.Remove the pressure gauge and tube. Retighten the
sealing screw in the pressure test point. Ensure a gas
tight seal is made.
Classic FF -
Propane Installation & Servicing
25
Page 26
INSTALLATION
46
INITIAL LIGHTING - continued
15.Swing the control box back into
its working position and secure.
16.Remove the boiler casing.
17.Refit the controls pod to the
boiler casing and tighten the 2
front fixing screws.
18.Refit the complete casing to the
boiler.
19.Close the pod door.
INSTALLATION
47
GENERAL CHECKS
Make the following checks for correct operation:
1. Set the boiler thermostat knob to position 6 and operate the
Mains on/off switch. Check that the main burner lights and
extinguishes in response.
2. The correct operation of ANY programmer and all other
system controls should be proved. Operate each control
separately and check that the main burner or circulating
pump, as the case may be, responds.
3. Check that the casing is sealed correctly and compressing
the sealing strip all around the casing.
4. Water Circulating System
a. With the system HOT, examine all water connections for
soundness.
b. With the system still hot, turn off the gas, water and
electricity supplies to the boiler and drain down in order
to complete the flushing process.
c. Refill and vent the system, clear all air locks and again
check for water soundness.
d. Balance the system.
5. Finally set the controls to the user's requirements.
The temperatures quoted below are approximate and vary
between installations:
Knob SettingFlow Temperature
°C°F
154130
260140
366150
471160
577170
682180
WARNING.
The boiler MUST NOT be
operated with the casing removed.
48
HANDING OVER
After completing the installation and commissioning of the system the
installer should hand over to the householder by the following actions:
1. Hand the User's Instructions to the Householder and explain
his or her responsibilities under the current Gas Safety
(Installation and Use) or rules in force.
2. Draw attention to the Lighting Instruction label affixed to the
controls pod door.
3. Explain and demonstrate the lighting and shutting down
procedures.
4. The operation of the boiler and the use and adjustment of
ALL system controls should be fully explained to the
Householder, to ensure the greatest possible fuel
economy, consistent with household requirements of
both heating and hot water consumption.
Advise the User of the precautions necessary to prevent
damage to the system and to the building, in the event of
the system remaining inoperative during frosty conditions.
5. Explain the function and the use of the boiler thermostat and
external controls.
6. Explain the function of the boiler overheat thermostat and
7. Explain and demonstrate the function of time and
8. If any programmer is fitted, then draw attention to the
9. After installation, commissioning and customer hand-
10.Stress the importance of regular servicing by a CORGI
26
emphasise that if cutout persists, the boiler should be
turned off and a CORGI registered installer consulted. In
IE contact a Competent Person.
temperature controls, radiator valves etc., for the economic
use of the system.
Programmer User's Instructions and hand them to the
Householder.
over, please complete the
book and leave this with the customer. For IE, it is
necessary to complete a "Declaration of Conformity" to
indicate compliance to I.S. 813:2002.
registered installer and that a comprehensive service
should be carried out AT LEAST ONCE A YEAR. In IE
servicing work must be carried out by a Competent Person.
Classic FF -
Propane Installation & Servicing
appliance log
Page 27
SERVICING
49
SCHEDULE
To ensure the continued safe and efficient operation of the
appliance, it is recommended that it is checked at regular
intervals and serviced as necessary.
The frequency of servicing will depend upon the installation
condition and usage, but should be carried out at least
annually. It is the law that any service work must be carried out
by CORGI registered installer. In IE service work must be
carried out by a Competent Person.
