ICP DAS USA I-7531 User Manual

Page 1
The i-7531 CAN Repeater
Quick Start User Guide
1. Introduction
This user guide describes how to implement the i-7531 module into users’ applications in a quick and easy way. Therefore, it only provides the basic concepts. If users want to know more detail information about the i­7531, please refer to the user manual of i-7531 in the product CD or visit our website as follow:
http://www.icpdas.com/products/Remote_IO/can_bus/i-7531.htm
The purpose of this document is focused on helping users to quickly familiarize themselves with the i-7531 module. For example, users can apply the i-7531 module as follow figure:
Original
CAN bus
Backbone use
Backbone of CAN bus
i-7531
CAN branch
Electronic isolation
Extended use
i-7531
Extended
CAN bus
i-7531 i-7531
CAN branch CAN branch
i-7531
Extended
CAN bus
Electronic isolation
i-7531 CAN Repeater Quick Start User Guide (ver. 1.3, 2008/03/25) -----1
Page 2
& Communication
2. Hardware Structure
CAN Port 2
Status LED of Power
CAN_L
20
GND
CAN_H
(CAN)
i-7531
CAN bus Repeater
Support CAN 2.0A/2.0BPhoto-isolation: 2500 VrmsExpand the number of CAN busesMountable on DIN Rail
3000V Isolation
Frame Ground
FG
11
1
CAN_L
CAN Port 1
(CAN)
CAN_H
GND
FG
10
(R)VS+
(B)GND
Power Input
Frame Ground
When the i-7531 is turned on, the status LED will be display with red light. Moreover, when a message passes through i-7531, the status LED will be twinkle once with yellow light while the red light is still on.
Note1: Twinkling rate correlates with baud rate of CAN bus. Users may
see no twinkling when the twinkling period is too short because of the higher baud rate of CAN bus. Besides, the yellow LED could look like always on when bus loading is heavy.
i-7531 CAN Repeater Quick Start User Guide (ver. 1.3, 2008/03/25) -----2
Page 3
3. Terminator Resistor Setting
According to the ISO 11898 specifications, the CAN bus network must be terminated by one terminal resistor on each end of CAN bus for proper operation.
The JP2 of i-7531 is used for adjusting terminal resistor (120) on CAN Port 1, and the JP3 of i-7531 is used for adjusting terminal resistor on CAN Port 2.
Before setting terminal resistor (120) of i-7531, user needs to open the cover of i-7531 first. Those locations of JP2 and JP3 are shown as following figure:
The following connection statuses present the condition if the terminal resistor is enabled (default) or disabled.
Disable
(Deactivate)
Enable
(Activate)
4. Configuration Installation
Step1: Modify JP2 and JP3 of i-7531 according to user’s application.
Step2: Connect two different CAN buses using i-7531 as follow figure:
i-7531 CAN Repeater Quick Start User Guide (ver. 1.3, 2008/03/25) -----3
Page 4
CAN Port 2
CAN_GND Earth Ground
CAN DEVICE
5
1
3
CAN_H
CAN_L
9
6
Power
CAN Port 1
CAN_L
CAN_H
CAN_GND
Power GND
+10VDC ~ +30VDC
Earth Ground
Note2: Roughly speaking, wiring of CAN_GND and FG can improve the
capability of anti-interference of CAN bus system in harsh environment, but this is not necessary.
Note3: When users want to calculate the total bus line length, i-7531
need also be considered.
According recommended specific line delay 5ns/m, one i-7531 (~200ns delay) should be considered as one 40m bus line.
For more information, please refer to the user manual of i-7531.
i-7531 CAN Repeater Quick Start User Guide (ver. 1.3, 2008/03/25) -----4
Loading...