As the installer you may wish to undertake the service contract
yourself or alternatively offer to the customer the benefits of the
Caradon Ideal Services, details of which are outlined in the
household pack supplied with this boiler.
a. Light the boiler and carry out a pre-service check, noting
any operational faults. Operate the boiler for at least 20
minutes. Check the gas consumption.
b. Connect a suitable gas analyser to the sampling point on
the top RHS of the back panel. For correct boiler operation
the CO/CO
than 0.004 ratio. If this is the case and the gas input is at
least 90% of the nominal, then no further action need be
taken. If not, proceed to paragraph c.
content of the flue gas should not be greater
2
c. Clean the main burner. Refer to Frame 53.
d. Clean the heat exchanger. Refer to Frame 52.
e. Clean the main and pilot injectors. Refer to Frame 53.
f. Remove any debris from inside the base of the casing.
g. Check that the flue terminal is unobstructed and that the
flue system is sealed correctly.
h. If the appliance has been installed in a compartment,
check that the ventilation areas are clear.
The servicing procedures are covered more fully in Frames 50
to 54 and must be carried out in sequence.
WARNING
Disconnect the electrical supply and turn off gas supply.
IMPORTANT. After completing the servicing or exchange of
components always test for gas soundness and carry out
functional checks as appropriate.
When work is complete the casing MUST be correctly refitted,
ensuring that a good seal is made.
T
he boiler must NOT be operated if the casing is not fitted.
Note.
components, the boiler casing must be removed (Frame 50).
.
In order to carry out either servicing or replacement of
50
BOILER CASING REMOVAL
1. If the Classic Sealed System Unit is fitted lift off the casing.
2. Open the controls pod door and release the 2 captive screws
at the bottom of the casing. Swing the bottom of the boiler
casing out until the controls pod casing has cleared the
controls, then unhook the casing top from the back panel.
Retain the casing in a safe place. Where the removal of the
casing is impaired by a pelmet, the instruction in Frame 2
should be followed.
3. Isolate the gas supply at the service cock fitted to the boiler.
51
BURNER AND AIR BOX REMOVAL
1. Remove the screw retaining the front burner support
bracket to the combustion chamber. Remove the M5 pozi
situated at the LH bottom rear of the burner and pull the
burner downwards to disengage the retention tab.
Remove burner to a safe place for inspection and
cleaning.
2. Remove the control box fixing screw. Pull the box forward
and downward to disengage.
SERVICING
3. Pull the HT lead connection off the printed circuit board and
pull the lead upwards through the bottom panel grommet.
4. Remove the four screws retaining the air box /pilot
assembly to the vertical manifold and carefully remove the
assembly
Classic FF -
Propane Installation & Servicing
27
Page 28
SERVICING
52
CLEANING THE FAN ASSEMBLY / THE FLUEWAYS
1. Remove the 2 silicon rubber tubes from the fan sensing
points.
2. Disconnect the fan leads.
3a. Rear flue
Slacken the M4 screw securing the flue connector to the
fan. Disconnect the connector from the fan and slide
into the flue.
3b.Side or top flue
Slacken off two M4 screws securing the flue elbow and
flue connector. Disconnect the flue connector from the
elbow and slide into the flue. Remove the flue elbow.
4. Disconnect the silicon rubber tube from the rear of the
collector hood.
5. Slacken the two M5 nuts on the front tie rods, releasing
the tie rods from the combustion chamber.
6. Remove the M5 central fixing screw at the rear of the
collector hood and remove collector hood/fan assembly.
7. Check that the fan impeller runs freely. Remove any
debris from the impeller with a soft brush.
8. Remove the flue baffles.
9. Remove all loose deposits from the heat exchanger,
particularly between the fins, using a suitable brush.
10.Reassemble in reverse order, ensuring the fan leads
and 3 sensing tubes are reconnected.
53
CLEANING THE BURNER AND PILOT ASSEMBLY
1. Brush off any deposits that may have fallen on to the
SERVICING
burner head, ensuring that the flame ports are
unobstructed, and remove any debris that may have
collected. Note.
be used.
2. Remove the main burner injector and ensure that there is
no blockage or damage. Clean or renew as necessary.
3. Refit the injector, using an approved jointing compound
sparingly.
4. Inspect the pilot burner and ignition / detection electrode.
Ensure that they are clean and in good condition.
54
REASSEMBLY
Reassemble the boiler in the following order:
1. Refit the flue baffles.
2. Inspect the collector hood rope gasket and replace, if
necessary, ensuring that the self adhesive rope is fitted
centrally onto the lip of the collector hood / fan assembly.
The boiler efficiency will be adversely affected if
incorrectly fitted. Refit the collector hood and retain with
the 2 front tie rods and the rear central fixing screw.
Tighten the nuts and screw. Ensure that the sealing
gasket is compressed. Refit the pressure pipe.
3. Refit the positive pressure tubes on the top of the fan
housing. Reconnect the electrical leads.
Brushes with metallic bristles must not
Check that:
a. The pilot burner injector is not blocked or damaged. Refer
to Frame 61 for removal details.
b. The pilot burner is clean and unobstructed.
c. The ignition / detection electrode is clean and
undamaged.
d. The ignition / detection lead is in good condition.
e. The spark gap is correct (Frame 61). Clean or renew as
necessary.
The pilot shield is located around the pilot assembly
Note.
bracket and is located by the electrode retaining nut.
5. Reconnect the gas supply and the electrical wiring.
Refer to Frames 36 & 38.
6. Check the sightglass in the boiler casing. Clean or
renew as necessary. Refer to Frame 57.
7. Check for gas soundness. Check the gas service cock
and pressure test point.
8. Refit the boiler casing (refer to Frame 46). Note that it is
not necessary to disturb the controls casing pod.
9. Close the controls pod door.
4. Refit the air box assembly and burner. Ensure that the
burner front fixing is refitted.
28
Classic FF -
Propane Installation & Servicing
Page 29
55
GAS PRESSURE ADJUSTMENT
SERVICING
PILOT
The pilot is factory set to maximum and no further adjustment is
possible. If after removing and checking the injector (as detailed
in Frame 61) and ensuring that there is an inlet pressure of 37
mbar available, the pilot does not light then contact Caradon
Ideal Limited.
Relight in accordance with 'Initial Lighting.' Refer to Frame 45.
REPLACEMENT OF PARTS
56
GENERAL
When replacing any component:
1. Isolate the electricity supply.
2. Turn OFF the gas supply.
3. Remove the boiler casing - refer to Frame 50.
IMPORTANT. When work is complete the casing must
be correctly refitted, ensuring that a good seal is made.
MAIN BURNER
After any servicing, reference should be made to Table 2
which quotes details of the rated output with the related
burner setting pressure and the heat input.
Note.
In order to assist fault finding the control box printed circuit
board is fitted with 2 indicator lights which represent the following
boiler conditions:
Neon I3.Mains electricity ON.
Neon SG1. Flashes to indicate spark operation (stops after
detection).
The boiler MUST NOT be operated if the casing is not fitted.
57
SIGHTGLASS REPLACEMENT
1. Refer to Frame 56.
2. Unfasten the two nuts and washers holding the sightglass
assembly to the casing front panel.
3. When fixing the new assembly, ensure that the parts are in the
correct order. The frame must have the return edge at the
bottom.
4. Retighten the 2 nuts to ensure an airtight seal. Do NOT
overtighten.
6. Replace the boiler casing. Refer to Frame 54.
58
OVERHEAT THERMOSTAT REPLACEMENT
1. Refer to Frame 56.
2. Remove the control box fixing screws.
3. Swing the control box down into the servicing position.
4. Pull off the electrical connections at the thermostat. Remove the
5. Fit the new thermostat and reassemble in reverse order.
6. Check the operation of the boiler.
SERVICING
backnut retaining the thermostat to the bracket. Withdraw the
thermostat phial from the heat exchanger pocket.
Classic FF -
Propane Installation & Servicing
29
Page 30
59
THERMOSTAT CONTROL, THERMISTOR SENSOR LEAD & ON/OFF SWITCH
REPLACEMENT
Refer also to Frame 56.
A. Remove the fixing screws
B. Swing the control box down into the servicing position.
Thermostat control
1. Pull the knob off the shaft.
2. Remove the backnut securing the thermostat control to
the control box.
3. Pull off the Molex connector from the printed circuit
board.
4. Replace and reassemble in reverse order.
Thermistor sensor lead
5. Pull the sensor lead connector off the printed circuit
board and cut the cable strap securing the thermistor
harness to the bottom panel of the control box (if fitted)
and remove the strap.
6. Remove the sensor from the heat exchanger pocket
and unclip from the back panel.
7. Remove the strain relief bush from the back panel
base.
8. Remove the sensor
lead through the
grommet in the control
box.
9. Replace and
reassemble in reverse
SERVICING
order, ensuring the
new cable strap is
fitted and securing the
thermistor harness.
SERVICING
On/off switch
10.Disconnect the
electrical connectors
from the rear of the
switch.
11. Press in the 2 side
retaining clips and
remove the switch.
12.Reassemble in
reverse order.
30
Classic FF -
Propane Installation & Servicing
Page 31
SERVICING
60
LIMIT THERMOSTAT REPLACEMENT
1. Refer to Frame 56.
2. Remove the limit thermostat assembly from the boiler
flow pipe.
3. Disconnect the electrical connectors
4. Replace and reassemble in reverse order, taking care
to correctly position the limit thermostat as shown in
the orientation diagram opposite.
61
PILOT BURNER REPLACEMENT
1. Refer to Frame 56.
2. Remove the burner and air box assembly. Refer to Frame
51.
3. Remove the electrode retaining nut and remove the pilot
shield and electrode.
4. Unscrew the central pilot fixing screw and lift the pilot clear
of the pilot injector. The pilot injector may now be unscrewed
if required.
5. Replace the pilot burner (injector if necessary) and retain
with the M4 screw previously removed. Ensure the copper
sealing washer is replaced when refitting the pilot injector.
SERVICING
6. Replace the electrode and pilot shield, retaining
both with the electrode nut. Check the spark gap.
7. Reassemble in reverse order.
8. Check the operation of the boiler.
9. The pilot is factory set to maximum and no further
adjustment is possible. Ensure there is an inlet
pressure of 20 mbar available. Also check burner
ignition and cross-lighting.
Classic FF -
Propane Installation & Servicing
31
Page 32
SERVICING
62
IGNITION ELECTRODE AND LEAD REPLACEMENT
1. Refer to Frame 56.
2. Remove the burner and air box assembly. Refer to Frame 51.
3. Remove the electrode retaining nut.
4. Remove the pilot shield.
5. Remove the spark electrode and integral lead.
6. Refit the new electrode and lead in reverse order.
Ensure that the pilot shield is replaced.
7. Check the spark gap. Refer to Frame 61.
8. Reassemble in reverse order.
9. Check the operation of the boiler.
63
MAIN BURNER & MAIN BURNER INJECTOR REPLACEMENT
1. Refer to Frame 56.
2. Remove the screw retaining the front burner
support strap to the combustion chamber.
3. Remove the M5 pozi screw, situated at the left
hand bottom rear of the burner. Pull the burner
downwards to disengage the retention tab and
remove the burner.
SERVICING
4. At this stage the main burner injector can be
removed, checked, cleaned or replaced as
required. Ensure that an approved jointing
compound us used sparingly.
5. Fit the new burner, ensuring that the retention tab
is correctly located in the air box slot and
reassemble in reverse order.
6. Check the burner for cross-lighting and flame
stability.
64
GAS CONTROL VALVE REPLACEMENT
Note.
Refer also to Frame 75 of 'Exploded Views' for
illustration of the procedure detailed below.
1. Refer to Frame 56.
2. Remove the burner and air box assembly. Refer to
Frame 51.
3. Remove the fixing screws.
Swing the control box down into the servicing position.
4. Disconnect the gas control valve electrical leads.
5. Undo the gas cock union .
6. Whilst supporting the gas control valve, remove the 2
screws retaining the manifold to the back panel.
32
7. Remove the gas control / manifold assembly.
8. Remove the 4 screws retaining the manifold to the gas
control valve, and fit the manifold to the new valve.
Ensure that the new control is fitted the correct way round
(an arrow engraved on back indicates the direction of
flow).
9. Transfer the gas cock union to the new gas control valve,
using an approved jointing compound.
10.Reassemble in reverse order.
11. Check the operation of the boiler.
Classic FF -
Propane Installation & Servicing
Page 33
SERVICING
65
FAN REPLACEMENT
1. Refer to Frame 56.
2. Remove the 2 silicon rubber tubes from the fan sensing points.
3. Disconnect the fan leads.
4a. Rear flue. Slacken the M4 screw securing the flue connector to the
fan. Disconnect the connector from the fan and slide into the flue.
4b.Side or top flue. Slacken off two M4 screws securing the flue elbow
and flue connector. Disconnect the flue connector from the elbow
and slide into the flue. Remove the flue elbow.
5. Disconnect the silicon rubber tube from the rear of the collector hood.
6. Slacken the two M5 nuts on the front tie rods, releasing the tie rods
from the combustion chamber.
7. Remove the M5 central fixing screw at the rear of the collector hood
and remove collector hood / fan assembly.
8. Remove the three M4 screws retaining the fan to the collector hood.
9. Fit the new fan and reassemble in reverse order, ensuring the fan
leads, and 3 sensing tubes are reconnected.
10.Check the operation of the boiler.
66
AIR PRESSURE SWITCH (APS) REPLACEMENT
1. Refer to Frame 56.
2. Remove the APS fixing screw.
3. Remove both sensing tubes from the APS.
4. Remove the 3 electrical connections from the
APS.
5. Fit the new APS and reassemble in reverse order.
6. Check the operation of the boiler.
67
PRINTED CIRCUIT BOARD (PCB) REPLACEMENT
Refer to Frame 74 of 'Exploded Views' for
Note.
illustration of the procedure detailed below.
1. Refer to Frame 56.
2. Remove the fixing screws and swing the control box down
into the servicing position.
3. Disconnect the detection lead from the PCB.
4. Unplug all the Molex connectors from the PCB.
SERVICING
5. Disengage the PCB from the mounting posts and withdraw
from the control box.
6. Fit the new PCB and reassemble in reverse order.
7. Check the operation of the boiler.
Fuse.
To change the fuse, prise it out of the holder and disengage
the fuse. Refer to Frame 74 for fuse location.
68
COMBUSTION CHAMBER INSULATION REPLACEMENT
1. Refer to Frame 56.
2. Remove the burner and air box assembly.
Refer to Frame 51.
3. Remove the 4 tie rods.
4. Remove the combustion chamber.
5. Remove the 2 side panel retaining brackets.
6. Remove the side insulation panels.
Classic FF -
Propane Installation & Servicing
7. Remove the front and rear
insulation panels.
8. Fit the new front and rear
insulation panels.
9. Fit the new side panels and
retain with the brackets and
screws previously removed.
10.Reassemble in reverse order.
33
Page 34
SERVICING
69
HEAT EXCHANGER REPLACEMENT
Note.
Refer to Frame 7 (Boiler Assembly - Exploded view) for
illustration of the procedure detailed below.
1. Refer to Frame 56.
2. Remove the burner / air box assembly. Refer to Frame 51.
3. Drain the system.
4. Disconnect the water connections. If compression fittings
are used then cut the pipes both above and below the
fittings, in order to allow the heat exchange assembly to
be removed. Remove the heat exchanger drain plug and
drain the residual water into a suitable receptacle.
5. Remove the fan / collector hood assembly. Refer to
Frame 52.
6. Remove the combustion chamber by unscrewing the 4 tie
rods.
7. Remove the thermostat sensors from the pockets on the
heat exchanger by removing the M3 screws and plates.
8. Slacken 3 turns only the 4 heat exchanger / interpanel
retaining screws.
9. Lift the heat exchanger / interpanel assembly upward and
forward to disengage key hole fixings. Pull the assembly
downward to clear the water pipes from the back panel.
10.Remove the 2 rubber sealing grommets from the top of the
back panel to facilitate fitting the new assembly.
11. Fit the new heat exchanger assembly, complete with water
pipes, and hang it on the key hole slots and screws.
Retighten the screws.
12.Replace the 2 rubber sealing grommets.
13.Reassembly in reverse order.
14.Remake all water connections, ensuring that the
compression fittings (if used) are correctly refitted.
15.Fully test all functions, including water and gas soundness.
70
CASING SEAL REPLACEMENT
1. Refer to Frame 56.
2. Remove the old seal from the bottom edge of the
casing and also from the edges of the boiler back
panel.
3. Fit the new self adhesive seals.
SERVICING
4. Replace the boiler casing.
71
PROGRAMMER REPLACEMENT (IF FITTED)
1. Refer to Frame 56.
2. Remove the fixing screws and
swing the control box down into
the servicing position.
3. Pull off the terminal
connections from back of
programmer.
4. Compress the lugs at each
side of the programmer and
withdraw it from the control
panel.
5. Fit the new programmer in
reverse order.
6. Set the programmer to the
desired programme and check
the operation of the boiler.
34
Classic FF -
Propane Installation & Servicing
Page 35
START
Is the mains on neon 'I3' illuminated?
YES
Is there a live supply on EITHER
terminal of overheat 'stat?
NO
YES
Is there a live supply on BOTH
terminals of overheat 'stat?
FAULT FINDING
Check mains supply and fuses.
Check programmer and system
The following are parts commonly required due to damage or expendability.
Their failure or absence is likely to affect safety or performance of this appliance.
The list is extracted from the British Gas List of Parts, which contains all available
spare parts.
The full list is held by British Gas, Caradon Ideal Limited distributors and
merchants.
When replacing any part on this appliance use only spare parts that you can be assured conform to the safety and performance
specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
35Boiler casing assembly complete with sightglass assy, insulation
and M5 x 16 dogpoint pozipan head screws1171 471
37Controls casing door with Lighting Instr.1171 475
39E85-313Casing sealing pack complete with screws1171 479
45E83-682Overheat thermostat1171 950
59Limit thermostat1173 353
36
Classic FF -
Propane Installation & Servicing
Page 37
72
SHORT PARTS LIST
9
12
LIST OF PARTS
13
13 A
14
15
17
24
73
BOILER CASING ASSEMBLY
26
30
18
39
19
23
59
45
cla 6113
Classic FF -
Propane Installation & Servicing
37
Page 38
74
CL1870
Solenoidvalve
Sealinggasket
Sealinggasket
10
11
13
12
16
42
17
CONTROL BOX - Exploded view
LIST OF PARTS
LEGEND
19.Control box.
21.Thermostat potentiometer.
23.Printed circuit board.
26.Thermostat knob.
58.Mains on/off switch.
75
BURNER ASSEMBLY - Exploded View
LEGEND
10.Burner manifold
11. Air box and pilot assembly.
12.Main burner.
13.Main burner injector.
16.Pilot shield.
17.Gas control valve.
42.Gas service cock.
38
Classic FF -
Propane Installation & Servicing
Page 39
NOTES
Classic FF -
Propane Installation & Servicing
39
Page 40
The code of practice for the installation,
commissioning & servicing of central heating systems
THIS SYMBOL IS YOUR
ASSURANCE OF QUALITY
These appliances are designed for use with Natural
Gas only. They have been tested and conform with the
provisions of BS. 6332 and BS. 5258.
Technical Training
The Ideal Boilers Technical Training Centre offers a series
of first class training courses for domestic, commercial and
industrial heating installers, engineers and system
specifiers.
For details of courses please ring: ............. 01482 498432
CERTIFIED PRODUCT
Manufactured under a BS EN ISO 9001: 1994
Quality System accepted by BSI
Caradon Ideal Limited pursues a policy of continuing
improvement in the design and performance of its products. The
right is therefore reserved to vary specification without notice.
P.O. Box 103, National Ave, Kingston upon Hull,
Ideal Installer/Technical Helpline: 01482 498663
www.idealboilers.com
March 2003UIN 157365 A04
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.